20. System SpecificationsPower Consumption: <strong>BCT</strong>-<strong>128</strong> ............................... 65 Watts<strong>BCT</strong>-<strong>256</strong> ............................... 75 WattsInput Voltage: <strong>BCT</strong>-<strong>128</strong> <strong>and</strong> <strong>BCT</strong>-<strong>256</strong> ......... 120VAC, 60Hz or 220VAC, 50HzInput Number of Channels Reading Range Accuracy *Cells Up to <strong>256</strong> 0 to 20V 0.1% of reading 0.01VOverall Volts 1 0 to 300V 0.1% of reading 0.2V0 to 600V 0.1% of reading 0.4VCurrent 1 0 to 3000A 0.1% of reading 3AIntertiers 8 0 to 3V 0.1% of reading 1mVAlarms Warning ShutdownCell 0 to 20V 0 to 20VOverall Volts 0 to 600V 0 to 600VCurrent N/A 20% of program current for 10 secIntertiers 200mV N/AHardware N/A ImmediateCell VoltagesOverall VoltsCurrentIntertiersRAM UpdateInput Data Points10mV0.17% of reading1AStored At Reading ChangesEnd of test reading onlyEvery 10 minutes or 1K buffer*Accuracy guaranteed from 40F to 120F to 95% relative humidity, non-condensing. Beyond the ratedtemperature range, accuracy may be degraded by 0.05% per F.79