29.11.2012 Views

CTA Report, Draft 1, ISP Review - US Chemical Safety and Hazard ...

CTA Report, Draft 1, ISP Review - US Chemical Safety and Hazard ...

CTA Report, Draft 1, ISP Review - US Chemical Safety and Hazard ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

panels <strong>and</strong> lights down inside the blend room. The pressure wave vented out of the building, damaging<br />

metal wall panels on both the south <strong>and</strong> east outer walls.<br />

Figure 6. Collapsed firewall <strong>and</strong> metal panels at south end of line 405 blend room.<br />

5.2.4 Fire <strong>and</strong> Explosion at Line 403<br />

The pressure wave <strong>and</strong> fireball produced by the secondary dust explosion above the line 405 blend room<br />

propagated west along the ceiling toward line 403. Several plant personnel described a rolling fireball<br />

traveling in that direction. Evidence of the path of the pressure wave <strong>and</strong> fireball included:<br />

• A collapsed firewall between lines 403 <strong>and</strong> 405 (Figure 7).<br />

• Metal wall panels above the line 403 blend room on the east side that were blown to the west.<br />

• Burnt residue on the building’s roof trusses.<br />

The fireball also ignited semi-cured pelts stored in the open area between lines 403 <strong>and</strong> 405.<br />

37