earings, contacts, etc The electricians apparently refused to use It<br />

Panametrics Ultrasonic Flow Meter<br />

They recently received the Panametrlcs two-channel ultrasonic flow meter and training on<br />

how to use It The technical specialist has studied the manual and plans to use It for<br />

measuring mazut<br />

Fluke Power Harmonics Analyzer<br />

The Fluke power analyzer IS being used for measurements only In secondary Circuits up<br />

to 100V, 0 2, 0 3, 0 5 amp A more SUitable application would be In primary Circuits It has<br />

been useful for preparing current phase diagrams and use In HV sWltchyard CirCUits for<br />

checking measurements from current and voltage transformers<br />

They know that harmOniCs from large motors are a serious problem and the Fluke would<br />

be a valuable Instrument for analYZing, but It IS not the responsibility of their de<strong>part</strong>ment<br />

Instromet Encal Gas Chromatograph<br />

The Instromet gas chromatograph has not yet been Installed because of financial<br />

problems, and trying to deCide where It should be located They said there IS no space In<br />

the natural gas metering substation control house, and have deCided to remodel a secure<br />

room near Unit 2 They have a contract With another organization to Install about 50m of<br />

sample line from the main gas distribution line to bOiler room They Will raise walls to<br />

ceiling to enclose room and proVide insulation They were asked where they Will vent<br />

sample and calibration gases to atmosphere and where KCal output Signal would be<br />

Integrated With meter station flow, pressure and temperature logging on computer They<br />

do not yet know The Instrument and accessories are stili packed In boxes and It IS<br />

questionable If equipment Will be Installed and commissioned by the end of August<br />

Zirtek Boiler Oxygen Analyzers<br />

The two Zirtek oxygen probes are Installed on Unit 3 bOIler angled downward above a<br />

burner on each Side ThiS IS not a good location because of the pOSSibility of flame<br />

Impingement and high temperature and slag damage Zirtek engineer recommended<br />

location higher up In radiant section In fire box Recommended temperature range for<br />

ZirCOnium OXide cell long term performance IS 600 to about <strong>12</strong>00°C<br />

The reason probes were Installed on Unit 3 IS the fuel split IS about 90% coal, 5% gas and<br />

5% mazut and burner deSign results In unstable flame and IneffiCient combustion DUring<br />

the commiSSIOning test, oxygen was measured at 11-<strong>12</strong>% and 870-900°C The bOIler IS<br />

presently shut down for repairs<br />

5906-01102A18/31 197/Burshtyn