YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

8 <strong>SRD960</strong> PSS EVE0109 A-(en)<strong>SRD960</strong> with HART communication<strong>SRD960</strong>-xHxxxxSignal InputTwo wire systemReverse polarity protection. . standard featureSignal range ............4to20mAOperating range. .........3.6to21.5mAVoltage range of unloadedinput signal .............12to48VLoad ..................420Ohms,8.4Vat20mACommunication signal .....HART,1200 Baud, FSK(Frequency Shift Key)modulated on 4 to 20 mA0.5 Vpp at 1kOhm loadInput impedance Zi. .......Z=320Ohmsfor ac voltage 0.5 to 10 kHz with < 3 dB non-linearityCable capacity and inductance see HART standardspecifications. (e.g. C < 100 nF).Impedance of other devices at the input (parallel or serial)must be within HART spec.Applications without communication require not to exceedinput capacitance parallel to the input not higher than 100 μF.Start-up time (init phase) . . . approx. 2 secInterruption time without power down:-withLCD..............85ms 1)-withLED..............75ms 1)<strong>SRD960</strong> with FoxCom communication<strong>SRD960</strong>-xFxxxxSignal InputTwo wire systemReverse polarity protection. . standard featureInput ..................digitalvoltage range of supply input DC 8 to 48 VSupply current ...........approx.9mAatDC24VCommunication signal .....FoxComdigital,4800Baud,FSK (Frequency Shift Key)modulated on supply voltage0.5 Vpp at 500 Ohms load.Input impedance .........Z=500Ohms(for ac voltage 3 kHz to 15 kHz)Start-up time (init phase) approx. 2 secInterruption time without power down:-withLCD..............85ms 1)-withLED..............75ms 1)ConfigurationLocal / Display ...........seepage4Software ...............VALcare(FDT-Software)Hardware...............ModemPC10I/A Series System ........FBM43,FBM243,246 2)in connection with CP60ConfigurationLocal / Display ...........seepage 4Software ...............VALcare(FDT-Software)Hardware. ..............Modem MOD991 for PC, IBMcompatibleHand Terminal ...........HARTHand held terminalI/A Series System ........onrequestOther control systems .....AMS, Siemens SIMATIC PDM(ProcessDeviceManager)1) Worst case conditions 4-20mA, with position feedback option, i/p-outputwith max. current


PSS EVE0109 A-(en) <strong>SRD960</strong> 9<strong>SRD960</strong> with communication PROFIBUS-PA and FOUNDATION Fieldbus H1<strong>SRD960</strong>-xPxxxx or <strong>SRD960</strong>-xQxxxxPROFIBUS-PADatatransfer............according to PROFIBUS- PAprofile class B based on EN50170 andDIN 19245 part 4GSDfile................theactualfilecanbedownloadedfrom our homepageConfigurationLocal / Display ...........seepage 4Software ...............VALcare(FDT-Software)Hardware. ..............PC-orPCMCIA-interfacesfrom SoftingI/A Series System ........withFBM223Other control systems .....AllProfibus-PA- compatible,e.g. Siemens SIMATIC PDM(ProcessDevice Manager)FOUNDATION Fieldbus H1Datatransfer............according to FieldbusFOUNDATION SpecificationRev. 1.4, Link-Master (LAS).FunctionBlocks..........AO,Transducer,Resource,PID, 2xDI, DODD files ................theactualfilecanbedownloadedfrom our homepageConfigurationLocal / Display ...........seepage 4Software ...............VALcare(FDT-Software)or National InstrumentsNI-FBUS configuratorHardware. ..............FBUS-interfaces(AT-FBUSand PCMCIA- FBUS)I/A Series System ........withFBM220/221Other control systems .....AllFieldbus FOUNDATIONH1-compatible.Fisher Rosemount Delta-V,Honeywell, Yokogawa, ABBFor both fieldbus versionsInput signal .............digitalSupply voltage ...........DC9to32V*)max. Supply voltage. ......DC48VOperatingcurrent.........10.5mA±0.5(base current)Currentamplitude ........±8mAFaultcurrent.............basecurrent+0mA(base current + 4 mA by means of independentFDE-safety circuit) according to IEC 1158-2Start-up time (init phase) . . . approx. 2 secOperating valuesBus connection ..........Fieldbus interface basedon IEC 1158-2 according to FISCO-Model(see Electrical certifications)Power supply ............Power supply is achieveddependant on the application by means of fieldbuspower supply units or segment coupler*) Data of ”Intrinsically Safe” version


