The Infrared thermometer was used up until SIX months ago to find problems, but batterres<br />

died and they cannot find 2 Hrvlna ($1 10) to buy four new ones The electrrclan used It<br />

to check a large "fuse" on a transmiSSion tower which was overheating from a short CircUit<br />

and could have been a serrous safety InCident They used It to check insulation and covers<br />

on bOIler burners They also used It to find and repair insulation on steam lines from<br />

bOIlers They did not seem to be aware of other uses for checking temperatures of motors,<br />

bearrngs, contacts, etc The electrrclans apparently refused to use It<br />

They recently received the Panametncs two-channel ultraSOnic flow meter and training on<br />

how to use It. The technical specialist has studied the manual and plans to use It for<br />

measunng mazut<br />

The Fluke power analyzer IS being used for measurements only In secondary CirCUits up<br />

to 100V, 02,03,05 amp A more sUitable application would be In pnmary Circuits It has<br />

been useful for preparrng current phase diagrams and use In HV sWltchyard CirCUits for<br />

checking measurements from current and voltage transformers<br />

They know that harmOniCs from large motors are a serrous problem and the Fluke would<br />

be a valuable Instrument for analyzmg, but it is not the responsibility of their de<strong>part</strong>ment<br />

The Instromet gas chromatograph has not yet been Installed because of finanCial<br />

problems, and trying to deCide where It should be located They said there IS no space In<br />

• the natural gas meterrng substatIon control house, and have deCIded to remodel a secure<br />

room near Unit 2 They have a contract With another organization to Install about 50m of<br />

sample line from the main gas dlstnbutlon line to bOiler room They Will raise walls to<br />

ceiling to enclose room and prOVide Insulation They were asked where they Will vent<br />

sample and calibration gases to atmosphere and where KCal output Signal would be<br />

• mtegrated With meter station flow, pressure and temperature logging on computer They<br />

do not yet know The Instrument and accessones are stili packed In boxes and It IS<br />

questionable If eqUipment Will be Installed and commissioned by the end of August<br />

The two Zirtek oxygen probes are Installed on Unit 3 bOiler angled downward above a<br />

• burner on each Side ThiS IS not a good location because of the pOSSibility of flame<br />

Impingement and high temperature and slag damage Zirtek engineer recommended<br />

location higher up In radiant section In fire box Recommended temperature range for<br />

ZirCOnium OXide cell long term performance IS 600 to about <strong>12</strong>00°C<br />

• The reason probes were Installed on Unit 3 IS the fuel split IS about 90% coal, 5% gas and<br />

5% mazut and burner deSign results In unstable flame and IneffiCient combustion Dunng<br />

the commissIoning test, oxygen was measured at 11-<strong>12</strong>% and 870-900 o e The bOiler IS<br />

presently shut down for repairs<br />

•<br />

•<br />

Some of the experts wanted to Install probes the same way at all 16 burners Our<br />

ImpreSSion IS that they do not want to relocate the probes higher In the furnace<br />

13