Technical guide - 6th edition 2010<strong>Electrical</strong> <strong>installation</strong> <strong>h<strong>and</strong>book</strong><strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices


<strong>Electrical</strong> <strong>installation</strong> <strong>h<strong>and</strong>book</strong><strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devicesFirst edition 2003Second edition 2004Third edition 2005Fourth edition 2006Fifth edition 2007Sixth edition 2010Published by <strong>ABB</strong> SACEvia Baioni, 35 - 24123 Bergamo (Italy)All rights reserved


<strong>Electrical</strong> <strong>installation</strong> <strong>h<strong>and</strong>book</strong><strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devicesGeneral aspectsPart 1<strong>Protection</strong> <strong>and</strong> <strong>control</strong> devicesPart 2<strong>Electrical</strong> devices


General aspectsIndexIntroduction ............................................................................................................... 61 St<strong>and</strong>ards1.1 General aspects.............................................................................................. 71.2 IEC St<strong>and</strong>ards for electrical <strong>installation</strong>.......................................................... 19


IntroductionScope <strong>and</strong> objectivesThe scope of this electrical <strong>installation</strong> <strong>h<strong>and</strong>book</strong> is to provide the designer <strong>and</strong>user of electrical plants with a quick reference, immediate-use working tool. Thisis not intended to be a theoretical document, nor a technical catalogue, but, inaddition to the latter, aims to be of help in the correct definition of equipment,in numerous practical <strong>installation</strong> situations.The dimensioning of an electrical plant requires knowledge of different factorsrelating to, for example, <strong>installation</strong> utilities, the electrical conductors <strong>and</strong> othercomponents; this knowledge leads the design engineer to consult numerousdocuments <strong>and</strong> technical catalogues. This electrical <strong>installation</strong> <strong>h<strong>and</strong>book</strong>, however,aims to supply, in a single document, tables for the quick definition of themain parameters of the components of an electrical plant <strong>and</strong> for the selectionof the protection devices for a wide range of <strong>installation</strong>s. Some applicationexamples are included to aid comprehension of the selection tables.<strong>Electrical</strong> <strong>installation</strong> <strong>h<strong>and</strong>book</strong> usersThe electrical <strong>installation</strong> <strong>h<strong>and</strong>book</strong> is a tool which is suitable for all those who areinterested in electrical plants: useful for installers <strong>and</strong> maintenance techniciansthrough brief yet important electrotechnical references, <strong>and</strong> for sales engineersthrough quick reference selection tables.Validity of the electrical <strong>installation</strong> <strong>h<strong>and</strong>book</strong>Some tables show approximate values due to the generalization of the selectionprocess, for example those regarding the constructional characteristics ofelectrical machinery. In every case, where possible, correction factors are givenfor actual conditions which may differ from the assumed ones. The tables arealways drawn up conservatively, in favour of safety; for more accurate calculations,the use of DOCWin software is recommended for the dimensioning ofelectrical <strong>installation</strong>s.6 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>


1 St<strong>and</strong>ards1.1 General aspectsIn each technical field, <strong>and</strong> in particular in the electrical sector, a conditionsufficient (even if not necessary) for the realization of plants according to the“status of the art” <strong>and</strong> a requirement essential to properly meet the dem<strong>and</strong>sof customers <strong>and</strong> of the community, is the respect of all the relevant laws <strong>and</strong>technical st<strong>and</strong>ards.Therefore, a precise knowledge of the st<strong>and</strong>ards is the fundamental premisefor a correct approach to the problems of the electrical plants which shall bedesigned in order to guarantee that “acceptable safety level” which is neverabsolute.Juridical St<strong>and</strong>ardsThese are all the st<strong>and</strong>ards from which derive rules of behavior for the juridicalpersons who are under the sovereignty of that State.Technical St<strong>and</strong>ardsThese st<strong>and</strong>ards are the whole of the prescriptions on the basis of whichmachines, apparatus, materials <strong>and</strong> the <strong>installation</strong>s should be designed, manufactured<strong>and</strong> tested so that efficiency <strong>and</strong> function safety are ensured.The technical st<strong>and</strong>ards, published by national <strong>and</strong> international bodies, arecircumstantially drawn up <strong>and</strong> can have legal force when this is attributed bya legislative measure.Electrotechnics <strong>and</strong>ElectronicsApplication fieldsTelecommunicationsMechanics, Ergonomics<strong>and</strong> SafetyInternational Body IEC ITU ISOEuropean Body CENELEC ETSI CENThis technical collection takes into consideration only the bodies dealing with electrical <strong>and</strong> electronictechnologies.IEC International Electrotechnical CommissionThe International Electrotechnical Commission (IEC) was officially founded in1906, with the aim of securing the international co-operation as regardsst<strong>and</strong>ardization <strong>and</strong> certification in electrical <strong>and</strong> electronic technologies. Thisassociation is formed by the International Committees of over 40 countries allover the world.The IEC publishes international st<strong>and</strong>ards, technical guides <strong>and</strong> reports whichare the bases or, in any case, a reference of utmost importance for any national<strong>and</strong> European st<strong>and</strong>ardization activity.IEC St<strong>and</strong>ards are generally issued in two languages: English <strong>and</strong> French.In 1991 the IEC has ratified co-operation agreements with CENELEC (Europeanst<strong>and</strong>ardization body), for a common planning of new st<strong>and</strong>ardization activities<strong>and</strong> for parallel voting on st<strong>and</strong>ard drafts.<strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 7


1 St<strong>and</strong>ards1.1 General aspectsCENELEC European Committee for Electrotechnical St<strong>and</strong>ardizationThe European Committee for Electrotechnical St<strong>and</strong>ardization (CENELEC) wasset up in 1973. Presently it comprises 31 countries (Austria, Belgium, Bulgaria,Cyprus, Croatia, Czech Republic, Denmark, Estonia, Finl<strong>and</strong>, France, Germany,Greece, Hungary, Icel<strong>and</strong>, Irel<strong>and</strong>, Italy, Latvia, Lithuania, Luxembourg, Malta,Netherl<strong>and</strong>s, Norway, Portugal, Pol<strong>and</strong>, Romania, Slovakia, Slovenia, Spain,Sweden, Switzerl<strong>and</strong>, United Kingdom) <strong>and</strong> cooperates with 12 affiliates (Albania,Belarus, Georgia, Bosnia <strong>and</strong> Herzegovina, Tunisia, Former Yugoslav Republicof Macedonia, Serbia, Libia, Montenegro, Turkey, Ukraine <strong>and</strong> Israel) which havefirst maintained the national documents side by side with the CENELEC ones<strong>and</strong> then replaced them with the Harmonized Documents (HD).There is a difference between EN St<strong>and</strong>ards <strong>and</strong> Harmonization Documents(HD): while the first ones have to be accepted at any level <strong>and</strong> without additionsor modifications in the different countries, the second ones can be amendedto meet particular national requirements.EN St<strong>and</strong>ards are generally issued in three languages: English, French <strong>and</strong>German.From 1991 CENELEC cooperates with the IEC to accelerate the st<strong>and</strong>ardspreparation process of International St<strong>and</strong>ards.CENELEC deals with specific subjects, for which st<strong>and</strong>ardization is urgentlyrequired.When the study of a specific subject has already been started by the IEC, theEuropean st<strong>and</strong>ardization body (CENELEC) can decide to accept or, whenevernecessary, to amend the works already approved by the Internationalst<strong>and</strong>ardization body.8 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>EC DIRECTIVES FOR ELECTRICAL EQUIPMENTAmong its institutional roles, the European Community has the task of promulgatingdirectives which must be adopted by the different member states <strong>and</strong>then transposed into national law.Once adopted, these directives come into juridical force <strong>and</strong> become a referencefor manufacturers, installers, <strong>and</strong> dealers who must fulfill the dutiesprescribed by law.Directives are based on the following principles:• harmonization is limited to essential requirements;• only the products which comply with the essential requirements specified bythe directives can be marketed <strong>and</strong> put into service;• the harmonized st<strong>and</strong>ards, whose reference numbers are published in theOfficial Journal of the European Communities <strong>and</strong> which are transposedinto the national st<strong>and</strong>ards, are considered in compliance with the essentialrequirements;• the applicability of the harmonized st<strong>and</strong>ards or of other technical specificationsis facultative <strong>and</strong> manufacturers are free to choose other technical solutionswhich ensure compliance with the essential requirements;• a manufacturer can choose among the different conformity evaluation procedureprovided by the applicable directive.The scope of each directive is to make manufacturers take all the necessarysteps <strong>and</strong> measures so that the product does not affect the safety <strong>and</strong> healthof persons, animals <strong>and</strong> property.