10 <strong>SRD960</strong> PSS EVE0109 A-(en)<strong>SRD960</strong> as <strong>Position</strong> Transmitter stand alone unit<strong>SRD960</strong> -TxQInput .................Stroke/Rotaryangle bymeans of conductiveplastic precisionpotentiometerOutput ................TwowiresystemSignal range ............4to20mA/20to4mAor free configuration3.8to20.5mAPermitted load ...........R bmax = (Us–12 V) / 0.02 A [](Us = supply voltage)Power supplyReverse polarity protection. . standard featureSupply voltage ...........Us=DC12to36VPermitted ripple ..........


PSS EVE0109 A-(en) <strong>SRD960</strong> 11ADDITIONAL EQUIPMENTAdditional Inputs / Outputs, built into any <strong>SRD960</strong> -B or COrder in Model Code: <strong>SRD960</strong>–ooýoooooooo Order in Model Code: <strong>SRD960</strong>–ooýooooooooTwo binary outputs (limit signals) [item 1]Stroke / angle derivated from positioner feedback,configurablegalvanically separated 2 limit signals, two-wire system,according to DIN 19234, for external supplysupply voltage ..........DC8to48VLogic:limit value not exceeded ...2.2mA (typ.6mA)device fault ...........40mA/10V(power derated)Reference: AB1 for upper, AB2 for lower limitTerminals for AB1 ........81+,82–AB2 83+, 84–Explosion protection thereto see page 7.Parts set for subsequent mounting:Code P ................EW426346021<strong>Position</strong> feedback 4 to 20 mA [item 2]Stroke / angle derivated from positioner feedback,1 output analog, galvanically separated, two-wire systemaccording to DIN 19234, for external supplysupply voltage. .........DC8to48Vsignal range ...........3.8to21.5mA0 % and 100 % configurabledevicefault............


12 <strong>SRD960</strong> PSS EVE0109 A-(en)ADDITIONAL EQUIPMENT(continued)Additional Inputs / Outputs, built into any <strong>SRD960</strong> -B or COrder in Model Code: <strong>SRD960</strong>–ooýoooooooo Order in Model Code: <strong>SRD960</strong>–ooýooooooooTwo Binary Contact Inputs [item 3]Two independent binary inputs, supplied by the basicdevice, for connection of sensors. A connected switch isloaded with 3 V, 150 A.Both binary inputs can be used for diagnostics or alsoconfigurable for the control functions.Switch 1 Switch 2 Actuator control functionclose close normal operationopen close go to stop at 0 %close open go to stop at 100 %open open hold last positionTerminals for EB1 ........13+,14–EB2 ........15+,16–Requirements for connected switches:Capacitance in parallel .....10kOhmsHysteresis..............2to5kOhmsFor application with .......-mechanical switches- opto couper outputs- open collector / drainoutputs of transistorcircuitsTwo Binary Signal Inputs/Outputs [item 4]Two Binary Inputs/Outputs are configure by the device asInput or as output, as well as the kind of Signals as on/off oras to NAMUR signal in accordance (DIN 19234).Configured as NAMUR:Input/OutputLogic 0. ................>0.35mA,2.2mA


PSS EVE0109 A-(en) <strong>SRD960</strong> 13ADDITIONAL EQUIPMENT(continued)Additional Inputs/Outputs built into any <strong>SRD960</strong> -B or COrder in Model Code: <strong>SRD960</strong>–ooýooooooooBuilt-in Limit Switch [item 6]Inductive Limit Switchstandard version (SJ2-N) . . . . . . Code Tsecurity version (SJ2-SN). . . . . . Code U- in three wire technology(SI 2-K08-AP7). .......... . . Code RStroke / angle derivated from positioner feedback,two-wire systemOutput.................2inductive proximity sensorsacc. to DIN 19 234 or NAMUR for connection toswitching amplifier with intrinsically safe control circuit 1)Current consumptionvane clear .............>2.2mAvaneinterposed.........


