APPENDIX G: Logic Tree Diagram<br />

Seven deaths,<br />

37 injuries<br />

Employees<br />

present<br />

Secondary cascading dust<br />

explosions in confined<br />

areas <strong>and</strong> rapidly spreading<br />

fire<br />

Fire from<br />

secondary dust<br />

explosions<br />

spread<br />

throughout<br />

production areas<br />

Combustible dust<br />

suspended in the<br />

production areas<br />

in explosive<br />

concentrations<br />

Firewall<br />

placement in<br />

production area<br />

LTA<br />

Production area<br />

was not designed<br />

with blastresistant<br />

physical<br />

barriers<br />

Normal<br />

Force from Line 405<br />

explosion suspends<br />

combustible dust in<br />

production areas<br />

Accumulated<br />

combustible dust on<br />

flat surfaces<br />

throughout<br />

production areas<br />

See<br />

Subtree A<br />

Combustible dust<br />

was generated by<br />

inappropriate<br />

methods used to<br />

clean process<br />

equipment<br />

Housekeeping<br />

program did not<br />

adequately<br />

control<br />

combustible<br />

dusts<br />

Ledges <strong>and</strong> other<br />

horizontal flat<br />

surfaces within<br />

facility not<br />

minimized<br />

Building design for<br />

h<strong>and</strong>ling combustible<br />

dusts LTA<br />

Building design<br />

for h<strong>and</strong>ling<br />

combustible<br />

dusts LTA<br />

See<br />

Subtree C<br />

See<br />

Subtree C<br />