1 St<strong>and</strong>ards1.1 General aspects“Low Voltage” Directive 2006/95/CEThe Low Voltage Directive refers to any electrical equipment designed for useat a rated voltage from 50 to 1000 V for alternating current <strong>and</strong> from 75 to1500 V for direct current.In particular, it is applicable to any apparatus used for production, conversion,transmission, distribution <strong>and</strong> use of electrical power, such as machines,transformers, devices, measuring instruments, protection devices <strong>and</strong> wiringmaterials.The following categories are outside the scope of this Directive:• electrical equipment for use in an explosive atmosphere;• electrical equipment for radiology <strong>and</strong> medical purposes;• electrical parts for goods <strong>and</strong> passenger lifts;• electrical energy meters;• plugs <strong>and</strong> socket outlets for domestic use;• electric fence <strong>control</strong>lers;• radio-electrical interference;• specialized electrical equipment, for use on ships, aircraft or railways, whichcomplies with the safety provisions drawn up by international bodies in whichthe Member States participate.Directive EMC 2004/108/CE (“Electromagnetic Compatibility”)The Directive on electromagnetic compatibility regards all the electrical <strong>and</strong> electronicapparatus as well as systems <strong>and</strong> <strong>installation</strong>s containing electrical <strong>and</strong>/or electronic components. In particular, the apparatus covered by this Directiveare divided into the following categories according to their characteristics:• domestic radio <strong>and</strong> TV receivers;• industrial manufacturing equipment;• mobile radio equipment;• mobile radio <strong>and</strong> commercial radio telephone equipment;• medical <strong>and</strong> scientific apparatus;• information technology equipment (ITE);• domestic appliances <strong>and</strong> household electronic equipment;• aeronautical <strong>and</strong> marine radio apparatus;• educational electronic equipment;• telecommunications networks <strong>and</strong> apparatus;• radio <strong>and</strong> television broadcast transmitters;• lights <strong>and</strong> fluorescent lamps.The apparatus shall be so constructed that:a) the electromagnetic disturbance it generates does not exceed a level allowingradio <strong>and</strong> telecommunications equipment <strong>and</strong> other apparatus to operateas intended;b) the apparatus has an adequate level of intrinsic immunity to electromagneticdisturbance to enable it to operate as intended.An apparatus is declared in conformity to the provisions at points a) <strong>and</strong> b) whenthe apparatus complies with the harmonized st<strong>and</strong>ards relevant to its productfamily or, in case there aren’t any, with the general st<strong>and</strong>ards.<strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 9


1 St<strong>and</strong>ards1.1 General aspectsCE conformity markingThe CE conformity marking shall indicate conformity to all the obligations imposedon the manufacturer, as regards his products, by virtue of the EuropeanCommunity directives providing for the affixing of the CE marking.When the CE marking is affixed on a product, it represents a declaration of themanufacturer or of his authorized representative that the product in questionconforms to all the applicable provisions including the conformity assessmentprocedures. This prevents the Member States from limiting the marketing <strong>and</strong>putting into service of products bearing the CE marking, unless this measureis justified by the proved non-conformity of the product.Flow diagram for the conformity assessment procedures established by the Directive2006/95/CE on electrical equipment designed for use within particular voltage range:Technical fileEC declaration ofconformityManufacturerThe manufacturerdraw up the technicaldocumentationcovering the design,manufacture <strong>and</strong>operation of theproductThe manufacturerguarantees <strong>and</strong> declaresthat his products are inconformity to the technicaldocumentation <strong>and</strong> to thedirective requirementsASDC008045F0201Naval type approvalThe environmental conditions which characterize the use of circuit breakers foron-board <strong>installation</strong>s can be different from the service conditions in st<strong>and</strong>ardindustrial environments; as a matter of fact, marine applications can require<strong>installation</strong> under particular conditions, such as:- environments characterized by high temperature <strong>and</strong> humidity, including saltmistatmosphere (damp-heat, salt-mist environment);- on board environments (engine room) where the apparatus operate in thepresence of vibrations characterized by considerable amplitude <strong>and</strong> duration.In order to ensure the proper function in such environments, the shipping registersrequire that the apparatus has to be tested according to specific typeapproval tests, the most significant of which are vibration, dynamic inclination,humidity <strong>and</strong> dry-heat tests.10 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>


1 St<strong>and</strong>ards1.1 General aspects<strong>ABB</strong> SACE circuit-breakers (Tmax-Emax) are approved by the following shippingregisters:• RINA Registro Italiano Navale Italian shipping register• DNV Det Norske Veritas Norwegian shipping register• BV Bureau Veritas French shipping register• GL Germanischer Lloyd German shipping register• LRs Lloyd’s Register of Shipping British shipping register• ABS American Bureau of Shipping American shipping registerIt is always advisable to ask <strong>ABB</strong> SACE as regards the typologies <strong>and</strong> the performancesof the certified circuit-breakers or to consult the section certificatesin the website http://bol.it.abb.com.Marks of conformity to the relevant national <strong>and</strong>international St<strong>and</strong>ardsThe international <strong>and</strong> national marks of conformity are reported in the followingtable, for information only:COUNTRY Symbol Mark designation Applicability/OrganizationEUROPE – Mark of compliance with theharmonized European st<strong>and</strong>ardslisted in the ENEC Agreement.AUSTRALIA AS Mark <strong>Electrical</strong> <strong>and</strong> non-electricalproducts.It guarantees compliance withSAA (St<strong>and</strong>ard Association ofAustralia).AUSTRALIA S.A.A. Mark St<strong>and</strong>ards Association of Australia(S.A.A.).The Electricity Authority of NewSouth Wales Sydney AustraliaAUSTRIA Austrian Test Mark Installation equipment <strong>and</strong>materialsOV E<strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 11


1 St<strong>and</strong>ards1.1 General aspectsCOUNTRY Symbol Mark designation Applicability/OrganizationAUSTRIAÖVE IdentificationThreadCablesBELGIUM CEBEC Mark Installation materials <strong>and</strong> electricalappliancesBELGIUM CEBEC Mark Conduits <strong>and</strong> ducts, conductors<strong>and</strong> flexible cordsBELGIUMCertification ofConformityInstallation material <strong>and</strong> electricalappliances (in case there are noequivalent national st<strong>and</strong>ards orcriteria)CANADA CSA Mark <strong>Electrical</strong> <strong>and</strong> non-electricalproducts.This mark guarantees compliancewith CSA (Canadian St<strong>and</strong>ardAssociation)CHINA CCC Mark This mark is required for a widerange of manufactured productsbefore being exported to or soldin the Peoples Republic of Chinamarket.Czech Republic EZU’ Mark Electrotechnical Testing InstituteSlovakiaRepublicEVPU’ MarkElectrotechnical Research <strong>and</strong>Design Institute12 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>