PSS EVE0109 A-(en) <strong>SRD960</strong> 15ATTACHMENT PREPARATIONOrder in Model Code: <strong>SRD960</strong>–ooooooooýooThe <strong>Universal</strong> <strong><strong>Position</strong>er</strong> needs a linking piece for attachmentto the different brands of actuators.The standard Mounting Adapter is marked with Option N.Mounting AdapterPreparation for attachment to:• NAMUR, according to IEC 534-6• Direct mounting to FoxPak and FoxTop actuators, withy1-d air supply (no external tubing for y)• Rotary actuators acc. to VDI/VDE 3845Order Option N.Preparation for attachment to:• Rotary actuators acc. to VDI/VDE 3845Order Option R.4Preparation for attachment to:• Integrated mounting with air connections on rear• Rotary actuators acc. to VDI/VDE 3845Order Option T.6Preparation for attachment to:• NAMUR, according to VDI/VDE 3847• Rotary actuators acc. to VDI/VDE 3845Order Option D.,as Option N, but no y1-d air supply (with external tubingfor y)Order Option F..


16 <strong>SRD960</strong> PSS EVE0109 A-(en)FUNCTIONAL DESIGNATIONS#!! =& '" ! = ! > ! ? ! @ = &#$% $ # '$1 Cable gland 1)2 Plug, interchangeable with Pos. 1 1)3 Connection 2) (11 +/12 –) for input (w) orterminals (11 / 12) for bus connection IEC 1158-23a Connection 2) for additional inputs / outputs4 Ground connection5 Female thread G ¼ or ¼-18 NPT 3) for output I (y1)6 Female thread G ¼ or ¼-18 NPT 3) for air supply (s)7 Female thread G ¼ or ¼-18 NPT 3) for output II (y2)8 Direct attachment hole for output I (y1)9 Feedback shaft10 Connection manifold for attachment to stroke actuators(see page 17 for details)11 Connection base for attachment to rotary actuators12 Cover with window and push buttons12a Push button protection cover (option -X)13a Key Œ MENU13b Key – DOWN13c Key + UP13d Key ! ENTER / STORE15 pneumatic unit with amplifier and connection16 4 screws for connection of pneumatic unit18 built-in pressure gauges for air-supply, output Y1and output Y219 Cover for electronic connection compartment20 Protection screw for electronic connection- andelectronic compartment21 Air vent, dust and water protected(IP65 and NEMA 4X)22 Data label25 Tip jacks, 2 mm dia.26 Arrow is perpendicular to shaft 9 at angle 0 degree1) See cable glands BUSG on page 19. The device is supplied with dustprotection covers2) Screw terminals or WAGO Cage clamps3) Type of thread marked on housing


