EN / ACS800-31/U31 Hardware Manual - Simark Controls
EN / ACS800-31/U31 Hardware Manual - Simark Controls
EN / ACS800-31/U31 Hardware Manual - Simark Controls
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
35Before installationThe drive must be installed in an upright position with the cooling section facing awall. Check the installation site according to the requirements below. Refer tochapter Dimensional drawings for frame details.Requirements for the installation siteSee chapter Technical data for the allowed operation conditions of the drive.WallThe wall should be as close to vertical as possible, of non-flammable material andstrong enough to carry the weight of the unit. Check that there is nothing on the wallto inhibit the installation.FloorThe floor/material below the installation should be non-flammable.Free space around the unitRequired free space around the drive to enable cooling air flow, service andmaintenance is shown below in millimetres and [inches].200 [7.9]50 [2.0] 50 [2.0]200 [7.9]IP21 (UL 1)Cooling air flowMechanical installation