1 St<strong>and</strong>ards1.1 General aspectsCOUNTRY Symbol Mark designation Applicability/OrganizationCROATIA KONKAR <strong>Electrical</strong> Engineering InstituteDENMARKDEMKOApproval MarkLow voltage materials.This mark guarantees thecompliance of the product withthe requirements (safety) of the“Heavy Current Regulations”FINLANDSafety Markof the ElektriskaInspektoratetLow voltage material.This mark guarantees thecompliance of the product withthe requirements (safety) of the“Heavy Current Regulations”FRANCE ESC Mark Household appliancesFRANCE NF Mark Conductors <strong>and</strong> cables – Conduits<strong>and</strong> ducting – InstallationmaterialsFRANCENF IdentificationThreadCablesFRANCE NF Mark Portable motor-operated toolsFRANCE NF Mark Household appliances<strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 13


1 St<strong>and</strong>ards1.1 General aspectsCOUNTRY Symbol Mark designation Applicability/OrganizationGERMANY VDE Mark For appliances <strong>and</strong> technicalequipment, <strong>installation</strong> accessoriessuch as plugs, sockets, fuses,wires <strong>and</strong> cables, as well as othercomponents (capacitors, earthingsystems, lamp holders <strong>and</strong> electronicdevices)GERMANYVDEIdentification ThreadCables <strong>and</strong> cordsGERMANY VDE Cable Mark For cables, insulated cords, <strong>installation</strong>conduits <strong>and</strong> ductsGERMANYgeprüfteSicherheitVDE-GS Markfor technicalequipmentSafety mark for technicalequipment to be affixed after theproduct has been tested <strong>and</strong> certifiedby the VDE Test Laboratoryin Offenbach; the conformity markis the mark VDE, which is grantedboth to be used alone as well asin combination with the mark GSHUNGARY MEEI Hungarian Institute for Testing<strong>and</strong> Certification of <strong>Electrical</strong>EquipmentJAPAN JIS Mark Mark which guarantees compliancewith the relevant JapaneseIndustrial St<strong>and</strong>ard(s).IRELAND IIRS Mark <strong>Electrical</strong> equipmentIRELAND IIRS Mark <strong>Electrical</strong> equipmentMARKOFCONFORMITYI.I.R.S.14 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>


APPROVED TO SINGAPORE STANDARDMARCA DE CONFORMIDAD A NORMAS UNE1 St<strong>and</strong>ards1.1 General aspectsCOUNTRY Symbol Mark designation Applicability/OrganizationITALY IMQ Mark Mark to be affixed on electricalmaterial for non-skilled users;it certifies compliance with theEuropean St<strong>and</strong>ard(s).NORWAYNorwegian ApprovalMarkM<strong>and</strong>atory safety approval for lowvoltage material <strong>and</strong> equipmentNETHERLANDS KEMA-KEUR General for all equipmentKEURPOLAND KWE <strong>Electrical</strong> productsBRUSSIACertification of Conformity<strong>Electrical</strong> <strong>and</strong> non-electrical products.It guarantees compliancewith national st<strong>and</strong>ard (Gosst<strong>and</strong>ardof Russia)SINGAPORE SISIR <strong>Electrical</strong> <strong>and</strong> non-electricalproductsSLOVENIA SIQ Slovenian Institute of Quality <strong>and</strong>MetrologySPAIN AEE <strong>Electrical</strong> products.The mark is under the <strong>control</strong> ofthe Asociación ElectrotécnicaEspañola (Spanish ElectrotechnicalAssociation)<strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 15


1 St<strong>and</strong>ards1.1 General aspectsCOUNTRY Symbol Mark designation Applicability/OrganizationSPAIN AENOR Asociación Española de Normalizacióny Certificación.(Spanish St<strong>and</strong>arization <strong>and</strong>Certification Association)SWEDENSEMKOMarkM<strong>and</strong>atory safety approval for lowvoltage material <strong>and</strong> equipment.SWITZERLAND Safety Mark Swiss low voltage material subjectto m<strong>and</strong>atory approval (safety).SWITZERLAND – Cables subject to m<strong>and</strong>atoryapprovalSWITZERLAND SEV Safety Mark Low voltage material subject tom<strong>and</strong>atory approvalUNITEDKINGDOMCERTIFICATIONTRADE MARKASTA MarkMark which guarantees compliancewith the relevant “BritishSt<strong>and</strong>ards”UNITEDKINGDOMBASEC MarkMark which guarantees compliancewith the “British St<strong>and</strong>ards” forconductors, cables <strong>and</strong> ancillaryproducts.UNITEDKINGDOMBASECIdentification ThreadCables16 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>


APPROVED TO BRITISH STANDARDAN INDEPENDENT LABORATORYTES TIN G FOR P UBLIC S AFETY1 St<strong>and</strong>ards1.1 General aspectsCOUNTRY Symbol Mark designation Applicability/OrganizationUNITEDKINGDOMBEABSafety MarkCompliance with the “British St<strong>and</strong>ards”for household appliancesUNITEDKINGDOMBSISafety MarkCompliance with the “BritishSt<strong>and</strong>ards”UNITEDKINGDOMBEABKitemarkCompliance with the relevant“British St<strong>and</strong>ards” regardingsafety <strong>and</strong> performancesU.S.A.UNDERWRITERSLABORATORIESMark<strong>Electrical</strong> <strong>and</strong> non-electricalproductsL I S T E D(Product Name)(Control Number)U.S.A.UNDERWRITERSLABORATORIESMark<strong>Electrical</strong> <strong>and</strong> non-electricalproductsU.S.A. UL Recognition <strong>Electrical</strong> <strong>and</strong> non-electricalproductsCEN CEN Mark Mark issued by the EuropeanCommittee for St<strong>and</strong>ardization(CEN): it guarantees compliancewith the European St<strong>and</strong>ards.CENELEC Mark Cables<strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 17


1 St<strong>and</strong>ards1.1 General aspectsCOUNTRY Symbol Mark designation Applicability/OrganizationCENELEC Harmonization Mark Certification mark providingassurance that the harmonizedcable complies with the relevantharmonized CENELEC St<strong>and</strong>ards– identification threadEC Ex EUROPEA Mark Mark assuring the compliancewith the relevant European St<strong>and</strong>ardsof the products to be usedin environments with explosionhazardsCEEel CEEel Mark Mark which is applicable to somehousehold appliances (shavers,electric clocks, etc).EC - Declaration of ConformityThe EC Declaration of Conformity is the statement of the manufacturer, whodeclares under his own responsibility that all the equipment, procedures orservices refer <strong>and</strong> comply with specific st<strong>and</strong>ards (directives) or other normativedocuments.The EC Declaration of Conformity should contain the following information:• name <strong>and</strong> address of the manufacturer or by its European representative;• description of the product;• reference to the harmonized st<strong>and</strong>ards <strong>and</strong> directives involved;• any reference to the technical specifications of conformity;• the two last digits of the year of affixing of the CE marking;• identification of the signer.A copy of the EC Declaration of Conformity shall be kept by the manufactureror by his representative together with the technical documentation.18 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>


1 St<strong>and</strong>ards1.2 IEC St<strong>and</strong>ards for electrical<strong>installation</strong>The following pages list the main St<strong>and</strong>ards which refer to the most commonlow voltage electrical applications <strong>and</strong> report their publication years.The St<strong>and</strong>ards might have been amended, but the relevant amendaments arenot mentioned here.STANDARD YEAR TITLEIEC 60027-1 1992 Letter symbols to be used in ectricaltechnology - Part 1: GeneralIEC 60034-1 2010 Rotating electrical machines - Part 1: Rating<strong>and</strong> performanceIEC 60617-DB-Snapshot 2010 Graphical symbols for diagramsIEC 61082-1 2006 Preparation of documents used inelectrotechnology - Part 1: RulesIEC 60038 2009 IEC st<strong>and</strong>ard voltagesIEC 60664-1 2007 Insulation coordination for equipment withinlow-voltage systems - Part 1: Principles, requirements<strong>and</strong> testsIEC 60909-0 2001 Short-circuit currents in three-phase a.c. systems- Part 0: Calculation of currentsIEC 60865-1 1993 Short-circuit currents - Calculation of effects -Part 1: Definitions <strong>and</strong> calculation methodsIEC 60076-1 2000 Power transformers - Part 1: GeneralIEC 60076-2 1993 Power transformers - Part 2: Temperature riseIEC 60076-3 2000 Power transformers - Part 3: Insulation levels,dielectric tests <strong>and</strong> external clearances in airIEC 60076-5 2006 Power transformers - Part 5: Ability to withst<strong>and</strong>short circuitIEC/TR 60616 1978 Terminal <strong>and</strong> tapping markings for powertransformersIEC 60076-11 2004 Power transformers - Part 11: Dry-type transformersIEC 60445 2010 Basic <strong>and</strong> safety principles for man-machineinterface, marking <strong>and</strong> identification - Identificationof equipment terminals <strong>and</strong> conductorterminationsIEC 60073 2002 Basic <strong>and</strong> safety principles for man-machineinterface, marking <strong>and</strong> identification – Codingfor indicators <strong>and</strong> actuatorsIEC 60447 2004 Basic <strong>and</strong> safety principles for man-machineinterface, marking <strong>and</strong> identification - ActuatingprinciplesIEC 60947-1 2007 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part1: General rulesIEC 60947-2 2009 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part2: Circuit-breakers<strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 19


