Cell % Failure - The percentage of cell failure is used by Capacity test reports <strong>and</strong> may bemodified at report time. The value was previously fixed at 80% for reports, but may now bechanged.NOTE: Changing the threshold, rated time, <strong>and</strong> percentage failure values affects which cellsare indicated on the report as failing.13.6. Options ScreenClick the Options tab to display the Options dialog box.Figure 37. OptionsReport Title <strong>and</strong> Report Footer - Edit or add text in these boxes if required. The ReportTitle always prints (unless there is no title text), but you must select the Footer Text Printedcheck box to print the footer. To print the page number <strong>and</strong> date, select the Footer PageNumber <strong>and</strong> Footer Date Printed check boxes.Exp<strong>and</strong> All Test Results Graphs - Select this box to display a Drill Down Report for eachcell that fails minimum voltage threshold level. This report (graph) appears on screens underthe Results tab on the View Reports Form screen. To have the Results tab appear, select TestResults on the Summary dialog box. (Refer to Drill Down Reports.)Include Power in Report - Select this box to list power in reports, in addition to voltage <strong>and</strong>current. This box is available when the test data is not for constant power.Start Capacity Calculation at Target - Select this box to calculate the capacity when thetarget value is found. All the test times in the report are adjusted by this time. For example, ifit takes four seconds to find the target, then all the times in the test report will be minus fourseconds. NOTE: If Calculate Capacity at Target was selected during test setup, this option isnot available.45

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!