Table 11: Terminal Reheat Lockout Adjustment (Part 2 of 2)Reheat Stage (RehtConfParameter)Analog Reheat Stage(AO2 OALK Parameter)On/Off Reheat Stage(BO5 OALK Parameter)(2): On/Off Duct Reheat Only N/A Set the on/off reheat stageto the desired temperature.(3): On/Off Peripheral ReheatOnly(4): Analog Duct Reheat <strong>and</strong>On/Off Peripheral ReheatConfiguring the <strong>TEC</strong>2664Z-2 Rooftop <strong>Control</strong>lerThe <strong>TEC</strong>2664Z-2 Rooftop <strong>Control</strong>ler comes from the factory with default settings<strong>for</strong> all configurable parameters. The default settings are shown in Table 12. Accessthe Installer Configuration Menu on the rooftop controller to reconfigure theparameters.To access the Installer Configuration Menu, press <strong>and</strong> hold the MENU key <strong>for</strong>approximately 8 seconds. Once the Installer Configuration Menu begins, press theNO key to scroll through the parameters listed in Table 12. When the desiredparameter appears, use the YES key to choose the desired selection option. Pressthe YES key <strong>and</strong> then the NO key to continue scrolling through the parameters.When the rooftop controller is in the Installer Configuration Menu <strong>and</strong> leftunattended <strong>for</strong> approximately 8 seconds, the rooftop controller reverts to the AutoScroll Display.Configuring Input DI1N/ASet the analog reheat stageto the desired temperature.This setting can be differentthan the on/off reheat stagetemperature setting.Set the on/off reheat stageto the desired temperature.Set the on/off reheat stageto the desired temperature.This setting can be differentthan the analog reheat stagetemperature setting.When DI1 is configured <strong>for</strong> an alarm condition, an alarm condition appears locallywhen the input is closed. An alarm message is included on the Auto Scroll Display,<strong>and</strong> when the message appears, the backlight momentarily lights up.The DI1 input can be configured to the selection options included in Table 12.Table 12: <strong>TEC</strong>2664Z-2 Rooftop <strong>Control</strong>ler Installer Configuration Menu (Part 1 of 5)ParameterAppearingon DisplayRTC MAC 1Description <strong>and</strong> DefaultSets a unique device address <strong>for</strong>the rooftop controller on the <strong>MS</strong>/<strong>TP</strong>network.Default: 4Note: This parameter setting mustbe the same as the RTCMAC parameter setting <strong>for</strong>all zone controllersassociated with this rooftopcontroller.Selection OptionsRange: 004 to 127Note: When setting the device address, press the UP/DOWN arrowkeys to change the device address in increments of 1; press<strong>and</strong> hold the UP/DOWN arrow keys to change the deviceaddress in increments of 10.32<strong>TEC</strong> <strong>Zoning</strong> <strong>Control</strong> <strong>System</strong> <strong>for</strong> <strong>St<strong>and</strong></strong>-<strong>Alone</strong> <strong>and</strong> <strong>BACnet®</strong> <strong>MS</strong>/<strong>TP</strong> Networked ApplicationsTechnical Bulletin

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!