1 St<strong>and</strong>ards1.2 IEC st<strong>and</strong>ards for electrical <strong>installation</strong>STANDARD YEAR TITLEIEC 60947-3 2008 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part3: Switches, disconnectors, switch-disconnectors<strong>and</strong> fuse-combination unitsIEC 60947-4-1 2009 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part4-1: Contactors <strong>and</strong> motor-starters – Electromechanicalcontactors <strong>and</strong> motor-startersIEC 60947-4-2 2007 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part4-2: Contactors <strong>and</strong> motor-starters – AC semiconductormotor <strong>control</strong>lers <strong>and</strong> startersIEC 60947-4-3 2007 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear -Part 4-3: Contactors <strong>and</strong> motor-starters – ACsemiconductor <strong>control</strong>lers <strong>and</strong> contactors fornon-motor loadsIEC 60947-5-1 2009 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part5-1: Control circuit devices <strong>and</strong> switchingelements - Electromechanical <strong>control</strong> circuitdevicesIEC 60947-5-2 2007 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part5-2: Control circuit devices <strong>and</strong> switchingelements – Proximity switchesIEC 60947-5-3 2005 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part5-3: Control circuit devices <strong>and</strong> switchingelements – Requirements for proximity deviceswith defined behaviour under fault conditionsIEC 60947-5-4 2002 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear -Part 5: Control circuit devices <strong>and</strong> switchingelements – Section 4: Method of assessing theperformance of low energy contacts. SpecialtestsIEC 60947-5-5 2005 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part5-5: Control circuit devices <strong>and</strong> switchingelements - <strong>Electrical</strong> emergency stop devicewith mechanical latching functionIEC 60947-5-6 1999 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part5-6: Control circuit devices <strong>and</strong> switchingelements – DC interface for proximity sensors<strong>and</strong> switching amplifiers (NAMUR)IEC 60947-6-1 2005 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part6-1: Multiple function equipment – Transferswitching equipmentIEC 60947-6-2 2007 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part6-2: Multiple function equipment - Control <strong>and</strong>protective switching devices (or equipment)(CPS)IEC 60947-7-1 2009 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part7: Ancillary equipment - Section 1: Terminalblocks for copper conductors20 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>


1 St<strong>and</strong>ards1.2 IEC st<strong>and</strong>ards for electrical <strong>installation</strong>STANDARD YEAR TITLEIEC 60947-7-2 2009 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear - Part7: Ancillary equipment - Section 2: Protectiveconductor terminal blocks for copperconductorsIEC 61439-1 2009 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gearassemblies - Part 1: General rulesIEC 60439-2 2005 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gearassemblies - Part 2: Particular requirements forbusbar trunking systems (busways)IEC 60439-3 2001 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gearassemblies - Part 3: Particular requirementsfor low-voltage switchgear <strong>and</strong> <strong>control</strong>gearassemblies intended to be installed in placeswhere unskilled persons have access for theiruse - Distribution boardsIEC 60439-4 2004 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gearassemblies - Part 4: Particular requirements forassemblies for construction sites (ACS)IEC 60439-5 2006 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gearassemblies - Part 5: Particular requirementsfor assemblies for power distribution in publicnetworksIEC 61095 2009 Electromechanical contactors for household<strong>and</strong> similar purposesIEC/TR 60890 1987 A method of temperature-rise assessmentby extrapolation for partially type-testedassemblies (PTTA) of low-voltage switchgear<strong>and</strong> <strong>control</strong>gearIEC/TR 61117 1992 A method for assessing the short-circuitwithst<strong>and</strong> strength of partially type-testedassemblies (PTTA)IEC 60092-303 1980 <strong>Electrical</strong> <strong>installation</strong>s in ships. Part 303:Equipment - Transformers for power <strong>and</strong>lightingIEC 60092-301 1980 <strong>Electrical</strong> <strong>installation</strong>s in ships. Part 301:Equipment - Generators <strong>and</strong> motorsIEC 60092-101 2002 <strong>Electrical</strong> <strong>installation</strong>s in ships - Part 101:Definitions <strong>and</strong> general requirementsIEC 60092-401 1980 <strong>Electrical</strong> <strong>installation</strong>s in ships. Part 401:Installation <strong>and</strong> test of completed <strong>installation</strong>IEC 60092-201 1994 <strong>Electrical</strong> <strong>installation</strong>s in ships - Part 201:System design - GeneralIEC 60092-202 1994 <strong>Electrical</strong> <strong>installation</strong>s in ships - Part 202:System design - <strong>Protection</strong><strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 21


1 St<strong>and</strong>ards1.2 IEC st<strong>and</strong>ards for electrical <strong>installation</strong>STANDARD YEAR TITLEIEC 60092-302 1997 <strong>Electrical</strong> <strong>installation</strong>s in ships - Part 302: Lowvoltageswitchgear <strong>and</strong> <strong>control</strong>gear assembliesIEC 60092-350 2008 <strong>Electrical</strong> <strong>installation</strong>s in ships - Part 350:General construction <strong>and</strong> test methods ofpower, <strong>control</strong> <strong>and</strong> instrumentation cables forshipboard <strong>and</strong> offshore applicationsIEC 60092-352 2005 <strong>Electrical</strong> <strong>installation</strong>s in ships - Part 352:Choice <strong>and</strong> <strong>installation</strong> of electrical cablesIEC 60364-5-52 2009 <strong>Electrical</strong> <strong>installation</strong>s of buildings - Part 5-52:Selection <strong>and</strong> erection of electrical equipment– Wiring systemsIEC 60227Polyvinyl chloride insulated cables of ratedvoltages up to <strong>and</strong> including 450/750 V2007 Part 1: General requirements2003 Part 2: Test methods1997 Part 3: Non-sheathed cables for fixed wiring1997 Part 4: Sheathed cables for fixed wiring2003 Part 5: Flexible cables (cords)2001 Part 6: Lift cables <strong>and</strong> cables for flexibleconnections2003 Part 7: Flexible cables screened <strong>and</strong>unscreened with two or more conductorsIEC 60228 2004 Conductors of insulated cablesIEC 60245Rubber insulated cables - Rated voltages up to<strong>and</strong> including 450/750 V2008 Part 1: General requirements1998 Part 2: Test methods1994 Part 3: Heat resistant silicone insulated cables2004 Part 4: Cord <strong>and</strong> flexible cables1994 Part 5: Lift cables1994 Part 6: Arc welding electrode cables1994 Part 7: Heat resistant ethylene-vinyl acetaterubber insulated cables2004 Part 8: Cords for applications requiring highflexibilityIEC 60309-2 2005 Plugs, socket-outlets <strong>and</strong> couplers for industrialpurposes - Part 2: Dimensional interchangeabilityrequirements for pin <strong>and</strong> contact-tubeaccessoriesIEC 61008-1 2010 Residual current operated circuit-breakerswithout integral overcurrent protection forhousehold <strong>and</strong> similar uses (RCCBs) - Part 1:General rulesIEC 61008-2-1 1990 Residual current operated circuit-breakerswithout integral overcurrent protection forhousehold <strong>and</strong> similar uses (RCCB’s). Part 2-1:Applicability of the general rules to RCCB’sfunctionally independent of line voltage22 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>


