LAB 1: <strong>1756</strong>-<strong>EWEB</strong> <strong>Module</strong><br />

Only the atomic data types<br />

of BOOL, SINT, INT,<br />

DINT, REAL <strong>and</strong><br />

STRING can be displayed<br />

in a Data View<br />

12. Click the Add button to add the tag to the new data view.<br />

13. Click the Create View button to create the data view. (Note: A data view may<br />

contain more than one tag of various types.)<br />

14. Once the data view is created, we see a list of all the data views. Click the<br />

My_View.xml link under “View Filename” to see the data view you just created.<br />

Notice that an error is displayed where the tag’s value should be. The <strong>EWEB</strong> module<br />

data views can not retrieve data directly from I/O. If we wish to access this data, we<br />

must reference the data through an alias tag in the controller.<br />

15. Click on the Data Views tab <strong>and</strong> then click the Edit button for your data view.<br />

s<br />

16. Click the Edit button for the tag we created.<br />

17. Once the view enters edit mode, change the Tag Name to “DI12_to_IB16D.”<br />

18. Click the Update button followed by the Save View button.<br />

Page 5<br />

The <strong>EWEB</strong> data<br />

views cannot read<br />

directly from I/O.