Location Damage Cause<br />

Line 402 Metal wall panel separating lines 402<br />

<strong>and</strong> 403 pushed westward<br />

Line 401<br />

North wall of<br />

chemical room<br />

East wall of<br />

plant north of<br />

loading dock<br />

South wall of<br />

plant near new<br />

cylindrical dust<br />

collector<br />

West wall of<br />

plant near<br />

south wall<br />

North wall of<br />

plant near<br />

west corner<br />

Production<br />

area<br />

Baghouses on<br />

lines 403 <strong>and</strong><br />

405<br />

Dust collectors<br />

on lines 401<br />

<strong>and</strong> 402<br />

Metal panels of blend room enclosure,<br />

particularly in northeast portion,<br />

permanently deformed outward<br />

Steel columns in blend room<br />

permanently bent to west<br />

Concrete block masonry firewalls on<br />

south end collapsed or severely<br />

deformed<br />

Building roof above blend room<br />

enclosure destroyed<br />

Sliding door bent <strong>and</strong> concrete block<br />

wall deformed<br />

Higher explosion overpressure in vents through<br />

wall panel<br />

Higher explosion overpressure inside blend<br />

room due to confinement<br />

Higher explosion overpressure generated in<br />

confined area between blend room roof <strong>and</strong><br />

ceiling<br />

Higher explosion overpressure from line 401<br />

Metal curtain wall pushed outward Higher explosion overpressure from line 405<br />

vented outside building<br />

Metal curtain wall pushed outward Higher explosion overpressure from line 405<br />

vented outside building<br />

Metal curtain wall pushed outward Higher explosion overpressure from line 401<br />

vented outside building<br />

Loading dock door bent Higher explosion overpressure from line 401<br />

vented outside building<br />

Charred combustible material adhered<br />

to vertical surfaces; horizontal<br />

surfaces, covered by combustible<br />

material, primarily charred at exposed<br />

exterior surfaces<br />

Bags burned up Fires inside baghouses<br />

Access doors on dust collectors blown<br />

off<br />

Slow burning of combustible phenolic resin<br />

material throughout production area; hot gases<br />

freely exp<strong>and</strong>ing throughout building prevented<br />

large overpressures from developing outside of<br />

blend rooms <strong>and</strong> confined areas above blend<br />

room roofs<br />

Higher pressure inside dust collectors due to fire<br />

or venting of explosion overpressure<br />

102