1 St<strong>and</strong>ards1.2 IEC st<strong>and</strong>ards for electrical <strong>installation</strong>STANDARD YEAR TITLEIEC 61008-2-2 1990 Residual current operated circuit-breakerswithout integral overcurrent protection forhousehold <strong>and</strong> similar uses (RCCB’s). Part 2-2:Applicability of the general rules to RCCB’sfunctionally dependent on line voltageIEC 61009-1 2010 Residual current operated circuit-breakers withintegral overcurrent protection for household<strong>and</strong> similar uses (RCBOs) - Part 1: GeneralrulesIEC 61009-2-1 1991 Residual current operated circuit-breakers withintegral overcurrent protection for household<strong>and</strong> similar uses (RCBO’s) Part 2-1: Applicabilityof the general rules to RCBO’s functionallyindependent of line voltageIEC 61009-2-2 1991 Residual current operated circuit-breakers withintegral overcurrent protection for household<strong>and</strong> similar uses (RCBO’s) - Part 2-2: Applicabilityof the general rules to RCBO’s functionallydependent on line voltageIEC 60670-1 2002 Boxes <strong>and</strong> enclosures for electrical accessoriesfor household <strong>and</strong> similar fixed electrical<strong>installation</strong>s - Part 1: General requirementsIEC 60669-2-1 2009 Switches for household <strong>and</strong> similar fixedelectrical <strong>installation</strong>s - Part 2-1: Particularrequirements – Electronic switchesIEC 60669-2-2 2006 Switches for household <strong>and</strong> similar fixedelectrical <strong>installation</strong>s - Part 2: Particular requirements- Section 2: Remote-<strong>control</strong> switches(RCS)IEC 60669-2-3 2006 Switches for household <strong>and</strong> similar fixedelectrical <strong>installation</strong>s - Part 2-3: Particularrequirements – Time-delay switches (TDS)IEC 60079-10-1 2009 Explosive atmospheres Part 10 -1: Cassificationof area - explosive gas atmospheresIEC 60079-14 2007 Explosive atmospheres Part 14: <strong>Electrical</strong><strong>installation</strong> design, selection <strong>and</strong> erectionIEC 60079-17 2007 <strong>Electrical</strong> apparatus for explosive gasatmospheres - Part 17: Inspection <strong>and</strong>maintenance of electrical <strong>installation</strong>s inhazardous areas (other than mines)IEC 60269-1 2009 Low-voltage fuses - Part 1: GeneralrequirementsIEC 60269-2 2010 Low-voltage fuses. Part 2: Supplementaryrequirements for fuses for use by authorizedpersons (fuses mainly for industrial application)examples of st<strong>and</strong>ardized system of fuses A to J<strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 23


1 St<strong>and</strong>ards1.2 IEC st<strong>and</strong>ards for electrical <strong>installation</strong>STANDARD YEAR TITLEIEC 60269-3 2010 Low-voltage fuses - Part 3-1: Supplementaryrequirements for fuses for use by unskilledpersons (fuses mainly for household <strong>and</strong> similarapplications) - Sections I to IV: examples ofst<strong>and</strong>ardized system of fuses A to FIEC 60127-1/10 Miniature fuses -2006 Part 1: Definitions for miniature fuses <strong>and</strong>general requirements for miniature fuse-links2010 Part 2: Cartridge fuse-links1988 Part 3: Sub-miniature fuse-links2005 Part 4: Universal Modular Fuse-Links (UMF)Through-hole <strong>and</strong> surface mount types1988 Part 5: Guidelines for quality assessment ofminiature fuse-links1994 Part 6: Fuse-holders for miniature cartridgefuse-links2001 Part 10: User guide for miniature fusesEC 60364-1 2005 Low-voltage electrical <strong>installation</strong>sPart 1: Fundamental principles, assessment ofgeneral characteristics, definitionsIEC 60364-4-41 2005 Low-voltage electrical <strong>installation</strong>sPart 4-41: <strong>Protection</strong> for safety - <strong>Protection</strong>against electric shockIEC 60364-4-42 2010 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 4-42: <strong>Protection</strong> for safety - <strong>Protection</strong>against thermal effectsIEC 60364-4-43 2008 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 4-43: <strong>Protection</strong> for safety - <strong>Protection</strong>against overcurrentIEC 60364-4-44 2007 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 4-44: <strong>Protection</strong> for safety - <strong>Protection</strong>against voltage disturbances <strong>and</strong>electromagnetic disturbancesIEC 60364-5-51 2005 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 5-51: Selection <strong>and</strong> erection of electricalequipment Common rulesIEC 60364-5-52 2009 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 5-52: Selection <strong>and</strong> erection of electricalequipment Wiring systemsIEC 60364-5-53 2002 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 5-53: Selection <strong>and</strong> erection of electricalequipment Isolation, switching <strong>and</strong> <strong>control</strong>IEC 60364-5-54 2002 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 5-54: Selection <strong>and</strong> erection of electricalequipment Earthing arrangements, protectiveconductors <strong>and</strong> protective bonding conductors24 <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices | <strong>ABB</strong>


1 St<strong>and</strong>ards1.2 IEC st<strong>and</strong>ards for electrical <strong>installation</strong>STANDARD YEAR TITLEIEC 60364-5-55 2008 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 5-55: Selection <strong>and</strong> erection of electricalequipment Other equipmentIEC 60364-6 2006 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 6: VerificationIEC 60364-7 2004…2010 <strong>Electrical</strong> <strong>installation</strong>s of buildingsPart 7: Requirements for special <strong>installation</strong>sor locationsIEC 60529 2001 Degrees of protection provided by enclosures(IP Code)IEC 61032 1997 <strong>Protection</strong> of persons <strong>and</strong> equipment byenclosures - Probes for verificationIEC/TR 61000-1-1 1992 Electromagnetic compatibility (EMC)Part 1: General - Section 1: application <strong>and</strong>interpretation of fundamental definitions <strong>and</strong>termsIEC/TR 61000-1-3 2002 Electromagnetic compatibility (EMC)Part 1-3: General - The effects of high-altitudeEMP (HEMP) on civil equipment <strong>and</strong> systems<strong>ABB</strong> | <strong>Protection</strong>, <strong>control</strong> <strong>and</strong> electrical devices 25


Part 1<strong>Protection</strong> <strong>and</strong> <strong>control</strong> devicesIndex1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.1 Circuit-breaker nameplates................................281.2 Main definitions..................................................311.3 Types of releases...............................................351.3.1 Thermomagnetic releases <strong>and</strong>only magnetic releases............................351.3.2 Electronic releases..................................381.3.3 Residual current devices.........................442 General characteristics2.1 <strong>Electrical</strong> characteristics of circuit breakers........502.2 Trip curves.........................................................582.2.1 Software “Curves 1.0”.............................592.2.2 Trip curves of thermomagneticreleases..................................................602.2.3 Functions of electronic releases...............652.3 Limitation curves................................................902.4 Specific let-through energy curves.....................932.5 Temperature derating.........................................942.6 Altitude derating...............................................1062.7 <strong>Electrical</strong> characteristics of switchdisconnectors..................................................1073 <strong>Protection</strong> coordination3.1 <strong>Protection</strong> coordination ...................................1143.2 Discrimination tables........................................1233.3 Back-up tables................................................1563.4 Coordination tables betweencircuit breakers <strong>and</strong> switch disconnectors........1624 Special applications4.1 Direct current networks....................................1664.2 Networks at particular frequencies; 400 Hz<strong>and</strong> 16 2/3 Hz..................................................1834.2.1 400 Hz networks...................................1834.2.2 16 2/3 Hz networks..............................1964.3 1000 Vdc <strong>and</strong> 1000 Vac networks...................2004.4 Automatic Transfer Switches............................2125 Switchboards5.1 <strong>Electrical</strong> switchboards....................................2145.2 MNS switchboards..........................................2295.3 ArTu distribution switchboards.........................230Annex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboards ..........................233Annex B: Temperature rise evaluationaccording to IEC 60890..........................................243Annex C: Application examples:Advanced protection functions with PR123/P <strong>and</strong>PR333/P releases ...................................................257


