System Start-Up ProcedurePress the down key and then the enter key to select Status. Verify that all power, batteryand intelligence modules are detected by the system and are functioning correctly by scrolling downand reviewing all status screens. Please note that the intelligence modules are monitored underthe “Miscellaneous” Status Screen (submenu under Status).Bat Voltage: 218VBat Capacity 100.0%Runtime: 01hr 30min32 Batts, 00BadTypical Status ScreenIf a problem is reported, ensure that the system component in question is correctlyinstalled. If the problem persists, refer to Basic Troubleshooting.From the Control Menu, choose Turn Load On.Load On LED should now be lit.Turn Load OnDo Self TestSimulate <strong>Power</strong> FailGraceful RebootControl Menu ScreenLOAD ONON BATTUPS Load is ON.BYPASSFAULTConfirm Menu ScreenThe UPS is now ready to support the load equipment.For further operation, <strong>Power</strong>View features, and configuration, see Basic OperationGuide and Product <strong>Manual</strong> CD (shipped with unit) and visit our website: www.apc.com.If you are using a network connection, please refer to the enclosed Product <strong>Manual</strong> CD.<strong>Symmetra</strong> ® <strong>PX</strong> 10-80 kW, 208V – Operation & Maintenance Guide – 990-1430 REV01 33