15.12. Overall Battery Calibration1. Calibrate if As-Found readings are not within specification: 0.1% of reading 0.4V.2. Complete the Overall Battery – After Calibration section of the Calibration Record asfollows:3. Set the DMM to volts.4. Connect the DMM to the CS-<strong>2000</strong> 50V – 600V jacks.5. Adjust the CS-<strong>2000</strong> for a DMM reading of 350V.6. Type the actual reading into the Overall Battery – Voltage Measured box.7. Tab to the Intertier box. The Calibration K value changes.8. Adjust the CS-<strong>2000</strong> for a DMM reading of 75V. Record the voltage on the CalibrationRecord under DMM Input.9. In the Present Readings area, observe the value in the Battery OV box. Record the valueunder Overall Battery – As-Left.10. Adjust the CS-<strong>2000</strong> for a DMM reading of 350V. Record the voltage under DMM Input.11. Observe the value in the Battery – OV box. Record the value under Overall Battery – As-Left.12. Adjust the CS-<strong>2000</strong> for a DMM reading of 600V. Record the voltage under DMM Input.13. Observe the value in the Battery – OV box. Record the value under Overall Battery – As-Left.14. Remove the DMM from the CS-<strong>2000</strong>.68