The Infrared thermometer was used up until SIX months ago to find problems, but batterres<br />
died and they cannot find 2 Hrvlna ($1 10) to buy four new ones The electrrclan used It<br />
to check a large "fuse" on a transmiSSion tower which was overheating from a short CircUit<br />
and could have been a serrous safety InCident They used It to check insulation and covers<br />
on bOIler burners They also used It to find and repair insulation on steam lines from<br />
bOIlers They did not seem to be aware of other uses for checking temperatures of motors,<br />
bearrngs, contacts, etc The electrrclans apparently refused to use It<br />
They recently received the Panametncs two-channel ultraSOnic flow meter and training on<br />
how to use It. The technical specialist has studied the manual and plans to use It for<br />
measunng mazut<br />
The Fluke power analyzer IS being used for measurements only In secondary CirCUits up<br />
to 100V, 02,03,05 amp A more sUitable application would be In pnmary Circuits It has<br />
been useful for preparrng current phase diagrams and use In HV sWltchyard CirCUits for<br />
checking measurements from current and voltage transformers<br />
They know that harmOniCs from large motors are a serrous problem and the Fluke would<br />
be a valuable Instrument for analyzmg, but it is not the responsibility of their de<strong>part</strong>ment<br />
The Instromet gas chromatograph has not yet been Installed because of finanCial<br />
problems, and trying to deCide where It should be located They said there IS no space In<br />
• the natural gas meterrng substatIon control house, and have deCIded to remodel a secure<br />
room near Unit 2 They have a contract With another organization to Install about 50m of<br />
sample line from the main gas dlstnbutlon line to bOiler room They Will raise walls to<br />
ceiling to enclose room and prOVide Insulation They were asked where they Will vent<br />
sample and calibration gases to atmosphere and where KCal output Signal would be<br />
• mtegrated With meter station flow, pressure and temperature logging on computer They<br />
do not yet know The Instrument and accessones are stili packed In boxes and It IS<br />
questionable If eqUipment Will be Installed and commissioned by the end of August<br />
The two Zirtek oxygen probes are Installed on Unit 3 bOiler angled downward above a<br />
• burner on each Side ThiS IS not a good location because of the pOSSibility of flame<br />
Impingement and high temperature and slag damage Zirtek engineer recommended<br />
location higher up In radiant section In fire box Recommended temperature range for<br />
ZirCOnium OXide cell long term performance IS 600 to about <strong>12</strong>00°C<br />
• The reason probes were Installed on Unit 3 IS the fuel split IS about 90% coal, 5% gas and<br />
5% mazut and burner deSign results In unstable flame and IneffiCient combustion Dunng<br />
the commissIoning test, oxygen was measured at 11-<strong>12</strong>% and 870-900 o e The bOiler IS<br />
presently shut down for repairs<br />
•<br />
•<br />
Some of the experts wanted to Install probes the same way at all 16 burners Our<br />
ImpreSSion IS that they do not want to relocate the probes higher In the furnace<br />
13