<strong>AADvance</strong> <strong>Safety</strong> <strong>Manual</strong>Table 10:Output ModulesModulesDigital Outputs8451, 24V dc, 8channel.+9851/2 TA,24V dc,8 Channel,Simplex/DualTÜV CertifiedConfiguration1oo1D, 1oo2 or2oo2DConditionsDe-energize to action (normally energized): SIL3with 1 or 2 modules fitted. 2oo2D with dualoutput modules fitted.Energize to trip (normally de-energized): SIL2 with1 module fitted and SIL3 with 2 modules fitted.Note: Faulty modules must be repaired orreplaced within the MTTRTable 11:Auxiliary ModulesModulesProcessor Base9100I/O Base9300 (3-way)Conditions<strong>Safety</strong>-related and can be used for safety critical applications inSIL2 with 2 modules fitted or SIL3 applications with 2 or 3modules fitted.<strong>Safety</strong>-related and can be used for safety critical applications inSIL3.Note: Revisions of modules are subject to change. A list of the released versions isheld by TÜV or can be obtained from ICS Triplex Technology Limited.Internal DiagnosticsThe <strong>AADvance</strong> controller embodies sophisticated internal diagnostic systems toidentify faults that develop during operation and raise appropriate alarm and statusindications. The diagnostic systems run automatically and check for system faultsassociated with the controller (processor and I/O modules), and field faults associatedwith field I/O circuits.Note: <strong>Safety</strong> wiring principles shall be employed for field loops if it is necessary for theUser to guard against short circuit faults between I/O channels (e.g. to <strong>com</strong>ply withNFPA-72 requirements).The diagnostic systems report a serious problem immediately, but filter non-essentialitems to avoid spurious alarms. The diagnostic systems monitor such non-essentialitems periodically, and need a number of occurrences of a potential fault beforereporting it as a problem.4-12 Document number 553630 Issue 7: February 2010

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!