®<strong>GRX</strong>-<strong>TVI</strong> <strong>Ten</strong> <strong>Volt</strong> <strong>Interface</strong><strong>GRX</strong>-<strong>TVI</strong>Power <strong>Interface</strong>stvi-1 04.07.04Description• Provides capability for a GRAFIK Eye 3000 SeriesControl Unit to switch and dim fluorescent lightsthat have Lutron Eco-10TM (TVE Series) ElectronicDimming Ballasts.• Switches and dims any 0-10V electronicfluorescent dimming ballast powered by 100-277V(ballast must provide 0-10V source). Switches upto 16A of electronic capacitive fluorescent ballasts.• Switches motors up to 1/4HP @ 100-127V, 1/2HP@ 200-277V.• Up to five <strong>Ten</strong> <strong>Volt</strong> <strong>Interface</strong>s may be connected toone Control Unit zone. This allows one zone tocontrol up to five 16A circuits of Eco-10TM (TVESeries) Electronic Dimming Ballasts or five motors.• Provides 100-277V power to loads.• Requires 100-127V or 200-240V power forinternal operations.Job Name:RSPECIFICATION SUBMITTALModel Numbers:PageJob Number:


Specifications®<strong>GRX</strong>-<strong>TVI</strong>Power <strong>Interface</strong>stvi-2 04.07.04Power• Load (output) power: 100-277V.Phase independent of lighting control.O-10V Dimming ControlOutput rating: 10µA-300mA. Sinks current only.Zone CapacityUp to five <strong>Ten</strong> <strong>Volt</strong> <strong>Interface</strong>s per Control Unitzone.Key Design Features• Complies with Standard UL 508.• Provides a Class 2 isolated 0-10V output signalthat conforms to EN60929 and IEC929.• Accepts a phase control signal (100-127V or200-240V; 50/60Hz).TerminalsAccept up to two #12 AWG (2.5mm 2 )conductors.Physical Design• Wall-mounted. Indoor use only. Type 1 enclosure.• Weight: 4.25 lbs. (2kg).Switching Load Types and CapacitiesSource/Load TypeFluorescent• Lutron Eco-10TM(TVE Series)• Electronic CapacitiveNon-Dim• Other Manufacturers’0-10V BallastsIncandescentLow-<strong>Volt</strong>ageMetal HalideNeon/Cold CathodeMotor100-127V200-277V16A16A16A16A16A16A16A230V (CE)--16A16A16A16A16A16A1/4 HP@ 100-120V1/2 HP @ 200-277VEnvironment32-104°F (0-40°C). Relative humidity less than90% non-condensing.Job Name:RSPECIFICATION SUBMITTALModel Numbers:PageJob Number:


¨220- 100-240V 120VH2N2 DH2 H1 N1 N1 SH1100-277VDimensions And Mounting®<strong>GRX</strong>-<strong>TVI</strong>Power <strong>Interface</strong>stvi-3 04.07.04• Mount only where ambient temperature is 32-104°F (0-40°C).• Allow 4.5” (114mm) between <strong>Interface</strong>s when mounting severalin a vertical layout.• Mount so that line (mains) voltage wiring is at least 6 feet (1.8m)from sound or electronic equipment and wiring.• Mount within 7° of true vertical.Front ViewSide ViewCover OpenMounting Holes.25" (6mm) diameterWallOutput Power andSwitching to LoadControlCircuit0-10V DimmingControlCOOPERSBURG, PA 18036 U.S.A.<strong>GRX</strong>-<strong>TVI</strong>0-10V INTERFACE CONTROLControl Input: 100-120V,220-240V 50/60HzSwitches:100-277VACSwitchedIncandescentFluorescentMagnetic Low-voltageElectronic Low-voltageMotorRating <strong>GRX</strong>-<strong>TVI</strong> Input Rating16AIH 2 0.02A5AIDH 2 0.1A16A16A0-10V Output Rating1/4 HP@120V Max. 0.3A1/2 HP@277V12.5"(318mm)11.75"(298mm)Control InputsLoad Switched0-10VMax 0.3AGROUNDCONNECTIONS4.0"(102mm)6.1"(155mm)3.30"(84mm)Job Name:RSPECIFICATION SUBMITTALModel Numbers:PageJob Number:


220-100-127V N2 DL2/DH2 L1/H1 N1 N1 SL1/SH1 + –240V100-L2/H2277V0-10VControl InputsLoad SwitchedMax 0.3A®<strong>GRX</strong>-<strong>TVI</strong>Power <strong>Interface</strong>stvi-4 04.07.04Wiring From One Distribution Panel or Circuit Breaker(100-240V Only)• Each terminal can accept up to two #12 AWG (2.5mm 2 )conductors.• L1/H1 is the Live/Hot feed to power the load.• L2/H2 (on the control circuit terminals) supplies operatingpower for the <strong>Ten</strong> <strong>Volt</strong> <strong>Interface</strong>.• Choose the correct L2/H2 terminal for your operating power.– Leave one terminal empty - do not use both.– Do not connect 277V to either L2/H2 terminal.– Make sure L2/H2 is on the same phase as DL2/DH2(Dimmed Live/Dimmed Hot) from the lighting control.• Run separate neutrals for load circuit - no common neutrals.<strong>GRX</strong>-<strong>TVI</strong><strong>GRX</strong>-3106 Control UnitZONE 2ZONE 4ZONE 6HOT/LIVESSACU WIRE ONLYCLASS 21 2 3 4USACLASS 2IECPELVDistributionPanelZONE 1ZONE 3ZONE 5NEUTRALDimmedHot/LiveNeutralHot/LiveHot/LiveNeutralEarth/GroundL2/H2 220-240VL2/H2 100-120VN2DL2/DH2L1/H1N1N1SL1/SH1Earth/GroundConnections0-10VSwitched Hot/LiveNeutralLED0-10VDC Control Signal Wires -DO NOT CONNECT TO LINEVOLTAGE. Lutron is not liablefor damage due to miswiring.To additional ballasts–+Switched HotNeutral–+Switched HotNeutral0-10VDC BallastEarth/Ground0-10VDC BallastEarth/GroundJob Name:RSPECIFICATION SUBMITTALModel Numbers:PageJob Number:


220-100-127V N2 DL2/DH2 L1/H1 N1 N1 SL1/SH1 + –240V100-L2/H2277V0-10VControl InputsLoad SwitchedMax 0.3A®<strong>GRX</strong>-<strong>TVI</strong>Power <strong>Interface</strong>sWiring From Two Distribution Panels or Circuit Breakerstvi-5 04.07.04• Each terminal can accept up to two #12 AWG (2.5mm 2 )conductors.• L1/H1 is the Live/Hot feed to power the load.• L2/H2 (on the control circuit terminals) supplies operatingpower for the <strong>Ten</strong> <strong>Volt</strong> <strong>Interface</strong>.• Choose the correct L2/H2 terminal for your operating power.– Leave one terminal empty - do not use both.– Do not connect 277V to either L2/H2 terminal.– Make sure L2/H2 is on the same phase as DL2/DH2(Dimmed Live/Dimmed Hot) from the lighting control.• Run separate neutrals for load circuit - no common neutrals.• Panels can have different phases and/or voltages.<strong>GRX</strong>-<strong>TVI</strong><strong>GRX</strong>-3106 Control UnitZONE 2ZONE 4ZONE 6HOT/LIVESSACU WIRE ONLYCLASS 21 2 3 4USACLASS 2IECPELVDistributionPanel ADistributionPanel BZONE 1ZONE 3ZONE 5NEUTRALDimmedHot/LiveNeutralHot/LiveHot/LiveNeutralEarth/GroundHot/LiveNeutralEarth/GroundL2/H2 220-240VL2/H2 100-120VN2DL2/DH2L1/H1N1N1SL1/SH10-10VSwitched Hot/LiveNeutralEarth/GroundConnectionsLED0-10VDC Control Signal Wires -DO NOT CONNECT TO LINEVOLTAGE. Lutron is not liablefor damage due to miswiring.To additional ballasts–+Switched HotNeutral–+Switched HotNeutral0-10VDC BallastEarth/Ground0-10VDC BallastEarth/GroundJob Name:RSPECIFICATION SUBMITTALModel Numbers:PageJob Number: