C A T A L O G U E4.3<strong>Electronics</strong> – <strong>Power</strong> <strong>Supplies</strong><strong>Electronics</strong> – <strong>Power</strong> <strong>Supplies</strong>Switch-mode power suppliesUnregulated power suppliesUPS control unitFuse protection for 24 V DC circuitsIP 65 switched-mode power supply / Electrical-cabinet socket outletABCDEAppendixWeidmüller ServiceGlossary/Technical appendixIndexSearch according to type or order number, Addresses worldwideVWXI


Product overview<strong>Power</strong> supplies – Overviewconnect<strong>Power</strong> 1ph PRO-Mconnect<strong>Power</strong> 3ph PRO-Mconnect<strong>Power</strong> PRO-MExtension modules• Single-phase switched-mode powersupply modules, very thin design• High degree of efficiency• <strong>Power</strong> category 70...1,000 W• Up to five devices can be connectedin parallel without a diode module• International approvals• 3-phase switched-mode power supplymodules, very thin design• High degree of efficiency• <strong>Power</strong> category 120...1,000 W• Up to five devices can be connectedin parallel without a diode module• International approvals• Capacity module for increasing thepeak current• Diode modules for redundantconstruction• Relay module for monitoring the outputvoltageconnect<strong>Power</strong> PRO-MApplication solutions connect<strong>Power</strong> 1ph PRO-H connect<strong>Power</strong> 3ph PRO-H• Wide-range input85...264 V AC80...430 V DC• Alarm relay• Metal snap-on foot• International approvals• Single-phase switch-mode powersupplies• High MTBF values• Cl. I Div. 2 + ATEX• Performance class: 70 to 600 W• Output: 12, 24, 36 and 48 V DCSimilar toillustration• 3-phase switch-mode power supplies• High MTBF values• Cl. I Div. 2 + ATEX• Performance class: 480/960 Wconnect<strong>Power</strong> PRO-HMulti-phaseconnect<strong>Power</strong> PRO-HRedundancy modulesconnect<strong>Power</strong> 1ph ECOLINESimilar toillustration• Multi-phase switch-mode powersupplies• 85...132 / 187...550 V AC• UL approval• Performance class: 180 to 600 W• 15 A or 25 A• 100 % load sharing• Remote On/Off• International approvals• Cl. I Div. 2 + ATEX• Single-phase switched-mode powersupply modules• Compact form• Metal housing• <strong>Power</strong> category 70…1,000 W• International approvalsII


Product overviewconnect<strong>Power</strong> 3ph ECOLINEconnect<strong>Power</strong> ECOLINEDiode modulesconnect<strong>Power</strong> 1ph INSTAPOWER• 3-phase switched-mode power supplymodules• Compact form• Metal housing• <strong>Power</strong> category 120…1,000 W• International approvals• Diode module for 100 % decoupling ofswitched-mode power supply modules• Optimum doubling of output power• Redundancy operation• Up to 40 A output current can be set• International approvals• Single-phase switched-mode powersupply modules for the distribution board• Compact form• <strong>Power</strong> category 24 and 48 W• Universal input and output voltage5…48 V• International approvalsconnect<strong>Power</strong> 1ph WAVEPOWER connect<strong>Power</strong> 1ph connect<strong>Power</strong> 3ph• Single-phase switched-mode powersupply unit• Slim design 22.5 mm• <strong>Power</strong> category 12 W• International approvalsconnect<strong>Power</strong> DC/DC converters• Single-phase switched-mode powersupply modules• Metal housing• <strong>Power</strong> category 55 W and 160 W• Universal input and output voltage 5…48 V• International approvals• 300-watt performance category, with active PFCcompact<strong>Power</strong> 1phunregulated power supplies• 3-phase switched-mode power supply modules• Metal housing• Up to 5 devices can be directlyconnected in parallel• Professional display and processingof` all relevant signal states• International approvalscompact<strong>Power</strong> 3phunregulated power supplies• Compact form• Metal housing• Universal input and output voltage of5 V to 48 V• International approvals• Single-phase unregulated powersupplies• Compact form• Standard voltage ~230/400 V toIEC38 +/– 15 V tap• Reliable short-circuit and overloadprotection• 3-phase unregulated power supplies• Compact form• Nominal voltage to IEC38 +/- 5 V tap• Reliable short-circuit and overloadprotectionIII


Product overview<strong>Power</strong> supplies – Overviewconnect<strong>Power</strong>UPS control unitWAVEGUARDField<strong>Power</strong> ®IP 65 switched-mode power supply• Uninterruptible power supplies• Battery control module• Ideal for charging 12 V and 24 Vbatteries• Professional display and processingof all relevant signal states• International approvalsElectrical-cabinet socket outlet• Electronic fusing• Visual fault indication and potential-freecontact• Reset input• Compact form• 3-phase switch-mode power supply unit, 24 V / 5 Aon Field<strong>Power</strong> ® power bus, 5 x 2.5...6 mm²• Integrated input fuse• Decentralised 24 V DC generation anddistribution for widely distributed facilities• Reduced voltage drops in DC systems• Increased energy efficiency because ofminimal transmission losses• Simple installation in electrical cabinet• TS 35 module can be rail mounted• VDE mark of conformity• Two-pole with earthing contactIV


Product overviewV


Product overview<strong>Power</strong> supplies – SelectionPRO-MMains1phInput voltage85...265 V AC,80...370 V DCInput frequency50 / 60 HzCE, cURus, cULus;C-Tick, GLOutput voltage24 VOutput current 3 A 5 A 7.5 A 10 A 20 AOrder-No. 8951330000 8951340000 8951350000 8951360000 8951370000Page A.5 A.5 A.6 A.6 A.7PRO-M expansion modulesMains1phInput voltage85...265 V AC,80...430 V DC,Input frequency50 / 60 HzCE, cURus*, cULus;C-TrickGL (in preparation)Output voltage Diode module Diode module Relay module Capacity moduleOutput current 20 A 40 AOrder-No. 1222210000 1222220000 1222230000 1222240000Page A.10 A.10 A.11 A.12PRO-HMains1phInput voltage85...264 V AC,85...132 / 187...265 V AC(Depending on model)Input frequency50 / 60 HzCE; UL; CSA; Class IDiv.2; ATEX Zone 2(Depending on model)Output voltage 12 V 12 V 24 VSimilar to illustration24 V 24 V 24 VOutput current 6 A 12 A 3.8 A 3.8 A (CL 2) 7.5 A 15 AOrder-No. 1105430000 1105440000 1105790000 1194410000 1105810000 1105820000Page A.17 A.17 A.18 A.18 A.19 A.19VI


Product overviewPRO-MMains1ph / 3phInput voltage85...265 V AC,120...300 V DCInput frequency50 / 60 HzCE, cURus, cULus;C-TickOutput voltage 1ph / 24 V 3ph / 24 VOutput current 40 A 5 A 10 A 20 A 40 AOrder-No. 8951380000 8951390000 8951400000 8951410000 8951420000Page A.7 A.8 A.8 A.9 A.9PRO-M application solutionsMains1phInput voltage85...265 V AC,80...430 V DC,Input frequency50 / 60 HzCE, cURus*, cULus;C-TrickGL (in preparation)Output voltage24 VOutput current10 AOrder-No. 1165480000Page A.15PRO-HMains1phInput voltage85...264 V AC,85...132 / 187...265 V AC(Depending on model)Input frequency50 / 60 HzCE; UL; CSA; Class IDiv.2; ATEX Zone 2(Depending on model)Similar to illustration Similar to illustration Similar to illustrationOutput voltage 24 V 36 V 48 V 48 V 48 V 48 VOutput current 25 A 16.5 A 2 A 4 A 7.5 A 12.5 AOrder-No. 1105840000 1194430000 1194420000 1105850000 1105860000 1105870000Page A.20 A.20 A.21 A.21 A.22 A.22VII


Product overview<strong>Power</strong> supplies – SelectionPRO-HMains3phInput voltage*400...500 V AC,*100...500 V AC*Depending on modelInput frequency50 / 60 HzCE; UL; UR;*ATEX*Depending on model Similar to illustration Similar to illustration Similar to illustration Similar to illustrationRated input voltage 400 V 500 V 400 V 500 VOutput voltage 24 V 24 V 24 V 24 VOutput current 20 A 20 A 40 A 40 AOrder-No. 1194440000 1194450000 1194460000 1194470000Page A.23 A.23 A.24 A.24PRO-H redundancy moduleMains1phInput voltage85...265 V AC,120...300 V DC,110...370 V DC*Input frequency50 / 60 HzCE, UL, UR, Class IDiv.2; ATEX*Not all modelsOutput voltage 24 V 24 VOutput current 15 A 20 AOrder-No. 1105880000 1105890000Page A.27 A.27INSTAPOWERMains1phInput voltage85...265 V AC,120...300 V DC,110...370 V DC*Input frequency50 / 60 HzCE, cURus*, cULus;*Not all modelsclass 2 class 2Output voltage 5 V 12 VOutput current 2 A 5 A 1.5 A 4 AOrder-No. 9928890005 8754960000 9928890012 8754970000Page A.42 A.43 A.41 A.44VIII


Product overviewPRO-HMains1ph/2phInput voltage*400...500 V AC,*100...500 V AC*Depending on modelInput frequency50 / 60 HzCE; UL; UR;*ATEX*Depending on modelRated input voltageSimilar to illustration Abb. ähnlich100...500 V ACSimilar to illustration100...500 V ACSimilar to illustration100...500 V ACOutput voltage 24 V 24 V 24 VOutput current 7.5 A 15 A 25 AOrder-No. 1194480000 1194490000 1194310000Page A.25 A.25 A.26INSTAPOWERMains1phInput voltage85...265 V AC,120...300 V DC,110... 370 V DCInput frequency50 / 60 HzCE, cURus*, cULus;GS**Not all modelsclass 2 class 2Output voltage 15 V 24 V 28 V 48 VOutput current 1.5 A 1 A 2 A 1 A 1 AOrder-No. 9928890015 9928890024 8739140000 9928890028 8879230000Page A.41 A.40 A.45 A.40 A.46IX


Product overview<strong>Power</strong> supplies – Selectionconnect<strong>Power</strong>Mains1phInput voltage85...265 V AC*,120...300 V DC*Input frequency50 / 60 HzCE, UR / UL, CSA*Not all modelsOutput voltage 5 V 15 V 24 VOutput current 3 A 8 A 3 A 8 A 2.3 AOrder-No. 9927480005 9925340005 9927480012 9925340012 9927480024Page A.49 A.51 A.49 A.51 A.48ECOLINEMains1phInput voltage90...265 V ACInput frequency50 / 60 HzPartially switchablefrom 115 / 230 V ACCE, cURus*, cULus*;GL*, GOST*Not all modelsOutput voltage24 VOutput current 3 A 5 A 10 A 20 A 40 AOrder-No. 8708660000 8708670000 8708680000 8778870000 8862780000Page A.30 A.31 A.32 A.33 A.34ECOLINE diode modules40 V DC max.CE, cURus, cULus;GOSTOutput voltage40 VOutput current 2 x 10 A 2 x 20 AOrder-No. 8710620000 8768650000Page A.39 A.39X


Product overviewconnect<strong>Power</strong>Mains1ph / 3phInput voltage85...265 V AC*,120...300 V DC*Input frequency50 / 60 HzCE, UR / UL, CSA*Not all modelsOutput voltage 1ph / 24 V 1ph / 48 V 3ph / 24 VOutput current 6.5 A 12.5 A 1.04 A 3.5 A 2.3 AOrder-No. 9925340024 9916250024 9927480048 9925340048 9917790324Page A.50 A.52 A.48 A.50 A.53ECOLINEMains3phInput voltage3x 340...575 V AC,Input frequency50 / 60 HzCE, cURus, cULus;GL*, GOST*Not all modelsOutput voltage24 VOutput current 5 A 10 A 20 A 40 AOrder-No. 8862730000 8708700000 8708710000 8708730000Page A.35 A.36 A.37 A.38WAVEPOWERMains1ph85...264 V AC120...300 V DCCE, UL, CSAOutput voltage24 VOutput current0.5 AOrder-No. 9918840024Page A.47XI


Product overview<strong>Power</strong> supplies – Selectionconnect<strong>Power</strong> DC/DC converterInput voltage9...16 V DCCE, UL / UR, CSA,Class 1, Div.2Output voltage 12 V 15 V 24 VOutput current 3 A 3 A 2 AOrder-No. 9919371212 9919371215 9919371224Page A.55 A.55 A.55compact<strong>Power</strong> 1ph unregulated power suppliesMains1phInput voltage230 V / 400 V ± 15 VInput frequency50 / 60 HzCE, cURus, cULusOutput voltage24 VOutput current 1.5 A 3 A 6 A 8 A 11 A 18 AOrder-No. 8575260000 8575270000 8575280000 8575300000 8575310000 8575320000Page B.4 B.4 B.5 B.5 B.6 B.6WAVEGUARDwithscrew connectionRated voltage24 V DCCE, cURusOutput voltage24 VOutput current 1.6 A 3.15 A 6.3 A 8 A 0.5...5 AOrder-No. 8618890000 8618910000 8618930000 8618940000 8710270000Page D.4 D.4 D.5 D.5 D.6XII


Product overviewconnect<strong>Power</strong> DC/DC converterInput voltage18...30 V DCCE, UL / UR, CSA,Class 1, Div.2Output voltage 5 V 12 V 15 V 24 VOutput current 8 A 3 A 3 A 2 AOrder-No. 9919372405 9919372412 9919372415 9919372424Page A.56 A.56 A.54 A.54compact<strong>Power</strong> 3ph unregulated power suppliesMains3phInput voltage3x 400 V ± 5 %Input frequency50 / 60 HzCE, cURus, cULusOutput voltage24 VOutput current 11 A 18 A 22 A 26 A 32 A 42 AOrder-No. 8628620000 8628630000 8628650000 8628660000 8628670000 8628680000Page B.7 B.7 B.8 B.8 B.9 B.9WAVEGUARDwith tensionclamp connectionRated voltage24 V DCCE, cURusOutput voltage24 VOutput current 1.6 A 3.15 A 6.3 A 8 A 0.5...5 AOrder-No. 8621040000 8621030000 8621020000 8621010000 8727630000Page D.4 D.4 D.5 D.5 D.6XIII


Product overview<strong>Power</strong> supplies – SelectionUPS control unitMains1ph85...265 V AC120...300 V DCInput frequency50 / 60 HzCE, UR / UL, CSAOutput voltage 12 V 24 VOutput current max. 15 A max. 15 AOrder-No. 9916280012 9916280024Page C.3 C.4Field<strong>Power</strong> ® IP 65 switched-mode power supplyMains3phInput voltage400 V ACOutput voltage 24 V 24 VOutput current 5 A 5 AOrder-No. 1132320000 1101940000Page E.4 E.5Electrical-cabinet socket outletEarthed socketoutlet for theTS35 mounting railVDEOutput voltage250 V ACOutput current16 AOrder-No. 8734580000Page E.13XIV


Switch-mode power suppliesContentsSwitch-mode power suppliesSwitch-mode power supplies Overview A.2connect<strong>Power</strong> PRO-M A.4Aconnect<strong>Power</strong> PRO-H A.16connect<strong>Power</strong> ECOLINE A.30connect<strong>Power</strong> INSTAPOWER A.40connect<strong>Power</strong> WAVEPOWER A.47connect<strong>Power</strong> A.48connect<strong>Power</strong> DC/DC converter A.54A.1


Switch-mode power suppliesSwitch-mode power supplies – OverviewSwitch-mode power suppliesAThe switch-mode power supplies feature a high degree ofefficiency, compact dimensions and minimal heat generation.They are an excellent, reliable solution for providing power in allautomation applications – safely providing 24 V DC voltage.The different product series are optimised for the automationindustry: they feature Ex approvals for the processing industry, aflat shape perfect for distribution tasks within buildings, orprovide decentralised control voltages.be used reliably in all applications because of their highefficiency and their resistance to both short circuits andoverloads.Especially for the PRO-M family, Weidmüller offers a system ofone- and three-phase switch-mode power supplies that can beexpanded with additional modules to create system solutions.The proper system can be assembled for any applications: withredundancy circuits with decoupled outputs, monitoring of theoutput voltage or triggering of circuit breakers.All-purpose usage: with a wide range of AC/DC inputs, single-,double- or three-phase versions, and a wide temperature range.Additional performance increases are possible using a simpleparallel circuitry. Weidmüller switch-mode power supplies canA.2


Switch-mode power supplies – OverviewSwitch-mode power suppliesAC / DCInternational useThanks to wide-range input (both DCas well as AC voltages can be used; noswitching required) and extensiveapprovals (UL/CSA and GL(EMC 1 – bridge)).Parallel connectionAModule power can be increased byconnecting upto five power supplies inparallel without diode module.connect<strong>Power</strong>connect<strong>Power</strong> PRO-MNarrowfrom 33 mmSpace-saving configuration in theswitching cabinet through very narrowhousing construction and side-by-sideconnectability.connect<strong>Power</strong> PRO-H+70 °Cto–25 °CRobustWide temperature range from–25 °C … +70 °C.Wide choiceThe right power supply for everyapplication: 1-phase 3 A, 5 A, 7.5 A, 10 A,20 A, 40 A and 3-phase 5 A, 10 A, 20 A,40 A.connect<strong>Power</strong> ECOLINEconnect<strong>Power</strong> INSTAPOWERconnect<strong>Power</strong> WAVEPOWERconnect<strong>Power</strong>connect<strong>Power</strong> DC/DC convertersA.3


Switch-mode power suppliesconnect<strong>Power</strong> PRO-Mconnect<strong>Power</strong>PRO-MAL (+)N (–)PETwo-Phase operation also possibleL1 (+)L2 (–)L3PEACACDCDCPermissible maximum continuous current [A]Max. limiting average on state current [A]Type\Temp. 45°C 50°C 55°C 60°C 65°C 70°C1ph 24V / 3A 3.6 3.4 3.2 3 2.6 2.31ph 24V / 5A 6 5.7 5.3 5 4.4 3.81ph 24V / 7.5A 9 8.5 8 7.5 6.6 5.61ph 24V / 10A 12 11.3 10.7 10 8.8 7.51ph 24V / 20A 24 22.7 21.3 20 17.5 151ph 24V / 40A 48 45.3 42.7 40 35 303ph 24V / 5A 6 5.7 5.3 5 4.4 3.83ph 24V / 10A 12 11.3 10.7 10 8.8 7.53ph 24V / 20A 24 22.7 21.3 20 17.5 153ph 24V / 40A 48 45.3 42.7 40 35 30+–+–Technical dataGeneral technical dataCurrent limiting> 120 % I NAmbient temp. operating / storage temperature –25 °C … +70 °C / –40 °C … +85 °CMax. perm. air humidity (operation)5 %…95 % RHDegree of protectionIP20Class of protectionI, with PE connectionOvervoltage categoryIIPollution degree 2Insulation voltage3 kV I/O / 2 kV I/earth / 0.5 kV O/earthMTBF> 500,000 h acc. to IEC 1709 (SN29500)Protection against reverse voltages from the load30…35 V DCParallel connection optionyes, without diode moduleHousing versionmetal, corrosion resistantIndicationoperation, green LEDMounting position, installation noticehorizontal on mounting rail TS35, 50 mm spacing top and bottom for freeair circulation, can be mounted side by side with no space in betweenEMC / shock / vibrationNoise emission acc. to EN55022Class BNoise immunity tests acc. toEN61000-4-2 (ESD), EN61000-4-3 und EN61000-4-8 (Fields),EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6 (conducted),EN61000-4-11 (Dips)Limiting of mains voltage harmonic currents Acc. to EN 61000-3-2Resistance against vibration and shockAcc. to EN50178, shock: 5g in all directionsElectrical safety (applied standards)Electrical equipment of machinesAcc. to EN60204Safety transformers for switched-mode power unitsAcc. to EN61558-2-17Machinery with electronic equipmentAcc. to EN50178 / VDE0160Safety extra-low voltageSELV acc. to EN60950, PELV acc. to EN60204Protective separation / protection against electrical shock VDE0100-410 / acc. to DIN57100-410Protection against dangerous shock currentsAcc. to VDE0106-101Project-planning dataType 24 V / 3 A 24 V / 5 A 24 V / 7.5 A 24 V / 10 A 24 V / 20 A 24 V / 40 A 24 V / 5 A 24 V / 10 A 24 V / 20 A 24 V / 40 A1 - phase 3 - phaseRated input voltage 100...240 V AC 3 x 400...500 V ACMains voltage range 85...264 V AC 3 x 320...575 V ACMains input current 1.3...0.6 A 2.1...0.9 A 2.1...0.9 A 2.8...1.2 A 5.6...2.4 A 11.1...4.7 A 0.3...0.28 A 0.55...0.5 A 1.0...0.9 A 2.5...2.0 ARec. fuse [char..] 2 A / D I / II 4 A / D I / II 6 A / D I / II 6 A / D I / II 10 A / D I / II 16 A / D I / II 2 A / D I / II 2 A / D I / II 2 A / D I / II 4 A / D I / II6 A, [B] 6 A, [B] 10 A, [B] 10 A, [B] 20 A, [B] 25 A, [B] - - - 10 A, [B]2...4 A, [C] 3...5 A, [C] 5...10 A, [C] 5...10 A, [C] 10...12 A, [C] 14...16 A, [C] 1...2 A, [C] 2...3 A, [C] 3...5 A, [C] 6...8 A, [C]Efficiency @ 230 V AC, @ 3x400 V AC 90 % 90 % 91 % 90 % 90 % 91 % 90 % 90 % 90 % 91 %Rated power loss [W] 8 W 13 W 18 W 27 W 53 W 95 W 13 W 27 W 53 W 95 WInstallation width mm 33 40 50 60 121 180 40 60 121 180Input terminalsScrew connectionConductor, solid min/max mm 2 0.5...6 0.5...6 0.08...4 0.5...6 0.5...6Conductor, flexible min/max mm 2 0.5...2.5 0.5...2.5 0.5...2.5 0.5...2.5 0.5...2.5Conductor, AWG/kcmil min/max 26 / 12 26 / 10 28 / 12 26 / 12 26 / 12Output terminalsScrew connectionNumber plus/minus 2 / 2 2 / 3Conductor, solid min/max mm 2 0.5...6 0.5...6 0.5...16 0.5...6 0.5...6 0.5...16Conductor, flexible min/max mm 2 0.5...2.5 0.5...2.5 2.5...10 0.5...2.5 0.5...2.5 2.5...10Conductor, AWG/kcmil min/max 26 / 12 26 / 10 22 / 6 26 / 12 26 / 10 22 / 6A.4


connect<strong>Power</strong>PRO-MCP M SNT 70 W 24 V 3 ACP M SNT 120 W 24 V 5 Aconnect<strong>Power</strong> PRO-MSwitch-mode power suppliesALHL (+)N (–)PEACDC+–L (+)N (–)PEACDC+–WWith DC connection, note polarityWith DC connection, note polarityTechnical dataInputrated input voltageInput voltage range ACFrequency range ACDC input voltage rangeAC current consumptionDC current consumptionInput fuse (internal) / making currentRecommended back-up fuse*)100...240 V AC (wide-range input)85…264 V AC (Derating @ 100 V AC: 2.5 % / V)47...63 Hz80…370 V DC (Derating @ 120 V DC: 1 % / V)0.6 A @ 230 V AC / 1.1 A @ 115 V AC0.25 A @ 370 V DC / 0.7 A @ 120 V DCYes / max. 40 A2 A / DI, safety fuse100...240 V AC (wide-range input)85…264 V AC (Derating @ 100 V AC: 2.5 % / V*)47...63 Hz80…370 V DC (Derating @ 120 V DC: 1 % / V)1.1 A @ 230 V AC / 2.0 A @ 115 V AC0.4 A @ 370 V DC / 1.2 A @ 120 V DCYes / max. 40 A4 A / DI, safety fuse6 A, Char. B, circuit breaker6 A, Char. B, circuit breakerOutputrated output voltageOutput voltageresidual ripple, breaking spikesRated (nominal) output current @ U Nomcontinous output current @ 24 V DC<strong>Power</strong>boost @ 24 V DC, 60 °CGeneral dataDegree of efficiency<strong>Power</strong> factor (approx.)AC failure bridging time @ I NomParallel connection optionLength x width x heightWeightApprovals2...4 A, Char. C, circuit breaker24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N3 A @ 60 °C3.6 A @ 45 °C, 3.2 A @ 55 °C, 2.3 A @ 70 °C3.6 A for 1 min, ED = 5 %90 % @ 230 V AC / 88 % @ 115 V AC> 0.6 @ 230 V AC / > 0,65 @ 115 V AC> 100 ms @ 230 V AC / > 20 ms @ 115 V ACyes, max. 5125 / 33 / 130 mm0.57 kg3...5 A, Char. C, circuit breaker24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N5 A @ 60 °C6.0 A @ 45 °C, 5.3 A @ 55 °C, 3.8 A @ 70 °C6 A for 1 min, ED = 5 %90 % @ 230 V AC / 88 % @ 115 V AC> 0.5 @ 230 V AC / > 0.6 @ 115 V AC> 100 ms @ 230 V AC / > 20 ms @ 115 V ACyes, max. 5125 / 40 / 130 mm0.7 kgCE; cURus; cULus; C-TickCE; cURus; cULus; C-TickConnection dataConductor connection systemNumber of terminalsWire cross-section, rigid min/maxWire cross-section, flexible min/maxWire cross-section, AWG/kcmil min/maxmm²mm²InputOutputScrew connectionScrew connection3 for L/N/PE 4 (++ / --)0.5 / 6 0.5 / 60.5 / 2.5 0.5 / 2.526 / 12 26 / 12InputOutputScrew connectionScrew connection3 for L/N/PE 5 (++ / ---)0.5 / 6 0.5 / 60.5 / 2.5 0.5 / 2.526 / 12 26 / 12Note*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!Ordering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP M SNT 70W 24V 3A 1 8951330000CP M SNT 120W 24V 5A 1 8951340000NoteAccessoriesA.5


Switch-mode power suppliesconnect<strong>Power</strong> PRO-Mconnect<strong>Power</strong>PRO-MCP M SNT 180 W 24 V 7.5 ACP M SNT 250 W 24 V 10 AALHL (+)N (–)PEACDC+–L (+)N (–)PEACDC+–WWith DC connection, note polarityWith DC connection, note polarityTechnical dataInputrated input voltageInput voltage range ACFrequency range ACDC input voltage rangeAC current consumptionDC current consumptionInput fuse (internal) / making currentRecommended back-up fuse100...240 V AC (wide-range input)85…264 V AC (Derating @ 100 V AC: 2.5 % / V)47...63 Hz80…370 V DC (Derating @ 120 V DC: 1 % / V)0.9 A @ 230 V AC / 1.8 A @ 115 V AC0.6 A @ 370 V DC / 1.7 A @ 120 V DCYes / max. 40 A6 A / DI, safety fuse100...240 V AC (wide-range input)85…264 V AC (Derating @ 100 V AC: 2.5 % / V)47...63 Hz80…370 V DC (Derating @ 120 V DC: 1 % / V)1.2 A @ 230 V AC / 2.4 A @ 115 V AC0.8 A @ 370 V DC / 2.3 A @ 120 V DCYes / max. 12 A4 A / DI,safety fuse10 A, Char. B, circuit breaker10 A, Char. B, circuit breakerOutputrated output voltageOutput voltageresidual ripple, breaking spikesRated (nominal) output current @ U Nomcontinous output current @ 24 V DC<strong>Power</strong>boost @ 24 V DC, 60 °CGeneral dataDegree of efficiency<strong>Power</strong> factor (approx.)AC failure bridging time @ I NomParallel connection optionLength x width x heightWeightApprovals6 A, Char. C, circuit breaker24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N7,5 A @ 60 °C9.0 A @ 45 °C, 8.0 A @ 55 °C, 5.6 A @ 70 °C9 A for 1 min, ED = 5 %91 % @ 230 V AC / 88 % @ 115 V AC> 0.94 @ 230 V AC / > 0.99 @ 115 V AC> 20 ms @ 230 V AC / > 20 ms @ 115 V ACyes, max. 5150 / 50 / 130 mm1.05 kg3...4 A, Char. C, circuit breaker24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N10 A @ 60 °C12 A @ 45 °C, 10.7 A @ 55 °C, 7.5 A @ 70 °C12 A for 1 min, ED = 5 %90 % @ 230 V AC / 87 % @ 115 V AC> 0.99 @ 230 V AC / > 0.97 @ 115 V AC> 20 ms @ 230 V AC / > 20 ms @ 115 V ACyes, max. 5150 / 60 / 130 mm1.2 kgCE; cURus; cULus; C-TickCE; cURus; cULus; C-TickConnection dataConductor connection systemNumber of terminalsWire cross-section, rigid min/maxWire cross-section, flexible min/maxWire cross-section, AWG/kcmil min/maxmm²mm²InputOutputScrew connectionScrew connection3 for L/N/PE 5 (++ / ---)0.5 / 6 0.5 / 60.5 / 2.5 0.5 / 2.526 / 12 26 / 12InputOutputScrew connectionScrew connection3 for L/N/PE 5 (++ / ---)0.5 / 6 0.5 / 60.5 / 2.5 0.5 / 2.526 / 12 26 / 12Note*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!Ordering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP M SNT 180W 24V 7,5A 1 8951350000CP M SNT 250W 24V 10A 1 8951360000NoteAccessoriesA.6


connect<strong>Power</strong>PRO-MCP M SNT 500 W 24 V 20 Aconnect<strong>Power</strong> PRO-MCP M SNT 1000 W 24 V 40 ASwitch-mode power suppliesALHL (+)N (–)PEACDC+–L (+)N (–)PEACDC+–WWith DC connection, note polarityWith DC connection, note polarityTechnical dataInputrated input voltageInput voltage range ACFrequency range ACDC input voltage rangeAC current consumptionDC current consumptionInput fuse (internal) / making currentRecommended back-up fuse100...240 V AC (wide-range input)85…264 V AC (Derating @ 100 V AC: 2.5 % / V)47...63 Hz80…370 V DC (Derating @ 120 V DC: 1 % / V)2.4 A @ 230 V AC / 4.8 A @ 115 V AC1.5 A @ 370 V DC / 4.6 A @ 120 V DCYes / max. 5 A6 A / DI, safety fuse100...240 V AC (wide-range input)85…264 V AC (Derating @ 100 V AC: 2.5 % / V)47...63 Hz80…370 V DC (Derating @ 120 V DC: 1 % / V)4.7 A @ 230 V AC / 9.6 A @ 115 V AC2.9 A @ 370 V DC / 9.1 A @ 120 V DCYes / max. 5 A16 A / DI, safety fuse16 A, Char. B, circuit breaker20 A, Char. B, circuit breakerOutputrated output voltageOutput voltageresidual ripple, breaking spikesRated (nominal) output current @ U Nomcontinous output current @ 24 V DC<strong>Power</strong>boost @ 24 V DC, 60 °CGeneral dataDegree of efficiency<strong>Power</strong> factor (approx.)AC failure bridging time @ I NomParallel connection optionLength x width x heightWeightApprovals6…8 A, Char. C, circuit breaker24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N20 A @ 60 °C24 A @ 45 °C, 22.7 A @ 55 °C, 15 A @ 70 °C24 A for 1 min, ED = 5 %90 % at 230 V AC / > 85 % at 115 V AC> 0.98 @ 230 V AC / > 0.99 @ 115 V AC> 20 ms @ 230 V AC / > 20 ms @ 115 V ACyes, max. 3150 / 121 / 130 mm2.2 kg16 A, Char. C, circuit breaker24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N40 A @ 60 °C48 A @ 45 °C, 42.7 A @ 55 °C, 30 A @ 70 °C48 A for 1 min, ED = 5 %91 % @ 230 V AC / 88 % @ 115 V AC> 0.99 @ 230 V AC / > 0.99 @ 115 V AC> 20 ms @ 230 V AC / > 20 ms @ 115 V ACyes, max. 3150 / 180 / 130 mm3.9 kgCE; cURus; cULus; C-TickCE; cURus; cULus; C-TickConnection dataConductor connection systemNumber of terminalsWire cross-section, rigid min/maxWire cross-section, flexible min/maxWire cross-section, AWG/kcmil min/maxmm²mm²InputOutputScrew connectionScrew connection3 for L/N/PE 5 (++ / ---)0.5 / 6 0.5 / 60.5 / 2.5 0.5 / 2.526 / 10 26 / 10InputOutputScrew connectionScrew connection3 for L/N/PE 5 (++ / ---)0.5 / 6 0.5 / 160.5 / 2.5 2.5 / 1026 / 10 22 / 6Note*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!Ordering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP M SNT 500W 24V 20A 1 8951370000CP M SNT 1000W 24V 40A 1 8951380000NoteAccessoriesA.7


Switch-mode power suppliesconnect<strong>Power</strong> PRO-Mconnect<strong>Power</strong>PRO-MCP M SNT3 120 W 24 V 5 ACP M SNT3 250 W 24 V 10 AALL1 (+)L2 (–)AC+L1 (+)L2 (–)AC+HL3PEDC–L3PEDC–WWith DC connection, note polarityTwo-phase operation also possibleWith DC connection, note polarityTwo-phase operation also possibleTechnical dataInputrated input voltageInput voltage range ACFrequency range ACDC input voltage rangeAC current consumptionDC current consumptionInput fuse (internal) / making currentRecommended back-up fuse3 x 400...3 x 500 V AC (wide-range input)3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC47...63 Hz450...800 V DC (max. 500 V DC acc. to UL508)0.28 A @ 3 x 500 V AC / 0.3 A @ 3 x 400 V AC0.18 A @ 800 V DC / 0.3 A @ 450 V DCNo / max. 50 A2 A / DI, safety fuse3 x 400...3 x 500 V AC (wide-range input)3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC47...63 Hz450...800 V DC (max. 500 V DC acc. to UL508)0.5 A @ 3 x 500 V AC / 0.55 A @ 3 x 400 V AC0.35 A @ 800 V DC / 0.6 A @ 450 V DCNo / max. 50 A2 A / DI, safety fuse2...3 A, Char. C, circuit breaker2...3 A, Char. C, circuit breakerOutputrated output voltageOutput voltageresidual ripple, breaking spikesRated (nominal) output current @ U Nomcontinous output current @ 24 V DC<strong>Power</strong>boost @ 24 V DC, 60 °CGeneral dataDegree of efficiency<strong>Power</strong> factor (approx.)AC failure bridging time @ I NomParallel connection optionLength x width x heightWeightApprovals24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N5 A @ 60 °C6.0 A @ 45 °C, 5.3 A @ 55 °C, 3.8 A @ 70 °C6 A for 1 min, ED = 5 %89 % @ 3 x 500 V AC / 90 % @ 3 x 400 V AC> 0.55 @ 3 x 500 V AC / > 0.65 @ 3 x 400 V AC> 50 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V ACyes, max. 5125 / 40 / 130 mm0.7 kg24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N10 A @ 60 °C12 A @ 45 °C, 10.7 A @ 55 °C, 7.5 A @ 70 °C12 A for 1 min, ED = 5 %89 % @ 3 x 500 V AC / 90 % @ 3 x 400 V AC> 0.65 @ 3 x 500 V AC / > 0.75 @ 3 x 400 V AC> 40 ms @ 3 x 500 V AC / > 20 ms @ 3 x 400 V ACyes, max. 5150 / 60 / 130 mm1.25 kgCE; cURus; cULus; C-TickCE; cURus; cULus; C-TickConnection dataConductor connection systemNumber of terminalsWire cross-section, rigid min/maxWire cross-section, flexible min/maxWire cross-section, AWG/kcmil min/maxmm²mm²InputOutputScrew connectionScrew connection4 for L1/L2/L3/PE 5 (++ / ---)0.08 / 4 0.5 / 60.5 / 2.5 0.5 / 2.528 / 12 26 / 12InputOutputScrew connectionScrew connection4 for L1/L2/L3/PE 5 (++ / ---)0.5 / 6 0.5 / 60.5 / 2.5 0.5 / 2.526 / 12 26 / 12Note*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!Ordering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP M SNT3 120W 24V 5A 1 8951390000CP M SNT3 250W 24V 10A 1 8951400000NoteAccessoriesA.8


connect<strong>Power</strong>PRO-MCP M SNT3 500 W 24 V 20 Aconnect<strong>Power</strong> PRO-MCP M SNT3 1000 W 24 V 40 ASwitch-mode power suppliesALL1 (+)L2 (–)AC+L1 (+)L2 (–)AC+HL3PEDC–L3PEDC–WWith DC connection, note polarityTwo-phase operation also possibleWith DC connection, note polarityTwo-phase operation also possibleTechnical dataInputrated input voltageInput voltage range ACFrequency range ACDC input voltage rangeAC current consumptionDC current consumptionInput fuse (internal) / making currentRecommended back-up fuse3 x 400...3 x 500 V AC (wide-range input)3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC47...63 Hz450...800 V DC (max. 500 V DC acc. to UL508)0.9 A @ 3 x 500 V AC / 0.95 A @ 3 x 400 V AC0.7 A @ 800 V DC / 1.2 A @ 450 V DCNo / max. 50 A4 A / DI, safety fuse3 x 400...3 x 500 V AC (wide-range input)3 x 320...3 x 575 V AC / 2 x 360...2 x 575 V AC47...63 Hz450...800 V DC (max. 500 V DC acc. to UL508)2.0 A @ 3 x 500 V AC / 2.5 A @ 3 x 400 V AC1.3 A @ 800 V DC / 2.4 A @ 450 V DCNo / max. 60 A6 A / DI, safety fuse3...5 A, Char. C, circuit breaker10 A, Char. B, circuit breaker6...8 A, Char, C, circuit breakerOutputrated output voltageOutput voltageresidual ripple, breaking spikesRated (nominal) output current @ U Nomcontinous output current @ 24 V DC<strong>Power</strong>boost @ 24 V DC, 60 °CGeneral dataDegree of efficiency<strong>Power</strong> factor (approx.)AC failure bridging time @ I NomParallel connection optionLength x width x heightWeightApprovals24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N20 A @ 60 °C24 A @ 45 °C, 21.3 A @ 55 °C, 15 A @ 70 °C24 A for 1 min, ED = 5 %89 % @ 3 x 500 V AC / 90 % @ 3 x 400 V AC> 0.69 @ 3 x 500 V AC / > 0.82 @ 3 x 400 V AC> 25 ms at 3 x 500 V AC / > 20 ms at 3 x 400 V ACyes, max. 3150 / 121 / 130 mm2.2 kg24 V DC ± 1 %22.5...29.5 V DC (adjustable via potentiometer on front)< 50 mV pp@ 24 V DC, I N40 A @ 60 °C48 A @ 45 °C, 42.7 A @ 55 °C, 30 A @ 70 °C48 A for 1 min, ED = 5 %91 % @ 3 x 500 V AC / 91 % @ 3 x 400 V AC> 0.6 @ 3 x 500 V AC / > 0.6 @ 3 x 400 V AC> 25 ms at 3 x 500 V AC / > 20 ms at 3 x 400 V ACyes, max. 3150 / 180 / 130 mm4 kgCE; cURus; cULus; C-TickCE; cURus; cULus; C-TickConnection dataConductor connection systemNumber of terminalsWire cross-section, rigid min/maxWire cross-section, flexible min/maxWire cross-section, AWG/kcmil min/maxmm²mm²InputOutputScrew connectionScrew connection4 for L1/L2/L3/PE 5 (++ / ---)0.5 / 6 0.5 / 60.5 / 2 0.5 / 2.526 / 10 26 / 10InputOutputScrew connectionScrew connection4 for L1/L2/L3/PE 5 (++ / ---)0.5 / 6 0.5 / 160.5 / 2.5 0.5 / 1026 / 10 22 / 6Note*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!Ordering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP M SNT3 500W 24V 20A 1 8951410000CP M SNT3 1000W 24V 40A 1 8951420000NoteAccessoriesA.9


Switch-mode power suppliesconnect<strong>Power</strong> PRO-MPRO-M: Diode modules,capacity module and relay moduleCP M DM20CP M DM40AL1+ 3+4+1+ 3+4+HW1-2-2+1112142122243-4-1-2-2+1112142122243-4-Technical dataInput dataRated input voltageInput voltage range ACInput currentOutput dataRated output voltageOutput voltageRated (nominal) output current @ U NContinous output current @ 24 V DCVoltage monitoringSwitching thresholdsPotential free, floating contactsGeneral dataDegree of efficiencyLength x width x heightmmWeightAmbient temperature (operational) / Storage temperatureMax. permitted humidity (operational)Degree of protectionClass of protectionPollution degreeInsulation voltage I/O to housingMTBFMounting position, installation noticeEMC / shock / vibrationNoise emission acc. to EN55022Noise immunity tests acc. toResistance against vibration and shockElectrical safety (applied standards)Electrical equipment of machinesSafety transformers for switched-mode power unitsSafety extra low voltageApprovalsPendingConnection dataConductor connection systemNumber of terminalsConductor cross section, rigid min/maxConductor cross section, flexible min/maxConductor cross section, AWG/kcmil min/maxNotemm²mm²24 V DC18…30 V DC2 x 10 A or 1 x 20 A24 V DCInput voltage - 0.7 V20 A DC @ 60 °C24 A @ 45 °C22.5 A @ 55 °C15 A @ 70 °Cyes, in both inputs21.6 V DC, relay is on for <strong>Power</strong> Good20.4 V DC, relay is off for <strong>Power</strong> FailMax. 30 V DC / 1 A, CO contact> 97 % @ 24 V input voltage150 x 34 x 1300.3 kg-25…+70 °C / -40 °C…+85 °C5 %…95 % RHIP20III, without PE connection, for SELV20.5 kV> 500.000 h according to IEC 1709 (SN29500)Horizontal on TS35 mounting rail, with 50 mm space at topand bottom. Direct side by side mounting allowed.Class BEN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6(conducted)1 g according to EN50178 / 15 g in all directionsaccording to EN60204according to EN50178 / VDE0160SELV according to EN60950, PELV according to EN60204CE, TUV, cULus, GL, GOSTInputOutputScrew connectionScrew connection4 (1+, 2+, 1-, 2-) 4 (3+, 4+, 3-, 4-)0.5 / 6 0.5 / 60.5 / 2.5 0.5 / 2.526 / 12 26 / 1224 V DC18…30 V DC2 x 20 A or 1 x 40 A24 V DCInput voltage - 0.7 V40 A @ 60 °C48 A @ 45 °C45 A @ 55 °C30 A @ 70 °Cyes, in both inputs21.6 V DC, relay is on for <strong>Power</strong> Good20.4 V DC, relay is off for <strong>Power</strong> FailMax. 30 V DC / 1 A, CO contact> 97 % @ 24 V input voltage150 x 60 x 1300.6 kg-25…+70 °C / -40 °C…+85 °C5 %…95 % RHIP20III, without PE connection, for SELV20.5 kV> 500.000 h according to IEC 1709 (SN29500)Horizontal on TS35 mounting rail, with 50 mm space at topand bottom. Direct side by side mounting allowed.CLass BEN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6(conducted)1 g according to EN50178 / 15 g in all directionsaccording to EN60204according to EN50178 / VDE0160SELV according to EN60950, PELV according to EN60204CE, TUV, cULus, GL, GOSTInputOutputScrew connectionScrew connection4 (1+, 2+, 1-, 2-) 4 (3+, 4+, 3-, 4-)0.5 / 16 0.5 / 162.5 / 10 2.5 / 1022 / 6 22 / 6Ordering dataType Qty. Order No.CP M DM20 1 1222210000Type Qty. Order No.CP M DM40 1 1222220000A.10


PRO-M: Diode modules,capacity module and relay moduleCP M RM24connect<strong>Power</strong> PRO-MSwitch-mode power suppliesA11red+HL1214black–WTechnical dataInput dataRated input voltageInput voltage range DCOutput dataVoltage monitoringSwitching thresholdsPotential free, floating contactsGeneral dataLength x width x heightmmWeightAmbient temperature (operational) / Storage temperatureMax. permitted humidity (operational)Degree of protectionClass of protectionPollution degreeInsulation voltage I/O to housingMTBFMounting position, installation notice24 V DC18…30 V DCyes21.6 V DC, relay is on for <strong>Power</strong> Good20.4 V DC, relay is off for <strong>Power</strong> FailMax. 30 V DC / 1 A, CO contact22 x 33 x 2875 g-25…+70 °C / -40 °C…+85 °C5 %…95 % RHIP20III, without PE connection, for SELV20.5 kV> 500.000 h according to IEC 1709 (SN29500)Plugged in to the front of the PRO-M power supplyEMC / shock / vibrationNoise emission acc. to EN55022Noise immunity tests acc. toResistance against vibration and shockElectrical safety (applied standards)Electrical equipment of machinesSafety transformers for switch mode power unitsSafety extra low voltageApprovalsPendingConnection dataConductor connection systemNumber of terminalsConductor cross section, rigid min/maxConductor cross section, flexible min/maxConductor cross section, AWG/kcmil min/maxmm²mm²Class BEN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6(conducted), EN61000-4-11 (Dips)1 g according to EN50178 / 15 g in all directionsaccording to EN60204according to EN50178 / VDE0160SELV according to EN60950, PELV according to EN60204CE, TUV, cULus, GL, GOSTInputOutput10 cm cable (red/black) with ferrules PUSH IN3 (Changeover contact)0.2 / 1.50.2 / 1.524 / 16NoteOrdering dataType Qty. Order No.CP M RM24 1 1222230000A.11


Switch-mode power suppliesconnect<strong>Power</strong> PRO-MPRO-M: Diode modules,capacity module and relay moduleCP M CAPPulse triggering for cable circuit breakers:with the Weidmüller capacitance moduleThe following conditions apply to the table entries:• Ambient temperature of 20 °C• Inner resistance of the circuit breakers is taken into account• Half of the rated current flows to a neighbouring circuitbefore the short circuit is formed• DC-compatible circuit breakers: Siemens 5SY seriesAL1+2+H111214+<strong>Power</strong> supply+CAP moduleLoadW1-2-Distance in mTechnical dataInput dataRated input voltageInput voltage range DCOutput dataPeak current outputRecovery time for the capacitorVoltage monitoringSwitching thresholdsPotential free, floating contactsGeneral dataLength x width x heightmmWeightAmbient temperature (operational) / Storage temperatureMax. permitted humidity (operational)Degree of protectionClass of protectionPollution degreeInsulation voltage I/O to housingMTBFMounting position, installation noticeEMC / shock / vibrationNoise emission acc. to EN55022Noise immunity tests acc. toResistance against vibration and shockElectrical safety (applied standards)Electrical equipment of machinesSafety transformers for switched-mode power unitsSafety extra low voltageApprovalsPendingConnection dataConductor connection systemNumber of terminalsConductor cross section, rigid min/maxConductor cross section, flexible min/maxConductor cross section, AWG/kcmil min/maxmm²mm²24 V DC18…30 V DCDepending on loadapprox. 1 syes21.6 V DC, relay is on for <strong>Power</strong> Good20.4 V DC, relay is off for <strong>Power</strong> FailMax. 30 V DC / 1 A, CO contact150 x 34 x 1300.4 kg-25…+70 °C / -40 °C…+85 °C5 %…95 % RHIP20III, without PE connection, for SELV20.5 kV> 500.000 h according to IEC 1709 (SN29500)Horizontal on TS35 mounting rail, with 50 mm space at topand bottom. Direct side by side mounting allowed.Class BEN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6(conducted), EN61000-4-11 (Dips)1 g according to EN50178 / 15 g in all directionsaccording to EN60204according to EN50178 / VDE0160SELV according to EN60950, PELV according to EN60204CE, TUV, GLcULus, GOSTInputOutputScrew connectionScrew connection4 (++--) 3 (Changeover contact)0.5 / 6 0.5 / 60.5 / 4 0.5 / 2.526 / 12 26 / 12Fuse trippingConductor cross section B6B100.75 mm 2 10 m1.0 mm 2 14 m 6 m1.5 mm 2 20 m 9 m2.5 mm 2 30 m 15 m4 mm 2 50 m 24 m6 mm 2 B160.75 mm 21.0 mm 21.5 mm 2 4 m2.5 mm 2 6 m4 mm 2 10 m6 mm 2 16 mC2C40.75 mm 2 11 m 6 m1.0 mm 2 14 m 8 m1.5 mm 2 21 m 12 m2.5 mm 2 34 m 19 m4 mm 2 32 m6 mm 2 C6 C100.75 mm 2 3 m1.0 mm 2 3,5 m 2 m1.5 mm 2 5,5 m 3 m2.5 mm 2 9 m 5 m4 mm 2 14 m 8 m6 mm 2 12 mNoteOrdering dataType Qty. Order No.CP M CAP 1 1222240000A.12


Switch-mode power suppliesAA.13


Switch-mode power suppliesAconnect<strong>Power</strong> PRO-MPRO-M: Application solution forwind powerSwitched-mode power supply with wide-range inputApplication solution for wind power:• 80 ... 430 V DC input• Alarm contact• Metal snap-on footPreliminary product data!Technical dataGeneral technical dataOutput characteristic curve / current limitIU / > 120 % I NEarth discharge current< 3.5 mAAmbient temperature (operational) / Storage temperature –25 °C … +70 °C / –40 °C … +85 °CMax. permitted humidity (operational)5 %…95 % RHDegree of protectionIP20Class of protectionI, with PE connectionPollution degree 2Insulation voltage3 kV AC 1 min. / 2 kV AC 1 min. / 0.5 kV AC 1 min.MTBF> 500,000 h according to IEC 1709 (SN29500)Protection against reverse voltages from the load30…35 V DCCan be connected in parallelYes, without diode moduleHousing versionMetal, corrosion resistantSignal indicationOperations, green/red LEDMounting position, installation noticeHorizontal on TS35 mounting rail, with 50 mm of clearance at topand bottom for air circulation. Can be mounted side by side withno space in between. Suitable for installation in rotating systems.EMC / shock / vibrationNoise emission acc. to EN55022Class BNoise immunity tests acc. toEN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6(conducted), EN61000-4-11 (Dips)Limiting of mains voltage harmonic currentsaccording to EN61000-3-2Resistance against vibration and shockaccording to EN50178, Shock: 5 g in all directionsElectrical safety (applied standards)Electrical equipment of machinesaccording to EN60204Safety transformers for switched-mode power unitsaccording to EN61558-2-17Safety transformers for switched-mode power unitsaccording to EN50178 / VDE0160Safety extra low voltageSELV according to EN60950, PELV according to EN60204Protective separation / protection against electrical shock VDE0100-410 / according to DIN57100-410Protection against dangerous shock currentsaccording to VDE0106-101A.14


PRO-M: Application solution forwind powerCP M SNT 250 W 24 V 10 A UWconnect<strong>Power</strong> PRO-MSwitch-mode power suppliesAPreliminary product data!LHL (+)N (–)PEACU 100 ms @ 230 V AC / > 20 ms @ 100 V ACYes / Max. 2 devices155 x 60 x 1301.2 kgOperational lamp, red/greenFloating (voltage-free), NO contact (DCOK = 1)yesCE, CB-Scheme, cULus, cURus, C-Tick, GLInputOutputScrew connectionScrew connection3 for L/N/PE 6 (Alarm contact/++/--)0.5 / 6 0.5 / 60.5 / 2.5 0.5 / 2.526 / 12 26 / 12*) Recommendation applies only for AC operation; the max. permissibleoperating voltage must be observed in all cases!Type Qty. Order No.CP M SNT 250W 24V 10A UW 1 1165480000AccessoriesA.15


Switch-mode power suppliesconnect<strong>Power</strong> PRO-Hconnect<strong>Power</strong>PRO-HAL (+)N (–)PEACDCMax. limiting average on state current [A]Type\Temp. 40 °C 50 °C 60 °C 70 °C1 ph 12 V / 6 A 6.0 5.7 5.4 4.51 ph 12 V / 12 A 12.0 9.5 7.0 3.71 ph 24 V / 3.8 A 3.8 3.1 2.5 1.71 ph 24 V / 7.5 A 7.5 6.3 5.0 3.31 ph 24 V / 15 A 15.0 12.5 10.0 6.71 ph 24 V / 25 A 25.0 22.5 20.0 13.31 ph 36 V / 16.5 A 16.5 15.0 13.3 9.01 ph 48 V / 2 A 2.0 1.6 1.3 0.81 ph 48 V / 4 A 4.0 3.3 2.5 1.71 ph 48 V / 7.5 A 7.5 6.3 5.0 3.31 ph 48 V / 12.5 A 12.5 11.3 10.0 7.53 ph 24 V / 20 A 20.0 20.0 20.0 15.03 ph 24 V / 40 A 40.0 40.0 40.0 30.01-2 ph 24 V / 7.5 A 7.5 6.3 5.0 3.31-2 ph 24 V / 15 A 15.0 12.5 10.0 6.71-2 ph 24 V / 25 A 25.0 22.5 20.0 13.3+–Technical dataGeneral technical dataCurrent limiting> 100 % I NAmbient temp. operating / storage temperature -25…+70 °C -25 °C…+85 °CMax. perm. air humidity (operation)95 % RHDegree of protectionIP20Class of protectionI, with PE connectionPollution degree 2Insulation voltage input/output 4 kV I/O 2 kV I/earth 0.5 kV O/earthMTBF according to IEC 61709 CP T … 70/90 W > 1.8 Mio. hCP T … 140 W > 1.2 Mio. hCP T … 180/360/600 W > 0.9 Mio. hProtection against reverse voltages from the load16 V DC / 35 V DC / 63 V DCParallel connection optionyes, without diode moduleHousing versionmetal, corrosion resistantOverload protectionThermal protection, autom. restartShort circuit protectionUnlimited, autom. restartIndicationDual LED Operational: Green LED; Error: Red LEDMounting position, installation noticeHorizontal on TS35 mounting rail, with 80 mm space at top andbottom. Side by side mounting with 50 mm clearance.Signal indication<strong>Power</strong> Good signal Trigger point 12 V version 9…11 V DC24 V version 18...22 V DC48 V version 36...44 V DCPotential free, floating signal contact NO contact 30 V DC/1.0 A max. for 12/24 V DC modules48 V DC/ 0.5 A max. for 36/48 V DC modulesActive output signal 70 W 11 V DC ± 1 V DC / 20 mA max.140 W 11 V DC ± 1 V DC / 40 mA max.90 W 22 V DC ± 2 V DC / 10 mA max.180/360/600 W 24 V DC 22 V DC± 2 V DC / 20 mA max.180/360/600 W 48 V DC 44 V DC± 4 V DC / 15 mA max.EMC / shock / vibrationNoise emission acc. to EN55022Class BNoise immunity tests acc. toEN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),EN61000-4-4 (Burst), EN61000-4-5 (Surge), EN610004-6(conducted), EN61000-4-11 (Dips)Limiting of mains voltage harmonic currentsaccording to EN61000-3-2Vibration IEC 60068-2-63 axes, sinus, 10 – 55 Hz, 1 g, 1 oct./min.Shock IEC 60068-2-273 axes, 15 g, half sinus, 11 msElectrical safety (applied standards)Electrical equipment of machinesaccording to EN60204Safety transformers for switched-mode power unitsaccording to EN61558-2-4Machinery with electronic equipmentaccording to EN50178Safety extra low voltageSELV according to EN60950CP T SNT...Output <strong>Power</strong> [% Pmax]100908070605040-2590 W180 W360 W600 W40 50 60 70Temperature [°C]70 W140 WOutput <strong>Power</strong> [% Pmax]10090807060504085 90 100 110 115 132 187 230 264Input Voltage [VAC]A.16


connect<strong>Power</strong>PRO-HCP T SNT 70 W 12 V 6 ACP T SNT 140 W 12 V 12 Aconnect<strong>Power</strong> PRO-HSwitch-mode power suppliesATechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC100...240 V AC (wide-range input)85...264 V AC47...63 Hz1.0 A @ 230 V AC /2.0 A @ 115 V AC4 A / < 20 A (230 V AC)6...16 A, Char. B, circuit breaker12 V DC ± 1 %12…14 V DC (adjustable via potentiometer on front)100 mV SS@ 12 V DC, I N6 A @ 40 °C6.0 A @ 40 °C5.4 A @ 60 °C4.5 A @ 70 °C100...240 V AC (autoselect)85…132 V AC / 187...264 V AC47...63 Hz1.4 A @ 230 V AC /2.5 A @ 115 V AC4 A / < 20 A (230 V AC)6...16 A, Char. B, circuit breaker12 V DC ± 1 %12…14 V DC (adjustable via potentiometer on front)100 mV ss@ 12 V DC, I N12 A @ 40 °C12.0 A @ 40 °C7.0 A @ 60 °C3.7 A @ 70 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmmtyp. 82 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5110 x 35 x 1100.5 kgtyp. 85 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5110 x 54 x 1100.7 kgCE, UR 60950-1, UL508,CE, UR 60950-1, UL508,CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2), ATEX zone 2CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2), ATEX zone 2Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputpluggable srew connection3 (L/N/PE) 5 (+/- / Signal)0.5…2.5 1.0…2.5 0.2…2.524…12 18…12 32…127.00.5 ...0.6 NmInputOutputpluggable srew connection3 (L/N/PE) 7 (+/- / Signal)0.5…2.5 1.0…2.5 0.2…2.524…12 18…12 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T SNT 70W 12V 6A 1 1105430000CP T SNT 140W 12V 12A 1 1105440000NoteAccessoriesA.17


Switch-mode power suppliesconnect<strong>Power</strong> PRO-Hconnect<strong>Power</strong>PRO-HCP T SNT 90 W 24 V 3.8 ACP T SNT 90 W 24 V 3.8 A CL2ATechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC100...240 V AC (wide-range input)85...264 V AC47...63 Hz1.0 A @ 230 V AC /2.1 A @ 115 V AC4 A / < 20 A (230 V AC)6...16 A, Char. B, circuit breaker24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N3.8 A @ 40 °C3.8 A @ 40 °C2.5 A @ 60 °C1.7 A @ 70 °C100...240 V AC (wide-range input)85...264 V AC47...63 Hz1.0 A @ 230 V AC /2.1 A @ 115 V AC4 A / < 20 A (230 V AC)6...16 A, Char. B, circuit breaker24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N3.8 A @ 40 °C3.8 A @ 40 °C2.5 A @ 60 °C1.7 A @ 70 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmmtyp. 85 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5110 x 35 x 1100.5 kgtyp. 85 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5110 x 35 x 1100.5 kgCE, UR 60950-1, UL508,CE, UR 60950-1, UL508, CSA22.2 no.107, ANSI/ISACSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2), ATEX zone 212.12.01(Cl.1,Div2), EN60950 sec. 2,5, NEC Class2, UL1310Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputpluggable srew connection3 (L/N/PE) 5 (+/- / Signal)0.5…2.5 0.5…2.5 0.2…2.524…12 24…12 32…127.00.5 ...0.6 NmInputOutputpluggable srew connection3 (L/N/PE) 5 (+/- / Signal)0.5…2.5 0.5…2.5 0.2…2.524…12 24…12 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T SNT 90W 24V 3.8A 1 1105790000CP T SNT 90W 24V 3.8A CL2 1 1194410000NoteAccessoriesA.18


connect<strong>Power</strong>PRO-HCP T SNT 180 W 24 V 7.5 ACP T SNT 360 W 24 V 15 Aconnect<strong>Power</strong> PRO-HSwitch-mode power suppliesATechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC100...240 V AC (autoselect)85…132 V AC / 187...264 V AC47...63 Hz1.4 A @ 230 V AC / 2.5 A @ 115 V AC4 A / < 20 A (230 V AC)6...16 A, Char. B, circuit breaker24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N7.5 A @ 40 °C7.5 A @ 40 °C5.0 A @ 60 °C3.3 A @ 70 °C100...240 V AC (autoselect)85…132 V AC / 187...264 V AC47...63 Hz2.5 A @ 230 V AC / 5.0 A @ 115 V AC6.3 A / < 25 A (230 V AC)10...16 A, Char. B, circuit breaker24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N15 A @ 40 °C15.0 A @ 40 °C10.0 A @ 60 °C6.7 A @ 70 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmmtyp. 88 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5110 x 54 x 1100.7 kgtyp. 87 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5110 x 80 x 1101.1 kgCE, UR 60950-1, UL508,CE, UR 60950-1, UL508,CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2), ATEX zone 2CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2), ATEX zone 2Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputpluggable srew connection3 (L/N/PE) 7 (+/- / Signal)0.5…2.5 0.5…2.5 0.2…2.524…12 24…12 32…127.00.5 ...0.6 NmInputOutputpluggable srew connection3 (L/N/PE) 7 (+/- / Signal)0.5…2.5 1.0…2.5 0.2…2.524…12 18…12 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T SNT 180W 24V 7.5A 1 1105810000CP T SNT 360W 24V 15A 1 1105820000NoteAccessoriesA.19


Switch-mode power suppliesconnect<strong>Power</strong> PRO-Hconnect<strong>Power</strong>PRO-HCP T SNT 600 W 24 V 25 ACP T SNT 600 W 36 V 16.5 AATechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC100...240 V AC (autoselect)85…132 V AC / 187...264 V AC47...63 Hz5.0 A @ 230 V AC /10.0 A @ 115 V AC12 A / < 30 A (230 V AC)16…25 A, Char. B, circuit breaker24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N25 A @ 40 °C25.0 A @ 40 °C20.0 A @ 60 °C13.3 A @ 70 °C100...240 V AC (autoselect)85…132 V AC / 187...264 V AC47...63 Hz1.0 A @ 230 V AC /2.0 A @ 115 V AC12 A / < 30 A (230 V AC)16…25 A, Char. B, circuit breaker36 V DC ± 1 %36…42 V DC (adjustable via potentiometer on front)100 mV SS@ 36 V DC, I N16.5 A @ 40 °C16.5 A @ 40 °C13.3 A @ 60 °C9.0 A @ 70 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmmtyp. 89 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5125 x 165 x 1252.8 kgtyp. 87 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5125 x 165 x 1252.8 kgCE, UR 60950-1, UL508,CE, UR 60950-1, UL508,CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2), ATEX zone 2CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2)Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmInputOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T SNT 600W 24V 25A 1 1105840000CP T SNT 600W 36V 16.5A 1 1194430000NoteAccessoriesA.20


connect<strong>Power</strong>PRO-HCP T SNT 90 W 48 V 2 ACP T SNT 180 W 48 V 4 Aconnect<strong>Power</strong> PRO-HSwitch-mode power suppliesSimilar toillustrationATechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC100...240 V AC (wide-range input)85...264 V AC47...63 Hz1.0 A @ 230 V AC /2.1 A @ 115 V AC4 A / < 20 A (230 V AC)6...16 A, Char. B, circuit breaker48 V DC ± 1 %48…56 V DC (adjustable via potentiometer on front)100 mV SS@ 48 V DC, I N2 A @ 40 °C2.0 A @ 40 °C1.3 A @ 60 °C0.8 A @ 70 °C100...240 V AC (autoselect)85…132 V AC / 187...264 V AC47...63 Hz1.4 A @ 230 V AC /2.5 A @ 115 V AC4 A / < 25 A (230 V AC)6...16 A, Char. B, circuit breaker48 V DC ± 1 %48…56 V DC (adjustable via potentiometer on front)100 mV SS@ 48 V DC, I N4 A @ 40 °C4.0 A @ 40 °C2.5 A @ 60 °C1.7 A @ 70 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmmtyp. 87 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5110 x 35 x 1100.5 kgtyp. 90 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5110 x 54 x 1100.7 kgCE, UR 60950-1, UL508,CE, UR 60950-1, UL508,CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2)CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2), ATEX zone 2Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputpluggable srew connection3 (L/N/PE) 5 (+/- / Signal)0.5…2.5 0.5…2.5 0.2…2.524…12 24…12 32…127.00.5 ...0.6 NmInputOutputpluggable srew connection3 (L/N/PE) 7 (+/- / Signal)0.5…2.5 0.5…2.5 0.2…2.524…12 24…12 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T SNT 90W 48V 2A 1 1194420000CP T SNT 180W 48V 4A 1 1105850000NoteAccessoriesA.21


Switch-mode power suppliesconnect<strong>Power</strong> PRO-Hconnect<strong>Power</strong>PRO-HCP T SNT 360 W 48 V 7.5 ACP T SNT 600 W 48 V 12.5 AATechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC100...240 V AC (autoselect)85…132 V AC / 187...264 V AC47...63 Hz2.5 A @ 230 V AC /5.0 A @ 115 V AC6.3 A / < 25 A (230 V AC)10...16 A, Char. B, circuit breaker48 V DC ± 1 %48…56 V DC (adjustable via potentiometer on front)100 mV SS@ 48 V DC, I N7.5 A @ 40 °C7.5 A @ 40 °C5.0 A @ 60 °C3.3 A @ 70 °C100...240 V AC (autoselect)85…132 V AC / 187...264 V AC47...63 Hz5.0 A @ 230 V AC /10.0 A @ 115 V AC12 A / < 30 A (230 V AC)16…25 A, Char. B, circuit breaker48 V DC ± 1 %48…56 V DC (adjustable via potentiometer on front)100 mV SS@ 48 V DC, I N12.5 A @ 40 °C12.5 A @ 40 °C10.0 A @ 60 °C7.5 A @ 70 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmmtyp. 89 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5110 x 80 x 1101.1 kgtyp. 91 % @ 230 V ACmin. 20 ms @ 230 V AC / min. 10 ms @ 115 V ACyes, max. 5125 x 165 x 1252.8 kgCE, UR 60950-1, UL508,CE, UR 60950-1, UL508,CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2), ATEX zone 2CSA22.2 no.107, ANSI/ISA 12.12.01(Cl.1,Div2), ATEX zone 2Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputpluggable srew connection3 (L/N/PE) 7 (+/- / Signal)0.5…2.5 1.0…2.5 0.2…2.524…12 18…12 32…127.00.5 ...0.6 NmInputOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T SNT 360W 48V 7.5A 1 1105860000CP T SNT 600W 48V 12.5A 1 1105870000NoteAccessoriesA.22


connect<strong>Power</strong>PRO-HCP T SNT3 480 W 24 V 20 A/400connect<strong>Power</strong> PRO-HCP T SNT3 480 W 24 V 20 A/500Switch-mode power suppliesSimilar toillustrationSimilar toillustrationATechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC400 V AC320…440 V AC47...63 Hz6 A, Char. B, circuit breaker24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N20.0 A @ 40 °C20.0 A @ 40 °C20.0 A @ 60 °C15.0 A @ 70 °C500 V AC400…550 V AC47...63 Hz6 A, Char. B, circuit breaker24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N20.0 A @ 40 °C20.0 A @ 40 °C20.0 A @ 60 °C15.0 A @ 70 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmmtyp. 92 %min. 20 msyes125 x 80 x 1251.05 kgtyp. 92 %min. 20 msyes125 x 80 x 1251.05 kgCE, UR 60950-1, UL508, CSA22.2 no.107CE, UR 60950-1, UL508, CSA22.2 no.107Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmInputOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T SNT3 480W 24V 20A/400 1 1194440000CP T SNT3 480W 24V 20A/500 1 1194450000NoteAccessoriesA.23


Switch-mode power suppliesconnect<strong>Power</strong> PRO-Hconnect<strong>Power</strong>PRO-HCP T SNT3 960 W 24 V 40 A/400CP T SNT3 960 W 24 V 40 A/500ASimilar toillustrationSimilar toillustrationTechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC400 V AC320…440 V AC47...63 Hz6 A, Char. B, circuit breaker24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N40.0 A @ 40 °C40.0 A @ 40 °C40.0 A @ 60 °C30.0 A @ 70 °C500 V AC400…550 V AC47...63 Hz6 A, Char. B, circuit breaker24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N40.0 A @ 40 °C40.0 A @ 40 °C40.0 A @ 60 °C30.0 A @ 70 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmmtyp. 92 %min. 20 msyes125 x 165 x 1252.35 kgtyp. 92 %min. 20 msyes125 x 165 x 1252.35 kgCE, UR 60950-1, UL508, CSA22.2 no.107CE, UR 60950-1, UL508, CSA22.2 no.107Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmInputOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T SNT3 960W 24V 40A/400 1 1194460000CP T SNT3 960W 24V 40A/500 1 1194470000NoteAccessoriesA.24


connect<strong>Power</strong>PRO-HCP T SNT3 180 W 24 V 7.5 Aconnect<strong>Power</strong> PRO-HCP T SNT3 360 W 24 V 15 ASwitch-mode power suppliesSimilar toillustrationSimilar toillustrationATechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC100…500 V AC selectable85…132 V AC / 187…550 V AC50/60 Hz< 23 A @ 230 V AC24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N7.5 A @ 40 °C7.5 A @ 40 °C5.0 A @ 60 °C3.3 A @ 70 °C100…500 V AC selectable85…132 V AC / 187…550 V AC50/60 Hz< 23 A @ 230 V AC24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N15.0 A @ 40 °C15.0 A @ 40 °C10.0 A @ 60 °C6.7 A @ 70 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmmtyp. 88 %min. 20 msyes110 x 54 x 1100.5 kgtyp. 88 %min. 20 msyes125 x 80 x 1251.1 kgCE, UR 60950-1, UL508, CSA22.2 no.107CE, UR 60950-1, UL508, CSA22.2 no.107Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmEingangOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmInputOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T SNT3 180W 24V 7.5A 1 1194480000CP T SNT3 360W 24V 15A 1 1194490000NoteAccessoriesA.25


Switch-mode power suppliesconnect<strong>Power</strong> PRO-Hconnect<strong>Power</strong>PRO-HCP T SNT3 600 W 24 V 25 AASimilar toillustrationTechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DCGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmm100…500 V AC selectable85…132 V AC / 187…550 V AC50/60 Hz< 50 A @ 230 V AC24 V DC ± 1 %24…28 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N25.0 A @ 40 °C25.0 A @ 40 °C20.0 A @ 60 °C13.3 A @ 70 °Ctyp. 88 %min. 20 msyes125 x 190 x 1253.0 kgCE, UR 60950-1, UL508, CSA22.2 no.107Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputScrew connection3 (L/N/PE) 7 (+/- / Signal)1.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmOrdering dataConnection systemScrew connectionType Qty. Order No.CP T SNT3 600W 24V 25A 1 1194310000NoteAccessoriesA.26


connect<strong>Power</strong>PRO-HRedundancy modulesCP T RM 10CP T RM 20connect<strong>Power</strong> PRO-HSwitch-mode power suppliesATechnical dataInputRated Input voltageInput voltage range ACFrequency range ACCurrent consumption ACInput fuse (internal) / Making currentRecommended back up fuseOutputRated output voltageOutput voltageResidual ripple, breaking spikesNominal output current @ U NContinous output current @ 24 V DC24 V DC24 V DC ± 1 %24…27 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N15.0 A @ 40 °C24 V DC24 V DC ± 1 %24…27 V DC (adjustable via potentiometer on front)100 mV SS@ 24 V DC, I N25.0 A @ 40 °CGeneral dataDegree of efficiencyAC failure bridging time @ I NParallel connection optionLength x width x heightWeightApprovalsmm110 x 35 x 1100.4 kg110 x 54 x 1100.45 kgCE, UR 60950-1, UL508, CSA22.2 no.107, ATEX zone 2CE, UR 60950-1, UL508, CSA22.2 no.107, ATEX zone 2Connection DataConnection systemNumber of terminalsConductor cross section, rigid/flexible min/maxConductor cross section, AWG/kcmil min/maxStripping length (mm)Tightening torqueNotemm²mm²mmInputOutputScrew connection4 41.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmInputOutputScrew connection4 41.0…4.0 2.0…4.0 0.2…2.518…10 12…10 32…127.00.5 ...0.6 NmOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP T RM 10 1 1105880000CP T RM 20 1 1105890000NoteAccessoriesA.27


Switch-mode power suppliesAPRO-H Dimensional drawings35.0 (1.38)- - + +Output24 -27 VInputs ON38.5 (1.52)110.0 (4.33)54.0 (2.13)DC 24V / 25 AInputs ON24 -27 V38.5 (1.52)110.0 (4.33)(4.33)110.0(4.33)DC IN 1 DC IN 2- + - +80.0 (3.15)110.0DC IN 1 DC IN 280.0 (3.15)5.0(0.20)25.0(0.98)5.0(0.20)5.0(0.20)25.0(0.98)14.5(0.57)54.0 (2.13)110.0 (4.33)(4.33)SPconnect<strong>Power</strong> PRO-HCP T RM 10CP T RM 2035.0 (1.38)110.0 (4.33)DC ONDC OK38.5 (1.52)DC ONDC OK38.5 (1.52)O/P ADJ.O/P ADJ.(4.33)110.0PE NL80.0 (3.15)110.0PE NL80.0 (3.15)5.0(0.20)25.0(0.98)5.0(0.20)5.0(0.20)25.0(0.98)14.5(0.57)P/SPSRemoteRemoteP/SCP T SNT 70 W / 90 WCP T SNT 180 W / 140 WA.28


P/SPSRemotePRO-H Dimensional drawings80.0 (3.15)125.0 (4.92)connect<strong>Power</strong> PRO-HSwitch-mode power suppliesDC ONDC OKA125.045.0 (1.77)(4.92)O/P ADJ.86.5 (3.41)PE NL25.0(0.98)25.0(0.98)123.0(4.84)21.0(0.83)5.0(0.20)25.0(0.98)46.0 17.0(1.81)(0.67)25.0(0.98)165.0 (6.50)125.0 (4.92)45.0 (1.77)(4.92)125.0DC ON86.5 (3.41)PE N LDC OKO/P ADJ.RemoteP SP/SCP T SNT 360 W / 480 WCP T SNT 600 W / 960 WA.29


Switch-mode power suppliesconnect<strong>Power</strong> ECOLINEconnect<strong>Power</strong> single-phaseHCP SNT 70 W 24 V 3 AALWVin ACEMCFilterRectifierFlybackConverterOutputRecctifier& FilterVout DCOutput CurrentFeedbackCheck & Sharecurrent controlOVP, OTP12Signal Relay1114Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionStatus relay / CO contactInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standardsMounting position, installation noticeInstallation adviceWeightApprovals85...264 V AC / 110...370 V DC2 A @ 100...240 V AC50/ 60 HzFusible link 2.5 A (T) / 250 VVaristor24...28 V DC (adjustable via poti)3 A72 W< 100 mV pp/ bandwidth 20 MHz105 %..130 % I constof max. output load; automatic reset29...34 V10 ms @ 115 V AC / 20 ms @ 230 V AC< 2 %Recommended with diode module250 V AC (max. 30 V DC) / 1 A0.5 kV1.5 kV3 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C80 %Green LEDEN 60950 (SELV)EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3horizontally, on terminal rail TS 35Clearance: above/below ≥ 3 cm0.55 kgcULus; cURus; GL; GOSTME25; CEDerating curveCurrent (A)43.532.521.510.500 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output2.5 / 0.13 / 4110 / 55.5 / 125For redundancy operation or to maintain the alert function, onlyoperate with diode module.Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 70W 24V 3A 1 8708660000NoteAccessoriesA.30


connect<strong>Power</strong> single-phaseHCP SNT 120 W 24 V 5 Aconnect<strong>Power</strong> ECOLINESwitch-mode power suppliesLWAVIN ACEMC &FilterRectifier& FilterForwardConverterOut Rectifier& FilterVOUT DCPWMControllerPhotocouplerPhotocouplerVoltagefeedbackOVPSignalRelay111214Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionStatus relay / CO contactInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standardsMounting position, installation noticeInstallation adviceWeightApprovals88...132 V AC/176...264 V AC selectable; 250...370 V DC3 A @ 115 V AC / 2 A @ 230 V AC50/ 60 HzFusible link 4 A (T) / 250 VVaristor24...28 V DC (adjustable via poti)5 A120 W< 100 mV pp/ bandwidth 20 MHz105 %..130 % I constof max. output load; automatic reset29...34 V20 ms @ 115 V AC / 20 ms @ 230 V AC< 2 %Recommended with diode module250 V AC (max. 30 V DC) / 1 A0.5 kV1.5 kV3 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C84 %Green LEDEN 60950 (SELV)EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3horizontally, on terminal rail TS 35Clearance: above/below ≥ 3 cm0.65 kgcULus; cURus; GL; GOSTME25; CEDerating curveCurrent (A)65432100 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output2.5 / 0.13 / 4110 / 65.5 / 125For redundancy operation or to maintain the alert function, onlyoperate with diode module.Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 120W 24V 5A 1 8708670000NoteAccessoriesA.31


Switch-mode power suppliesconnect<strong>Power</strong> ECOLINEconnect<strong>Power</strong> single-phaseHCP SNT 250 W 24 V 10 AALWVIN ACEMCInputRectifier& FilterForwardConverterOutputRectifier& FilterVOUT DCPWMControlPhotocouplerFeedbackSignalRelay111214Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionStatus relay / CO contactInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standardsMounting position, installation noticeInstallation adviceWeightApprovals88...132 V AC/176...264 V AC selectable; 250...370 V DC3.6 A @ 115 V AC / 2 A @ 230 V AC50/ 60 HzFusible link 5 A (T) / 250 VVaristor24...28 V DC (adjustable via poti)0.1…10 A240 W< 100 mV pp/ bandwidth 20 MHz105 %..130 % I constof max. output load; automatic reset30...36 V10 ms @ 115 V AC / 15 ms @ 230 V AC< 2 %Recommended with diode module250 V AC (max. 30 V DC) / 1 A0.5 kV1.5 kV3 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C84 % @ 230 V ACGreen LEDEN 60950 (SELV)EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3horizontally, on terminal rail TS 35Clearance: above/below ≥ 3 cm1.6 kgcULus; cURus; GL; GOSTME25; CEDerating curveCurrent (A)1210864200 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.13 / 6110 / 125.5 / 125For redundancy operation or to maintain the alert function, onlyoperate with diode module.Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 250W 24V 10A 1 8708680000NoteAccessoriesA.32


connect<strong>Power</strong> single-phaseHCP SNT 500 W 24 V 20 Aconnect<strong>Power</strong> ECOLINESwitch-mode power suppliesLWAVIN ACEMIInputRectiefier& FilterForwardConverterOutputRectifier& FilterVOUT DCPWMFeedbackSignalRelay111214Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionStatus relay / CO contactInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standardsMounting position, installation noticeInstallation adviceWeightApprovals88...132 V AC/176...264 V AC selectable; 250...370 V DC9 A @ 115 V AC / 6 A @ 230 V AC50/ 60 HzFusible link 10 A (T) / 250 VVaristor24...28 V DC (adjustable via poti)2...20 A @ 200...240 V AC; 2...16 A @ 100...120 V AC480 W< 100 mV pp/ bandwidth 20 MHz105 %..130 % I constof max. output load; automatic reset30...36 V10 ms @ 115 V AC / 15 ms @ 230 V AC< 2 %Recommended with diode module250 V AC (max. 30 V DC) / 1 A0.5 kV1.5 kV3 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C86 %Green LEDEN 60950 (SELV)EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3horizontally, on terminal rail TS 35Clearance: above/below ≥ 3 cm2 kgcULus; cURus; GL; GOSTME25; TUEV; CEDerating curveCurrent (A)30201000 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.13 / 6110 / 227.5 / 125For redundancy operation or to maintain the alert function, onlyoperate with diode module.Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 500W 24V 20A 1 8778870000NoteAccessoriesA.33


Switch-mode power suppliesconnect<strong>Power</strong> ECOLINEconnect<strong>Power</strong> single-phaseHCP SNT 1000 W 24 V 40 AALWVIN ACEMC &FilterRectifier& FilterForwardConverterOut Rectifier& FilterVOUT DCPWMControllerPhotocouplerPhotocouplerVoltagefeedbackOVPSignalRelay111214Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionStatus relay / CO contactInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standardsMounting position, installation noticeInstallation adviceWeightApprovals85…264 V AC12 A @ 115 V AC; 4.8 A @ 230 V AC50/ 60 HzFusible link 15 A (T) / 250 VVaristor24...28 V DC (adjustable via poti)40 A960 W< 100 mV pp/ bandwidth 20 MHz105 %...125 % I constof max. output load; automatic reset29...34 V20 ms @ 115 V AC / 20 ms @ 230 V AC< 2 %Recommended with diode module250 V AC (max. 30 V DC) / 1 A0.5 kV1.5 kV3 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C89 %Green LEDEN 60950 (SELV)EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3horizontally, on terminal rail TS 35Clearance: above/below ≥ 3 cm4.4 kgCEDerating curveCurrent (A)504030201000 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.13 / 6125 / 240 / 150For redundancy operation or to maintain the alert function, onlyoperate with diode module.Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 1000W 24V 40A 1 8862780000NoteAccessoriesA.34


connect<strong>Power</strong> 3-phaseHCP SNT3 120 W 24 V 5 Aconnect<strong>Power</strong> ECOLINESwitch-mode power suppliesLWAVIN ACEMC &FilterRectifier& FilterForwardConverterOut Rectifier& FilterVOUT DCPWMControllerPhotocouplerPhotocouplerVoltagefeedbackOVPSignalRelay111214Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionStatus relay / CO contactInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standardsMounting position, installation noticeInstallation adviceWeightApprovals3x400 V AC / 400...500 V AC ±15 %0.8 A @ 400 V AC47...63 HzExternal via 3 circuit-breakers up to 6...16 A, char. CVaristor24...28 V DC (adjustable via poti)5 A120 W< 100 mV pp/ bandwidth 20 MHz105 %..130 % I constof max. output load; automatic reset29...34 V> 20 ms @ 400 V AC< 2 %Recommended with diode module250 V AC (max. 30 V DC) / 1 A0.5 kV1.5 kV3 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C85 % @ 400 V ACGreen LEDEN 60950 (SELV)EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3horizontally, on terminal rail TS 35Clearance: above/below ≥ 3 cm1.5 kgCE; cURus; UL; GOSTME25Derating curveCurrent (A)65432100 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.13 / 4110 / 90 / 125For redundancy operation or to maintain the alert function, onlyoperate with diode module.Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT3 120W 24V 5A 1 8862730000NoteAccessoriesA.35


Switch-mode power suppliesconnect<strong>Power</strong> ECOLINEconnect<strong>Power</strong> 3-phaseHCP SNT3 250 W 24 V 10 AALW3ph VIN ACAC/DCConverterOutputVoltagecontrolOutput CurrentCheck & ControlVOUT DCAnti SurgeCircuitOCPOutputCurrentProtectionR SENSEOTP/OVPOutputVoltageProtectionSignalRelay111214Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionStatus relay / CO contactInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standardsMounting position, installation noticeInstallation adviceWeightApprovals3x400 V AC / 400...500 V AC ±15 %0.95 A @ 400 V AC47...63 HzExternal via 3 circuit-breakers up to 2…3 A, char. CVaristor24...28 V DC (adjustable via poti)10 A250 W< 100 mV pp/ bandwidth 20 MHz105 %..130 % I constof max. output load; automatic reset29...34 V> 10 ms @ 400 V AC< 2 %Recommended with diode module250 V AC (max. 30 V DC) / 1 A0.5 kV1.5 kV3 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C88 % @ 400 V ACGreen LEDEN 60950 (SELV)EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3horizontally, on terminal rail TS 35Clearance: above/below ≥ 3 cm1.5 kgcULus; cURus; GL; GOSTME25; CEDerating curveCurrent (A)1210864200 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.13 / 6110 / 125.5 / 125For redundancy operation or to maintain the alert function, onlyoperate with diode module.Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT3 250W 24V 10A 1 8708700000NoteAccessoriesA.36


connect<strong>Power</strong> 3-phaseHCP SNT3 500 W 24 V 20 Aconnect<strong>Power</strong> ECOLINESwitch-mode power suppliesLWA3ph VIN ACAC/DCConverterOutputVoltagecontrolOutput CurrentCheck & ControlVOUT DCAnti SurgeCircuitOCPOutputCurrentProtectionR SENSEOTP/OVPOutputVoltageProtectionSignalRelay111214Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionStatus relay / CO contactInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standardsMounting position, installation noticeInstallation adviceWeightApprovals3x400 V AC / 400...500 V AC ±15 %1.7 A @ 400 V AC47...63 HzExternal via 3 circuit-breakers up to 3…6 A, char. CVaristor24...28 V DC (adjustable via poti)20 A480 W< 100 mV pp/ bandwidth 20 MHz105 %..130 % I constof max. output load; automatic reset30...34 V> 10 ms @ 400 V AC< 2 %Recommended with diode module250 V AC (max. 30 V DC) / 1 A0.5 kV1.5 kV3 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C88 %Green LEDEN 60950 (SELV)EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3horizontally, on terminal rail TS 35Clearance: above/below ≥ 3 cm3 kgcULus; cURus; GL; GOSTME25; CEDerating curveCurrent (A)3025201510500 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.13 / 6110 / 227.5 / 125For redundancy operation or to maintain the alert function, onlyoperate with diode module.Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT3 500W 24V 20A 1 8708710000NoteAccessoriesA.37


Switch-mode power suppliesconnect<strong>Power</strong> ECOLINEconnect<strong>Power</strong> 3-phaseHCP SNT3 1000 W 24 V 40 AALW3ph VIN ACAC/DCConverterOutputVoltagecontrolOutput CurrentCheck & ControlVOUT DCAnti SurgeCircuitOCPOutputCurrentProtectionR SENSEOTP/OVPOutputVoltageProtectionSignalRelay111214Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionStatus relay / CO contactInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standardsMounting position, installation noticeInstallation adviceLength x width x heightWeightApprovals3x400 V AC / 400...500 V AC ±15 %3.4 A @ 400 V AC47...63 HzExternal via 3 circuit-breakers up to 6...16 A, char. CVaristor24...28 V DC (adjustable via poti)40 A960 W< 100 mV pp/ bandwidth 20 MHz105 %..130 % I constof max. output load; automatic reset29...34 V> 10 ms @ 400 V AC< 2 %Direct for same type250 V AC (max. 30 V DC) / 1 A0.5 kV1.5 kV3 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C88 %Green LEDEN 60950 (SELV)EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3horizontally, on terminal rail TS 35Clearance: above/below ≥ 3 cm125 / 280 / 150 mm3.5 kgCE; cURus; UL; GOSTME25; GLDerating curveCurrent (A)504030201000 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)mm²InputOutput4 / 0.1 / 6 10 / 0.3 / 16NoteClamping range identical for input and signalling contactOrdering dataConnection systemScrew connectionType Qty. Order No.CP SNT3 1000W 24V 40A 1 8708730000NoteAccessoriesA.38


connect<strong>Power</strong> diode moduleHCP DM 10CP DM 20connect<strong>Power</strong> ECOLINESwitch-mode power suppliesLWA+V -V+V -VE1 E2 -VE1 E2 -VTechnical dataInputInput voltageInput currentOutputOutput voltageOutput currentGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadDIN Rail compatibilityMounting position, installation noticeInstallation adviceLength x width x heightWeightApprovals40 V DC max.2 x 0...10 A max.U in- 0.5 V typical0...20 A max. or 10 A max. for redundancy operation-10 °C...+55 °C-20 °C...+85 °C95.5 %TS 35horizontally, on terminal rail TS 35Clearance: side ≥ 2 cm; above/below ≥ 10 cm110 / 55.5 / 125 mm0.4 kgcULus; cURus; GOSTME25; CE40 V DC max.2 x 0...20 A max.U in- 0.5 V typical0...40 A max. or 20 A max. for redundant operations-10 °C...+55 °C-20 °C...+85 °C97.5 %TS 35horizontally, on terminal rail TS 35Clearance: side ≥ 2 cm; above/below ≥ 10 cm110 / 55.5 / 125 mm0.4 kgcULus; cURus; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)mm²InputOutput4 / 0.13 / 6 4 / 0.13 / 6InputOutput4 / 0.13 / 6 10 / 0.32 / 16NoteOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP DM 10 1 8710620000CP DM 20 1 8768650000NoteAccessoriesA.39


Switch-mode power suppliesconnect<strong>Power</strong> INSTAPOWERconnect<strong>Power</strong> single-phaseCP SNT 24 W 28 V 1 ACP SNT 24 W 24 V 1 AALFUSE+LFUSE+N−N−Technical dataInputInput voltageInput currentInput frequency, max.making current limitInput fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadMax. capacitance at outputInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStandardsApprovalsEMC standards85...265 V AC, 120...300 V DC460 mA @ 115 V AC; 250 mA @ 230 V AC50/ 60 HzThermistor2 A time-lag fuse (internal)Varistor28 V DC1 A28 W< 2 %Surge current / thermal cut-outVaristor35 ms @ 115 V AC / 160 ms @ 230 V AC0,5 %8000 µF0.5 kV1.5 kV3 kV4 kV-20 °C...+50 °C-40 °C...+85 °C78 %EN 50178, EN 60950, IEC950CSA; GOSTME25; CEEN 61000-6 /-2, -385...265 V AC, 120...300 V DC460 mA @ 115 V AC; 250 mA @ 230 V AC50/ 60 HzThermistor2 A time-lag fuse (internal)Varistor24 V DC1 A24 W< 2 %Surge current / thermal cut-outVaristor35 ms @ 115 V AC / 160 ms @ 230 V AC0,5 %8000 µF0.5 kV1.5 kV3 kV4 kV-20 °C...+50 °C-40 °C...+85 °C78 %EN 50178, EN 60950, IEC950UL508; CSA; Cl. I Div. 2; GOSTME25; CE; Class2EN 61000-6 /-2, -3DimensionsClamping range (nominal / min. / max.)Length x width x heightmm²mmInput/Output4 / 0.08 / 462.5 / 52 / 90.5Input/Output4 / 0.08 / 462.5 / 52 / 90.5NoteDerating loss: 33 % @ 60 °CDerating loss: 33 % @ 60 °COrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP SNT 24W 28V 1A 1 9928890028CP SNT 24W 24V 1A 1 9928890024NoteAccessoriesA.40


connect<strong>Power</strong> single-phaseCP SNT 24 W 15 V 1.5 Aconnect<strong>Power</strong> INSTAPOWERCP SNT 24 W 12 V 1.5 ASwitch-mode power suppliesALFUSE+LFUSE+N−N−Technical dataInputInput voltageInput currentInput frequency, max.making current limitInput fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadMax. capacitance at outputInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStandardsApprovalsEMC standards85...265 V AC, 120...300 V DC460 mA @ 115 V AC; 250 mA @ 230 V AC50/ 60 HzThermistor2 A time-lag fuse (internal)Varistor15 V DC1.5 A22.5 W< 2 %Surge current / thermal cut-outVaristor35 ms @ 115 V AC / 160 ms @ 230 V AC0,5 %8000 µF0.5 kV1.5 kV3 kV4 kV-20 °C...+50 °C-40 °C...+85 °C78 %EN 50178, EN 60950, IEC950CSA; GOSTME25; CEEN 61000-6 /-2, -385...265 V AC, 120...300 V DC460 mA @ 115 V AC; 250 mA @ 230 V AC50/ 60 HzThermistor2 A time-lag fuse (internal)Varistor12 V DC1.5 A18 W< 2 %Surge current / thermal cut-outVaristor35 ms @ 115 V AC / 160 ms @ 230 V AC0,5 %8000 µF0.5 kV1.5 kV3 kV4 kV-20 °C...+50 °C-40 °C...+85 °C78 %EN 50178, EN 60950, IEC950CSA; GOSTME25; CEEN 61000-6 /-2, -3DimensionsClamping range (nominal / min. / max.)Length x width x heightmm²mmInput/Output4 / 0.08 / 462.5 / 52 / 90.5Input/Output4 / 0.08 / 462.5 / 52 / 90.5NoteDerating loss: 33 % @ 60 °CDerating loss: 33 % @ 60 °COrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP SNT 24W 15V 1.5A 1 9928890015CP SNT 24W 12V 1.5A 1 9928890012NoteAccessoriesA.41


Switch-mode power suppliesconnect<strong>Power</strong> INSTAPOWERconnect<strong>Power</strong> single-phaseLCP SNT 24 W 5 V 2 AAW HLFUSE+N−Technical dataInputInput voltageInput currentInput frequency, max.making current limitInput fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadMax. capacitance at outputInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStandardsApprovalsEMC standards85...265 V AC, 120...300 V DC460 mA @ 115 V AC; 250 mA @ 230 V AC50/ 60 HzThermistor2 A time-lag fuse (internal)Varistor5 V DC2 A10 W< 2 %Surge current / thermal cut-outVaristor35 ms @ 115 V AC / 160 ms @ 230 V AC0,5 %8000 µF0.5 kV1.5 kV3 kV4 kV-20 °C...+50 °C-40 °C...+85 °C78 %EN 50178, EN 60950, IEC950CSA; GOSTME25; CEEN 61000-6 /-2, -3DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.08 / 462.5 / 52 / 90.5Derating loss: 33 % @ 60 °COrdering dataConnection systemScrew connectionType Qty. Order No.CP SNT 24W 5V 2A 1 9928890005NoteAccessoriesA.42


connect<strong>Power</strong> single-phaseLCP SNT 25 W 5 V 5 Aconnect<strong>Power</strong> INSTAPOWERSwitch-mode power suppliesW HALFUSE+N−Technical dataInputInput voltageInput currentInput frequency, max.making current limitInput fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadMax. capacitance at outputInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStandardsApprovalsEMC standards85...264 V AC / 110...370 V DC500 mA at rated load @ 230 V AC50/ 60 HzYesFusible link 2.5 A (T) / 250 V4...8 V DC (adjustable via poti)5 A25 W120 mV pp105 %...150 % I constof max. output load; automatic resetVaristor11 ms @ 115 V AC / 50 ms @ 230 V AC1 %8000 µF0.5 kV1.5 kV3 kV4 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C70 %EN 50178 (PELV), EN 60950 (SELV)CE; cCSAus; cURus; cULus; Class2EN 55011, EN 55022, EN 61000-3-2,-3, EN 61000-6-2,-3,-4Derating curveCurrent (A)65432100 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output2.5 / 0.5 / 462.5 / 70 / 90.5Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 25W 5V 5A 1 8754960000NoteAccessoriesA.43


Switch-mode power suppliesconnect<strong>Power</strong> INSTAPOWERconnect<strong>Power</strong> single-phaseLCP SNT 48 W 12 V 4 AAW HLFUSE+N−Technical dataInputInput voltageInput currentInput frequency, max.making current limitInput fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadMax. capacitance at outputInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStandardsApprovalsEMC standards85...264 V AC / 110...370 V DC500 mA at rated load @ 230 V AC50/ 60 HzYesFusible link 2.5 A (T) / 250 V9...15 V DC (adjustable via poti)4 A48 W120 mV pp105 %...150 % I constof max. output load; automatic resetVaristor11 ms @ 115 V AC / 50 ms @ 230 V AC1 %8000 µF0.5 kV1.5 kV3 kV4 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C75 %EN 50178 (PELV), EN 60950 (SELV)cCSAus; cULus; cURus; UL; CE; Class2EN 55011, EN 55022, EN 61000-3-2,-3, EN 61000-6-2,-3,-4Derating curveCurrent (A)65432100 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output2.5 / 0.5 / 462.5 / 70 / 90.5Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 48W 12V 4A 1 8754970000NoteAccessoriesA.44


connect<strong>Power</strong> single-phaseLCP SNT 48 W 24 V 2 Aconnect<strong>Power</strong> INSTAPOWERSwitch-mode power suppliesW HALFUSE+N−Technical dataInputInput voltageInput currentInput frequency, max.making current limitInput fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadMax. capacitance at outputInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStandardsApprovalsEMC standards85...264 V AC / 110...370 V DC500 mA at rated load @ 230 V AC50/ 60 HzYesFusible link 2.5 A (T) / 250 V15...28 V DC (adjustable via poti)2 A48 W120 mV pp105 %...150 % I constof max. output load; automatic resetVaristor11 ms @ 115 V AC / 50 ms @ 230 V AC1 %8000 µF0.5 kV1.5 kV3 kV4 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C78 %EN 50178 (PELV), EN 60950 (SELV)CE; cCSAus; cULus; cURus; UL; Class2EN 55011, EN 55022, EN 61000-3-2,-3, EN 61000-6-2,-3,-4Derating curveCurrent (A)32.521.510.500 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output2.5 / 0.5 / 462.5 / 70 / 90.5Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 48W 24V 2A 1 8739140000NoteAccessoriesA.45


Switch-mode power suppliesconnect<strong>Power</strong> INSTAPOWERconnect<strong>Power</strong> single-phaseLCP SNT 48 W 48 V 1 AAW HLFUSE+N−Technical dataInputInput voltageInput currentInput frequency, max.making current limitInput fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadMax. capacitance at outputInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStandardsApprovalsEMC standards85...264 V AC / 110...370 V DC500 mA at rated load @ 230 V AC50/ 60 HzYesFusible link 2.5 A (T) / 250 V46...55 V DC (adjustable via poti)1 A48 W120 mV pp105 %...150 % I constof max. output load; automatic resetVaristor11 ms @ 115 V AC / 50 ms @ 230 V AC1 %8000 µF0.5 kV1.5 kV3 kV4 kV-10 °C...+70 °C (derating from 55 °C)-20 °C...+85 °C80 %EN 50178 (PELV), EN 60950 (SELV)CE; cCSAus; cURus; UL; Class2EN 55011, EN 55022, EN 61000-3-2,-3, EN 61000-6-2,-3,-4Derating curveCurrent (A)21,510,500 10 20 30 40 50 60 70 80Ambient temperature (°C)DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output2.5 / 0.5 / 462.5 / 70 / 90.5Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 48W 48V 1A 1 8879230000NoteAccessoriesA.46


connect<strong>Power</strong> single-phaseLCP SNT 12 W 24 V 0.5 Aconnect<strong>Power</strong> WAVEPOWERSwitch-mode power suppliesHWATechnical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standards<strong>Power</strong> factor correctionApprovals85...265 V AC, 120...300 V DC260 mA @ 115 V AC; 180 mA @ 230 V AC50/ 60 Hz2 A time-lag fuse (internal)Varistor24 V DC0.5 A12 W0.1 %Surge current / thermal cut-outVaristor30 ms @ 115 V AC / 80 ms @ 230 V AC0.6 %No0.5 kV1.5 kV3 kV4 kV-20 °C...+50 °C-40 °C...+85 °C80 %Green LEDEN 50178, EN 60950, IEC950IEC 61000-6 /-2, -3NoCSA; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output2.5 / 0.5 / 2.5112.4 / 22.5 / 92.4Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 12W 24V 0.5A 1 9918840024NoteAccessoriesSupply voltage 24 V and 0 V can be cross-connected with ZQV 2.5N/2A.47


Switch-mode power suppliesconnect<strong>Power</strong>connect<strong>Power</strong> single-phaseHCP SNT 55 W 48 V 1.04 ACP SNT 55 W 24-28 V 2.3 AAWL++LFUSE+LFUSE+NN++Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standards<strong>Power</strong> factor correctionApprovals85...265 V AC, 120...300 V DC1.1 A @ 115 V AC; 0.55 A @ 230 V AC50/ 60 Hz2 A time-lag fuse (internal)Varistor48 V DC1.04 A50 W< 50 mV effSurge current / thermal cut-outVaristor30 ms @ 115 V AC / 180 ms @ 230 V AC1 %No0.5 kV1.5 kV3 kV3 kV-20 °C...+40 °C-40 °C...+85 °C78 %Green LEDEN 50178, EN 60950, IEC950IEC 61000-6 /-2, -3NoCSA; GOSTME25; CE85...265 V AC, 120...300 V DC1.1 A @ 115 V AC; 0.55 A @ 230 V AC50/ 60 Hz2 A time-lag fuse (internal)Varistor24...28 V DC2.3 A55 W< 50 mV effSurge current / thermal cut-outVaristor30 ms @ 115 V AC / 180 ms @ 230 V AC1 %No0.5 kV1.5 kV3 kV3 kV-20 °C...+40 °C-40 °C...+85 °C78 %Green LEDEN 50178, EN 60950, IEC950IEC 61000-6 /-2, -3NoCSA; Cl. I Div. 2; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightmm²mmInput/Output4 / 0.1 / 4131 / 57 / 98Input/Output4 / 0.1 / 4131 / 57 / 98NoteDerating loss: 2.1 A / 24 V @ 50 °C; 1.5 A / 24 V @ 60 °CDerating loss: 2.1 A / 24 V @ 50 °C; 1.5 A / 24 V @ 60 °COrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP SNT 55W 48V 1.04A 1 9927480048CP SNT 55W 24-28V 2.3A 1 9927480024NoteAccessoriesBracket for wall mounting: 7920560000Bracket for wall mounting: 7920560000A.48


connect<strong>Power</strong> single-phaseHCP SNT 55 W 12-15 V 3 ACP SNT 55 W 5 V 3 Aconnect<strong>Power</strong>Switch-mode power suppliesWLA++LFUSE+LFUSE+NN++Technical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standards<strong>Power</strong> factor correctionApprovals85...265 V AC, 120...300 V DC1.1 A @ 115 V AC; 0.55 A @ 230 V AC50/ 60 Hz2 A time-lag fuse (internal)Varistor12...15 V DC3 A36 W< 50 mV effSurge current / thermal cut-outVaristor30 ms @ 115 V AC / 180 ms @ 230 V AC1 %No0.5 kV1.5 kV3 kV3 kV-20 °C...+40 °C-40 °C...+85 °C78 %Green LEDEN 50178, EN 60950, IEC950IEC 61000-6 /-2, -3NoCSA; GOSTME25; CE85...265 V AC, 120...300 V DC1.1 A @ 115 V AC; 0.55 A @ 230 V AC50/ 60 Hz2 A time-lag fuse (internal)Varistor5 V DC3 A15 W< 50 mV effSurge current / thermal cut-outVaristor30 ms @ 115 V AC / 180 ms @ 230 V AC1 %No0.5 kV1.5 kV3 kV3 kV-20 °C...+40 °C-40 °C...+85 °C78 %Green LEDEN 50178, EN 60950, IEC950IEC 61000-6 /-2, -3NoCSA; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightmm²mmInput/Output4 / 0.1 / 4131 / 57 / 98Input/Output4 / 0.1 / 4131 / 57 / 98NoteDerating loss: 2.1 A / 24 V @ 50 °C; 1.5 A / 24 V @ 60 °CDerating loss: 2.1 A / 24 V @ 50 °C; 1.5 A / 24 V @ 60 °COrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP SNT 55W 12-15V 3A 1 9927480012CP SNT 55W 5V 3A 1 9927480005NoteAccessoriesBracket for wall mounting: 7920560000Bracket for wall mounting: 7920560000A.49


Switch-mode power suppliesconnect<strong>Power</strong>connect<strong>Power</strong> single-phaseHCP SNT 160 W 48 V 3.5 ACP SNT 160 W 24-28 V 6.5 AAWLTechnical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standards<strong>Power</strong> factor correctionApprovalsmin. 85/138 V AC, max. 195/250 V AC, typ. 115...230 V AC2.9 A @ 115 V AC; 1.45 A @ 230 V AC50/ 60 Hz6.3 A time-lag fuse (internal)Varistor48 V DC3.5 A168 W0.2 % effOverload current and surge protectionVaristor40 ms @ 115 V AC / 50 ms @ 230 V AC1 %No0.5 kV1.5 kV3 kV3 kV0 °C...+50 °C-40 °C...+85 °C85 %Green LEDEN 50178, EN 60950, IEC950EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3NoGOSTME25; CEmin. 85/138 V AC, max. 195/250 V AC, typ. 115...230 V AC2.9 A @ 115 V AC; 1.45 A @ 230 V AC50/ 60 Hz6.3 A time-lag fuse (internal)Varistor24...28 V DC6.5 A156 W0.2 % effOverload current and surge protectionVaristor40 ms @ 115 V AC / 50 ms @ 230 V AC1 %No0.5 kV1.5 kV3 kV3 kV0 °C...+50 °C-40 °C...+85 °C85 %Green LEDEN 50178, EN 60950, IEC950EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3NoCE; UL; CSA; GOSTME25DimensionsClamping range (nominal / min. / max.)Length x width x heightmm²mmInput/Output4 / 0.1 / 4175 / 57 / 127Input/Output4 / 0.1 / 4175 / 57 / 127NoteDerating loss: 10 % @ 60 °CDerating loss: 10 % @ 60 °COrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP SNT 160W 48V 3.5A 1 9925340048CP SNT 160W 24-28V 6.5A 1 9925340024NoteAccessoriesBracket for wall mounting: 7920560000Bracket for wall mounting: 7920560000A.50


connect<strong>Power</strong> single-phaseHCP SNT 160 W 12-15 V 8 ACP SNT 160 W 5 V 8 Aconnect<strong>Power</strong>Switch-mode power suppliesWLATechnical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standards<strong>Power</strong> factor correctionApprovalsmin. 85/138 V AC, max. 195/250 V AC, typ. 115...230 V AC2.9 A @ 115 V AC; 1.45 A @ 230 V AC50/ 60 Hz6.3 A time-lag fuse (internal)Varistor12...15 V DC8 A96 W0.2 % effOverload current and surge protectionVaristor40 ms @ 115 V AC / 50 ms @ 230 V AC1 %No0.5 kV1.5 kV3 kV3 kV0 °C...+50 °C-40 °C...+85 °C85 %Green LEDEN 50178, EN 60950, IEC950EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3NoGOSTME25; CEmin. 85/138 V AC, max. 195/250 V AC, typ. 115...230 V AC2.9 A @ 115 V AC; 1.45 A @ 230 V AC50/ 60 Hz6.3 A time-lag fuse (internal)Varistor5 V DC8 A40 W0.2 % effOverload current and surge protectionVaristor40 ms @ 115 V AC / 50 ms @ 230 V AC1 %No0.5 kV1.5 kV3 kV3 kV0 °C...+50 °C-40 °C...+85 °C85 %Green LEDEN 50178, EN 60950, IEC950EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3NoGOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightmm²mmInput/Output4 / 0.1 / 4175 / 57 / 127Input/Output4 / 0.1 / 4175 / 57 / 127NoteDerating loss: 10 % @ 60 °CDerating loss: 10 % @ 60 °COrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP SNT 160W 12-15V 8A 1 9925340012CP SNT 160W 5V 8A 1 9925340005NoteAccessoriesBracket for wall mounting: 7920560000Bracket for wall mounting: 7920560000A.51


Switch-mode power suppliesconnect<strong>Power</strong>connect<strong>Power</strong> single-phaseHCP SNT 300 W 24 V 12.5 AAWLTechnical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionSignalling delayMonitoring functionInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standards<strong>Power</strong> factor correctionDeratingApprovals86...265 V AC, 100...200 V DC; typ 115...230 V AC3.3 A @ 115 V AC; 1.65 A @ 230 V AC50/ 60 HzThermistorVaristor22...28 V DC adjustable12.5 A300 Wat 100 kHz: 2 mV pp, At 120 Hz: 20 mV AC effOverload current and surge protectionVaristor40 ms @ 115 V AC / 40 ms @ 230 V AC0.2 %Yes, max. 5 devices, active current splitting2 sOutput voltage, current, temperature0.5 kV1.5 kV3 kV4 kV-15°C...+50°C (@ 100 % duty cycle)-40 °C...+85 °C80 %Current limiting: LED yellow / Error: LED red/ On: LED greenEN 50178, EN 60950, IEC950EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3PFC passiveDerating: 20 % @ 60 °CCSA; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.1 / 4101 / 240 / 155Ordering dataConnection systemScrew connectionType Qty. Order No.CP SNT 300W 24V 12.5A 1 9916250024NoteAccessoriesBracket for wall mounting: 7920560000A.52


connect<strong>Power</strong> 3-phaseHCP SNT 380-480 V AC / 24 Vconnect<strong>Power</strong>Switch-mode power suppliesWLATechnical dataInputInput voltageInput currentInput frequency, max.Input fuseSurge protectionOutputOutput voltageOutput currentOutput powerMax. residual rippleOverload protectionSurge protectionMains failure bridge-over timeControl at 10...100 % loadParallel connection optionOverload protectionInsulation coordination (EN 50 178)electrical isolation, output-earthelectrical isolation, input-earthelectrical isolation, input-outputelectrical isolation, I/O railGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadStatus indicationStandardsEMC standards<strong>Power</strong> factor correctionApprovals306... 550 V AC, typ.: 360...480 V AC120 mA @ 360 V AC; 100 mA @ 230 V AC50/ 60 Hz3 x 1 A time-lag fuse (internal)Varistor24 V DC2.3 A55 W< 50 mV effSurge current / thermal cut-outVaristor120 ms @ 360 V AC / 120 ms @ 480 V AC1 %NoSurge current / thermal cut-out0.5 kV1.5 kV3 kV3 kV0 °C...+50 °C-40 °C...+85 °C85 %Green LEDEN 50178, EN 60950, IEC950EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3NoCE; UL; GOSTME25;DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.1 / 4168 / 60 / 108Derating loss: 10 % @ 85 °COrdering dataConnection systemScrew connectionType Qty. Order No.CP-SNT 380-480VAC/24V 1 9917790324NoteAccessoriesBracket for wall mounting: 7920560000A.53


Switch-mode power suppliesconnect<strong>Power</strong> DC/DC converterconnect<strong>Power</strong>HCP DCDC 50 W 22-24 V DC 2 ACP DCDC 50 W 15 V DC 3 AAWLChopperTransformerRectifier andfilteringChopperTransformerRectifier andfilteringTechnical dataInputInput voltageInput fuseOutputOutput voltageOutput currentOverload protectionGeneral dataAmbient temperatureStorage temperatureStatus indicationSwitching frequencyApprovals18...30 V DC, typ. 24 V DCinternal22...24 V DC2 ASurge current cut-out with self-reset0 °C...+40 °C max. rated load-40 °C...+85 °CGreen LED200 kHzUL508; CSA; Cl. I Div. 2; GOSTME25; CE18...30 V DC, typ. 24 V DCinternal15 V DC3 ASurge current cut-out with self-reset0 °C...+40 °C max. rated load-40 °C...+85 °CGreen LED200 kHzUL508; CSA; Cl. I Div. 2; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightmm²mmInput/Output4 / 0.1 / 4131 / 57 / 98Input/Output4 / 0.1 / 4131 / 57 / 98NoteOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP DCDC 50W 22-24V 2A 1 9919372424CP DCDC 50W 15V 3A 1 9919372415NoteAccessoriesBracket for wall mounting: 7920560000Bracket for wall mounting: 7920560000A.54


CP DCDC 50 W 12 V DC 3 ACP DCDC 50 W 20-24 V DC 2 Aconnect<strong>Power</strong> DC/DC converterCP DCDC 50 W 15 V DC 3 ASwitch-mode power suppliesAChopperTransformerRectifier andfilteringChopperTransformerRectifier andfilteringChopperTransformerRectifier andfiltering9...16 V DC, typ 12 V DCinternal9...16 V DC, typ 12 V DCinternal9...16 V DC, typ 12 V DCinternal12 V DC3 ASurge current cut-out with self-reset22...24 V DC2 ASurge current cut-out with self-reset15 V DC3 ASurge current cut-out with self-reset0 °C...+40 °C max. rated load-40 °C...+85 °CGreen LED200 kHzUL508; CSA; Cl. I Div. 2; GOSTME25; CE0 °C...+40 °C max. rated load-40 °C...+85 °CGreen LED200 kHzUL508; CSA; Cl. I Div. 2; GOSTME25; CE0 °C...+40 °C max. rated load-40 °C...+85 °CGreen LED200 kHzUL508; CSA; Cl. I Div. 2; GOSTME25; CEInput/Output4 / 0.1 / 4131 / 57 / 98Input/Output4 / 0.1 / 4131 / 57 / 98Input/Output4 / 0.1 / 4131 / 57 / 98Type Qty. Order No.CP DCDC 50W 12V 3A 1 9919371212Type Qty. Order No.CP DCDC 50W 22-24V 2A 1 9919371224Type Qty. Order No.CP DCDC 50W 15V 3A 1 9919371215Bracket for wall mounting: 7920560000Bracket for wall mounting: 7920560000Bracket for wall mounting: 7920560000A.55


Switch-mode power suppliesconnect<strong>Power</strong> DC/DC converterconnect<strong>Power</strong>HCP DCDC 50 W 12 V DC 3 ACP DCDC 50 W 5 V DC 8 AAWLChopperTransformerRectifier andfilteringChopperTransformerRectifier andfilteringTechnical dataInputInput voltageInput fuseOutputOutput voltageOutput currentOverload protectionGeneral dataAmbient temperatureStorage temperatureStatus indicationSwitching frequencyApprovals18...30 V DC, typ. 24 V DCinternal12 V DC3 ASurge current cut-out with self-reset0 °C...+40 °C max. rated load-40 °C...+85 °CGreen LED200 kHzUL508; CSA; Cl. I Div. 2; GOSTME25; CE18...30 V DC, typ. 24 V DCinternal5 V DC8 ASurge current cut-out with self-reset0 °C...+40 °C max. rated load-40 °C...+85 °CGreen LED200 kHzUL508; CSA; Cl. I Div. 2; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightmm²mmInput/Output4 / 0.1 / 4131 / 57 / 98Input/Output4 / 0.1 / 4131 / 57 / 98NoteOrdering dataConnection systemType Qty. Order No.Type Qty. Order No.Screw connectionCP DCDC 50W 12V 3A 1 9919372412CP DCDC 50W 5V 8A 1 9919372405NoteAccessoriesBracket for wall mounting: 7920560000Bracket for wall mounting: 7920560000A.56


Unregulated power suppliesContentsUnregulated power suppliesUnregulated power supplies Overview B.2Unregulated power supplies – compact<strong>Power</strong> B.4BB.1


Unregulated power suppliesUnregulated power supplies – OverviewUnregulated power supplies – compact<strong>Power</strong>BCompact power supply units are important links in the powersupplies for controllers. They are utilised where processes orcontrol voltages are required that vary from the mains voltage.Transformers provide the electrical isolation between the inputcircuit and the output circuit.The minimum requirement (to VDE 0550) is 2,000 V.Screw terminals secure the input-side connection to the mains.The single-phase devices are rated for a nominal voltage of~230 ± ~15 V, or ~400 V ± ~15 V, 50/60 Hz, the 3-phasedevices for 3 x 400 V ± 5 %. The secondary DC voltage fromthe transformer is conducted to a bridge rectifier where it isrectified.The pulsating DC voltage is then fed from the rectifier andfiltered to a low residual ripple by means of an electrolyticcapacitor.This DC voltage is then fed to the output terminal. These aredesigned as pluggable screw terminals. A varistor is integratedin the output circuitry to attenuate voltage peaks. The operatingstatus is indicated by means of a green LED via the outputcircuit. Devices with 600 W and higher are equipped with a fan.Single-phase unregulated power suppliesThree-phase unregulated power suppliesB.2


Unregulated power supplies – OverviewUnregulated power suppliesWell-balanced spectrum for optimum economyBlock diagram for single-phase devices CP NTThe output currents of these practical products are defined byway of two ambient temperatures.Size selection is based on the maximum effectiveness of thecomponents.Adapted to standard voltages in accordance with IEC 38INPUT+15 V0 V–15 V230 V400 VPE.. . . .OUTPUT++24V DC--BBy choosing the appropriate terminals, the ± 15 V tappingcapability allows the single-phase devices to be connected tosix different nominal AC voltages: 215, 230, 245, 385, 400,415 V.The ± 5 % tapping capability allows the 3-phase devices to beconnected to three different nominal voltages: 380, 400, 415 V.Reliable short-circuit and overload protectionBlock diagram for 3-phase devicesCP NT3 250 / 400 / 500 WPEINPUTOUTPUT+5% 400 V –5% +5% 400 V –5% +5% 400 V –5% 3x+=+130° 24V DC~--Integrated on the secondary side in device sizes up to CP NT192 W, the FKS fuse protects against overloads andshortcircuits. For the devices CP NT 264 W and CP NT 432 W,this protection is achieved by means of a thermostatic switchbuilt into the transformer.Easy mountingKeyhole assembly simplifies mounting and saves time. Asnap-on fixing attachment for 35 mm DIN rails is available asan accessory for single-phase devices up to 144 W.Simply plugged into the device and secured with two screws,it ensures easiest possible mounting!Block diagram for 3-phase devicesCP NT3 600 / 750 / 1000 WPEINPUT+5% 400 V –5% +5% 400 V –5% +5% 400 V –5% 3x130°~=MOUTPUT++24V DC--0 VFailTransformers, vacuum-impregnated, painted black• No humming• Moisture cannot ingress into the windings• Windings mechanically secured• Improved heat dissipation from the windings• Good heat dissipationUnregulated power suppliessingle-phaseUnregulated power supplies3-phaseB.3


.. . . ... . . .Unregulated power suppliescompact<strong>Power</strong>compact<strong>Power</strong> single-phaseCP NT 36CP NT 72BINPUTOUTPUT+15V+0V+-15V 24VDC230V-400V-PEINPUTOUTPUT+15V+0V+-15V 24VDC230V-400V-PETechnical dataInputInput voltageInput currentInput frequency, max.No-load input currentExt. Back-up fuseOutputOutput voltageOutput current at 40 °COutput current at 55 °Coutput powerMax. residual rippleFuseProtective circuitInsulation coordination (EN 50 178)Electric shock protectionInsulation strengthInsulation classProtection classClass of protectionGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadMounting position, installation noticeInstallation adviceStatus indicationLength x width x heightWeightStandardsEMC standardsApprovals230 V/ 400 V ±15 V0.35 A/ 0.2 A50/ 60 Hz0,1 A / 0,06 A0.63 A / 0.315 A time-lag24 V DC SELV1.5 A1 A36 W< 5 %3 A time-lag flat cable-lug fuseVaristoracc. to BGV A34 kVBIP 20I-20 °C...+55 °C-20 °C...+80 °C80 %Arbitrary, horizontally, on terminal rail TS 35Direct mounting, TS 35 with clip-on plateGreen LED68 / 78 / 123 mm1.5 kgEN 60950, EN 61558-2-4, -6, 72/23/EWGEN 61000-6 /-2, -3cULus; GOSTME25; CE230 V/ 400 V ±15 V0.56 A/ 0.32 A50/ 60 Hz0,13 A / 0,08 A0.1 A / 0.63 A time-lag24 V DC SELV3 A2.5 A72 W< 5 %7.5 A time-lag flat cable-lug fuseVaristoracc. to BGV A34 kVBIP 20I-20 °C...+55 °C-20 °C...+80 °C83 %Arbitrary, horizontally, on terminal rail TS 35Direct mounting, TS 35 with clip-on plateGreen LED85 / 84 / 125 mm2.1 kgEN 60950, EN 61558-2-4, -6, 72/23/EWGEN 61000-6 /-2, -3cULus; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)mm²InputOutput2.5 / 0.13 / 2.5 2.5 / 0.5 / 4InputOutput2.5 / 0.13 / 2.5 2.5 / 0.5 / 4NoteOrdering dataConnection systemScrew connectionType Qty. Order No.CP NT 36W 24V 1.5A 1 8575260000Type Qty. Order No.CP NT 72W 24V 3A 1 8575270000NoteAccessoriesClip-in plate for TS35: 8588900000Clip-in plate for TS35: 8588910000B.4


.. . . ... . . .compact<strong>Power</strong> single-phaseCP NT 144CP NT 192compact<strong>Power</strong>Unregulated power suppliesINPUTOUTPUT+15V+0V+-15V 24VDC230V-400V-PEINPUTOUTPUT+15V+0V+-15V 24VDC230V-400V-PEBTechnical dataInputInput voltageInput currentInput frequency, max.No-load input currentExt. Back-up fuseOutputOutput voltageOutput current at 40 °COutput current at 55 °Coutput powerMax. residual rippleFuseProtective circuitInsulation coordination (EN 50 178)Electric shock protectionInsulation strengthInsulation classProtection classClass of protectionGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadMounting position, installation noticeInstallation adviceStatus indicationLength x width x heightWeightStandardsEMC standardsApprovals230 V/ 400 V ±15 V0.95 A/ 0.55 A50/ 60 Hz0,33 A / 0,19 A1.6 A / 1.0 A time-lag24 V DC SELV6 A5 A144 W< 5 %10 A time-lag flat cable-lug fuseVaristoracc. to BGV A34 kVBIP 20I-20 °C...+55 °C-20 °C...+80 °C88 %Arbitrary, horizontally, on terminal rail TS 35Direct mounting, TS 35 with clip-on plateGreen LED92 / 96 / 135 mm3.1 kgEN 60950, EN 61558-2-4, -6, 72/23/EWGEN 61000-6 /-2, -3cULus; GOSTME25; CE230 V/ 400 V ±15 V1.3 A/ 0.7 A50/ 60 Hz0,3 A / 0,16 A2.0 A / 1.25 A time-lag24 V DC SELV8 A7 A192 W< 5 %15 A time-lag flat cable-lug fuseVaristoracc. to BGV A34 kVBIP 20I-20 °C...+55 °C-20 °C...+80 °C90 %Direct mountingGreen LED105 / 105 / 145 mm4.3 kgEN 60950, EN 61558-2-4, -6, 72/23/EWGEN 61000-6 /-2, -3cULus; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)mm²InputOutput2.5 / 0.13 / 2.5 2.5 / 0.5 / 4InputOutput2.5 / 0.13 / 2.5 2.5 / 0.5 / 4NoteOrdering dataConnection systemScrew connectionType Qty. Order No.CP NT 144W 24V 6A 1 8575280000Type Qty. Order No.CP NT 192W 24V 8A 1 8575300000NoteAccessoriesClip-in plate for TS35: 8588920000B.5


.. . . ... . . .Unregulated power suppliescompact<strong>Power</strong>compact<strong>Power</strong> single-phaseCP NT 264CP NT 432BINPUTOUTPUT+15V+0V+-15V 24VDC230V-400V-PEINPUTOUTPUT+15V+0V+-15V 24VDC230V-400V-PETechnical dataInputInput voltageInput currentInput frequency, max.No-load input currentExt. Back-up fuseOutputOutput voltageOutput current at 40 °COutput current at 55 °Coutput powerMax. residual rippleFuseProtective circuitInsulation coordination (EN 50 178)Electric shock protectionInsulation strengthInsulation classProtection classClass of protectionGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadInstallation adviceStatus indicationLength x width x heightWeightStandardsEMC standardsApprovals230 V/ 400 V ±15 V1.8 A/ 1 A50/ 60 Hz0,5 A / 0,28 A3.15 A / 1.6 A time-lag24 V DC SELV11 A10 A264 W< 5 %Thermostatic switchVaristoracc. to BGV A34 kVBIP 20I-20 °C...+55 °C-20 °C...+80 °C93 %Direct mountingGreen LED113 / 120 / 165 mm6.1 kgEN 60950, EN 61558-2-4, -6, 72/23/EWGEN 61000-6 /-2, -3cULus; GOSTME25; CE230 V/ 400 V ±15 V2.5 A/ 1.3 A50/ 60 Hz0,54 A / 0,31 A4.0 A / 2.0 A time-lag24 V DC SELV18 A15 A432 W< 5 %Thermostatic switchVaristoracc. to BGV A34 kVBIP 20I-20 °C...+55 °C-20 °C...+80 °C95 %Direct mountingGreen LED135 / 135 / 185 mm9.1 kgEN 60950, EN 61558-2-4, -6, 72/23/EWGEN 61000-6 /-2, -3cULus; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)mm²InputOutput2.5 / 0.13 / 2.5 2.5 / 0.5 / 4InputOutput2.5 / 0.13 / 2.5 2.5 / 0.5 / 4NoteOrdering dataConnection systemScrew connectionType Qty. Order No.CP NT 264W 24V 11A 1 8575310000Type Qty. Order No.CP NT 432W 24V 18A 1 8575320000NoteAccessoriesB.6


compact<strong>Power</strong> 3-phaseCP NT3 250CP NT3 400compact<strong>Power</strong>Unregulated power suppliesBINPUTOUTPUT++5% +5% +5%400V 400V 400V=-5% -5% -5% 3x+130° 24VDCINPUTOUTPUT++5% +5% +5%400V 400V 400V=-5% -5% -5% 3x+130° 24VDCPE~--PE~--Technical dataInputInput voltageInput currentInput frequency, max.No-load input currentInput fuseExt. Back-up fuseOutputOutput voltageOutput current at 40 °C / 60 °Coutput powerMax. residual rippleFuseProtective circuitInsulation coordination (EN 50 178)Electric shock protectionInsulation strengthInsulation classProtection classClass of protectionGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadInstallation adviceFan signalLength x width x heightStatus indicationWeightStandardsEMC standardsApprovals3 x 400 V ±5 %0.5 A50/ 60 Hz0,1 A3 x primary thermostatic switch3 x 1.0 A time-lag24 V DC SELV11 A / 10 A250 W< 2 %External 10 A time-lagVaristoracc. to BGV A34 kVBIP 20I-20 °C...+60 °C-20 °C...+80 °C76 %Direct mountingNo integrated fan185 / 84 / 192 mmGreen LED4.7 kgEN 60950, EN 61558-2-4, -6, 72/23/EWGEN 61000-6 /-2, -3cCSAus; GOSTME25; CE3 x 400 V ±5 %0.75 A50/ 60 Hz0,11 A3 x primary thermostatic switch3 x 1.2 A time-lag24 V DC SELV18 A / 16 A400 W< 2 %External 16/18 A time-lagVaristoracc. to BGV A34 kVBIP 20I-20 °C...+60 °C-20 °C...+80 °C77 %Direct mountingNo integrated fan220 / 88 / 213 mmGreen LED6.9 kgEN 60950, EN 61558-2-4, -6, 72/23/EWGEN 61000-6 /-2, -3cCSAus; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)mm²InputOutput2.5 / 0.5 / 2.5 6 / 0.5 / 6InputOutput2.5 / 0.5 / 2.5 6 / 0.5 / 6NoteCondensation not allowedCondensation not allowedOrdering dataConnection systemScrew connectionType Qty. Order No.CP NT3 250W 24V 10A 1 8628620000Type Qty. Order No.CP NT3 400W 24V 15A 1 8628630000NoteAccessoriesB.7


Unregulated power suppliescompact<strong>Power</strong>compact<strong>Power</strong> 3-phaseCP NT3 500CP NT3 600BINPUTOUTPUT++5% +5% +5%400V 400V 400V=-5% -5% -5% 3x+130° 24VDCPE-~-INPUT+5% +5% +5%400V 400V 400V-5% -5% -5% 3x130°PE~=OUTPUT++24VDCM--0VFailTechnical dataInputInput voltageInput currentInput frequency, max.No-load input currentInput fuseExt. Back-up fuseOutputOutput voltageOutput current at 40 °C / 60 °Coutput powerMax. residual rippleFuseProtective circuitInsulation coordination (EN 50 178)Electric shock protectionInsulation strengthInsulation classProtection classClass of protectionGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadInstallation adviceFan signalLength x width x heightStatus indicationWeightStandardsEMC standardsApprovals3 x 400 V ±5 %0.9 A50/ 60 Hz0,13 A3 x primary thermostatic switch3 x 1.6 A time-lag24 V DC SELV22 A / 20 A500 W< 2 %External 20/22 A time-lagVaristoracc. to BGV A34 kVBIP 20I-20 °C...+60 °C-20 °C...+80 °C78 %Direct mountingNo integrated fan220 / 108 / 215 mmGreen LED10 kgEN 60950, EN 61558-2-4, -6, 72/23/EWGEN 61000-6 /-2, -3cULus; cCSAus; GOSTME25; CE3 x 400 V ±5 %1.2 A50/ 60 Hz0,15 A3 x primary thermostatic switch3 x 2 A time-lag24 V DC SELV26 A / 25 A600 W< 2 %External 25/26 A time-lagVaristoracc. to BGV A34 kVBIP 20I-20 °C...+60 °C-20 °C...+80 °C78 %Direct mountingOpen collector


compact<strong>Power</strong> 3-phaseCP NT3 750CP NT3 1000compact<strong>Power</strong>Unregulated power suppliesBINPUT+5% +5% +5%400V 400V 400V-5% -5% -5% 3x130°PE~=OUTPUT++24VDCM--0VFailINPUT+5% +5% +5%400V 400V 400V-5% -5% -5% 3x130°PE~=OUTPUT++24VDCM--0VFailTechnical dataInputInput voltageInput currentInput frequency, max.No-load input currentInput fuseExt. Back-up fuseOutputOutput voltageOutput current at 40 °C / 60 °Coutput powerMax. residual rippleFuseProtective circuitInsulation coordination (EN 50 178)Electric shock protectionInsulation strengthInsulation classProtection classClass of protectionGeneral dataAmbient temperatureStorage temperatureDegree of efficiency at max. loadInstallation adviceFan signalLength x width x heightStatus indicationWeightStandardsEMC standardsApprovals3 x 400 V ±5 %1.4 A50/ 60 Hz0,16 A3 x primary thermostatic switch3 x 2.5 A time-lag24 V DC SELV32 A / 30 A750 W< 2 %External 30/32 A time-lagVaristoracc. to BGV A34 kVBIP 20I-20 °C...+60 °C-20 °C...+80 °C77 %Direct mountingOpen collector


Unregulated power suppliesBB.10


ContentsUPS control unitUPS control unitUPS control unit Overview C.2UPS control unit C.3CC.1


Input: 100 - 120 V AC200 - 240 V AC50 / 60 HzOutput: 24 V DC 10 A6-10 A Cha r . Cmax. 250 V AC / 1 A30 V DC / 1 AL N PE 12 11 14 +V +V -V -VAdj.24...26 V DCUPS control unit – OverviewUPS control unitconnect<strong>Power</strong>When the power supply fails, UPS control units take over the12/24 V DC power supplies to the installation within seconds,and guarantee plant availability for a defined length of time.Switch-mode power supplies, battery control unit andbattery providing an uninterrupted power supply.CProfessional signalling guarantees that all relevant signalstatuses can be evaluated on the spot. Critical statuses can alsobe immediately redirected to a higher-level controller.230 V AC115 V AC8708680000CP SNT 250 W 24 V 10 A<strong>Power</strong> supplyThe battery module undertakes complete battery managementof the connected lead-acid batteries. Constant charging anddischarging plus electronic overcurrent protection guarantee anextremely long operational lifetime for the batteries.\%DC OK •Status r elays(change-overcontact)115/230 V AC50/60 HzBatterycont r ol unit+-PE PSN PSL PSLNPE+-+-Alarm contactAccumulator+-to the load ci r cuitC.2


UPS control unitconnect<strong>Power</strong>HCP-BBU 115-230 V AC / 12 V DCUPS control unitWLNgL BBU+++ -- -- + + -1 2 nLoadsCP/SNgL + +- -115/230V50/60HzTechnical dataInputInput voltageInput currentInput frequency, max.Input fusemaking current limitSurge protectionOutputOutput voltageOutput currentMains failure bridge-over timeBattery charging currentBattery voltageControl at input voltageGeneral dataAmbient temperatureStorage temperatureStatus indicationStandardsEMC standardsApprovals85...265 V AC; 120...300 V DC; typ.115...230 V AC ±10 %0.8 A @ 115 V AC; 0.5 A @ 230 V AC50 / 60 Hz2 A time-lag fuse (internal)ThermistorVaristor12 V DCmax. 15 A / max. 9.0 A for power supply3 A13,65 V0.2 %-20 °C...+50 °C-20 °C...+85 °CGreen LED (full charge): battery voltage > 14.75 V DC, YellowLED (low battery): battery voltage < 11 V DC, Yellow LED(charging): BBU is loading battery, Red LED (error): no ACinput voltage, Red LED (reversed battery): battery poles arereversedEN 50178, EN 60950, IEC950EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3CSA; Cl. I Div. 2; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.1 / 4161 / 72.5 / 127.5Ordering dataConnection systemScrew connectionType Qty. Order No.CP-BBU 115-230VAC / 12VDC 1 9916280012NoteAccessoriesBracket for wall mounting: 7920560000C.3


UPS control unitUPS control unitconnect<strong>Power</strong>HCP-BBU 115-230 V AC / 24 V DCWLNgL BBU+++ -- -- + + -1 2 nLoadsCP/SNgL + +- -115/230V50/60HzTechnical dataInputInput voltageInput currentInput frequency, max.Input fusemaking current limitSurge protectionOutputOutput voltageOutput currentMains failure bridge-over timeBattery charging currentBattery voltageControl at input voltageGeneral dataAmbient temperatureStorage temperatureStatus indicationStandardsEMC standardsApprovals85...265 V AC; 120...300 V DC; typ.115...230 V AC ±10 %1 A @ 115 V AC; 0.6 A @ 230 V AC50 / 60 Hz2 A time-lag fuse (internal)ThermistorVaristor24 V DCmax. 15 A / max. 9.0 A for power supply2 A27,3 V0.2 %-20 °C...+50 °C-20 °C...+85 °CGreen LED (full charge): battery voltage > 29.5 V DC, YellowLED (low battery): battery voltage < 22 V DC, Yellow LED(charging): BBU is loading battery, Red LED (error): no ACinput voltage, Red LED (reversed battery): battery poles arereversed, LED red (battery open): no battery is connectedEN 50178, EN 60950, IEC950EN 55011, EN 55022, EN 55024, EN 61000-6-2, 3CSA; Cl. I Div .2; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmInput/Output4 / 0.1 / 4161 / 72.5 / 127.5Ordering dataConnection systemScrew connectionType Qty. Order No.CP-BBU 115-230VAC / 24VDC 1 9916280024NoteAccessoriesBracket for wall mounting: 7920560000C.4


ContentsFuse protection for 24 V DC circuitsFuse protection for24 V DC circuitsFuse protection for 24 V DC circuits Overview D.2WAVEGUARD D.4DD.1


Fuse protection for 24 V DC circuits – OverviewFuse protection for24 V DC circuitsFuse protectionDA 24-V DC control voltage has become the standard in theautomation industry. Selective fuse protection is often usedwhen the power is being supplied by PLC-guided controllers.It divides the total load into separate, logically connected safetycircuits. For example, the CPU, actuators and sensors can beseparated in the load circuits. This selective load protectionhelps to decrease facility downtime and also to simplifytroubleshooting. When a disruption (short circuit) occurs ona standard protective system, the entire power supply isinterrupted. In a system using selective fuse protection, only thefuse in the one disrupted load circuit is triggered. If the fuse istriggered quick enough so that other loads (and particularly theCPU) can continue functioning properly, then various controlalgorithms can be used to deal with the disruption. It is thenpossible to shut down the facility in an orderly and controlledfashion.A fundamental problem when using ordinary fuses is that theytake a relatively long time to trigger. Usually, a switched-modepower supply is already well over the surge-current limit (typically120 % of I nom ) before its fuse triggers. Ordinary fuses aretherefore not suitable for constructing a selective fuse protectivesystem. Such systems present DC fuses with specialchallenges. They must be able to switch off quickly enough butthey must also be able to tolerate the start-up surge currentsfrom consumer loads.Weidmüller‘s electronic fuses, from ourestablished WAVEGUARD line, are the answer to both of thesechallenges: they are quick acting but can also tolerate start-upcurrents. You can easily implement selective load protectionusing our WAVEGUARD models.In addition, Weidmüller‘s electronic fuses feature a floating alarmcontact and a reset input. This allows a PLC controller to querythe status of the fuse or to perform an automated reset aftertroubleshooting. This provides you with a convenient method forremotely maintaining a complex facility. As a result, you saveboth time and money.D.2


Fuse protection for 24 V DC circuits – OverviewFuse protection for24 V DC circuitsResettingBlock diagram WaveGua rdWAVEGUARDS can be reset manually or by using an externalsignal. They can be reset remotely by simply applying a 24 Vsignal pulse on the reset input. The reset occurs on the fallingedge of the signal.Note: A cyclical automatic reset is not permitted and can leadto a malfunction.INPUT(8)24V(1)Reset(7)0VgnrtfailOUTPUT(9)24V(2)(3)NC contact50V uc /0.05ADSignallingA red LED displays when the electronic fuse has been triggered.An alert is also sent out over a floating alarm contact. A greenLED signals that the unit is switched on. The alarm contact usesa NC contact.WaveGua rdD.3


WAVEGUARDFuse protection for24 V DC circuitsL24 V DC 1.6 A24 V DC 3.15 AHWDINPUT24 V (8)(1)Reset0V(7)gnrtfailOUTPUT(9)24 V(2)NC contact(3)50 V uc /0.05 ACurrent20181614121086420( A )0 20 40 60 80 100 120 140 160Ti m e ( ms)Current242220181614121086420( A )0 10 15 20 25 30 35 40 45 50 55 60 65 70Ti m e ( ms)Technical dataInputRated control voltageRated currentResetOutputStatus relay / CO contactSignalling delayGeneral dataAmbient temperatureStorage temperatureStatus indicationStandardsEMC standardsSliding switchApprovals24 V DC1.6 AImpulse > 100 ms +24 V, falling edge ONNC contact, max. 50 V / 0.05 A; for low voltage only!3,5 ms typ.0°C...+55 °C (side by side)-20 °C...+85 °CLED green: OK, LED red: trippedEN 50178EN 55011, EN 61000-6-1, 2, 4OFF - wait 10 s - ON; on / offcURus; GOSTME25; CE24 V DC3.15 AImpulse > 100 ms +24 V, falling edge ONNC contact, max. 50 V / 0.05 A; for low voltage only!3,5 ms typ.0°C...+55 °C (side by side)-20 °C...+85 °CLED green: OK, LED red: trippedEN 50178EN 55011, EN 61000-6-1, 2, 4OFF - wait 10 s - ON; on / offcURus; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmScrew connection Tension clamp connection2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.592.4 / 22.5 / 72 92.4 / 22.5 / 72Periodic auto-reset not permitted; Tu=23 °C, single moduleScrew connection Tension clamp connection2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.592.4 / 22.5 / 72 92.4 / 22.5 / 72Periodic auto-reset not permitted; Tu=23 °C, single moduleOrdering dataScrew connectionTension clamp connectionType Qty. Order No.WGS 24Vdc 1,6A 1 8618890000WGZ 24Vdc 1,6A 1 8621040000Type Qty. Order No.WGS 24Vdc 3,15A 1 8618910000WGZ 24Vdc 3,15A 1 8621030000NoteAccessoriesSupply voltage +24 V and 0 V can be cross-connected with ZQV 2.5N/2Supply voltage +24 V and 0 V can be cross-connected with ZQV 2.5N/2D.4


WAVEGUARDL24 V DC 6.3 A24 V DC 8 AFuse protection for24 V DC circuitsHWINPUT24 V (8)(1)Reset0V(7)gnrtfailOUTPUT(9)24 V(2)NC contact(3)50 V uc /0.05 ACurrent262422201816141210864( A )0 10 15 20 25 30 35 40 45 50 55 60T i m e ( m s )Current( A )6560555045403530252015105T i m e ( m s )0 5 10 15 20 25 30 35 40 45 50DTechnical dataInputRated control voltageRated currentResetOutputStatus relay / CO contactSignalling delayGeneral dataAmbient temperatureStorage temperatureStatus indicationStandardsEMC standardsSliding switchApprovals24 V DC6.3 AImpulse > 100 ms +24 V, falling edge ONNC contact, max. 50 V / 0.05 A; for low voltage only!3,5 ms typ.0°C...+55 °C (side by side)-20 °C...+85 °CLED green: OK, LED red: trippedEN 50178EN 55011, EN 61000-6-1, 2, 4OFF - wait 10 s - ON; on / offcURus; GOSTME25; CE24 V DC8 AImpulse > 100 ms +24 V, falling edge ONNC contact, max. 50 V / 0.05 A; for low voltage only!3,5 ms typ.0°C...+55 °C (side by side)-20 °C...+85 °CLED green: OK, LED red: trippedEN 50178EN 55011, EN 61000-6-1, 2, 4OFF - wait 10 s - ON; on / offcURus; GOSTME25; CEDimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmScrew connection Tension clamp connection2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.592.4 / 22.5 / 72 92.4 / 22.5 / 72Periodic auto-reset not permitted; Tu=23 °C, single moduleScrew connection Tension clamp connection2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.592.4 / 22.5 / 72 92.4 / 22.5 / 72Periodic auto-reset not permitted; Tu=23 °C, single moduleOrdering dataScrew connectionTension clamp connectionType Qty. Order No.WGS 24Vdc 6,3A 1 8618930000WGZ 24Vdc 6,3A 1 8621020000Type Qty. Order No.WGS 24Vdc 8,0A 1 8618940000WGZ 24VDC 8,0A 1 8621010000NoteAccessoriesSupply voltage +24 V and 0 V can be cross-connected with ZQV 2.5N/2Supply voltage +24 V and 0 V can be cross-connected with ZQV 2.5N/2D.5


WAVEGUARDFuse protection for24 V DC circuitsL24 V DC 0.5...5 AHWINPUT24 V (8)(1)Reset(7)0VgnrtfailOUTPUT(9)24 V(2)NC contact(3)50 V uc /0.05 ADTechnical dataInputRated control voltageRated currentResetOutputStatus relay / CO contactSignalling delayGeneral dataAmbient temperatureStorage temperatureStatus indicationStandardsEMC standardsSliding switchApprovals24 V DC0.5...5 A adjustableImpulse > 100 ms +24 V, falling edge ONNC contact, max. 50 V / 0.05 A; for low voltage only!3,5 ms typ.0°C...+55 °C (side by side)-20 °C...+85 °CLED green: OK, LED red: trippedEN 50178EN 55011, EN 61000-6-1, 2, 4OFF - wait 10 s - ON; on / offcURus; CEDerating curveDynamic tripping characteristicTripping current: 0.5 ATripping current( A )2520151050Time (ms)0 20 40 60 80 100 120 140Tripping current: 5.0 ATripping current( A )2520151050Time (ms)0 20 40 60 80 100 120 140DimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mmScrew connection Tension clamp connection2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.592.4 / 22.5 / 72 92.4 / 22.5 / 72Periodic auto-reset not permitted; Tu=23 °C, single moduleOrdering dataScrew connectionTension clamp connectionType Qty. Order No.WGS 24Vdc 0.5...5A 1 8710270000WGZ 24Vdc 0.5...5A 1 8727630000NoteAccessoriesSupply voltage +24 V and 0 V can be cross-connected with ZQV 2.5N/2D.6


IP 65 switched-mode power supply /Electrical-cabinet socket outletContentsIP 65 switched-mode power supply /Electrical-cabinet socket outletIP 65 switched-mode power supply /Electrical-cabinet socket outletFactory automation E.2Field<strong>Power</strong> ® DC network E.4Field<strong>Power</strong> ® Control E.6Help with project planning E.11Drilling template E.12Electrical-cabinet socket outlet E.13EE.1


IP 65 switched-mode power supply /Electrical-cabinet socket outletFactory automationField<strong>Power</strong> ® DC networkWith decentralised fuse protection for spur linesThe demand for 24 V current in facilities has grown as productivity increases. Modularand decentralised topologies have long been firmly established. Yet the auxiliary poweris still often being generated in the electrical cabinet and transmitted with significantpower loss to the field using long cables. Standard compliant fuse protection for theselines is thus repeatedly ignored since such protection is difficult to implement on suchlong stretches.Field<strong>Power</strong> ® –Solutions for Decentralised AutomationProduct InformationThe new Field<strong>Power</strong> ® switch-mode power supply creates and protects the currentsupply directly at the consumer site. Its many features make it possible to operatehighly dependable and energy efficient DC power networks.EThe full line of Field<strong>Power</strong> ® productsis listed in our product information.(Order No. 1229860000)E.2


Factory automationIP 65 switched-mode power supply /Electrical-cabinet socket outletMore than just a power supplyThis power-bus-compatible power supply unit does nottrigger the 400 V group protective device when reactingto load current peaks. In addition to the power supply unit,the Field<strong>Power</strong> ® Terminal can also be used for quick anderror-free supply to other 400 V consumer loads.Voltage stability andsupply reliabilityActuating variable and load limit24.25 24V23.75V23.25V23U / V≤ 300msExtended application rangeThe Field<strong>Power</strong> ® switch-mode power supply can beoperated in practically any installed position in temperaturesranging from –30 to +50 °C. It can even be used inrefrigerated warehouses.210 2.5 5 5.3 7.5 10 12.5I / ALoadshare busE<strong>Power</strong>Boost for branch fuse protectionRail-mounted fuse protection for branch-offs can beinstalled into the Field<strong>Power</strong> ® power supply housing.The <strong>Power</strong>Boost from one or more power supplies canselectively trigger the fuse after a short circuit.Highly reliable power supplyThe power supply unit functions even if there is a phaseoutage. A <strong>Power</strong>Boost (2x I N for 300 ms) is available forstart-up and load currents. A high voltage stability canbe achieved especially when implementing multiple feedswith a load-balancing mechanism.When using multiple power feeds in decentralised24 V DC structures, different loads are placed onthe individual power supply units. Overloads oreven outages can occur as a result. TheField<strong>Power</strong> ® switch-mode power suppliesfeature passive and active load balancingmechanisms. An actuating variable is used toreduce the voltage as the load increases, so thatthe neighbouring components are supportedmore strongly. If a power supply unit exceeds itsrated current, the voltage on the load limit isreduced until the other power supplies assumethis load. Even when in this operational state, thevoltage remains at a high level. Complete loadbalancing is achieved with the point-to-pointconnections of all load share bus ports.DC-power system with Field<strong>Power</strong> ®switched-mode power supply units24 V DC400 V ACSimpleAC and DC are handled identically. The wire is positionedand contact is established with a simple turning movement.The 5-pin DC contact module has 2 x 24 V plus GND forpermanent and safety-compliant power supply, or forminimising voltage drops with two parallel 6-mm² wirecores each.DC power is distributed in parallel with the 400 Vpower bus. A uniform voltage level in the DCdistribution (even when using wires with reducedcross-sections) is made possible by multiple parallelfedpower supply units with high IP protection.E.3


IP 65 switched-mode power supply /Electrical-cabinet socket outletField<strong>Power</strong> ® DC networkField<strong>Power</strong> ® Box with decentralisedswitch-mode power supply• Field<strong>Power</strong> ® Box with three-phase 24 V / 5 Aswitched-mode power supply.• Close-to-load 24 V power generation anddistribution for decentralised DC-systems• Reduced voltage drops for copper-optimisedField<strong>Power</strong> ® Box 10P SNTField<strong>Power</strong> ® Box 10P SNT 4XVGWith 4 additional M20 cable glandsinstallations• More reliable power supply with constant voltage• Improved energy efficiency with minimaltransmission-related lossesL1L2AC+L3PEDC–EBasic operation is possible with two phases*Technical data Field<strong>Power</strong> ® BoxRated dataRated cross-section6 mm²6 mm²Rated voltage / Rated current800 V / 41 A800 V / 41 ARated impulse voltage8 kV8 kVGeneral dataUL 94 flammability rating5VA5VAIngress protection classIP 65IP 65Assembly temperature range, min. – max.10 °C … 40 °C10 °C … 40 °CAmbient temperature (operational)-30 °C …. +50 °C-30 °C …. +50 °CIDC connection clamping capacity - power cableClamping range, min.-max.2.5 mm² … 6 mm²2.5 mm² … 6 mm²Blade size0.6 x 3.5 mm0.6 x 3.5 mmPUSH IN connection clamping capacity - distributionClamping range, min.-max.0.75 mm² … 6 mm²0.75 mm² … 6 mm²Stripping length / Blade size14 mm / 0.6 x 3.5 mm14 mm / 0.6 x 3.5 mmNoteRefer to PT6 1957620000 for additional technical clampingspecifications.Refer to PT6 1957620000 for additional technical clampingspecifications.Technical data for power supplyInput dataRated input voltage400...480 V AC** -15 % / +5 % (3~, PE)400...480 V AC** -15 % / +5 % (3~, PE)Input fuse (internal)YesYesOutput dataRated output voltage24.25 V DC ± 50 mV (23.5…28.0 V DC)24.25 V DC ± 50 mV (23.5…28.0 V DC)Rated output current @ U rated<strong>Power</strong>boost @ 24 V DC, 0..5 A, ED = 10 %, three-phase5 A @ 24 V DC10 A, t ≤ 300 ms5 A @ 24 V DC10 A, t ≤ 300 msShort-circuit-proofYesYesOutput power @ 24 V DC120 W120 WConnection dataInputOutputInputOutputtype of connectionPlug-in connectorPlug-in connectorPlug-in connectorPlug-in connectorNumber of terminalsL1, L2, L3, PE +, +, -, -, COM ,NOL1, L2, L3, PE +, +, -, -, COM ,NOconductor cross-section, min.-max.0.5 mm² … 4 mm² 0.5 mm² … 4 mm²0.5 mm² … 4 mm² 0.5 mm² … 4 mm²Note* No power boost in two-phase mode or in current-limiting mode.** UL approval is pending.Refer to BG SNT PT6 1101940000 for additional technical specificationson the power supply.* No power boost in two-phase mode or in current-limiting mode.** UL approval is pending.Refer to BG SNT PT6 1101940000 for additional technical specificationson the power supply.Ordering dataType Qty. Order No.FP Box 10P SNT 1 1132320000Type Qty. Order No.FP Box 10P SNT 4XVG 1 1076510000NoteEnclosure seals can be ordered separately.Enclosure seals (3xD0, 2xD11, 2xD13, 2xD15) and PTDS 4 connectorare included in delivery.AccessoriesNotePT6 DC 1126840000 contact blockPT6 DC 1126840000 contact blockE.4


Switch-mode power supply 24 V / 5 A• Three-phase built-in 24-V/5-A power supplywith high degree of efficiency.• External heat sink reduces warming withinelectrical cabinet.• Resistant to vibration – in compliance withBG SNT PT6Field<strong>Power</strong> ® DC networkIP 65 switched-mode power supply /Electrical-cabinet socket outletEN 61373 Cat. 1b for decentralised machineswitchboxes.L1L2AC+L3PEDC–Basic operation is possible with two phases*Technical dataInput dataRated input voltageAC frequency rangeAC current consumptionStart-up surge current / start-up timeInput fuse (internal)Output dataRated output voltageMax. residual ripple, inrush peaksOutput deviationRated output current @ U rated<strong>Power</strong>boost @ 24 V DC, 0..5 A, ED = 10 %, three-phaseOutput characteristic curve / current limitShort-circuit-proofOutput power @ 24 V DCMains buffering @ I ratedEfficiencyProtection against reverse voltages from the loadGeneral dataAmbient temperature (operational)Ingress protection class, with PE connectionSurge category / Pollution severityMTBF according to IEC 1709 (SN29500)EMC / shock / vibrationNoise emission acc. to EN 55022 (class)Noise immunity testsResistance against vibration and shockElectrical safetyElectrical machine equipmentFor use with electronic equipmentSafety extra-low voltageConnection dataType of connectionNumber of terminalsConductor cross-section, min.-max.Note400 … 480 V AC** -15 % / +5 % (3~, PE)47 Hz - 63 Hz~ 0.4 A @ 400 V AC< 10 A @ 400 V AC / < 2 sYes24.25 V DC ± 50 mV (23.5 … 28.0 V DC)< 50 mVss @ 24 V DC / 5 A500 mV @ 0 … 5 A5 A @ 24 V DC10 A, t ≤ 300 msIU, 5.3 A ± 0.2 AYes120 W20 ms @ 400 V AC~ 86 % @ 400 V AC≤ 34 V-30 °C …. +50 °CIIII / 2> 500.000 h @ 25°CAaccording to EN 61000-6-2according to EN 61373 Cat. 1baccording to EN 60204according to EN 50178 / VDE 0160according to SELV: EN 60950 / PELV: EN 60204InputOutputPlug-in connectorPlug-in connectorL1, L2, L3, PE +, +, -, -, COM ,NO0.5 mm² … 4 mm² 0.5 mm² … 4 mm²* No power boost in two-phase mode or in current-limiting mode.** UL approval is pending.EOrdering dataType Qty. Order No.BG SNT PT6 1 1101940000NoteAssembly accessories are included in delivery.AccessoriesNoteE.5


61.5IP 65 switched-mode power supply /Electrical-cabinet socket outletField<strong>Power</strong> ® Control<strong>Power</strong>Terminal forAC/DC applicationsContact element for power distribution usinguncut wires with cross-sections from 2.5 to6 mm². Feed-in / T-branch tap viaPUSH IN connection (0.75 to 10 mm²) and/orplug-in connection (0.5 to 4 mm²). Clear wirePT6for AC applicationsPT6 DCfor DC applicationsmapping with DC labelling and coded on PE pole.• <strong>Power</strong> supply• <strong>Power</strong> distribution• <strong>Power</strong> branching53.9AC labellingDC labelling139.5ETechnical dataRated data according to IEC 60947-7-1Rated cross section6 mm²6 mm²Rated voltage / Rated current800 V / 41 A800 V / 41 ARated impulse voltage8 kV8 kVGeneral dataInsulation material/material colourPA/greyPA/greyUL 94 flammability ratingV0V0free from halogens/Silicone-freeYes/YesYes/YesIngress protection classIP 20IP 20Assembly temperature range, min. – max.10 °C ... 40 °C10 °C ... 40 °COperating temperature, min.-max.-40 °C ... 55 °C-40 °C ... 55 °CCan be codedYes/Coded on PEYes/Coded on PEIDC connection clamping capacity - power cablesolid, min.-max.1.5 mm²…6 mm²1.5 mm²…6 mm²stranded, min.-max.2.5 mm²…6 mm²2.5 mm²…6 mm²flexible, min.-max.2.5 mm²…6 mm²2.5 mm²…6 mm²flexible, min.-max.2.5 mm²…6 mm²2.5 mm²…6 mm²Blade size0.6 x 3.5 mm0.6 x 3.5 mmPUSH IN connection clamping capacity - distributionsolid, min.-max.0.5 mm²…6 mm²0.5 mm²…6 mm²stranded, min.-max.0.5 mm²…6 mm²0.5 mm²…6 mm²flexible, min.-max.0.5 mm²…10 mm²0.5 mm²…10 mm²flexible, wire end ferrule 8 mm, DIN 46228/1, min-max.0.5 mm²…6 mm²0.5 mm²…6 mm²flexible, wire end ferrule 8 mm, DIN 46228/4, min-max.0.5 mm²…6 mm²0.5 mm²…6 mm²flexible, wire end ferrule 12 mm, DIN 46228/1, min-max.0.5 mm²…6 mm²0.5 mm²…6 mm²flexible, wire end ferrule 12 mm, DIN 46228/4, min-max.0.5 mm²…6 mm²0.5 mm²…6 mm²flexible, min.-max.0.5 mm²…6 mm²0.5 mm²…6 mm²Stripping length / Blade size14 mm / 0.6 x 3.5 mm14 mm / 0.6 x 3.5 mmRated data according to ULStandardUL 1059UL 1059Rated voltage / Rated current600 V/30 A600 V/30 AAWG conductor (field wiring) min./max.14 /1014 /10NoteFor use with UL-listed TC-ER cablesFor use with UL-listed TC-ER cablesNoteUL approval is pending.Ordering dataType Qty. Order No.PT6 1 1957620000Type Qty. Order No.PT6 DC 1 1126840000NoteAccessoriesNotePlug-in connector PTS 4 1952120000Plug-in connector PTDS 4 1952130000Plug-in connector PTS 4 DC 1131730000Plug-in connector PTDS 4 DC 1009990000E.6


Connector for AC applicationsPlug-in connector for use by the pluggable outputof the contact elements. Individual wires can beconnected with PUSH IN method: for crosssectionsfrom 0.5 to 4 mm².Can be coded and locked, with printing forPTS 4PTDS 42 connections per poleField<strong>Power</strong> ® ControlIP 65 switched-mode power supply /Electrical-cabinet socket outlettrouble free wiring.Clear wire mapping with coding for PEconnections.55.45 27.355.45 27.336.152236.1522ETechnical dataRated data according to IEC 60947-7-1Rated cross section4 mm²4 mm²Rated voltage / Rated current690 V / 32 A690 V / 32 ARated impulse voltage8 kV8 kVGeneral dataType of mountingPluggedPluggedInsulation material/material colourPA GF/blackPA GF/blackUL 94 flammability ratingV0V0Continuous operating temp., min.-max.-50 °C ... 120 °C-50 °C ... 120 °COutgoing direction of conductor90°90°Test point2 mm2 mmCan be codedYes/Coded on PEYes/Coded on PEConductor connection systemPush InPush InNo. of poles55Number of connections / pole12Clamping capacity, Push-In connectionClamping range, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Solid, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Stranded, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, ferrule, 8 mm, DIN 46228/1, min-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, ferrule, 8 mm, DIN 46228/4, min-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, ferrule, 12 mm, DIN 46228/1, min-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, ferrule, 12 mm, DIN 46228/4, min-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Stripping length/Blade size12 mm / 3.0 x 0.5 mm12 mm / 3.0 x 0.5 mmRated data acc. to ULStandardUL 1059UL 1059Rated voltage/Rated current600 V/20 A600 V/20 AAWG conductor (field wiring), min./max.16 /1216 /12NoteOrdering dataType Qty. Order No.PTS 4 10 1952120000Type Qty. Order No.PTDS 4 10 1952130000NoteAccessoriesNoteZVR ZP2.5 locking element 1816130000ZVR ZP2.5 locking element 1816130000E.7


IP 65 switched-mode power supply /Electrical-cabinet socket outletField<strong>Power</strong> ® ControlPlug-in connectors forDC applicationsPlug-in connectors for use with the pluggableoutlet of the PT6 contact elements. Single-wirePUSH IN connection for wire cross-sectionsranging from 0.5 to 4 mm².Can be coded and latched down.PTS 4 DCPTDS 4 DC2 connections per poleClear wire mapping with DC labelling and codingfor PE connections.55.45 27.355.45 27.336.152236.1522ETechnical dataRated data according to IEC 60947-7-1Rated cross section4 mm²4 mm²Rated voltage / Rated current690 V / 32 A690 V / 32 ARated impulse voltage8 kV8 kVGeneral dataType of mountingPluggedPluggedInsulation material/material colourPA GF/blackPA GF/blackUL 94 flammability ratingV0V0Continuous operating temp., min.-max.-50 °C ... 120 °C-50 °C ... 120 °COutgoing direction of conductor90°90°Test point2 mm2 mmCan be codedYes/Coded on PEYes/Coded on PEConductor connection systemPush InPush InNo. of poles55Number of connections / pole12Clamping capacity, Push-In connectionClamping range, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Solid, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Stranded, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, ferrule, 8 mm, DIN 46228/1, min-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, ferrule, 8 mm, DIN 46228/4, min-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, ferrule, 12 mm, DIN 46228/1, min-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, ferrule, 12 mm, DIN 46228/4, min-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Flexible, min.-max.0.5 mm² … 4 mm²0.5 mm² … 4 mm²Stripping length/Blade size12 mm / 3.0 x 0.5 mm12 mm / 3.0 x 0.5 mmRated data acc. to ULStandardUL 1059UL 1059Rated voltage/Rated current600 V/20 A600 V/20 AAWG conductor (field wiring), min./max.16 /1216 /12NoteUL approval is pending.UL approval is pending.Ordering dataType Qty. Order No.PTS 4 DC 10 1131730000Type Qty. Order No.PTDS 4 DC 10 1009990000NoteAccessoriesNoteZVR ZP2.5 locking element 1816130000ZVR ZP2.5 locking element 1816130000E.8


HousingsThe housings can be assembled in the course ofthe mechanical work.The PT6 contact unit is simply snapped on with orwithout power bus.Optionally, the „TS 35 PT6“ mounting rail modulecan be used.GH 10P PT6Field<strong>Power</strong> ® ControlBG GH 10P 4XVG PT6With 4 additional M20 cable glandsIP 65 switched-mode power supply /Electrical-cabinet socket outletETechnical dataInsulating materialPC GF 10PC GF 10Material colourblackblackUL 94 flammability class5VA5VAHalogen free / Silicone freeYes / YesYes / YesDegree of protection when closedIP65IP65Temperature range-40 °C … 55 °C-40 °C … 55 °CCover attachmentScrewsScrewsHousing attachmentMounting tabsMounting tabsNoteClamping range of the cable glands 6–12 mmOrdering dataType Qty. Order No.GH 10P PT6 10 1121980000Type Qty. Order No.BG GH 10P 4XVG PT6 10 1121990000NoteHousing cover BG GHDE 10P PT6 1122200000Housing cover BG GHDE 10P HO PT6 1121950000Housing cover BG GHDE 10P PT6 1122200000Housing cover BG GHDE 10P HO PT6 1121950000AccessoriesType Qty. Order No.TS 35 PT6 10 1170690000Type Qty. Order No.TS 35 PT6 1 1170690000NoteUsable width of 54 mm,can be installed in 1070140000, 1121980000, 1121990000Usable width of 54 mm,can be installed in 1070140000, 1121980000, 1121990000E.9


192181IP 65 switched-mode power supply /Electrical-cabinet socket outletField<strong>Power</strong> ® ControlHousingsThe housings can be assembled in the course ofthe mechanical work.The PT6... contact unit is simply snapped on withor without power bus.Optionally, the „TS 35 PT6“ mounting rail modulecan be used.BG GHDE 10P PT6BG GHDE 10P HO PT667ETechnical dataInsulating materialMaterial colourUL 94 flammability classHalogen-free / Silicone-freeDegree of protection when closedTemperature rangeCover attachmentHousing attachmentPC GF 10black5VAYes / YesIP65-40 °C … 55 °CScrewsPC GF 10black5VAYes / YesIP65-40 °C … 55 °CScrewsNoteHousing height: 67 mmHousing height: 164 mmOrdering dataType Qty. Order No.BG GHDE 10P PT6 10 1122200000Type Qty. Order No.BG GHDE 10P HO PT6 10 1121950000NoteHousing base section GH 10P PT6 1121980000Housing base section BG GH 10P 4XVG PT6 1121990000Housing base section GH 10P PT6 1121980000Housing base section BG GH 10P 4XVG PT6 1121990000AccessoriesNoteE.10


Help with project planningField<strong>Power</strong> ® DC networkHelp with project planningIP 65 switched-mode power supply /Electrical-cabinet socket outletActuating variable and load limit24.25 24V23.75V23.25V23Loadshare busInput 400 V ~L1, L2, L3, hU / V≤ 300ms210 2.5 5 5.3 7.5 10 12.5I / A0.5 ... 4 mm 20.4 ... 0.5 NmSD 0.6 x 3.5 x 100Fault Relay ≤ 1 A / 24 VCOM, NOOutput 24 V DC 5 A+, +, -, -LOAD SHARE0.2 ... 1.5 mm 20.2 ... 0.25 NmSD 0.4 x 2.5 x 75LOAD SHARE bus connection:twisted pair cable(for example, Ölflex)EInstalled position≥ 15 mma)b)c) d)≥ 15 mmØ 6…12 mmDerating curve47.759.4<strong>Power</strong> in W150P max140130P rated120110100a)9080c)706050d)403020b)1000 10 20 30 40 50 60 70 80Tu in °CE.11


IP 65 switched-mode power supply /Electrical-cabinet socket outletDrilling templateDrilling templateField<strong>Power</strong> ® Box 10PE192177192165181E.12


Electrical-cabinet socket outletElectrical-cabinet socket outlet• Simple installation in electrical cabinet• TS35 module can be mounted on rail• VDE mark of conformity• Two-pole with earthing contactSchuko TS35IP 65 switched-mode power supply /Electrical-cabinet socket outletTechnical dataRated voltageRated voltage, max.Rated currentClamping range, nom.Tightening torqueAmbient temperatureOvervoltage categoryPollution severityProtection classApprovals230 V250 V16 A1.5 mm²1.3 Nm-20 °C...+40 °CII2IP 20VDE; CEEDimensionsClamping range (nominal / min. / max.)Length x width x heightNotemm²mm1.5 / 1 / 1.560 / 76 / 45Ordering dataConnection systemType Qty. Order No.Schuko TS35 10 8734580000NoteAccessoriesE.13


IP 65 switched-mode power supply /Electrical-cabinet socket outletEE.14


Weidmüller Solutions & ServiceContentsWeidmüller Solutions & ServiceWeidmüller Solutions & Service Customer specific solutions: best advice, best solutions V.2Digital support: RailDesigner ® , Product Assistant for Distributor Housing,Online product catalogue, M-Print ® PRO label designerV.8VV.1


Weidmüller Solutions & ServiceCustomer specific solutionsApplication specific solutions –Your requirements are our motivationEach industry has its own requirements calling for more andmore individual solutions aside from standard products. Yournew product might have to contend with severe conditions.Many applications are subjected to high mechanical strains –through vibration or directly applied forces. Extreme temperatureconditions or the application in hazardous areas are furtherfactors your product must be able to comply with. We offer youour competent and target-oriented support for the selection ofideal products for any application. Feel free to contact us!Individual product development, customer-specific assembly orapplication-specific products that are ready for use – with anindividual and perfect solution we want to help you to optimiseworking processes and to ensure your company’s sustainedefficiency today as well as for the future.Individual product developmentIn co-operation with you we will develop individual and futureorientedproducts on the highest technological level – tailoredto your application.Customer-specific assemblyAccording to your specifications we use our great productionexpertise and our broad product portfolio to set up the solutionmeeting your requirements.Application-specific productsOur cross-industrial solutions set standards: Set up for yourapplication, instantly ready for use and available from stock.VV.2


Individual product development for your successCustomer specific solutionsWeidmüller Solutions & ServiceWe have a passion for simple, innovative solutionsTogether we will develop innovative and future-oriented productstailored to your application. Our philosophy “One customer –one product” serves as background. It is not the product thatis the starting point, but you, your technical specifications andyour requirements.A connecting partnershipFor the development of individual products both partiescontribute their utmost experience and competence.We consider any challenge with our professional projectmanagement giving it a quality approach – from the idea anddesign phase via the development phase to the implementationand production. We place our complete knowledge in the fieldof electrical connectivity, enclosure and sealing technology aswell as signal conditioning at your disposal.Benefit from a reliable partner:• Increasing the efficiency of your development andproduction processesThe particular outsourcing of development and production ofyour components will shorten the time-to-market phase. It willminimise your efforts thus allowing you to concentrate on yourcore competences.• Taking benefit from our application and productionknow-howTake profit from the expertise of our application engineersand our specialists in the fields of connection technology,enclosure and surface technology as well as metal and plasticprocessing.• Increasing safety through professional projectmanagementThrough innovation workshops, feasability studies andprofitability analyses we define a requirement profile formingthe basis for the further development process. This makessure that you will decide for the best possible product.VV.3


Weidmüller Solutions & ServiceCustomer specific solutionsApplication specific products –solutions for industries and marketsIndustries and applications often have similar or even identicalrequirements for products or product assemblies. Applicationspecific products that are based on earlier realised solutions arenow directly available from stock.Your advantage: You get a suitable and cost efficientsolution within a minimum of time!Cross industrial solutions as standardIt is our aim to develop real solutions for you that offer theadditional advantage of a advantage of a truly flexible design.This means that an application specific product might havea supplementary input or a terminal you don’t need. Theadaptation for you, however, would in any case be muchcheaper than the complete unrolling of an individual job.Thus you cannot only save time but also money!Take multiple profit:• High availabilityApplication specific products are available from stock withoutdelay. So you can rely on the delivery of your products in duetime.• Advice from application engineersTake profit from our application engineers’ expertise. Theydevelop real solutions with added value for your applications.• Supportive softwareProject planning and evaluation made easy, with our softwaresolutions such as NetCalc, RailDesigner ® or Softclinic.• Worldwide application centresWe stay in constant dialogue with our application centresthus enhancing our application know how and being at yourdisposal anywhere you need us.VV.4


Customer specific assembly,tailored configurationCustomer specific solutionsTWeidmüller Solutions & ServiceYou want to bring costs down and increase your efficiency. Youwould like to fully concentrate on your core competences. Youare looking for a partner who will set up intelligent solutionsfor you, suiting your special requirements. We dispose of theapplication know how and the capacities to set up tailoredsolutions for you, fast, flexible and economically advantageous.Highest level of professional productionTake profit from our professional project management andour high level of production know how, e.g. in the ATEX area.We offer you a comprehensive portfolio of customer specificassemblies, from simple assembly to the modification of existingelectronics products.We offer co-operative support and advice for all of yourquestions and together with you we define the job assignment.In the further process we select the ideal components from abroad product portfolio composing them to a tailored solution.Our services include:• Adaptation and assembly of enclosuresfor all IP protection classes• ATEX solutions for hazardous areas• Assembly of heavy duty connectors• Assembly of terminal strips• Customer specific electronics solutions• Cable assemblyTake multiple profit:• Simplification of ordering and stockholdingOne solution – one item number! It will no longer be necessaryto order single components. Article variety and stockholdingwill be reduced.• Professional assemblyAll individual components will be pre-assembled thus reducingyour assembly time. This will save your time and money.• Less costs for documentationOur RailDesigner ® software will facilitate the generation ofparts lists or drawings.• Modern processing of enclosuresOur CNC processing centres adapt the enclosures to suityour tailored solution.VV.5


Weidmüller Solutions & ServiceCustomer specific solutionsCustomer specific assembly — consultation, product,development and production all come from one sourceOur application and manufacturing expertise has a decisive effecton all sections of modern connection technology. Their usetherefore forms an integral part of every solution.TEnclosuresPerfect protection and safety• Enclosures for all IP protection classes• ATEX enclosures for hazardous areas• Placement of inspection glasses, drill holes and threads• Elaborate machining operations like the milling of contours• Class C5 welding, according to DIN 6700, for stainless steeland sheet steel enclosures• Surface coating as and when required• Individual device and system markersHeavy duty connectorsPerfect connection with system• Placement of drill holes and cable glands• Equipped with plug-and-play components• Wiring of subassemblies• Cable assembly• All housings are available with individual laser markingVTerminal stripsConfiguration made to measure• Machining of mounting rails• Snapping components onto terminal rails• Placement of cross connections• Mounting of standard conductors• Marking of terminals, devices, conductors and cablesV.6


Customer specific solutionsWeidmüller Solutions & Service<strong>Electronics</strong>Individual solution from the beginning• Modular terminal blocks, component plugs, snap on bases,enclosures for electronics: integration of relevant electroniccomponents• Snap-on base: Component carrier design or simple wiring ofthe modules• Interface units• Modification of existing electronic products: Modification ofthe circuitry or specific calibration• Combination of components: Relays or optocouplers incombination with other componentsCable assemblyOur special service• Pre cutting of cables and conductors• Installation of- Heavy duty connectors- PCB connectors or DIN connectors• Conditioning of wire ends• Mounting of wire end ferrules and cable lugs• Connection of conductors to terminal railsVV.7


Weidmüller Solutions & ServiceDigital supportRailDesigner ®A faster way to configure and order terminal stripsThese days, time and cost efficiency are of the essence whenit comes to working in planning and production. RailDesigner ® ,our free configuration and purchasing software, uses its virtualassembly of mounting rails (assembled or unassembled) to helpyou with the design of your own completely personal solution.Wide selection from the current product portfolio“You can easily download software updates for RailDesigner ®from the internet.This means that you will always have access to the latestversion of our product database.”RailDesigner ® brings you substantial benefits:Less time requiredIt speeds up the process of acquiring quotations and placingorders because, for example, all processes can be initiateddirectly from the software. You configure your projects and therest virtually takes care of itself!User friendly operationAny potential errors are prevented by automatic installation tipsand clear project processing and management. So that you canplan your project realistically, RailDesigner ® offers both 2D and3D displays.Project planning that is compatible with your softwarePlan and design your projects easily using your usual CAEsoftware. With the integrated interface, transferring data fromyour CAE system has never been so simple. You can exportcomponent lists and terminal strip designs in various formats.Marking data is automatically transferred to the M-Print ® Prolabelling software.Simple purchasing of terminal stripsOnce you have completed the planning stages of your projectsin RailDesigner ® , you can choose to send all of your data tous by email. We then take over the assembly and deliver therequired configuration to you, along with anything else that youstill require for your project.VDownload the software for free and discover the advantages tousing RailDesigner ® atwww.raildesigner.deV.8


Product assistant for distribution boxes and assemblies –The perfect solution, in the shortest timeDigital supportWeidmüller Solutions & ServiceYou can easily and quickly select, combine and purchasethe required components, all with the help of the Weidmüllerproduct assistant for distribution boxes and assemblies.This means that you can quickly obtain your individual enclosuresolution. Your solution may include the following components:Numerous possible combinationsEnclosures with Ex-protection are supplied exclusively withterminal strips that are already fitted. The product assistantoffers you various approaches for industry variants so that youcan create the right enclosure variant.Empty enclosures without holesEmpty enclosures in various sizes of the Klippon ® K andKlippon ® POK series (aluminium and plastic) with matchingmounting rails.Empty enclosures with pre-threaded holesEmpty enclosures in different sizes from the Klippon ® K andKlippon ® POK series (aluminium and plastic), that are alreadyequipped with metric threaded holes.Mounting railsExactly tailored mounting rails for the enclosure sizes on offer.Terminal stripsMounting rails, which also perfectly match the offered enclosuresizes and are pre-fitted with terminals, optionally with screw ortension clamp connection.Distribution boxes with Ex-protectionEnclosures that are already assembled with a terminal strip andalready equipped with metric threaded holes.You can start off with any of the listed components and thenadd further components to the combination. This means that,for example, you can select the required terminal strip and theproduct assistant will then offer the matching enclosure variants.Or, you can start with the enclosure, and matching terminalstrips or mounting rails will then be chosen. The selectedproducts can then be directly included in the query list.Provision of all relevant dataDuring the selection, you can choose filters for the terminalstrips, such as length, connection technology or dimensionalcross-section and, for the enclosure, you can choose material,size, holes etc. If a product is then selected and combined, theuser can view all of the relevant data, including drawings andpictures. This means that you can extensively plan how theenclosure will be integrated into the customer‘s application.The product assistant is available athttp://galaxy.weidmueller.comVV.9


Weidmüller Solutions & ServiceDigital supportOnline product catalogueIf you have questions about the specifications and detailsof our products, perhaps even outside normalbusiness hours,then our online catalogue athttp://catalog.weidmueller.comopen 24 hours a day, 365 days a year, is the perfect sourcefor information. Besides product features and part numbers, itcontains extensive additional information on all product groups.For further information, offers and your personal contact, simplyconsult the Weidmüller website atwww.weidmueller.comWith one click selection for the product data sheetof your choice.M-Print ® PRO label designerThe comprehensive range of Weidmüller services includes theM-Print ® PRO software.This is a professional standard, Windows ® -based program forprinting and ordering labels and markers that is coordinated withour current printing systems and marking materials.M-Print ® PRO enables you to design your labelling materialsprofessionally and quickly. Texts, borders, lines, graphics,barcodes, serial numbers and photographs are all possible.The interface to RailDesigner ® or your CAE system enables thetransfer of all your configured data.VV.10


Glossary/Technical appendixContentsGlossary/Technical appendixGlossary/Technical appendix <strong>Power</strong> <strong>Supplies</strong> – Overview W.2Standards and approvals W.4Glossary W.6WW.1


Glossary/Technical appendix<strong>Power</strong> <strong>Supplies</strong> – Overview<strong>Power</strong> <strong>Supplies</strong> – Overview<strong>Power</strong> supplies are important links in the energy supply chainof automation systems. Unregulated power supplies orregulated switched-mode power supplies are at the heart ofevery electrical cabinet. 24 V DC has emerged as the standardcontrol voltage for the supply of electrical sub-assemblies andsystems. But other control voltages are also required. Thecorrect power supply is a critical factor for the reliable operationof the supplied components. Thus it must be chosen withparticular attention.<strong>Power</strong> supplies from Weidmüller, whether regulated orunregulated, have proven themselves reliable over manyyears in the supply of electrical sub-assemblies and systems.They perform reliably and safely – even under harsh industrialconditions – in all sectors of machine construction, industrialautomation, and the power and process industries.Weidmüller offers custom-fit solutions for practically all of yourrequirements:• Unregulated transformer power supplies• Primary switch-mode power supplies• DC/DC converters• Diode modules• UPS control modules• Electronic fusingHow they workUnregulated power supply units consist of a mains powertransformer that transforms the input voltage into different ACvoltage. The units then make use of a rectifier and a filter circuitto smooth out the DC output voltage.Mains (AC)Unregulated transformer power supplyOutputRegulated power supply units in the range up to 1,000 Ware usually designed as primary switched-mode power units.The mains AC voltage is then rectified and transformed in highfrequency to the secondary side using switching transistors andpower transformers. This is followed by the rectifier and filtercircuit in order to generate the DC output voltage. A controlcircuit compares the current and voltage on the output side tothe specified target values and then generates a control signalfor the switching transistors. This permits compensation forload changes and mains voltage fluctuations. As a result, theoutput voltage remains stable. These power supply units areincreasingly being operated with DC input voltages (for example,Weidmüller‘s PRO-M line of switched-mode power supplies).ControllerMains (AC/DC)OutputSwitched-mode power supplyWW.2


<strong>Power</strong> <strong>Supplies</strong> – OverviewGlossary/Technical appendixA DC/DC converter is a variation of the classic switchedmode power supply. The switching strategy is similar but thereis no input rectifier. Starting with a specified DC input voltage,DC/DC converters generate a different DC voltage at a similaror different level. They are used to adapt different voltage levelsand also for isolating potentials.ControllerMains (DC)OutputDC/DC converterIn use around the globeWeidmüller‘s power supply units have been designed foruse around the world. They can be used in practically allapplications throughout the world because of their CE labeland many other national and international approvals. Their wideinput voltage ranges and compatibility with various mains powerconnections improves their global appeal.Temperature rangeDuring operation, power supply units generate power losses. InWeidmüller‘s switched-mode power supplies, the resulting heatis dispersed using natural air currents only. The design, whichdoes not make use of a ventilation fan, is an example of ouruncompromised durability standard. Weidmüller‘s power supplyunits, depending on the model, can be used in temperaturesranging from -25 °C to +70 °C.Compact and efficient designWeidmüller‘s switched-mode power supplies are extra smallbecause they take advantage of the above-average degreeof efficiency offered by the latest technologies. The powersupplies from Weidmüller – whether they are book-shaped withminimised base surface, or variants with reduced height for usein distributor boxes – always provide the proper cost-savingsolution.WW.3


Glossary/Technical appendixStandards and approvalsStandards and approvalsStandard/ApprovalDIN EN 50178(VDE 0160)DIN EN 60950-1(VDE 0805-1)DIN EN 61558-1(VDE 0570-1)DIN EN 61558-2-17(VDE 0570 Teil 2-17)DIN EN 60204-1(VDE 0113-1)DIN VDE 0100-410DIN EN 61204-1DIN EN 60947-1DIN EN 61140IEC 38DescriptionElectronic equipment for use in power installationsIT Equipment – Safety –Part 1: General requirementsSafety of transformers, power supply units, throttles and similar devicesPart 1: General requirements and testsSafety of transformers, power supply units and similar devicesPart 2-17: Special requirements for switch-mode power supply transformersSafety of machinery – Electrical equipment of machinery –Part 1: General requirementsConstruction of power installations with rated voltages up to 1,000 VPart 4: Protective measuresChapter 41: Protection against electrical shock<strong>Power</strong> supply units for low voltages, with direct-current-output – propertiesLow-voltage switching devices – Part 1: General definitionsProtection against electrical shock - common requirements forfacilities and operating equipmentSupplementary notes relating to status of international standards and Europeanharmonisation of mains voltages 230/400 V73/23 EWG Electrical equipment for use within specific voltage limits(Low Voltage Directive)W2004/108/EG(89/336 EWG)2006/42/EG(98/37 EG)ULCSAGLUL1310UL1604Electromagnetic compatibility (EMC Directive)Safety of machines (directive covering mechanical equipment)Safety approval for the United States marketSafety approval for the Canadian marketTest specifications for electrical/electronic devices and systems for use in marine technologyClass 2 power supplies (limited energy)Electrical equipment for use in dangerous surroundingsW.4


Standards and approvalsGlossary/Technical appendixStandard/ApprovalSEMI F472006/95/EG(72/23/EWG)EN 60721-3-2EN 60664-1(VDE0110-1)DescriptionResistance of electronic devices against voltage dropsLow Voltage DirectiveClassification of surrounding conditionsInsulation coordination for electrical equipmentC22.2 No. 107.1 General standards for power supplies (Canadian standard)EN 61000-3-2EN 61000-4-xLimiting of mains voltage harmonic currentsInterference immunity testsWW.5


Glossary/Technical appendixGlossaryGlossaryAAC/DC converterAmbient temperature (operational)Conventional switched-mode power supplies generate a DC voltage from aAC voltage. For this reason they are sometimes also called AC/DC converters.Such devices are increasingly compatible for use with DC input voltages.The primary and secondary sides are typically electrically isolated.The ambient operating temperature (the min. and max. values) together with theoutput current and voltage ratings can be used to describe the power capabilities ofa power supply unit.BBurstA burst is a quick low-power burst pulse which can, for example, simulate weldingequipment phenomena. Similar phenomena can also result from switchingoperations on the mains supply. This test can be used to demonstrate immunityagainst quick transients.WCClass of protectionConnecting power supply unitsin parallelCoolingElectrical equipment is classified according to varying classes of protection. Theseclasses define the particular safety measures that are required to avoid an electricalshock. The most widely used power supplies correspond with protection class I. Thebasic requirement of protection class I is for a basic insulation and for the earthing ofall conductive housing parts. If the basic insulation fails, then the earthed conductivehousing serves to prevent an electrical shock. For this reason, devices in protectionclass I are equipped with an earth (PE) connection.<strong>Power</strong> supplies can only be connected in parallel when this is clearly permitted bythe manufacturer. Parallel connections are then normally tied to certain conditions.This is a typical way to increase the output power (for example, when extending afacility). <strong>Power</strong> supplies are also wired in parallel in order to design redundant powersupply systems. The parallel circuit is not wired straight though but connects usingdecoupling diodes.➝ RedundancyCooling is used by components or devices to prevent them from overheating. Avariety of cooling strategies are available – two of the most common are natural andforced-air cooling. Natural (convection-based) cooling takes advantage of the naturalair currents. Manufacturers must then ensure that there is sufficient air flow byspecifying the clearance gaps and mounting positions that are required above andbelow the ventilation openings. Forced-air cooling normally uses a fan to dissipateany heat that has been generated. When fans are used in a device, they have theeffect of increasing the likelihood of device outages. For this reason, a power supplywith natural cooling methods is generally preferred.W.6


GlossaryGlossary/Technical appendixDDC/DC converterDeratingA DC/DC converters are switched-mode power supplies that convert a specificDC voltage into another voltage. They are a variant of the AC/DC converter.DC/DC converters, in their simplest implementation, do not isolate voltage potentials.They are used only for adapting voltages. Improved DC/DC converters have isolatedvoltages. A safety isolating transformer in the power element ensures the requiredelectrical isolation. Besides the voltage adaptation, the isolation of the voltagepotentials is an important factor in this case.For power supply devices, derating generally refers to the reduction in power asinfluenced by the surrounding temperature and the input voltage. A temperaturederating often occurs starting at a surrounding temperature of 50 °C. The ratedpower is guaranteed up to this temperature. The available power continually declinesas the temperature heats up above this level. This is typically specified in %/K. Avoltage-dependent specification is another form of derating For switched-modepower supplies, the derating begins below a specific input voltage. So a switchedmodepower supply with a wide input range can typically work under full power with115 V AC input voltage. However at 85 V AC it can only produce 60 % of the powerrating. The coefficient is usually specified in %/V.105Temperature derating120Voltage deratingMax. current [%IN]10095908580757040 45 50 55 60 65 70 75Temperature [°C]Max. Current [%IN]10080604020070 90 110 130 150 170 190 210 230 250 270Main voltage [V]Diode modulesDiode modules are used to construct a redundant power supply system. They areimportant for decoupling the power supply unit. Thus, a short circuit that occurs onthe output of a power supply unit will not influence the output voltage.EEfficiencyEMC (electromagnetic compatibility)The degree of efficiency is equal to the ratio of output power to input power andis expressed in percent. The degree of efficiency can be between 70 and 90 %,depending on the dimensions and type of technology in use.Electromagnetic compatibility describes the interference emissions caused by anelectronic device and the level of immunity against external electrical influences.Interference emissions can be caused by cabling and wires or by radiated emissions.Immunity measures the resistance against such wire-based emissions and againstradiated emissions such as electrostatic fields and magnetic fields. Electric devicesmust also be protected against electrostatic discharges.WW.7


Glossary/Technical appendixGlossaryFFoldback characteristic curveThe foldback characteristic curve is a special type of output curve that protectsthe power supply unit from overloads. When a specific current limit is exceeded(for example, by 110 or 120 % of the nominal level), the current is limitedelectronically and lowered to a very low, safe value. This downward-slopingcharacteristic curve means that it is not sufficient to simply eliminate the overload.The load must be reduced significantly more so that the adjustment control canreturn to the normal voltage control. Thus this solution is not suitable for manyapplications and is becoming less popular.UUAINominalILimitIGGalvanic isolationHHiccup modeGalvanic (electrical) isolation ensures that no electrical connections can existbetween the primary and the secondary sides. Opto modules and transformers arethe typical components used.The hiccup mode is a special output characteristic curve that protects power supplyunits from overloads and short circuits. The unit switches off at a specified currentlimit (for example, 110 or 120 % on the nominal rating) and then switches back onafter a certain delay. This leads to a pulsating mode of operations which can onlyrevert to continual operations after the overload has been eliminated. The maindisadvantage here is that the connected consumer load must be restarted afterevery pause. A restart may not be possible with motors or large capacitive loadssince the restart current peak may once again exceed the defined limit.UU AWIILimitINominalttW.8


GlossaryGlossary/Technical appendixHold-up time(mains-failure bridging time)The hold-up time (also known as the mains-failure bridging time) is the interval fromthe start of the mains outage to the point in time when the output voltage can nolonger be maintained at its original level. The hold-up time indicates how long amains outage may last before it influences the output voltage. For DC powersupplies, EN 61204 requires a bridging time of at least 20 ms.UU Ahold-up time<strong>Power</strong> failure(cutoff)tIInput voltage rangeInrush currentThis refers to the minimum and maximum input voltage at which the rated outputspecifications can be maintained.The inrush current refers to the peak current that occurs when turning on aconsumer load. Switched-mode power supplies have storage capacitors in the inputwhich can cause significant current peaks while the mains power is being switchedon. A variety of circuitry solutions can be used to attenuate these current peaks. Inthe simplest solution, an inrush limiter is used. Active switching can be used in othercases. The peak current specification indicates which upstream fuse should be usedin the circuit. If a fuse is selected which is too sensitive, it can trigger when the mainspower is switched on.WW.9


Glossary/Technical appendixGlossaryIU characteristic curveThe IU characteristic curve is a special output characteristic curve that protectspower supply units from overloads and short circuits. It offers the best performancewith regards to overload and short circuit capabilities. A current limit is activated ata specific current level (for example, 110 or 120 % on the nominal rating). As theload continues to increase, the output voltage is reduced according to the currentlimit curve until it reaches a level approaching zero volts. Thus a pulsating mode ofoperations is avoided for short-term overloads. Large capacitive loads or motorsare brought back up along the slope of the current-limit characteristic curve. Aftera short circuit or overload is fixed, the IU characteristic curve offers the advantageof immediately returning to the normal voltage control mechanism. The full outputvoltage is then immediately available. The IU characteristic curve is becoming theestablished standard for modern power supplies. Additional variants are availablewhich pertain to the peak current capacity and the slope of the current-limitcharacteristic curve.UUAINominalILimitIMMains harmonicsMains system types<strong>Power</strong> supplies can experience harmonics caused by mains rectification on the inputside. These harmonics are multiples of the mains frequencies. Existing standardsdefine specific limit values since such harmonics can significantly lower the mainsquality.This refers to the types of mains supply systems. Systems differ in their method ofearthing and the implementation of the phase wire, PE wire and central-point wire.Common mains systems include the TN, IT and TT networks. The individual mainstypes can also differ in their voltage levels and frequencies.PRO-MPRO-MPRO-MPRO-ML N PETN-S MainsL1L2L3NPEL N PE L N PE L N PETN-C MainsTT MainsIT MainsL1L1L1L2L2L2L3L3L3PENNNWMTBF (mean time between failure)The MTBF is a statistical value that specifies the probability that a product will fail.It is typically specified in hours and normally assumes a temperature of 25 °C. Theprobability of failure depends largely on the ambient surroundings. The key variablesare the type of load and the ambient temperature.W.10


GlossaryGlossary/Technical appendixOOutput characteristic curvesOvervoltage categoryThe output characteristic curves of power supply devices are determined by currentand voltage. Unregulated devices do not have a current limit. In the case of anoverload or short circuit, fuses or temperature switches are used to protect thedevice. Regulated devices are protected against overload and short circuits bymeans of various output characteristic curves. In this case, the system attemptsto prevent any activation of fuses or temperature switches. The mandatory manualreset which follows an overload or short circuit can then be avoided. Commonoutput characteristic curves include the hiccup mode, the foldback characteristiccurve or the IU characteristic curve.➝ Hiccup mode, foldback characteristic curve, IU characteristic curve<strong>Power</strong> supply units are classified into overvoltage categories according to theimmunity against mains surges and transient voltages.PPELV (protective extra-low voltage)PFC (power factor correction)Pollution severity<strong>Power</strong>-boost or boost<strong>Power</strong> factorThis is a functional DC voltage with secure isolation according to EN 50178. As withSELV, a reinforced or double insulation is used between the primary and secondarysides. However, the secondary side is earthed.The power factor correction can be either passive or active in relation to powersupply devices. The reactive power resulting from the bridge rectification puts asignificant strain on the power supply network. The relatively poor power efficiencyfactor that results can be improved by using passive components (such as filters) oran active electronic mechanism. For switched-mode power supplies, PFC usuallyrefers to the active variant of the power factor correction. <strong>Power</strong> factors of almost 1can be reached when using an active PFC. Practically no reactive power is drawnfrom the mains supply network; therefore the strain on the mains network is relativelylow.Pollution severity describes the environment and ambient conditions that a devicerequires in order for it to function smoothly. Significant environmental variablesinclude condensation or air containing dust and oil.The power-boost function is the surge current handling capacity in the seconds tominutes range. This function is often required for starting up DC motors. DC motorshave a high start-up current and often require several seconds before they haveachieved their rated rotational speed. The power-boost function helps to optimisethis start-up phase.The power factor is the ratio of reactive power to apparent power. It is an indicatorof the device performance with respect to the load on the mains power network.Depending on the technology in use, the power factor for power supplies can bebetween 0.45 and nearly 1.WW.11


Glossary/Technical appendixGlossary<strong>Power</strong> loss<strong>Power</strong> rating<strong>Power</strong> supply units connected in seriesProtection degreePulsed current capacityFor power supply units, the power loss specification indicates the thermal outputemitted during nominal (rated) operations. This is a key specification used byengineers when designing the climate control systems within electrical cabinets. It iscalculated as the difference between the input and output power and can also takethe degree of efficiency into account.The continual output permitted under the rated conditions.<strong>Power</strong> supplies can only be connected in series when this is clearly permitted by themanufacturer. Such series connections are then normally tied to certain conditions.They can be used to increase the output voltage. This is not widely implemented.According to DIN EN 60529, devices can be classified according to their protectiondegrees. The numeric code (for example, IP20) defines two protection degrees:protection against touch or penetration by external objects (the first digit) andprotection against water penetration (the second digit). Switched-mode powersupplies intended for use in electrical cabinets or similar enclosures are oftendesigned with IP20 protection. The first digit (in this case, 2) ensures fingerprotection. The second digit (0) indicates that no protection against water isprovided.The pulsed current capacity describes the dynamic performance of a switchedmodepower supply. Capacitive consumer loads, with their high inrush currents, puta particular strain on a switched-mode power supply. Peak values are reached (inthe ms range) which amount to levels many times higher than the mains current. Ifthe current control mechanism reacts too quickly, this can lead to voltage drops andcan cause problems for loads which are connected in parallel. For this reason,power supplies are often equipped with a surge current limiting factor based ontime. This allows a high current output for only a few ms which can be much higherthan the rated current.WRRated control voltageRated input voltageRated output currentRated output voltageRedundancyThe nominal value of the sparkover voltage for the relay.The input voltage required at which, under the normal mains voltage fluctuations, theoutput levels can be kept stable. It usually corresponds to the rated voltage for theelectric utility‘s power grid.The long-term current permitted under the rated conditions.The nominal output voltage used for the rated specifications. It usually correspondsto the factory default output voltage.A power supply system is considered redundant if it is constructed so that it haspartial power supplies which are independent of each other and each of thesecan individually deliver the output load. When a fault occurs, therefore, it is stillpossible to continue to supply the connected rated load. In reality, at least twopower supplies are connected in parallel using decoupling diodes. In this way, ashort circuit in the output of one power supply will not lead to the failure of the entirepower supply system.➝ Diode modulesW.12


GlossaryGlossary/Technical appendixRegulated power supply unitsResidual rippleResistance to shockResponse timeSwitched-mode power supplies, as opposed to more common power supply units,have become established as the standard for the 10–1,000 W power range. Theyproduce a stable output voltage with minimal residual ripple, even when influencedby fluctuations in the mains voltage, mains frequency or load. Their small sizeand weight is a result of their superior efficiency degree. The electronic controlmechanism typically ensures a constant output voltage that varies ±1 %.The residual ripple describes the ratio of superimposed AC voltage to DC voltageon the output side of the power supplies. In addition to a percent specification, thesuperimposed ripple is often specified in mVss for switched-mode power supplies.Resistance to shock refers to mechanical immunity against impacts in any direction.This is a key factor while the product is being transported.The response time is the time that a power supply unit needs to compensate for adisturbance (for example, a load fluctuation).SSwitching frequencySwitched-mode power supplies are normally operated with switching frequenciesfrom 20 to 200 kHz. The HF or power transformer is switched on an off usingtransistors at this switching frequency. Small, compact units can be built with thismethod in comparison with the traditional 50/60 Hz transformers.Switched-mode power supply units The switching pulse can be either primary or secondary. Thus there are primaryswitched-mode and secondary switched-mode power supply units. Secondaryswitched-mode power supply units are no longer of much significance. The primaryswitched-mode power supplies are now the focus of attention. The pulse refers tothe high-frequency on and off switching of the transformer or transmitter in order totransmit energy. The high frequency allows the use of extra small inductive andcapacitive components, particularly for the transmitter. In comparison to transformerbasedpower supply units, the weight and volume required are much reduced.LNPE˜˜+-WW.13


Glossary/Technical appendixGlossarySelectivityWhen surge protection equipment is connected in series, selectivity refers to theability of only one upstream fuse to trigger selectively in the event of an overload.The differentiation can take into account current or also time. With DC power supplysystems, selectivity refers to the separate fusing of load circuits on the DC side. Inthis case as well, only the proper series fuse should trigger in the event of anoverload. Fuses in DC circuits play a critical role since the power supplies must reactto upcoming short circuits with a speedy cut-off or by limiting the current. Usuallyelectronic fuses are used for this purpose.63 AMainsMains25 A˜=<strong>Power</strong> <strong>Supplies</strong>16 ALoadSelectivity for fusesconnected in seriesLoad Load LoadSelectivity for DC systemsSELV (safety extra low voltage)SurgeSELV refers to extra-low safety voltages according to IEC/EN 60950. Reinforcedor doubled insulation between the primary and secondary sides is used to preventelectric shock. The output voltage here is sufficiently low so that it does not pose aninjury risk if a person comes into direct contact. Earthing on the secondary side ispossible but not required.A surge is a high-power voltage pulse which can be caused by, for example, alightning strike. The switching operations from large consumer loads can alsogenerate such voltage surges on the mains network. This testing procedure is usedto demonstrate the immunity against high-power voltage pulses.TTemperature rangeThe temperature range specifies the minimum and maximum ambient temperaturesfor which a device can start up and run continuously.UUnregulated power supply unitsUnregulated power supplies consist mainly of a transformer, a rectifier and an Elkosfilter. Since no controlling system is in place, mains voltage fluctuations influence theDC voltage side. Unregulated power supply units are very sturdy; they can be usedin applications where a stabilised DC voltage is not necessary (for example, powersupply to contactors).WVVibration resistanceVibration resistance describes the resistance against constant mechanical vibrationsthat occur during operations. Rail and ship applications place stricter demands forvibration resistance on the device.W.14


GlossaryGlossary/Technical appendixWWide-range inputModern switched-mode power supplies often feature a wide input range. They canbe run under a wide range of voltages: from min. to max. rated voltages includingthe tolerance limits. They do not require any manual range switching.Status: 21.09.2009WW.15


Glossary/Technical appendixWW.16


ContentsIndexIndexIndex Index Type X.2Index Order No. X.3Addresses worldwide X.6XX.1


Type Order No. Page Type Order No. PageIndex / TypeBBG GH 10P 4XVG PT6 1121990000 E.9BG GHDE 10P HO PT6 1121950000 E.10BG GHDE 10P PT6 1122200000 E.10BG SNT PT6 1101940000 E.5CCP DCDC 50W 12V 3A 9919371212 A.55CP DCDC 50W 12V 3A 9919372412 A.56CP DCDC 50W 15V 3A 9919372415 A.54CP DCDC 50W 15V 3A 9919371215 A.55CP DCDC 50W 22-24V 2A 9919372424 A.54CP DCDC 50W 22-24V 2A 9919371224 A.55CP DCDC 50W 5V 8A 9919372405 A.56CP DM 10 8710620000 A.39CP DM 20 8768650000 A.39CP M CAP 1222240000 A.12CP M DM20 1222210000 A.10CP M DM40 1222220000 A.10CP M RM24 1222230000 A.11CP M SNT 1000W 24V 40A 8951380000 A.7CP M SNT 120W 24V 5A 8951340000 A.5CP M SNT 180W 24V 7,5A 8951350000 A.6CP M SNT 250W 24V 10A 8951360000 A.6CP M SNT 250W 24V 10AUW 1165480000 A.15CP M SNT 500W 24V 20A 8951370000 A.7CP M SNT 70W 24V 3A 8951330000 A.5CP M SNT3 1000W 24V 40A 8951420000 A.9CP M SNT3 120W 24V 5A 8951390000 A.8CP M SNT3 250W 24V 10A 8951400000 A.8CP M SNT3 500W 24V 20A 8951410000 A.9CP NT 144W 24V 6A 8575280000 B.5CP NT 192W 24V 8A 8575300000 B.5CP NT 264W 24V 11A 8575310000 B.6CP NT 36W 24V 1.5A 8575260000 B.4CP NT 432W 24V 18A 8575320000 B.6CP NT 72W 24V 3A 8575270000 B.4CP NT3 1000W 24V 40A 8628680000 B.9CP NT3 250W 24V 10A 8628620000 B.7CP NT3 400W 24V 15A 8628630000 B.7CP NT3 500W 24V 20A 8628650000 B.8CP NT3 600W 24V 25A 8628660000 B.8CP NT3 750W 24V 30A 8628670000 B.9CP SNT 1000W 24V 40A 8862780000 A.34CP SNT 120W 24V 5A 8708670000 A.31CP SNT 12W 24V 0.5A 9918840024 A.47CP SNT 160W 12-15V 8A 9925340012 A.51CP SNT 160W 24-28V 6.5A 9925340024 A.50CP SNT 160W 48V 3.5A 9925340048 A.50CP SNT 160W 5V 8A 9925340005 A.51CP SNT 24W 12V 1.5A 9928890012 A.41CP SNT 24W 15V 1.5A 9928890015 A.41CP SNT 24W 24V 1A 9928890024 A.40CP SNT 24W 28V 1A 9928890028 A.40CP SNT 24W 5V 2A 9928890005 A.42CP SNT 250W 24V 10A 8708680000 A.32CP SNT 25W 5V 5A 8754960000 A.43CP SNT 300W 24V 12.5A 9916250024 A.52CP SNT 48W 12V 4A 8754970000 A.44CP SNT 48W 24V 2A 8739140000 A.45CP SNT 48W 48V 1A 8879230000 A.46CP SNT 500W 24V 20A 8778870000 A.33CP SNT 55W 12-15V 3A 9927480012 A.49CP SNT 55W 24-28V 2.3A 9927480024 A.48CP SNT 55W 48V 1.04A 9927480048 A.48CP SNT 55W 5V 3A 9927480005 A.49CP SNT 70W 24V 3A 8708660000 A.30CP SNT3 1000W 24V 40A 8708730000 A.38CP SNT3 120W 24V 5A 8862730000 A.35CP SNT3 250W 24V 10A 8708700000 A.36CP SNT3 500W 24V 20A 8708710000 A.37CP T RM 10 1105880000 A.27CP T RM 20 1105890000 A.27CP T SNT 140W 12V 12A 1105440000 A.17CP T SNT 180W 24V 7,5A 1105810000 A.19CP T SNT 180W 48V 4A 1105850000 A.21CP T SNT 360W 24V 15A 1105820000 A.19CP T SNT 360W 48V 7,5A 1105860000 A.22CP T SNT 600W 24V 25A 1105840000 A.20CP T SNT 600W 36V 16,5A 1194430000 A.20CP T SNT 600W 48V 12,5A 1105870000 A.22CP T SNT 70W 12V 6A 1105430000 A.17CP T SNT 90W 24V 3,8A 1105790000 A.18CP T SNT 90W 24V3,8ACL2 1194410000 A.18CP T SNT 90W 48V 2A 1194420000 A.21CP T SNT3 180W 24V 7,5A 1194480000 A.25CP T SNT3 360W 24V 15A 1194490000 A.25CP T SNT3 480W 24V20A/4 1194440000 A.23CP T SNT3 480W 24V20A/5 1194450000 A.23CP T SNT3 600W 24V 25A 1194310000 A.26CP T SNT3 960W 24V40A/4 1194460000 A.24CP T SNT3 960W 24V40A/5 1194470000 A.24CP-BBU 115-230VAC / 12VDC 9916280012 C.3CP-BBU 115-230VAC / 24VDC 9916280024 C.4CP-SNT 380-480VAC/24V 9917790324 A.53FFP Box 10P SNT 1132320000 E.4FP Box 10P SNT 4XVG 1076510000 E.4GGH 10P PT6 1121980000 E.9PPT6 1957620000 E.6PT6 DC 1126840000 E.6PTDS 4 1952130000 E.7PTDS 4 DC 1009990000 E.8PTS 4 1952120000 E.7PTS 4 DC 1131730000 E.8SSchuko TS35 8734580000 E.13TTS 35 PT6 1170690000 E.9TS 35 PT6 1170690000 E.9WWGS 24Vdc 0.5...5A 8710270000 D.6WGS 24Vdc 1,6A 8618890000 D.4WGS 24Vdc 3,15A 8618910000 D.4WGS 24Vdc 6,3A 8618930000 D.5WGS 24Vdc 8,0A 8618940000 D.5WGZ 24Vdc 0.5...5A 8727630000 D.6WGZ 24Vdc 1,6A 8621040000 D.4WGZ 24Vdc 3,15A 8621030000 D.4WGZ 24Vdc 6,3A 8621020000 D.5WGZ 24VDC 8,0A 8621010000 D.5XX.2