1.1 Circuit-breaker nameplates1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devicesMoulded-case circuit-breaker: SACE Tmax XTSeriesXTIRated operationalvoltage UeTmax XT1B 160 Ue=690V AC/500V DC Ui=800V Uimp=8kV S/N:Ue (V)230 415 525 690 250Icu (kA)25 18 6 3 18Ics (% Icu)100 100 100 100 100Tmax Cat A50-60Hz2P in seriesCat ASize1234567CIRCUIT-BREAKER TYPERated ultimate short-circuitbreaking capacity at 415 VacB = 18 kA (XT1)C = 25 kA (XT1)N = 36 kAS = 50 kAH = 70 kAL = 120 kA (XT2-XT4)V = 150 kA (XT2-XT4)In = 160ASACE TmaxXT1Bon 160IEC 60947-2<strong>ABB</strong> SACEItalyoffTESTSize160 A250 ARated insulationvoltage Ui; i.e. themaximum r.m.s. valueof voltage which thecircuit-breaker iscapable ofwithst<strong>and</strong>ing at thesupply frequencyunder specified testconditions.Rated impulsewithst<strong>and</strong> voltageUimp; i.e. the peakvalue of impulsevoltage which thecircuit-breaker canwithst<strong>and</strong> underspecified testconditions.Seriel numberCompliance with theinternationalSt<strong>and</strong>ardIEC 60947-2:“Low-Voltageswitchgear <strong>and</strong><strong>control</strong>gear-Circuitbreakers”.Rated ultimate shortcircuitbreaking capacity international St<strong>and</strong>ardAccording to the(Icu) <strong>and</strong> rated service IEC 60947-2, the circuitshort-circuit breaking breakers can be dividedcapacity (Ics) at into Category A, i.e.different voltage values. without a specifiedshort-time withst<strong>and</strong>current rating, orCategory B, i.e. with aspecified short-timewithst<strong>and</strong> current rating.In rated currentCE marking affixed on<strong>ABB</strong> circuit-breakers toindicate compliancewith the following CEdirectives:“Low Voltage Directive”(LVD) no. 2006/95/CE“ElectromagneticCompatibility Directive”(EMC) no. 89/336 EEC.28 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.1 Circuit breaker nameplatesMoulded-case circuit-breaker: Tmax TSeriesTSize1234567CIRCUIT-BREAKER TYPERated ultimate short-circuitbreaking capacity at 415 VacB = 16 kAC = 25 kAN = 36 kAS = 50 kAH = 70 kAL = 85 kA (for T2)L = 120 kA (for T4-T5-T7)L = 100 kA (for T6)V = 150 kA (for T7)V = 200 kARateduninterruptedcurrent160 A250 A320 A400 A630 A800 A1000 A1250 A1600 ATmax T2L160Ue (V)Icu (kA)Ics (% Icu)Cat ARated uninterruptedcurrent IuRated operationalvoltage UeIu=160A Ue=690V Ui=800V Uimp=8kV IEC 60947-2230 400/415 440 500 690 250 500 Made in Italy150 85 75 50 10 85 85 by <strong>ABB</strong> SACE75 75 75 75 75 75 7550-60Hz 2P 3Pin seriesRated insulationvoltage Ui; i.e. themaximum r.m.s. valueof voltage which thecircuit-breaker iscapable ofwithst<strong>and</strong>ing at thesupply frequencyunder specified testconditions.Rated impulsewithst<strong>and</strong> voltageUimp; i.e. the peakvalue of impulsevoltage which thecircuit-breaker canwithst<strong>and</strong> underspecified testconditions.Rated ultimate shortcircuitbreaking capacity(Icu) <strong>and</strong> rated serviceshort-circuit breakingcapacity (Ics) atdifferent voltage values.According to theinternational St<strong>and</strong>ardIEC 60947-2, the circuitbreakers can be dividedinto Category A, i.e.without a specifiedshort-time withst<strong>and</strong>current rating, orCategory B, i.e. with aspecified short-timewithst<strong>and</strong> current rating.CE marking affixed on<strong>ABB</strong> circuit-breakers toindicate compliancewith the following CEdirectives:“Low Voltage Directive”(LVD) no. 2006/95/CE“ElectromagneticCompatibility Directive”(EMC) no. 89/336 EEC.Compliance with theinternationalSt<strong>and</strong>ardIEC 60947-2:“Low-Voltageswitchgear <strong>and</strong><strong>control</strong>gear-Circuitbreakers”.ASDC008046F0201<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 29


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.1 Circuit breaker nameplatesAir circuit-breaker: EmaxCIRCUIT-BREAKER TYPESeriesESizeX112346Rated ultimate short-circuitbreaking capacity at 415 VacB = 42 kAN = 65 kA (50 kA E1)S = 75 kA (85 kA E2)H = 100 kAL = 130 kA (150 kA X1)V = 150 kA (130 kA E3)Rateduninterruptedcurrent630 A800 A1000 A1250 A1600 A2000 A2500 A3200 A4000 A5000 A6300 ARated uninterruptedcurrent IuSACE E3V 32Iu=3200A Ue=690VIcw=85kA x 1sCat B ~ 50-60 Hz IEC 60947-2made in Italy by<strong>ABB</strong>-SACEUeIcuIcs(V)(kA)(kA)230130100415130100440130100Rated operationalvoltage Ue5251008569010085Rated short-timewithst<strong>and</strong> current Icw;i.e. the maximumcurrent thatthe circuit-breaker cancarry during aspecified time.According to theinternational St<strong>and</strong>ardIEC 60947-2, the circuitbreakerscan be dividedinto Category A, i.e.without a specified shorttimewithst<strong>and</strong> currentrating, or Category B, i.e.with a specified short-timewithst<strong>and</strong> current rating.Rated ultimateshort-circuitbreaking capacity(Icu) <strong>and</strong> ratedservice shortcircuitbreakingcapacity (Ics) atdifferent voltagevalues.CE marking affixed on<strong>ABB</strong> circuit-breakers toindicate compliancewith the following CEdirectives:“Low Voltage Directive”(LVD) no. 2006/95/CE“ElectromagneticCompatibility Directive”(EMC) no. 89/336 EEC.Compliance with theinternational St<strong>and</strong>ardIEC 60947-2:“Low-Voltageswitchgear <strong>and</strong><strong>control</strong>gear-Circuitbreakers”.ASDC008048F020130 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.2 Main definitionsThe main definitions regarding LV switchgear <strong>and</strong> <strong>control</strong>gear are included in theinternational St<strong>and</strong>ards IEC 60947-1, IEC 60947-2 <strong>and</strong> IEC 60947-3.Main characteristicsCircuit-breakerA mechanical switching device, capable of making, carrying <strong>and</strong> breaking currentsunder normal circuit conditions <strong>and</strong> also making, carrying for a specifiedtime <strong>and</strong> breaking currents under specified abnormal circuit conditions suchas those of short-circuit.Current-limiting circuit-breakerA circuit-breaker with a break-time short enough to prevent the short-circuitcurrent reaching its otherwise attainable peak value.Plug-in circuit-breakerA circuit-breaker which, in addition to its interrupting contacts, has a set ofcontacts which enable the circuit-breaker to be removed.Withdrawable circuit-breakerA circuit-breaker which, in addition to its interrupting contacts, has a set ofisolating contacts which enable the circuit-breaker to be disconnected fromthe main circuit, in the withdrawn position, to achieve an isolating distance inaccordance with specified requirements.Moulded-case circuit-breakerA circuit-breaker having a supporting housing of moulded insulating materialforming an integral part of the circuit-breaker.DisconnectorA mechanical switching device which, in the open position, complies with therequirements specified for the isolating function.ReleaseA device, mechanically connected to a mechanical switching device, whichreleases the holding means <strong>and</strong> permits the opening or the closing of theswitching device.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 31


