Subtree A<br />
Second dust<br />
explosion above<br />
405 blend room<br />
Confinement above<br />
line 405 blend room<br />
Initial dust explosion<br />
suspended<br />
accumulated dust<br />
Initial dust explosion<br />
produced flame<br />
front<br />
Normal<br />
Dust accumulated<br />
above 405 blend<br />
room<br />
Initial dust explosion<br />
produced pressure<br />
wave/force<br />
Initial dust<br />
explosion around<br />
405 oven<br />
Building<br />
housekeeping<br />
program for<br />
combustible dust<br />
LTA<br />
Combustible dust<br />
dumped on top of 405<br />
blend room from<br />
airlock cleaning<br />
Line 405 baghouse was<br />
operating inefficiently<br />
releasing combustible<br />
dust from the process<br />
The bags within the<br />
baghouse were clogged<br />
Air lock cleaning<br />
procedures LTA<br />
Phenolic resin<br />
used in process<br />
is combustible<br />
405 oven in<br />
confined area<br />
Suspended<br />
combustible dust<br />
around 405 oven<br />
generated by<br />
inappropriate line<br />
cleaning<br />
practices<br />
Fire in 405 oven<br />
Dust formed a paste<br />
adhering to bags<br />
See<br />
Subtree C<br />
See<br />
Subtree C<br />
Moisture entered the<br />
baghouse<br />
Normal<br />
Normal<br />
See<br />
Subtree C<br />
See<br />
Subtree B<br />
Atmospheric moisture<br />
entered through holes<br />
in baghouse shell<br />
Fire water sprinkler<br />
piping broke inside<br />
baghouse<br />
125