Order No. Type Page Order No. Type Page10000000001009990000 PTDS 4 DC E.810700000001076510000 FP Box 10P SNT 4XVG E.411000000001101940000 BG SNT PT6 E.51105430000 CP T SNT 70W 12V 6A A.171105440000 CP T SNT 140W 12V 12A A.171105790000 CP T SNT 90W 24V 3,8A A.181105810000 CP T SNT 180W 24V 7,5A A.191105820000 CP T SNT 360W 24V 15A A.191105840000 CP T SNT 600W 24V 25A A.201105850000 CP T SNT 180W 48V 4A A.211105860000 CP T SNT 360W 48V 7,5A A.221105870000 CP T SNT 600W 48V 12,5A A.221105880000 CP T RM 10 A.271105890000 CP T RM 20 A.2711200000001121950000 BG GHDE 10P HO PT6 E.101121980000 GH 10P PT6 E.91121990000 BG GH 10P 4XVG PT6 E.91122200000 BG GHDE 10P PT6 E.101126840000 PT6 DC E.611300000001131730000 PTS 4 DC E.81132320000 FP Box 10P SNT E.411600000001165480000 CP M SNT 250W 24V 10AUW A.1511700000001170690000 TS 35 PT6 E.91170690000 TS 35 PT6 E.911900000001194310000 CP T SNT3 600W 24V 25A A.261194410000 CP T SNT 90W 24V3,8ACL2 A.181194420000 CP T SNT 90W 48V 2A A.211194430000 CP T SNT 600W 36V 16,5A A.201194440000 CP T SNT3 480W 24V20A/4 A.231194450000 CP T SNT3 480W 24V20A/5 A.231194460000 CP T SNT3 960W 24V40A/4 A.241194470000 CP T SNT3 960W 24V40A/5 A.241194480000 CP T SNT3 180W 24V 7,5A A.251194490000 CP T SNT3 360W 24V 15A A.2512200000001222210000 CP M DM20 A.101222220000 CP M DM40 A.101222230000 CP M RM24 A.111222240000 CP M CAP A.1219500000001952120000 PTS 4 E.71952130000 PTDS 4 E.71957620000 PT6 E.685700000008575260000 CP NT 36W 24V 1.5A B.48575270000 CP NT 72W 24V 3A B.48575280000 CP NT 144W 24V 6A B.58575300000 CP NT 192W 24V 8A B.58575310000 CP NT 264W 24V 11A B.68575320000 CP NT 432W 24V 18A B.686100000008618890000 WGS 24Vdc 1,6A D.48618910000 WGS 24Vdc 3,15A D.48618930000 WGS 24Vdc 6,3A D.58618940000 WGS 24Vdc 8,0A D.586200000008621010000 WGZ 24VDC 8,0A D.58621020000 WGZ 24Vdc 6,3A D.58621030000 WGZ 24Vdc 3,15A D.48621040000 WGZ 24Vdc 1,6A D.48628620000 CP NT3 250W 24V 10A B.78628630000 CP NT3 400W 24V 15A B.78628650000 CP NT3 500W 24V 20A B.88628660000 CP NT3 600W 24V 25A B.88628670000 CP NT3 750W 24V 30A B.98628680000 CP NT3 1000W 24V 40A B.987000000008708660000 CP SNT 70W 24V 3A A.308708670000 CP SNT 120W 24V 5A A.318708680000 CP SNT 250W 24V 10A A.328708700000 CP SNT3 250W 24V 10A A.368708710000 CP SNT3 500W 24V 20A A.378708730000 CP SNT3 1000W 24V 40A A.3887100000008710270000 WGS 24Vdc 0.5...5A D.68710620000 CP DM 10 A.3987200000008727630000 WGZ 24Vdc 0.5...5A D.687300000008734580000 Schuko TS35 E.138739140000 CP SNT 48W 24V 2A A.4587500000008754960000 CP SNT 25W 5V 5A A.438754970000 CP SNT 48W 12V 4A A.4487600000008768650000 CP DM 20 A.3987700000008778870000 CP SNT 500W 24V 20A A.3388600000008862730000 CP SNT3 120W 24V 5A A.358862780000 CP SNT 1000W 24V 40A A.3488700000008879230000 CP SNT 48W 48V 1A A.4689500000008951330000 CP M SNT 70W 24V 3A A.58951340000 CP M SNT 120W 24V 5A A.58951350000 CP M SNT 180W 24V 7,5A A.68951360000 CP M SNT 250W 24V 10A A.68951370000 CP M SNT 500W 24V 20A A.78951380000 CP M SNT 1000W 24V 40A A.78951390000 CP M SNT3 120W 24V 5A A.88951400000 CP M SNT3 250W 24V 10A A.88951410000 CP M SNT3 500W 24V 20A A.98951420000 CP M SNT3 1000W 24V 40A A.999100000009916250024 CP SNT 300W 24V 12.5A A.529916280012 CP-BBU 115-230VAC / 12VDC C.39916280024 CP-BBU 115-230VAC / 24VDC C.49917790324 CP-SNT 380-480VAC/24V A.539918840024 CP SNT 12W 24V 0.5A A.479919371212 CP DCDC 50W 12V 3A A.559919371215 CP DCDC 50W 15V 3A A.559919371224 CP DCDC 50W 22-24V 2A A.559919372405 CP DCDC 50W 5V 8A A.569919372412 CP DCDC 50W 12V 3A A.569919372415 CP DCDC 50W 15V 3A A.549919372424 CP DCDC 50W 22-24V 2A A.5499200000009925340005 CP SNT 160W 5V 8A A.519925340012 CP SNT 160W 12-15V 8A A.519925340024 CP SNT 160W 24-28V 6.5A A.509925340048 CP SNT 160W 48V 3.5A A.509927480005 CP SNT 55W 5V 3A A.499927480012 CP SNT 55W 12-15V 3A A.499927480024 CP SNT 55W 24-28V 2.3A A.489927480048 CP SNT 55W 48V 1.04A A.489928890005 CP SNT 24W 5V 2A A.429928890012 CP SNT 24W 12V 1.5A A.419928890015 CP SNT 24W 15V 1.5A A.419928890024 CP SNT 24W 24V 1A A.409928890028 CP SNT 24W 28V 1A A.40Index / Order No.XX.3


Addresses worldwideAddresses worldwideXAEUnited Arab EmiratesWeidmuller Middle East FZEP.O. Box 8591SAIF-ZoneSharjah – U. A. E.Phone +971 6 5572723Fax +971 6 5572724wme.info@weidmueller.comAR ArgentinaCPI SABauness 26601431 Buenos AiresPhone +54 11 45238008Fax + 54 11 45220546info@cpi.com.arwww.cpi.com.arAT AustriaWeidmüller GmbH.Industriezentrum Nö SüdStraße 2, Objekt M22355 Wiener NeudorfPhone +43 2236 6708-0Fax +43 2236 6708-199office.at@weidmueller.comAU AustraliaWeidmüller Pty. Ltd.P.O.Box 6944Huntingwood Drive 43Huntingwood,NSW, 2148Phone +61 2 9671-9999Fax +61 2 9671-9911info@weidmuller.com.auwww.weidmuller.com.auAZ AzerbaijanWest Industries Ltd.Caspian Plaza, 5-th Floor44 J. Jabbarly Str., BakuPhone +99412 499 15 15Fax +99412 499 14 93sales@west-i.comBA Bosnia and HerzegovinaBH ES ELEKTROSISTEM d.o.o.Bul. Vojvode S.Stepanovica kod br. 27278000 BiH - Banja LukaPhone +387 51 420-340Fax +387 51 420-341elsist@inecco.netwww.elektrosistem.baBE BelgiumWeidmüller Benelux B.V.Mechelsesteenweg 519 bus 6 en 71930 NossegemPhone +32 2 752 4070Fax +32 2 751 3606info@weidmueller.bewww.weidmueller.beBG BulgariaWeid-Bul EOOD1756 Sofia13, bul. "Kliment Ohridski"Phone +359 2 9632560Fax +359 2 9631098sofia@weidbul.comwww.weidbul.comBH BahrainKhayber Trading CompanyP.O. Box 1976 Manama,Phone +973 720747Fax +973 720331khayber@batelco.com.bhBR BrazilWeidmüller Conexel do BrasilRua Garcia Lorca, 17609695-900, Sao Paulo SPPhone +55 11 43669600Fax +55 11 43621677vendas@conexel.com.brwww.conexel.com.brBYBelarusTECHNIKON Ltd.Oktyabrskaya Str. 16/5Apt. 704, Minsk 220801Phone +375 17 2275830Fax +375 17 2275830technikon@belsonet.netCA CanadaW Interconnections CANADA Ltd.10 Spy Court, Markham,Ontario L3 R5 H6Phone +1 905 475-1507Fax +1 905 475-2798info1@weidmuller.cawww.weidmuller.caCH SwitzerlandWeidmüller Schweiz AGRundbuckstraße 28212 Neuhausen am RheinfallPhone +41 52 6740707Fax +41 52 6740708info@weidmueller.chwww.weidmueller.chCL ChileFelipe Bahamondes S.A./ATS AGROMaria Luisa Santander 0475Casilla 3425SantiagoPhone +56 2 341-1271Fax +56 2 341-1275felipe@atsintech.comCNChinaWeidmüller Interface InternationalTrading (Shanghai) Co., Ltd.25F, BM Intercontinental BusinessCenter,100 Yutong Road,Shanghai 200070P.R. ChinaPhone +86 21 22195008Fax +86 21 22195009www.cnweidmuller.comCO ColombiaAutomatización Avanzada S. A.Carrera 97 No.24c, 23 B44 Bogotá D. C.Phone +57 1 5478510Fax +57 1 4223044comercial@automatizacionavanzada.comwww.automatizacionavanzada.comCR Costa RicaELVATRON S.A.la Uruca 400 NorteBanco Costa RicaSan José Costa RicaPhone +506 2 961060Fax +506 5 200609dirk.haase@elvatron.comwww.elvatron.comCZ Czech RepublicWeidmüller s. r. o.Lomnického 5/170514000 Praha 4Phone +420 2 44001400Fax +420 2 44001499office@weidmueller.czwww.weidmueller.czDE GermanyWeidmüller GmbH & Co. KGP.O. Box 305432720 DetmoldOhmstraße 932758 DetmoldPhone +49 5231 1428-0Fax +49 5231 1428-116weidmueller@weidmueller.dewww.weidmueller.deDK DenmarkWexøe A/SLejrvej 313500 VaerloesePhone +45 45465800Fax +45 45465801wexoe@wexoe.dkwww.wexoe.dkECEcuadorElsystec S. A. ElectricidadSistemas y TecnologíaVasco de Contreras N35-25y Mañosca, QuitoPhone +593 2 2456510Fax+593 2 2456755Elsystec@uio.satnet.netEE EstoniaSoots Interface OÜPärnu mnt 14211317 TallinnPhone +372 5296177Fax +372 6096933info@sootsinterface.eewww.sootsinterface.eeEG EgyptStandard Electric (OMEGA)87, Mohamed Farid StreetHeliopolis, CairoPhone +20 26422977Fax +20 26422955stdelec@rite.comES SpainWeidmüller S. A.Narcis Monturiol 11-13Pol. Ind. Sudoeste08960 Sant Just DesvernBarcelonaPhone +34 93 4803386Fax +34 93 3718055weidmuller@weidmuller.eswww.weidmuller.esFI FinlandJUHA-ELEKTRO OYP. O. Box 57, 641 HelsinkiKylvöpolku 6, 680 HelsinkiPhone +358 10 8328 100Fax +358 10 8328 109info@juha-elektro.fiwww.juha-elektro.fiFR FranceWeidmüller E. U. R. L.12, Chaussée Jules CésarB.P. 263 Osny95523 Cergy Pontoise CedexPhone +33 1 34245500Fax +33 1 34245501mail@weidmuller.frGBGreat BritainWeidmüller Ltd.1 Abbey Wood RoadKings, West MallingME19 4YTPhone +44 1732 877000Fax +44 1732 874296marketing@weidmuller.co.ukGR GreeceElectrorama S.A.1 An. Martali Str.41335 LarissaPhone +30 2410 552533188Fax +30 2410 283463189valvizos@electrorama.com.grGreeceGA Contact Solutions11, Ippokratous Str.14452 Metamorfosi AttikaPhone +30 210 2823233Fax +30 210 2823233gasaless@gmail.comHK Hong KongUnited Equity LimitedSuite B, 11/F International IndustrialCentre2-8 Kwei Tei Street, Fotan, ShatinPhone +852 26876739Fax +852 26876735united_equity@sinatown.comHR CroatiaElektro Partner d.o.o.Slavonska Avenija 24/610000 ZagrebPhone +385 1 6184793Fax +385 1 6184795elektropartner@zg.t-com.hrHU HungaryWeidmüller KftGubacsi út 61097 BudapestPhone +36 1 3827700Fax +36 1 3827701info@weidmueller.huID IndonesiaPT. Nego ElectrindoRuko Mega Grosir Cempaka Mas,Blok I No 20 – 22Jl. Let.Jend. Suprato –Jakarta 10640Phone +62 21 42882255Fax +62 21 42882266sales@negoelectrindo.co.idIE IrelandPlease contact Weidmüller Ltd. inGreat BritainIL IsraelA.U.Shay Ltd.P.O. Box 10049Embar Street 23/25Petch-Tikwa 49222Phone +972 3 9233601Fax +972 3 9234601IsraelATEKA Ltd.23 Hayetzira St.Kiryat Aryeh49130 Petach-Tikva, IsraelPhone +972 3 9392344Fax +972 3 9243273marketing@ateka.co.ilwww.ateka.co.ilIN IndiaWeidmuller <strong>Electronics</strong> India Pvt. LtdPlot # 32, 3rd Floor, North CourtLane North Avenue, Opp Jogger's ParkKalyani Nagar, Maharastra411006 PunePhone +91 9049800960Nitish.Rajan@weidmueller.deIR IranTamin Ehtiajat Fani Tehran (TAF Co.)72, Iranshahr Ave.(Unit # 5)15816 TehranPhone +98 21 8831-7851Fax +98 21 8882-0268tafco@safineh.netIS IcelandSamey Automation CenterLyngas 13, 210 Garoabaer,Phone +354 510 5200Fax +354 510 5201samey@samey.isIT ItalyWeidmüller S.R.L.Via Albert Einstein 420092 Cinisello BalsamoMilanoPhone +39 02 660681Fax +39 02 6124945weidmuller@weidmuller.itwww.weidmuller.itJOJPKRKWJordanHORIZONSP.O.Box: 330607Amman Jordan 11133Phone +962 6 4882114Fax +962 6 4882115horizons@go.com.joJapanNihon Weidmüller Co. Ltd.Sphere Tower Tennoz,2-2-8 Higashi-Shinagawa,Shinagawa-Ku, Tokyo 140-0002Phone +81 3 6711-5300Fax +81 3 6711-5333www.weidmuller.co.jpKoreaWeidmüller Korea Co., Ltd.6floor, Sukyoung building, 242-54Nonhyun-dong, Kangnam-GuSeoul, KoreaZip: 135-830Phone +82 2 5160003Fax +82 2 5160090info@weidmuller.co.krKuwaitKANA CONTROLS GeneralTrading & Cont. CO. W.L.L.Al Rai Industrial Area,Plot 28-30, St. 31P.O.Box: 25593Safat, 13016Phone +966-474 1373/4Fax +966-474 1537info@kanacontrols.comX.4 2


Group companiesAgency abroadWithout own AgencyDEDEDEAddresses worldwideLB LebanonProgress Engineering & TradingEnterprisesAl Nahr StreetBeirutPhone +961 1 444664Fax +961 1 561880progress@inco.com.lbLT LithuaniaELEKTROS IRANGATinklu g.29a, 5319 PanevezysPhone +370 45582828Fax +370 45582727info@eliranga.ltLU LuxembourgPlease contact WeidmüllerBenelux B.V. in theNetherlandsLV LatviaSIA "ABI4"56A Daugavgrivas str.1007 RigaPhone +371 67470999Fax +371 67465637abi_4@tvnet.lvMD MoldovaBERHORD A&D srl44, srt. Sarmizegetusa 37/3Off 414. b-dul Decebal, 3,Chisinau, MD 2001Phone +373 22 507137Fax +373 22 507134atiuleanu@berhord.comME MontenegroPlease contactES-YU Elektrosistem in SerbiaMK MacedoniaELEKTRO – SMK dooelUL. III Makedonska brigada b.b.1000 SkopjePhone +389 22 460 295Fax +389 22 460 298Elektro-smk@telekabel.net.mkMT MaltaE. S. S., Electrical <strong>Supplies</strong>& Services Ltd104 J. Sciberras Str.Hamrun HMR 08Phone +356 21 255 777Fax +356 21 255 999robert@ess.com.mtMUMauritiusMUBELO Electrical LtdOffice 26, Gateway building,St Jean Road, Quatre BornesPhone +230 467 0989Fax +230 465 4051richard.mubelo@orange.muMX MexicoW Interconnections, S.A. DE C.V.Blvd. Hermanos Serdán No. 698Col. San Rafael OrientePuebla, C.P. 72029Phone +52 222 22686227clientes@weidmuller.com.mxMYMalaysiaConnect Plus Technology Sdn BhdNo. 43, Jalan PJS 11/22,Bandar Sunway, 46150 Petaling JayaSelangor Darul EhsanPhone +60 3 5633 7363Fax +60 3-5633 6562paul@cptech.com.mywww.cptech.com.myNL NetherlandsWeidmüller Benelux B.V.Franciscusweg 2211216 SE HilversumPostbus 15051200 BM HilversumPhone +31 35 6261261Fax +31 35 6232044info@weidmuller.nlNO NorwaySiv. Ing. J. F. Knudtzen A/SBillingstadsletta 97P.O. Box 1601378 NesbruPhone +47 66 983350Fax +47 66 980955firmapost@jfknudtzen.nowww.jfknudtzen.noNZ New ZealandCuthbert S. Steward Limited27 Te Puni StreetPOB 38496Petone, WellingtonPhone +64 4 5686156Fax +64 4 5686056info@weidmueller.deOM OmanDAN INTERNATIONAL LLC.PO.BOX 2901111 SeebPhone +968 503 677Fax +968 503 755yedu@danintl.comPE PeruIMGEPRO DEL PERU S.A.C.Jr. Arequipa 3410, Lima 31, PeruPhone / Fax +51 1 569-7678dbernardo@imgepro.com.pewww.imgepro.pePH PhilippinesEnclosure Systems Specialists IncW-15 La Fuerza Compound2241 Don Chino Roces AvenueMakati City 1231Phone +63 2 813 8580Fax +63 2 813 8596sales_encsys@pldtdsl.netPKPakistanKana Controls (Pak)Apartment No. 33 C IIIChenab Block,Allama Iqbal TownLahore, PakistanPhone +92 42 5419948+92 42 7845160Fax +92 42 5422895nadeem@kanapak.comwww.kanapak.comPL PolandWeidmüller Sp. z o.o.Ul. Goledzinowska 1003-302 WarszawaPhone +48 22 5100940Fax +48 22 5100941biuro@weidmuller.com.plwww.weidmuller.plPT PortugalWeidmüller Sistemas deInterface S. A.Estrada Outeiro Polima, R. AugustoDias da Silva, Lote B, Esct. 22785-515 Abóboda -São Domingosde RanaPhone +351 21 4459191Fax +351 21 4455871www.weidmueller.ptQAQatarDoha Motors Trading Co.(Technical Division)Post Box No. 145Airport RoadDoha - QatarPhone +974 465 1441Fax +974 465 0925dmtctech@qatar.net.qaRO RomaniaRominterface Impex SRLStr. Gh. Dem Teodorescu 30 A30916 Bucuresti - sector 3Phone +40 21 3220230Fax + 40 21 3228857office@rominterface.roRS SerbiaES-YU ElektrosistemPariske komune 4111070 Novi Beograd, SerbiaPhone +381 11 3018660Fax +381 11 2693608esyu@eunet.rswww.elektrosistem.co.rsRU RussiaWeidmüller Interface GmbH & Co. KGRepresentative OfficeWarshavskoye highway, 25A, bld. 6117105 MoscowPhone +7 4 95 771-6940Fax +7 4 95 771-6941info@weidmueller.ruwww.weidmueller.rusSA Saudi ArabiaAl Abdulkarim Holding Co.P.O Box. 4Dammam 31411Phone +9668337110Fax +9668338242salehsk@akh.com.sawww.akte.com.saSaudi Electric Supply Co.P.O. Box 3298Al Khobar 31952Phone +966 3 882 9546227Fax +966 3 882 9547Safdar.malik@sesco-ge.comSE SwedenWeidmüller ABAxel Daniessons väg 271P.O. box 31025200 49 MalmöPhone +46 (0) 7 71 43 00 44Fax +46 (0) 40 37 48 60info@weidmuller.sewww.weidmuller.seSG SingaporeWeidmuller Pte. Ltd.70 Bendemeer Road#04-03 LuzerneSingapore 339940Phone +65 6841 5311Fax +65 6841 5377info@weidmuller.com.sgwww.weidmuller.com.sgSI SloveniaELEKTROSPOJI d.o.o.Stegne 25, 1000 LjubljanaPhone +386 15113810Fax +386 15111604info@elektrospoji.siwww.elektrospoji.siSK SlovakiaELEKTRIS s.r.o.Elektrárenská 183104 BratislavaPhone +421 2 49200113Fax +421 2 49200119bratislava@elektris.skTHThailandPisanu Engineering Co., Ltd800/43-45 Soi TrakulsukAsoke-dindaeng Road,Dindaeng, Bangkok 10400Phone +66 2 245 9113Fax +66 2 6429220jayasankar@pisanu.co.thwww.pisanu.co.thTN TunisiaPlease contactWeidmüller E.U.R.L. in FranceTR TurkeyWeidmüller Elektronik Ticaret Ltd.SirketiKavacik Mah. Orhan Veli KanikCaddesi 9/134810 Beykoz – İstanbulPhone +90 216 5371070 (Pbx)Fax +90 216 5371077info@weidmuller.com.trwww.weidmuller.com.trTW TaiwanFittatek Co., Ltd.12F No. 185 Fu-Kuo Road,Tso Ying Dist, KaohsiungPhone +886 7 556 0858Fax +886 7 556 3279stanley@fittatek.com.twwww.fittatek.com.twTaiwanEucan Enterprise Ltd.No. 145 He Ping 2nd RdKaohsiungPhone +886 7 715 6610Fax +886 7 715 8748mark@eucan.com.twwww.eucan.com.twUA UkraineTEKO INTERFACE oooul. Lewanewskogo 603058 KievPhone +38 044 401 09 90Fax +38 044 401 08 64weidmueller@tekointerface.comwww.tekointerface.com.uaUSUnited StatesW-Interconnections Inc.821 Southlake Boulevard,Virginia - Richmond 23236Phone +1 804 7942877Fax +1 804 3792593info@weidmuller.comwww.weidmuller.comUY UruguayREWO Uruguay S.AAv. Bolivia 2001 Esq RocafuerteCarrasco Montevideo 11300Phone / Fax +598 260 48439clorda@rewouruguay.com.uyUZ UzbekistanOOO “Elektro Potential”Gani Mavljanova str., 2B100084 TashkentPhone +998 98-3003821Fax +998 71-1249286mz1958@yandex.ruVE VenezuelaSomerinca C.A.Quinta Sagrado Corazon de Jesus -3ra Transversal - Los Dos Caminos,Caracas 1070 - APhone +58 212 2352748Fax +58 212 2399341klocmoeller@cantv.netwww.kmsomerinca.com.veVNZAVietnamAUMI Co., LtdE1, La Thanh Hotel,218 Doi Can Street,Lieu Giai Ward, Ba Dinh District,Hanoi CityPhone +84 4762 8601Fax +84 4266 1391aumi@aumi.com.vnLinh Kim Hai Co,. Ltd78 Hoa Cuc Street Ward 7,Phu Bhuan District,Ho Chi Minh CityPhone +84 8517 1717Fax +84 8517 1818lkh@linhkimhai.com.vnNew Sky Co., Ltd44/28 Tan Hai Street,Ward 13, Tan Binh District,Ho Chi Minh CityPhone +84 8812 6593Fax +84 8812 6594newsky-e@hcm.vnn.vnwww.newsky-e.comSouth AfricaPhambili Interface (Pty) LtdP.O. Box 193, 1609 Johannesburg5 Bundo Road, Sebenza1610 Johannesburg, EndenvalePhone +27 11 452 1930Fax +27 11 452 6455sales@weidmuller.co.zawww.radinterface.co.zaDE Other countriesWeidmüller Interface GmbH & Co. KGPostfach 303032720 DetmoldKlingenbergstraße 1632758 DetmoldPhone +49 5231 14-0Fax +49 5231 14-2083info@weidmueller.dewww.weidmueller.comXX.53


IndexWe cannot guarantee that there are no mistakes in thepublications or software provided by us to the customer for thepurpose of making orders. We try our best to quickly correcterrors in our printed media.XAll orders are based on our general terms of delivery, which canbe reviewed on the websites of our group companies where youplace your order. On demand we can also send the general termsof delivery to you.X.6


www.weidmueller.comArgentinaAustraliaAustriaAzerbaijanBahrainBelarusBelgiumBosnia andHerzegovinaBrazilBulgariaCanadaChileChinaColombiaCosta RicaCroatiaCzech RepublicDenmarkEcuadorEgyptEstoniaFinlandFranceGermanyGreat BritainGreeceHong KongHungaryIcelandIndiaIndonesiaIranIrelandIsraelItalyJapanJordanKazakhstanKoreaKuwaitLatviaLebanonLithuaniaLuxembourgMacedoniaMalaysiaMaltaMexicoMoldovaNetherlandsNew ZealandNorwayOmanPakistanPeruPhilippinesPolandPortugalQatarRomaniaRussiaSaudi ArabiaSerbiaSingaporeSlovakiaSloveniaSouth AfricaSpainSwedenSwitzerlandTaiwanThailandTunisiaTurkeyUkraineUnited ArabEmiratesUnited StatesUruguayUzbekistanVenezuelaVietnamWeidmüller is a leading international provider of solutionsfor electrical connectivity, transmission and conditioningof power, signal and data in industrial environments.The company with headquarters in Detmold/Germanydevelops, produces and sells products in the field ofelectrical connectivity and electronics all over the world.Via a network of application specialists Weidmüller offersengineering services and develops application specificsolutions.The complete product and service portfolio consistentlyassures both Weidmüller and its customers ofcompetitive advantages and an increase in value.Order number:1282390000/05/2011/SMMD