12.07.2015 Views

Controls, Start-Up, Operation, Service And Troubleshooting - Carrier

Controls, Start-Up, Operation, Service And Troubleshooting - Carrier

Controls, Start-Up, Operation, Service And Troubleshooting - Carrier

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Table 10 — ComfortLink Display Menu StructureMODESETPOINTS INPUTS OUTPUTS CONFIGURATION TIMECLOCKRUNSTATUSAutoDisplay(VIEW)SERVICETESTManualTestMode(TEST)QuickTestMode(QUIC)TEMPERATURESPRESSURESOPERATINGMODESOperatingControlType(SLCT)OperatingModes(MODE)ALARMSUnitTemperatures(UNIT)Circuit APressures(PRC.A)CoolingSetpoints(COOL)GeneralInputs(GEN.I)Circuit AOutputs(CIR.A)DisplayConfiguration(DISP)Time of Day(TIME)ResetCurrentAlarms(R.ALM)CurrentAlarms(ALRM)RemoteUserInterface(R.CCN)Machine<strong>Start</strong>s/Hours(RUN)CompressorRun Hours(HOUR)Compressor<strong>Start</strong>s(STRT)Circuit ATemperatures(CIR.A)Circuit BPressures(PRC.B)HeatingSetpoints(HEAT)Circuit BOutputs(CIR.B)UnitConfiguration(UNIT)Day, Date(DATE)Circuit BTemperatures(CIR.B)Circuit CPressures(PRC.C)Misc.Setpoints(MISC)Circuit COutputs(CIR.C)<strong>Service</strong>Configurations(SERV)Schedule 1(SCH1)AlarmHistory(H.ALM)Circuit CTemperatures(CIR.C)GeneralOutputs(GEN.O)OptionsConfiguration(OPTN)Reset,Demand Limit,Master/Slave(RSET)Schedule 2(SCH2)Holidays(HOLI)Fan RunHours(FAN)<strong>Service</strong>MaintenanceConfiguration(MCFG)CompressorDisable(CP.UN)PredictiveMaintenance(MAIN)SoftwareVersions(VERS)Local Equipment Network — Information is transmittedbetween modules via a 3-wire communication bus orLEN (Local Equipment Network). External connection to theLEN bus is made at TB3.Board Addresses — All boards (except the main baseboard and the energy management module) have 8-positionDIP switches. Addresses for all boards are listed with the Input/Output Tables for each board.Control Module CommunicationRED LED — Proper operation of the control boards can bevisually checked by looking at the red status LEDs (lightemittingdiodes). When operating correctly, the red statusLEDs will blink in unison at a rate of once every 2 seconds. Ifthe red LEDs are not blink in unison, verify that correct poweris being supplied to all modules. Be sure that the main baseboard (MBB) is supplied with the current software. If necessary,reload current software. If the problem still persists,replace the MBB. A red LED that is lit continuously or blinkingat a rate of once per second or faster indicates that the boardshould be replaced.GREEN LED — All boards have a green LEN (SIO) LEDwhich should be blinking whenever power is on. If the LEDsare not blinking as described check LEN connections forpotential communication errors at the board connectors. SeeInput/Output Tables for LEN connector designations. A 3-wirebus accomplishes communication between modules. These3 wires run in parallel from module to module. The J9A connectoron the MBB provides communication directly to thescrolling marquee display or the Navigator display module.YELLOW LED — The MBB has one yellow LED. The<strong>Carrier</strong> Comfort Network ® (CCN) LED will blink during timesof network communication.<strong>Carrier</strong> Comfort Network (CCN) Interface — All30RB units can be connected to the CCN, if desired. The communicationbus wiring is a shielded, 3-conductor cable withdrain wire and is field supplied and installed. The system elementsare connected to the communication bus in a daisy chainarrangement. The positive pin of each system element communicationconnector must be wired to the positive pins of thesystem elements on either side of it, that is also required for thenegative and signal ground pins of each system element. Wiringconnections for CCN should be made at TB3. Consult theCCN Contractor’s Manual for further information. See Fig. 10.NOTE: Conductors and drain wire must be 20 AWG (AmericanWire Gage) minimum stranded, tinned copper. Individualconductors must be insulated with PVC, PVC/nylon, vinyl,Teflon, or polyethylene. An aluminum/polyester 100% foilshield and an outer jacket of PVC, PVC/nylon, chrome vinyl,or Teflon with a minimum operating temperature range of–20 C to 60 C is required. See Table 11 for recommended wiremanufacturers and part numbers.Fig. 10 — ComfortLink CCN Communication Wiring16

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!