15.6. Overall Battery As-Found1. Complete the Overall Battery – Before Calibration section of the Calibration Record asfollows:2. Set the DMM to volts.3. Connect the DMM to the CS-<strong>2000</strong> 50V – 600V jacks.4. Adjust the CS-<strong>2000</strong> for a DMM reading of 75V. Record the voltage on the CalibrationRecord under DMM Input.5. In the Present Readings area, observe the value in the Battery OV box. Record the valueunder Overall Battery – As-Found.6. Adjust the CS-<strong>2000</strong> for a DMM reading of 350V. Record the voltage under DMM Input.7. Observe the value in the OV box. Record the value under Overall Battery – As-Found.8. Adjust the CS-<strong>2000</strong> for a DMM reading of 600V. Record the voltage under DMM Input.9. Observe the value in the OV box. Record the value under Overall Battery – As-Found.10. Remove the DMM from the CS-<strong>2000</strong>.15.7. Intertier As-Found1. Complete the Intertier – Before Calibration section of the Calibration Record as follows:2. Set the DMM to volts.3. Connect the DMM to the CS-<strong>2000</strong> 0 – 200mV jacks.4. Adjust the CS-<strong>2000</strong> for a DMM reading of 150mV. Record the voltage on the CalibrationRecord under DMM Input.5. In the Present Readings area, observe the value in the IT 1 box. Record the value underIntertier – As-Found.6. Repeat steps 4 <strong>and</strong> 5 for Intertiers 2 through 8.7. Adjust the CS-<strong>2000</strong> for a DMM reading of 100mV. Record the voltage under DMMInput.8. In the Present Readings area, observe the value in the IT 1 box. Record the value underIntertier – As-Found.9. Repeat steps 7 <strong>and</strong> 8 for Intertiers 2 through 8.10. Adjust the CS-<strong>2000</strong> for a DMM reading of 50mV. Record the voltage under DMM Input.11. In the Present Readings area, observe the value in the IT 1 box. Record the value underIntertier – As-Found.12. Repeat steps 10 <strong>and</strong> 11 for Intertiers 2 through 8.13. Remove the DMM from the CS-<strong>2000</strong>.63

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!