Appendix 1OO 6T-29Effective Date: 02 July 2014Page 6 of 13EMLS – Lower Mainl<strong>and</strong> Area1.0 EMERGENCY MANUAL SHEDDING BLOCKS<strong>Manual</strong> load shedding may require up to 50% of the area load to be shed in 3 blocks within 5 minutes.The shedding described in the table in Section 2 is in order of priority within each block.If under frequency load shedding has occurred, some of the loads may already have been shed. Bold<strong>and</strong> underlined stations <strong>and</strong>/or their loads are part of the automatic under-frequency load sheddingscheme <strong>and</strong> might have been tripped should this auto shedding scheme have operated. MW (auto) inthe table summarizes the amount of load shed by automatic under frequency load shedding.Voltage should be monitored frequently while load is being shed. At the direction of the TC, circuitsshould be cut out as necessary to control the voltage.Once load shedding complete, switching should commence to restore station service to affectedstations.2.0 EMERGENCY MANUAL LOAD SHEDDING PROCEDURE<strong>Shedding</strong> should be carried out using the EMLS_OV screen as shown in Appendix 5 (Figure 1). Thereal time loading on each element to be shed is shown on the screen. Follow the steps in sequentialorder as listed in these tables to shed each block:EMLS Block 1at CYP openat WLT openat ALZ openat BND openDevice Affected Stations MW(man)MW(auto)60CB5, 60CB9HSB, LBY 25 060CB13 (T2, 60L89)60CB6, 60CB7 (open onefeed to CAP, GLR, HCT, JLN,JRI, NOR, NVR, SWP, VDK)60CB2, 60CB3 (T1)NXC, SWP, JRI, VDK, 350 13560CB5, 60CB6 (N.O.) DCV, NVR, ERW, NOR,60CB14 (T2)JLN, CAP, GLR, HCT60CB9 (T3)60CB7, 60CB1CHK, SMW, TMO, ALZ 203 5060CB6 (T2)60CB11, 60CB360CB4 (T3)25CB4,25CB5, 25CB6(T4/T1)12CB1, 12CB2 (N.O.), BND 131 012CB3, 12CB4 (T1)12CB5, 12CB6 (N.O.),12CB7, 12CB8 (T2)Total Block #1 709 185
EMLS Block 2at KI1 openat KI2 openOO 6T-29Effective Date: 02 July 2014Page 7 of 13Device Affected Stations MW(man)MW(auto)60CB10, 60CB15 (60L31)60CB1, 60CB20 (60l32)2CB4, 2CB5 (2L64)KI1, LF1,SEA,234 8860CB3, 60CB4 (T1)RIM, YVR,RSR, GDK,60CB6, 60CB7 (T2, 60L43) UNS,60CB9, 60CB10 (T3)UNY(60L46/38)at MAN open 2CB1, 2CB2 (2L55) CSN, SPG 236 0at MAN open 2CB4, 2CB5 (2L53)MAN 182 932CB3, 2CB6 (2L56)at SPG open2CB1, 2CB6 (2L44)Total Block #2: 652 181EMLS Block 3at MUR openat CSQ openDevice Affected Stations MW(man)MW(auto)2CB1, 2CB9 (2L50)496 1302CB3, 2CB4 (2L31)2CB2 (T1)2CB5, (T2)2CB6, 2CB7 (T3)2CB1 (2L20)CSQ, DGR, MUR(Vancouver downtownload)at NEL openat COK open12CB3, 12CB35 (T3)12CB34, 12CB12, 12CB2(T2)12CB1 (T1)25CB41, 25CB42 (T4)25CB43, 25CB44 (T5)25CB32, 25CB34 (T3)NEL (distribution load) 190 135COK (distribution load) 180 176Total Block #3: 866 441ALL LM BLOCKS TOTAL 2227 807