11.4.6. Recharge TestThe recharge test monitors the battery system while it is being recharged. For every twocell volts, the cell warning level is set to 2.33V. The OV warning levels are a multiple ofthese levels times the number of cells per string. On this test, the levels are high level(maximum) values.Figure 12. Setup - Test Setup: Recharge11.5. Test Setup ParametersThe following items are available on the Test Setup dialog boxes depending on the test typeselected.11.5.1. Rated TimeAvailable for test types: Performance, Modified PerformanceType the manufacturer’s specified rated time in the Rated Time box. This value isimportant for the on-line capacity calculation performed during a single step capacitytest. The format is hh:mm:ss. If doing a Modified Performance test, you may leave RatedTime blank.You may type 0 (zero) for Rated Time on a Modified Performance test. If this is done,the test does not calculate battery capacity at test time. You may enter a Rated Time atreport generation.11.5.2. Power TypeAvailable for test types: Performance, Modified Performance, Service, ChargerConstant Power <strong>and</strong> Constant Current - To define power type, click Constant Power orConstant Current. Power type determines if the programmed load is rated in watts oramps. The power type selected applies to all steps; you cannot switch between ConstantPower <strong>and</strong> Constant Current between steps.23

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!