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.2 Main definitionsFault types <strong>and</strong> currentsOverloadOperating conditions in an electrically undamaged circuit which cause anover-current.Short-circuitThe accidental or intentional connection, by a relatively low resistance orimpedance, of two or more points in a circuit which are normally at differentvoltages.Residual current (I ∆)It is the vectorial sum of the currents flowing in the main circuit of the circuitbreaker.Rated performancesVoltages <strong>and</strong> frequenciesRated operational voltage (U e)A rated operational voltage of an equipment is a value of voltage which, combinedwith a rated operational current, determines the application of the equipment<strong>and</strong> to which the relevant tests <strong>and</strong> the utilization categories are referred to.Rated insulation voltage (U i)The rated insulation voltage of an equipment is the value of voltage to whichdielectric tests voltage <strong>and</strong> creepage distances are referred. In no case themaximum value of the rated operational voltage shall exceed that of the ratedinsulation voltage.Rated impulse withst<strong>and</strong> voltage (U imp)The peak value of an impulse voltage of prescribed form <strong>and</strong> polarity which theequipment is capable of withst<strong>and</strong>ing without failure under specified conditionsof test <strong>and</strong> to which the values of the clearances are referred.Rated frequencyThe supply frequency for which an equipment is designed <strong>and</strong> to which theother characteristic values correspond.CurrentsRated uninterrupted current (I n)The rated uninterrupted current for a circuit-breaker is a value of current, thatthe circuit-breaker can carry during uninterrupted service.Rated residual operating current (I ∆n)It is the r.m.s. value of a sinusoidal residual operating current assigned to theCBR by the manufacturer, at which the CBR shall operate under specifiedconditions.Performances under short-circuit conditions32 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.2 Main definitionsRated making capacityThe rated making capacity of an equipment is a value of current, stated by themanufacturer, which the equipment can satisfactorily make under specifiedmaking conditions.Rated breaking capacityThe rated breaking of an equipment is a value of current, stated by the manufacturer,which the equipment can satisfactorily break, under specified breakingconditions.Rated ultimate short-circuit breaking capacity (I cu)The rated ultimate short-circuit breaking capacity of a circuit-breaker is themaximum short-circuit current value which the circuit-breaker can break twice(in accordance with the sequence O – t – CO), at the corresponding ratedoperational voltage. After the opening <strong>and</strong> closing sequence the circuit-breakeris not required to carry its rated current.Rated service short-circuit breaking capacity (I cs)The rated service short-circuit breaking capacity of a circuit-breaker is themaximum short-circuit current value which the circuit-breaker can break threetimes in accordance with a sequence of opening <strong>and</strong> closing operations(O - t - CO - t – CO) at a defined rated operational voltage (U e) <strong>and</strong> at a definedpower factor. After this sequence the circuit-breaker is required to carry itsrated current.Rated short-time withst<strong>and</strong> current (I cw)The rated short-time withst<strong>and</strong> current is the current that the circuit-breaker inthe closed position can carry during a specified short time under prescribedconditions of use <strong>and</strong> behaviour; the circuit-breaker shall be able to carry thiscurrent during the associated short-time delay in order to ensure discriminationbetween the circuit-breakers in series.Rated short-circuit making capacity (I cm)The rated short-circuit making capacity of an equipment is the value of shortcircuitmaking capacity assigned to that equipment by the manufacturer for therated operational voltage, at rated frequency, <strong>and</strong> at a specified power-factorfor ac.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 33


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.2 Main definitionsUtilization categoriesThe utilization category of a circuit-breaker shall be stated with reference towhether or not it is specifically intended for selectivity by means of an intentionaltime delay with respect to other circuit-breakers in series on the load side, undershort-circuit conditions (Table 4 IEC 60947-2).Category A - Circuit-breakers not specifically intended for selectivity undershort-circuit conditions with respect to other short-circuit protective devices inseries on the load side, i.e. without a short-time withst<strong>and</strong> current rating.Category B - Circuit-breakers specifically intended for selectivity under shortcircuitconditions with respect to other short-circuit protective devices in serieson the load side, i.e. with <strong>and</strong> intentional short-time delay provided for selectivityunder short-circuit conditions. Such circuit-breakers have a short-timewithst<strong>and</strong> current rating.A circuit-breaker is classified in category B if its I cwis higher than (Table 3 IEC60947-2):12·In or 5 kA, whichever is the greaterfor In ≤ 2500A30 kA for In > 2500A<strong>Electrical</strong> <strong>and</strong> mechanical durabilityMechanical durabilityThe mechanical durability of an apparatus is expressed by the number ofno-load operating cycles (each operating cycle consists of one closing <strong>and</strong>opening operation) which can be effected before it becomes necessary toservice or replace any of its mechanical parts (however, normal maintenancemay be permitted).<strong>Electrical</strong> durabilityThe electrical durability of an apparatus is expressed by the number of on-loadoperating cycles <strong>and</strong> gives the contact resistance to electrical wear under theservice conditions stated in the relevant product St<strong>and</strong>ard.34 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releasesA circuit-breaker must <strong>control</strong> <strong>and</strong> protect, in case of faults or malfunctioning,the connected elements of a plant. In order to perform this function, afterdetection of an anomalous condition, the release intervenes in a definite timeby opening the interrupting part.The protection releases fitted with <strong>ABB</strong> SACE moulded-case <strong>and</strong> air circuitbreakerscan <strong>control</strong> <strong>and</strong> protect any plant, from the simplest ones to thosewith particular requirements, thanks to their wide setting possibilities of boththresholds <strong>and</strong> tripping times.Among the devices sensitive to overcurrents, the following can be considered:• thermomagnetic releases <strong>and</strong> magnetic only releases;• microprocessor-based releases;• residual current devices.The choice <strong>and</strong> adjusting of protection releases are based both on the requirementsof the part of plant to be protected, as well as on the coordinationwith other devices; in general, discriminating factors for the selection are therequired threshold, time <strong>and</strong> curve characteristic.1.3.1 THERMOMAGNETIC RELEASES AND MAGNETIC ONLY RELEASESThe thermomagnetic releases use a bimetal <strong>and</strong> an electromagnet to detectoverloads <strong>and</strong> short-circuits; they are suitable to protect both alternating <strong>and</strong>direct current networks.The following table shows the types of thermo-magnetic <strong>and</strong> magnetic only tripunits available for SACE Tmax XT <strong>and</strong> Tmax T circuit-breakers.SACE Tmax XTCBsthermomagnetic releasesMF MA TMD TMA TMGXT1 - - - -XT2XT3 - -XT4 - -LegendaMF Fixed magnetic only releasesMA Adjustable magnetic only releasesTMG Thermomagnetic release for generator protectionTMD Thermomagnetic release with adjustable thermal <strong>and</strong> fixed magnetic thresholdTMA Thermomagnetic release with adjustable thermal <strong>and</strong> magnetic threshold<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 35


