11 Calibrating11.2. Updating revolution countersContinuedStepAction4. Select the axis to have its revolution counter updated by:• Ticking in the box to the left• Tapping Select all to update all axes.Then tap Update.5. A dialog box is displayed, warning that the updating operation cannot be undone:• Tap Update to proceed with updating the revolution counters.• Tap Cancel to cancel updating the revolution counters.Tapping Update updates the selected revolution counters and removes the tickfrom the list of axes.6.-Caution!If a revolution counter is incorrectly updated, it will cause incorrect robotpositioning, which in turn may cause damage or injury!Check the calibration position very carefully after each update.See section Checking the calibration position in either of the manuals: Instructionsfor Levelmeter Calibration or Calibration Pendulum Instruction, depending onwhich calibration method to be used. The Product manual for the robot alsocontains more information about calibration.3HAC 16590-1 Revision: B275