15.1. Shunt RatingUnder Setup, open the Load Bank dialog box. At the Shunt Rating Amps <strong>and</strong> per mV boxes,type the shunt value from the load banks. For example, if the shunt is stamped 600/100 (600amps at 100mV), type 600 in the Shunt Rating Amps box, then type 100 in the per mV box.Refer to Load Bank.15.2. <strong>BCT</strong>-<strong>2000</strong> Calibration SourceWhen calibrating the <strong>BCT</strong>-<strong>2000</strong>, the use of the CS-<strong>2000</strong> calibration source is recommended.If the CS-<strong>2000</strong> is not available, use the original sense lead harness to connect to an alternatevoltage source. Not using the original cables will result in inaccurate calibration because allinput signals are current limited by a resistor in each lead. The CS-<strong>2000</strong> simulates theseresistive leads.CAUTION: Using a source other than the CS-<strong>2000</strong> without the original sense leads willresult in inaccurate calibration.Make a photocopy of the <strong>BCT</strong>-<strong>2000</strong> Calibration Record each time the equipment iscalibrated. Retain these records in the event the equipment needs servicing in the future.15.3. Calibration SetupPrepare the <strong>BCT</strong> <strong>and</strong> CS-<strong>2000</strong> as follows:1. Power off the <strong>BCT</strong>-<strong>128</strong> or <strong>BCT</strong>-<strong>256</strong> <strong>and</strong> the CS-<strong>2000</strong>.2. Connect a ribbon cable from the CS-<strong>2000</strong> Cell connector to the <strong>BCT</strong> Cell 1 connector.3. Connect a ribbon cable from the CS-<strong>2000</strong> System connector to the <strong>BCT</strong> Systemconnector.4. When using the CS-<strong>2000</strong> (or equivalent) calibration source, calibrate the <strong>BCT</strong>-<strong>2000</strong>system without any battery cables or load control cables connected to the <strong>BCT</strong>-<strong>128</strong> or<strong>BCT</strong>-<strong>256</strong>.5. Key points to remember before power-up: If using a source other than the CS-<strong>2000</strong>, use the original sense lead harness to avoidinaccurate calibration. When using any calibration source, remove all battery cables <strong>and</strong> load cables fromthe <strong>BCT</strong>. Calibration must be performed only by technically qualified persons. Dangerousvoltages are present. If all as-found parameters are within specification, calibration is not required. If the preamp needs calibration, then the overall current <strong>and</strong> intertiers must becalibrated.6. Power on the <strong>BCT</strong> <strong>and</strong> the CS-<strong>2000</strong>.7. Start the <strong>BCT</strong>-<strong>2000</strong> software.61

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!