<strong>ABB</strong> i-bus ® <strong>EIB</strong><strong>Room</strong> <strong>thermostat</strong> solo ® , <strong>FM</strong><strong>Type</strong>: <strong>6124</strong>-<strong>xx</strong>ParametersThe default setting for the valuesis printed in bold type.<strong>Room</strong> temperature:– Change of current setpoint for inactiveautomatic sendingat 0.2 Kat 0.4 Kat 0.6 K…at 2.0 K– Send current setpoint if changes inactiveactive– Cyclic time for autom. sending no cyclical sendingof temp. differenceevery 3 min…every 20 minevery 30 minevery 60 min– Offset for temperature measurement –128 … 0 … 127(change in measured value by(-128 … 127)x0.1 K)– Detection of actual temperature internallyexternallySetpoints:– Base setpoint in °C (16 … 31) 21 °C(comfort temperature for heating)– Reduced heating in standby mode 4 Kin K (1…8)– Reduced heating during the night 4 Kin K (1…8)– Setpoint frost protection in °C (5…10) 7 °COnly for heating and cooling:– Insensitive range between heat 4 Kand cool in K (1 … 8)– Increased cooling in standby mode 2 Kin K (1 … 8)– Increased cooling during the night 4 Kin K (1 … 8)– Setpoint heat protection cooling disabled /30 °C / 35 °C / 40 °C / 44 °C– Toggle between heat and cool automaticallyexternally2 - 10 March 2003