108Cable typesCable sizing is based on NEC Table <strong>31</strong>0-16 for copper wires, 75°C (167°F) wire insulation at 40°C(104°F) ambient temperature. Not more than three current-carrying conductors in raceway or cable orearth (directly buried). For other conditions, dimension the cables according to local safety regulations,appropriate input voltage and the load current of the drive.Copper cables with concentric copper shieldMax. loadCable typecurrentAAWG/kcmil<strong>31</strong> 1044 857 675 488 <strong>31</strong>01 2114 1132 1/0154 2/0176 3/0202 4/0224 250 MCM or 2 x 1251 300 MCM or 2 x 1/0273 350 MCM or 2 x 2/0PDM code: 000969<strong>31</strong>-CCable EntriesInput, DC link and motor cable (per phase) terminal sizes, accepted cable diametersand tightening torques are given below.Frame size U1, V1, W1, U2, V2, W2, UDC+, UDC- Grounding PEWire sizeWire Ø(UL type 1)TighteningtorqueWire size TighteningtorqueAWG in. lbf ft AWG lbf ftR5 10...2/0 1.39 11.1 10...2/0 11.1R6 3/0 ... 350 MCM * 2.09 14.8...29.5 5...4/0 5.9* with cable lugs 6...2/0 AWG, tightening torque 14.8...29.5 lbf ftDimensions, weights and noiseFrame size UL type 1 NoiseHeight Width Depth Weightin. in. in. lb dBR5 32.03 10.43 15.35 143 70R6 38.19 11.81 17.28 220 73Technical data