DESCRIPTION COST<br />

2. SIlica Analyzer necessary for measuring demIneralIzer $9,000<br />

performance and quality of water beIng fed to bOIlers.<br />

SilIca In steam gOIng to turbInes will cause serious<br />

damage to blades.<br />

3. 011 Analyzer (laboratory) used for detectIng orgamcs $8,000<br />

breakthrough from makeup water treatment carbon<br />

filters before demineralizers. Hydrocarbon<br />

contamInatIon of demIneralIzer resins can cause<br />

irreparable damage and reduction of capacIty reqUIred<br />

for boiler feedwater makeup.<br />

4. Dissolved Oxygen Probes (feedwater) a speCIfic IOn $26,400<br />

oxygen probe analyzer is needed for contInUOUS<br />

monitoring for control of dIssolved oxygen In feedwater<br />

to each boiler between 50-250 ppb. ($2,200 each x<br />

<strong>12</strong>).<br />

5. Oxygen Analyzer (laboratory) as a lower cost alternate $2,500<br />

to onlIne monitoring, a modern portable oxygen<br />

analyzer can be used manually to obtaIn faster and<br />

more accurate readIngs than present.<br />

6. Conductivity and pH Meter (laboratory) used for testing $1,000<br />

water quality at water treatment, feedwater and<br />

condensate systems.<br />

7. Level Gauges for Four Mazut Tanks Important for $10,000<br />

measunng deliveries and consumptIon of fuel.<br />

8. CalIbratIOn Gases and MaIntenance for Zeigler CEM $6,000<br />

on No.3 Stack for measunng emissions from Umts 1,<br />

4, 9, 10, 11, <strong>12</strong><br />

9. Distributed Control System for Reconstructed Umt $350,000<br />

required for upgrading and automatIng combustIOn<br />

control system to comply with regulations for flame<br />

safety, as well as improvement of combustIon<br />

effiCIency as a result of automatIc control of fan<br />

dampers for combustiOn aIr and control valves for fuel<br />

to meet load. More rapid response to load changes WIll<br />

result In stable and effiCIent combustIOn whIch help<br />

lower maIntenance costs.<br />

10. Water Treatment Resins for DemineralIzers Required $1,500,000<br />

for making high quality makeup water for boilers to<br />

prevent damage, as well as to minimize chemical<br />

consumptIOn and discharge of regenerant waste.<br />

5906-01/02A/BURSHTYN/5f17/95 17