2 INSTALLATIONOPTIFLEX 1300 C2.6 Pre-installation requirementsINFORMATION!Obey the precautions that follow to make sure that the device is correctly installed.• Make sure that there is sufficent space on all sides.• Protect the signal converter from direct sunlight. If necessary, install the weather protectionaccessory.• Do not subject the signal converter to heavy vibrations. The devices are tested for vibrationand agree with EN 50178 and IEC 60068-2-6.2.7 How to prepare the tank before you install the deviceCAUTION!To avoid measuring errors and device malfunction, obey these precautions.2.7.1 Pressure and temperature rangesFigure 2-9: Pressure and temperature ranges1 Process connection temperatureThe process connection temperature must stay in the temperature range of the gasket material unless the device isa High-Temperature version. Refer to the table "Temperature ranges for gaskets" that follows and to "Technical data"on page 37.Ex devices: see supplementary operating instructions2 Ambient temperature for operation of the display-20...+60°C / -4...+140°FIf the ambient temperature is not between these limits, the display screen switches off automatically3 Ambient temperatureNon-Ex devices: -40...+80°C / -40...+175°FEx devices: see supplementary operating instructions4 Process pressureRefer to the table "Process pressure limits" that follows and "Pressure/temperature table for probe selection" in thehandbook.WARNING!The process connection temperature range must agree with the temperature limits of thegasket material. The operating pressure range is subject to the process connection used and theflange temperature.10www.krohne.com09/2010 - 4000049805 - QS OPTIFLEX 1300 R08 en
OPTIFLEX 1300 CINSTALLATION 2Temperature ranges for gasketsGasket materialProcess connection temperatureStandard versionHigh-Pressure version High-Temperature andHigh-Temperature /High-Pressureversions[°C] [°F] [°C] [°F] [°C] [°F]FKM/FPM -40…+200 -40…+390 -40…+150 -40…+300 -40…+300 -40…+570Kalrez ® 6375 -20…+200 -4…+390 -20…+150 -4…+300 -20…+300 -4…+570EPDM -50…+150 -58…+300 -50…+150 -58…+300 -50…+250 -58…+480INFORMATION!Ø4 mm / 0.15¨ single cable probe with FEP coating option only: The process connectiontemperature range is -20...+150°C / -4...+300°FINFORMATION!Single rod probes with protective sheath option only: The process connection temperature rangedepends on the protective sheath material selected.PP: -40...+90°C/-40…+194°F; PVDF: -50...+150°C /-58…+302°F; PVC: -15...+80°C / +5…+176°FProcess pressure limitsDevice versionMaximum process pressure[barg][psig]Ø8 mm / 0.3¨ single cable 40 1 580 1High-Pressure (HP) version 300 1 4350 1All other probe types and device versions 100 1 1450 11 Refer also to "Pressure / temperature table for probe selection" in the handbook09/2010 - 4000049805 - QS OPTIFLEX 1300 R08 enwww.krohne.com11
- Page 1 and 2: OPTIFLEX 1300 C Quick StartGuided R
- Page 3 and 4: OPTIFLEX 1300 CCONTENTS4 Start-up 3
- Page 5 and 6: OPTIFLEX 1300 CINSTALLATION 22.1 In
- Page 7 and 8: OPTIFLEX 1300 CINSTALLATION 22.3 Vi
- Page 9: OPTIFLEX 1300 CINSTALLATION 22.5 Tr
- Page 13 and 14: OPTIFLEX 1300 CINSTALLATION 21 23 3
- Page 15 and 16: OPTIFLEX 1300 CINSTALLATION 2INFORM
- Page 17 and 18: OPTIFLEX 1300 CINSTALLATION 2Figure
- Page 19 and 20: OPTIFLEX 1300 CINSTALLATION 22.10.4
- Page 21 and 22: OPTIFLEX 1300 CINSTALLATION 22.10.6
- Page 23 and 24: OPTIFLEX 1300 CINSTALLATION 22.10.8
- Page 25 and 26: OPTIFLEX 1300 CINSTALLATION 2You ca
- Page 27 and 28: OPTIFLEX 1300 CINSTALLATION 22.10.1
- Page 29 and 30: OPTIFLEX 1300 CINSTALLATION 22.11 E
- Page 31 and 32: OPTIFLEX 1300 CELECTRICAL CONNECTIO
- Page 33 and 34: OPTIFLEX 1300 CSTART-UP 44.1 Start-
- Page 35 and 36: OPTIFLEX 1300 CSTART-UP 44.3.4 How
- Page 37 and 38: OPTIFLEX 1300 CTECHNICAL DATA 55.1
- Page 39 and 40: OPTIFLEX 1300 CTECHNICAL DATA 5Othe
- Page 41 and 42: OPTIFLEX 1300 CTECHNICAL DATA 5Reso
- Page 43 and 44: OPTIFLEX 1300 CTECHNICAL DATA 55.2
2 INSTALLATION<strong>OPTIFLEX</strong> <strong>1300</strong> C2.6 Pre-installation requirementsINFORMATION!Obey the precautions that follow to make sure that the device is correctly installed.• Make sure that there is sufficent space on all sides.• Protect the signal converter from direct sunlight. If necessary, install the weather protectionaccessory.• Do not subject the signal converter to heavy vibrations. The devices are tested for vibrationand agree with EN 50178 and IEC 60068-2-6.2.7 How to prepare the tank before you install the deviceCAUTION!To avoid measuring errors and device malfunction, obey these precautions.2.7.1 Pressure and temperature rangesFigure 2-9: Pressure and temperature ranges1 Process connection temperatureThe process connection temperature must stay in the temperature range of the gasket material unless the device isa High-Temperature version. Refer to the table "Temperature ranges for gaskets" that follows and to "Technical data"on page 37.Ex devices: see supplementary operating instructions2 Ambient temperature for operation of the display-20...+60°C / -4...+140°FIf the ambient temperature is not between these limits, the display screen switches off automatically3 Ambient temperatureNon-Ex devices: -40...+80°C / -40...+175°FEx devices: see supplementary operating instructions4 Process pressureRefer to the table "Process pressure limits" that follows and "Pressure/temperature table for probe selection" in thehandbook.WARNING!The process connection temperature range must agree with the temperature limits of thegasket material. The operating pressure range is subject to the process connection used and theflange temperature.10www.krohne.com09/2010 - 4000049805 - QS <strong>OPTIFLEX</strong> <strong>1300</strong> R08 en