PSS EVE0109 A-(en) <strong>SRD960</strong> 17Model Codes <strong>SRD960</strong><strong>Universal</strong> <strong><strong>Position</strong>er</strong> <strong>SRD960</strong> 020110VersionSingle Acting . . . . . . . . . . . . . . . . . . . . -BDouble Acting . . . . . . . . . . . . . . . . . . . -C<strong>Position</strong> Transmitter (w/o pneumatic components) . -TLocal Control Panel (LCP960) For PST Monitoring . -LInput / CommunicationHART(4-20mA) . . . . . . . . . . . . . . . . . (g)(p) . HFoxCom (Digital) . . . . . . . . . . . . . . . . . (g)(p) . FProfibus PA based on IEC 1158-2 (MBP)according to FISCO (Fieldbus) . . . . . . . . . (g)()p . PFOUNDATION Fieldbus H1 based on IEC 1158-2 (MBP)according to FISCO (Fieldbus) . . . . . . . . . (g)(p) . Qnot applicable. . . . . . . . . . . . . . . . . . . . (f) . . XAdditional Inputs / OutputsWithout Additional Inputs / Outputs . . . . . . . . (n)(p) . . . . . NBinary Input - integrated. . . . . . . . . . . . . . (g)(p) . . . . . BBinary Output - integrated . . . . . . . . . . . . (g)(p) . . . . . PBinary Inputs/Outputs (mandatory for ESD application) . . . . . . EAnalog <strong>Position</strong> Feedback (4-20 mA) . . . . . . . . . . . . . . . Q- integrated and connected as Option Board . . . (g)(p)- stand alone feedback unit . . . . . . . . . . . . (f)(p)Potentiometer Input (for Remote Mounting - main unit)(g)(p) . . . . . DLimit Switches (standard version SJ2-N) . . . . . (g)(p) . . . . . TLimitSwitches(securityversionSJ2-SN) . . . . . (g)(p) . . . . . ULimit Switch (three-wire version) . . . . . . . . . (g)(p) . . . . . RMechanical Switches (Micro-Switches) . . . . . . (g)(p) . . . . . VDisplay / IndicationLEDs (cover without window and without external pushbuttons). . (p) . . SGrafical LCD (cover with window and with external pushbuttons) . (g) . . DLEDs (cover with window and with external pushbuttons) . . . . (g)(p). . LGaugesWithout Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SBuilt-In Gauges with scale in bar/psi. . . . . . . . (g)(p) . . . . . . . . . . . . MPneumatical Connection1/4-18NPT . . . . . . . . . . . . . . . . . . . (g)(p) . . . . . . . . . . . . . . . . NG1/4 . . . . . . . . . . . . . . . . . . . . . . . (g)(p) . . . . . . . . . . . . . . . . Gnot applicable . . . . . . . . . . . . . . . . . . . (f) . . . . . . . . . . . . . . . . . XElectrical Connection1/2 - 14 NPT (w/o cable glands or plugs for certified <strong>SRD960</strong>) . . . . . . . . . . . . . . . . . . 6M20 x 1.5 (w/o cable glands or plugs for certified <strong>SRD960</strong>) . . . . . . . . . . . . . . . . . . . 7Electrical Certification / Explosion protectionFlameproof II 2 G EEx d IIB/IIC T4/T5/T6 according to ATEX (w/o cable glands or plugs) . . . . . . . EDZExplosion-proof according to FM (w/o cable glands or plugs) . . . . . . . . . . (g)(p) . . . . . . . . FDZGOST Approved For Explosion-proof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GDZWithout Ex (with cable glands and plugs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ZZZMounting Preparation on <strong><strong>Position</strong>er</strong>NAMUR acc. to IEC 534-6 / Direct Mounting to Flowserve actuators FlowPak and FlowTop // Rotary Actuators according to VDI/VDE 3845 . . . . . . . . . . . . . . . . . . . . . . . . (p) . . . . . . NRotary Actuators according to VDI/VDE 3845 . . . . . . . . . . . . . . . . . . . . . . . . . . (p) . . . . . . RIntegrated attachment with air channels on back / Rotary Actuators according to VDI/VDE 3845 (g)(p) . . . . . TDirect mounting acc. to NAMUR VDI/VDE 3847 / Rotary Actuators according to VDI/VDE 3845(a)(g)(p). . . . . DNAMUR acc. to IEC 534-6 / Rotary Actuators according to VDI/VDE 3845 . . . . . . . . . . . . . . . . . . . FLanguageLCD Language in English / German / French . . (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ALCD Language in English / German / Spanish . . (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BLCD Language in English / German / Portuguese (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CLCD Language in English / German / Polish . . . (e)(g)(p). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DLCD Language in English / German / Czech. . . (e)(g)(p). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ELCD Language in English / German / Italian . . . (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FLCD Language in English / German / Turkish . . (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GLCD Language in English / German / Swedish. . (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HLCD Language in English / German / Finnish . . (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . JLCD Language in English / German / Chinese . (a)(e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KLCD Language in English / German / Russian . . (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LLCD Language in English / German / Hungarian. (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MLCD Language in English / German / Serbian . . (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N(continued on next page)


18 <strong>SRD960</strong> PSS EVE0109 A-(en)MODEL CODES <strong>SRD960</strong> (continued)LCD Language in English / German / Dutch . . . (e)(g)(p). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . OLCD Language in English / German / Romanian. (e)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PWithout . . . . . . . . . . . . . . . . . . . . . . (h)(p). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SOptionsDiaphragm Amplifier for double acting positioner. . . . . . . . . (j)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . -MPremium Diagnostics Features (made with built-in pressures sensors) (HART and FoxCom);Build in pressure sensors (analog, FF, Profibus) . . . . . . . (d)(g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . -BInfrared Interface for communication by means of IRCOM . . (d)(g)(k)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . -ICoverforprotectionoflocalpushbuttons . . . . . . . . . . . . (g)(k) . . . . . . . . . . . . . . . . . . . . . . . . . . . . -XApproved for SIL2 / SIL3 application . . . . . . . . . . . . . . . (i)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . -QCustom Configuration . . . . . . . . . . . . . . . . . . . . . . (g)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . -TATEX application down to -40°C . . . . . . . . . . . . . . . . . (l) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -FCertificate EN 10204-2.1 - Certificate of compliance with the order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -1Cage Clamp Connection (WAGO) instead of Screw terminals. . . (p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . -WFeedback-Unit for Remote Mounting - Version of <strong>Position</strong> Transmitter only with a potentiometer (m)(p). . . . . . . . . . . . . -HVersion for ESD Valve with PST functionalities . . . . . . . . . (b)(p) . . . . . . . . . . . . . . . . . . . . . . . . . . . . -ETag No. LabelingStamped With Weather Resistant Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -GStainless Steel Label Fixed With Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -L(a) Not released(b) ONLY WITH (additional Inputs/Outputs E) AND(Optional Feature -B)(d) Not available with Input / Communication D(e) Only with Display / Indication D(f) NOT WITH Version -B, Version C(g) Not available with Version -T(h) Not availalbe with Display / Indication D(i) Only available for Version single-acting -B inconnection with Input/Communication D and H(j) ONLY WITH (Version: C)(k) Not in connection with Display / Indication S(l) ONLY with Electrical Classification EDZ(m) Only available with Version T, Input/communication X,Additional inputs outputs N, Display S, Gauges S,Pneumatical connection X, Electrical classification EDZ orGDZ or ZZZ, Mounting preparation F, Language S(n) WITH (Version: B, C) ORWITH (Version: T) AND (Input: X) AND (Optional Features: H)(p) NOT WITH Version -LACCESSORIES, FOR ALL DEVICESBooster relays, Code LEXG -F, -G, -HConnection manifold, Code LEXG -K, -L, -D, -D1Lateral attachment to positionerAiroutput...............seetableonpage3! N " & 2 6IO O 0*O N " 2 6O OI! N " & 2 6O + @ A - : / /* I JA HB H@ K > A = ? JE C F I EJE A HI+ @ A - : / 0* I JA HB HI E C A = ? JE C F I EJE A HM EJD @ K > A @ K JF K J? = F = ? EJO N * N 0 # N $ # N $ # N * N 0 # N $ N # IN " & 2 6O+ @ A - : / .* I JA HB HI E C A = ? JE C F I EJE A H N * N 0 # N $ N # The use of boosters together with a spool valve amplifier is not recommended.So avoid to select LEXG-G with <strong>SRD960</strong>-CIn case of need select LEXG-G with <strong>SRD960</strong>-Cxxxxxxxxxxx-MO I! N / " O O N * N 0 & ! N N # + @ A - : / + A ? JE = EB @ M EJD / " JD HA = @ I7 K I A @ JD HA = @ I B HF HA I I K HA C = K C A = HA ? I A @> O A = I B ? I ? HA M 2 = HJ " # " !


PSS EVE0109 A-(en) <strong>SRD960</strong> 19Model Codes AccessoriesParts for Intelligent <strong><strong>Position</strong>er</strong>Attachment kitEBZGfor diaphragm actuators with casting yoke acc. NAMUR (incl. standard couple lever) . . . . . . . . . . . . . . . . . . . . . -H2for diaphragm actuators with pillar yoke acc. NAMUR (incl. standard couple lever) . . . . . . . . . . . . . . . . . . . . . . . -Kfor directly mounting (incl. standard couple lever) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Dfor mounting to rotary actuators acc. VDI/VDE 3845 (without bracket) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Rfor FlowTop / FlowPak . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -E1Further Attachment kits on request. See also http://www.foxboro-eckardt.com /Products /<strong><strong>Position</strong>er</strong>s /Attachment kitsCouple leverstandard (stroke max. 80 mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Aextended (stroke max. 120 mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Bextended (stroke max. 260 mm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -A1Manifold (for <strong>SRD960</strong>, SRD991 and SRI990)LEXGWith Connection G 1/4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -KBooster Relay (for <strong>SRD960</strong>, SRD991 and SRI990, with connection 1/4 - 18 NPT)for Version single acting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Ffor Version double acting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Gfor Version single acting with doubled output capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Hwith connection G1/4 - 18for Version single acting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -F1for Version double acting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -G1for Version single acting with doubled output capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -H1Booster Relay (mounted independent from positioner, for <strong>SRD960</strong>, SRD991 und SRI990, with connection G1/4)for Version single acting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -X1for Version double acting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Y1for Version single acting with doubled output capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -Z1AdapterADAdapter 1/2" NPT to 3/4" NPT (stainless steel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -A3Adapter M20 x 1.5 to 1/2" - 14 NPT (internal thread) (Brass nickel plated) . . . . . . . . . . . . . . . . . . . . . . . . . . . -A5Adapter M20 x 1.5 to 1/2" - 14 NPT (internal thread) (stainless steel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -A6Adapter M20 x 1.5 to PG13.5 (internal thread) (stainless steel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -A7Adapter M20 x 1.5 to G1/2" (internal thread) (stainless steel) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -A8Adapter (plastic) M20 x 1.5 to PG13.5 (internal thread) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -A9Cable GlandBUSGM20 x 1.5 stainless steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -S6M20 x 1.5 plastics, color gray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -K6M20 x 1.5 plastics, color blue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -K7M20 x 1.5 plastics, color white. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -K9M20 x 1.5 HF-cable gland for Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -P4M20 x 1.5 Plug-connector for Fieldbus (ss / threaded connection 7/8 - UN) . . . . . . . . . . . . . . . . . . . . . . . . . . -F2M20 x 1.5 Plug-connector for Fieldbus (ss / threaded connection M12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . -P3M20 x 1.5 stainless steel EEx d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -S7M20 x 1.5 brass zink plated EEx d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -S81/2-14 NPT cable gland 6…12 mm, Stainless steel, EEx d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -N11/2-14 NPT cable gland 6…12 mm, Steel zink plated, EEx d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -N21/2-14 NPT, brass zink plated, EEx d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -N3M20 x 1.5 Plug, plastic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -V3M20 x 1.5 Plug, EEx d / explosionproof certified, stainless steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -V41/2-14 NPT Plug, EEx d / explosionproof certified, stainless steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -V5M20 x 1.5 Plug, brass zink plated, EEx d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -V61/2-14 NPT Plug, brass zink plated, EEx d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -V7


20 <strong>SRD960</strong> PSS EVE0109 A-(en)DIMENSIONS – Direct attachment to stroke actuators! &&! # ! & E. A A @ > = ? A L A H + @ A - * / ) B H& % JH= L A !$ % $ $ "! ! ' " !&! # ' ! & ! # ". A A @ > = ? A L A H . N 2 = . N 6 F E + @ A - * / -! " # ' % %!+ = H H EA H > JB H? A ? JE J L = L A I JA ' &% # $% &! + A ? JE J O A K I E C JD A @ EHA ? J? A ? JE D A B HHA = H K JF K J1O O , A J= EI D = BJI JK > EI ' F A HF A @ E? K = HJ JD A = HH M $ JD A D K I E CN &$" " "# #'$ 4 E C N # ' %


&&PSS EVE0109 A-(en) <strong>SRD960</strong> 21Attachment to stroke actuators acc. to IEC 534-6 (NAMUR)LCD orientation can bechanged by means of localpush buttons under Menu9.9.2 to „flipped“, to ensurea correct orientation of thedisplay. E! &) JJ= ? D = JJ ? = I JE C O AM EJD = JJ= ? D A J EJ+ @ A - * / 0 ! # ' ! & ! # " K JE C > H = ? A J" N'! #" ! $ '! N'! #$ %$ "$ N &" ! $ ' ! ## ! #" '% ! # ! & #& ' #$" " # !% ' # ' $$ % #$ $) JJ= ? D A JJ F E= H O AM EJD = JJ= ? D A J EJ+ @ A - * / ! #% ' ! &! $$ %$ "!. A A @ > = ? A L A H + @ A - * / * B H$ JH= L A & !$ %! %$ "!! # ' ! & ! # ". A A @ > = ? A L A H + @ A - * / ) B H& % JH= L A $ %$ "F EA ? A I+ = H H EA H > JB H? A ? JE J L = L A I JA & ! '% & % #% &!


! # %22 <strong>SRD960</strong> PSS EVE0109 A-(en)DIMENSIONS – Attachment to rotary actuators acc. to VDI/VDE 3845Attachment diagram of bracket: 44"' # "# #&! 4" N$ # $ &% $ %# ' %# !" %" # & ": " ! '$ # $Delivery of bracket by manufacturer of actuatoror see EBZG -C1, -C2 or -C3


PSS EVE0109 A-(en) <strong>SRD960</strong> 23DIMENSIONS! &! & # # '! &N & N & N ! ' @ A A F " # # # % ! # # ' # # " E " " ' $ " N $ N $ N ! ' @ A A F ! ' # # " ' " % " ' % ! & ' % ## ' %' $ ! &N & " ! ! " # # & " % !$ " "


24 <strong>SRD960</strong> PSS EVE0109 A-(en)Additional Documentation for this productTechnical Information of Attachment Kits for <strong><strong>Position</strong>er</strong>s:TI EVE0011 A Overview of Attachment Kits of all positioners on actuators/valves of different manufacturersQuick Guide:QG EVE0109 A Extract of Master Instruction for an easy to use, easy understandable and fast start-up.This document highlights the most important.Master Instructions:MI EVE0109 A <strong>SRD960</strong> –HART and -FoxComMI EVE0109 D <strong>SRD960</strong> -PROFIBUS-PA and -FOUNDATION Fieldbus H1Technical Information for Fieldbus-Communication:TI EVE0109 P SRD991/960 -PROFIBUS-PATI EVE0109 Q SRD991/960 -FOUNDATION Fieldbus H1Master Instruction for HART-Communication:MI EVE0105 B HART with Hand-Held TerminalMaster Instruction for configuration- and operation-software PC20 and integration into Foxboro I/A Series System:MI 020-495 HART / FoxCom / PROFIBUS-PA und IRCOM with PC by means of PC20/ IFDCB 0193 VH I/A Series SystemAdditional Documentation for other productsProduct SpecificationsPSS EVE0105 A-(en) SRD991 Intelligent <strong><strong>Position</strong>er</strong>PSS EVE0107 A-(en) SRI990 Analog <strong><strong>Position</strong>er</strong>PSS EVE0102 A-(en) SRI986 Electro-Pneumatic <strong><strong>Position</strong>er</strong>PSS EVE0103 A-(en) SRI983 Electro-Pneumatic <strong><strong>Position</strong>er</strong>- explosion proof or EEx d versionPSS EVE0101 A-(en) SRP981 Pneumatic <strong><strong>Position</strong>er</strong>PSS EMO0100 A-(en) Accessories for devices with HART ProtocolSubject to alterations - reprinting, copying and translation prohibited. Products and publications are normallyquoted here without reference to existing patents, registered utility models or trademarks. The lack of any suchreference does not justify the assumption that a product or symbol is free.FOXBORO ECKARDT GmbHPostfach 50 03 47D-70333 StuttgartTel. # 49(0)711 502-0Fax # 49(0)711 502-597http://www.foxboro-eckardt.comhttp://www.foxboro.com/instrumentation DOKT 533 495 117