Rev. 9 December 15, 2012Rev. 9 December 15, 2012g. Close coordination with the Sprinkler System designer, HVAC designer, <strong>and</strong> doorhardware designer is required for connection <strong>of</strong> all sprinkler switches, buildingautomation panels (for air h<strong>and</strong>ling unit <strong>and</strong> smoke damper shutdown), <strong>and</strong> release <strong>of</strong>magnetic door hold-opens.h. For each new Simplex 4100U panel installed, request the following extra materials: 1mapnet card, 1 signal card, 1 power supply, <strong>and</strong> 5% <strong>of</strong> all types <strong>of</strong> devices (no lessthan one, no greater than 10).2. Materialsa. The following are the typical system components for any new addressable devices(Simplex unless noted otherwise):i. Network Display Unit with Voice <strong>and</strong> Fire Fighter Comm<strong>and</strong> Center: NDU forthe 4120 series fire alarm network panel.ii.3. InstallationFire Alarm Control Panel (network nodes): 4100U series.iii. Preaction System Panel: 4020 series.iv. Local Annunciator (LCD type): 4603 series.v. Manual Station: 2099 series.vi. Area Photoelectric Smoke Detector (analog): 4098 series.vii. Remote Alarm Indicator for Smoke Detector: 2098 series.viii. Area Heat Detector: 4098 series.ix. Duct Mounted Smoke Detector: 4098 series with remote test switch.x. Beam type Photoelectric Smoke Detector: 2098 series with remote test switch.xi. Individual Addressable Module (IAM): 2190 series.xii. Zone Addressable Module (ZAM): 2190 series.xiii. Cut-out Relays: MR-101/201 series.xiv. Speaker/Visual Unit: 2902/4903 series (wall mounted).xv. Visual Unit: 4904 series (wall mounted).xvi. Fire Fighter’s Jack: 2084 series.xvii. Fire Fighter Telephone: 2084 series.xviii. Cable: James Monroe or Windy City Wire. Types <strong>and</strong> sizes per themanufacturer’s recommendations; shall be red jacketed.xix. Conventional Wiring: Solid THHN type.a. All cabling shall be installed in conduit <strong>and</strong> painted to identify contents. Alldetection <strong>and</strong> audio/visual wiring <strong>and</strong> devices shall be Class A with supply <strong>and</strong> returnwiring running on opposite sides <strong>of</strong> the main corridors at a minimum. No t-tapping <strong>of</strong>conductors is allowed.90

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!