11.5.7. Calculate Capacity at TargetAvailable for test types: Performance, Modified PerformanceSelect this box to calculate the capacity when the target value is reached. The test timeadvances only when the target is reached. The test time, but not the test, stops if the loadfalls below target <strong>and</strong> resumes when the target is reached.11.5.8. Ignore Zero Target StepsAvailable for test types: Modified PerformanceIgnore Zero Target Steps in Capacity Calculation - Select this box to ignore stepswhen the load is targeted to 0 (zero) in the capacity calculation. For any steps targeted tozero, the time of that step will not be used in the capacity calculation.11.5.9. Charger High/Low Voltage WarningAvailable for test types: ChargerCharger High Voltage Warning <strong>and</strong> Charger Low Voltage Warning - Type values inthese boxes to activate a warning when high or low voltage levels are exceeded. If valuesare set to 0, the warning is not active.11.5.10. Recharge HoursAvailable for test types: RechargeRecharge Hours - Type the number of hours that the recharge will be monitored.26