1.3 Types of releases1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devicesPower distributionMCCBs XT1 XT2 XT3 XT4In Iu 160 160 250 2501,622,53,24TMD56,381012.51620TMD25TMG324050 TMD63TMA80TMG100TMD125TMG160200225 -250 TMD/TMGTMDTMAMotor protectionMCCBs XT2 XT3 XT4In Iu 160 250 25012MF48,51012,5 MF203252 MAMA80100125MA160200LegendaMF Fixed magnetic only releasesMA Adjustable magnetic only releasesTMG Thermomagnetic release for generator protectionTMD Thermomagnetic release with adjustable thermal <strong>and</strong> fixed magnetic thresholdTMA Thermomagnetic release with adjustable thermal <strong>and</strong> magnetic threshold36 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releasesPower distributionTmax TCBsthermomagnetic releasesMF MA TMF TMD TMA TMGT1 - - - -T2 - -T3 - - -T4 - - -T5 - - - -T6 - - - - -MCCBs T1 T2 T3 T4 T5 T6In Iu 160 160 250 250 400 630 630 8001,622,53,245TMD6,381012.516TMDTMG20 TMD TMD25TMDTMG32 TMD TMDTMD40 TMFTMGTMGTMD50 TMD TMD6380TMD100TMG TMD125TMG TMA160200250320 TMA400TMGTMATMG500630 TMA800 TMALegendaMF Fixed magnetic only releasesMA Adjustable magnetic only releasesTMG Thermomagnetic release for generator protectionTMF Thermomagnetic release with thermal <strong>and</strong> fixedmagnetic thresholdMCCBs T2 T3 T4In Iu 160 250 25011,622,53,2456,58,5MF10 MA1112,520 MA25 MA325280100125160200MAMAMATMD Thermomagnetic release with adjustable thermal<strong>and</strong> fixed magnetic thresholdTMA Thermomagnetic release with adjustable thermal<strong>and</strong> magnetic threshold<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 37


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releases1.3.2 ELECTRONIC RELEASESThese releases are connected with current transformers (three or four accordingto the number of conductors to be protected), which are positioned inside thecircuit-breaker <strong>and</strong> have the double functions of supplying the power necessaryto the proper functioning of the release (self-supply) <strong>and</strong> of detecting the valueof the current flowing inside the live conductors; therefore they are compatiblewith alternating current networks only.The signal coming from the transformers <strong>and</strong> from the Rogowsky coils isprocessed by the electronic component (microprocessor) which compares itwith the set thresholds. When the signal exceeds the thresholds, the trip of thecircuit-breaker is operated through an opening solenoid which directly acts onthe circuit-breaker operating mechanism.In case of auxiliary power supply in addition to self-supply from the currenttransformers, the voltage shall be 24 Vdc ± 20%.Besides the st<strong>and</strong>ard protection functions, releases provide:- measuraments of currents (Ekip LSI/LSIG + Ekip COM, Ekip M LRIU + Ekip COM,PR222, PR232, PR331, PR121);- measurament of currents,voltage,frequency,power,energy,power factor(PR223,PR332,PR122) <strong>and</strong> moreover for PR333 <strong>and</strong> PR123, the measurementof harmonic distortions is available;- serial comunication with remote <strong>control</strong> for a complete management ofthe plant (Ekip LSI/LSIG + Ekip COM, Ekip M LRIU + Ekip COM, PR222,PR223, PR232, PR331, PR332, PR333, PR121, PR122, PR123).The following table shows the types of electronic trip units available forSACE Tmax XT, Tmax T <strong>and</strong> Emax circuit-breakers.electronic releases with <strong>ABB</strong> circuit breakersEkip Ekip G Ekip N PR221 PR222 PR223 PR231 PR232 PR331 PR332 PR333 PR121 PR122 PR123CBsILILILS/ILSI LI LI LSI LILSILSIG LS/I LS/IILS/ILSILSIG LSIGILS/I LSI LSIGLSIGLSRcLSILSIGLSILSIGLSIGLSRcLSILSIGXT2 - - - - - - - - - - -XT4 - - - - - - - - - - -T2 - - - - - - - - - - - - -T4 - - - - - - - - - - -T5 - - - - - - - - - - -T6 - - - - - - - - - - -T7 - - - - - - - - - -X1 - - - - - - - - - - -E1 - - - - - - - - - - -E2 - - - - - - - - - - -E3 - - - - - - - - - - -E4 - - - - - - - - - - -E5 - - - - - - - - - - -E6 - - - - - - - - - - -38 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releasesThe following table shows the available rated currents with the SACE Tmax XT,Tmax T <strong>and</strong> Emax circuit- breakers.MCCBs XT2 XT4 T2 T4 T5 T6 T7In Iu 160 160 250 160 250 320 400 630 630 800 1000 800 1000 1250 160010 (1) - - - - - - - - - - - - -25 (1) - - - - - - - - - - - - -40 - - - - - - - - - - - - -63 - - - - - - - - - - -100 - - - - - - - - -160 (1) - - - - - - - - -250 - - (1) - - - - - - - - - -320 - - - - - - - - - - - -400 - - - - - - - - -630 - - - - - - - - -800 - - - - - - - - - -1000 - - - - - - - - - - -1250 - - - - - - - - - - - - -1600 - - - - - - - - - - - - - -(1)Not available for Ekip N <strong>and</strong> Ekip I; only for XT2 In=10 A not available with Ekip GThe following table shows the available rated currents for motor protection withthe SACE Tmax XT <strong>and</strong> Tmax T circuit- breakers.InSACE Tmax XTMCCBs XT2 160 XT4 160 XT4 250Trip unitsEkip MIEkip MLIU or LRIU20 n - - -25 - n - -32 n - - -40 - - n n52 n - - -63 - n n n100 n n n n160 - - - nInTmax TMCCBs T2 160 T4 250 T5 400 T6 800Trip unitsPR221MPLIPR222MPLRIU40 n - - -63 n - - -100 n n - -160 - n - -200 - n - -320 - - n -400 - - n -630 - - - n<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 39


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releasesE3H-V E3 N-S-H-V E3 S-H-V-LACBsE2S E2N- E2B-N-E3 N-S-S-L S-L E2B-H-VE1B-NN-SE4S-H-V E6V E6H-VX1B-N-L X1B-NIn Iu 630 800 1250 (2) 1600 2000 2500 3200 4000 3200 4000 5000 6300400 - - - - - -630 - - - - - -800 - - - - - - -1000 - - - - - - - -1250 - - - - - -1600 - - - - - - -2000 - - - - - - - -2500 - - - - - - - - -3200 - - - - - -4000 - - - - - - - - -5000 - - - - - - - - - - -6300 - - - - - - - - - - - -(2)Also for Iu = 1000 A (not available for E3V <strong>and</strong> E2L).Example of reading from the tableThe circuit-breaker type E3L is available with Iu=2000A <strong>and</strong> Iu=2500A, but it is notavailable with Iu=3200A.40 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releases1.3.2.1 PROTECTION FUNCTIONS OF ELECTRONIC RELEASESThe protection functions available for the electronic releases are:L - Overload protection with inverse long time delayFunction of protection against overloads with inverse long time delay <strong>and</strong>constant specific let-through energy; it cannot be excluded.L - Overload protection in compliance with Std. IEC 60255-3Function of protection against overloads with inverse long time delay <strong>and</strong> tripcurves complying with IEC 60255-3; applicable in the coordination with fuses<strong>and</strong> with medium voltage protections.S - Short-circuit protection with adjustable delayFunction of protection against short-circuit currents with adjustable delay; thanksto the adjustable delay, this protection is particularly useful when it is necessaryto obtain selective coordination between different devices.S 2- Double SThis function allows two thresholds of protection function S to be set independently<strong>and</strong> activated simultaneously, selectivity can also be achieved underhighly critical conditions.D - Directional short-circuit protection with adjustable delayThe directional protection, which is similar to function S, can intervene in adifferent way according to the direction of the short-circuit current; particularlysuitable in meshed networks or with multiple supply lines in parallel.I - Short-circuit protection with instantaneous tripFunction for the instantaneous protection against short-circuit.EFDP - Early Fault Detection <strong>and</strong> PreventionThanks to this function, the release is able to isolate a fault in shorter times thanthe zone selectivities currently available on the market.Rc - Residual current protectionThis function is particularly suitable where low-sensitivity residual currentprotection is required <strong>and</strong> for high-sensitivity applications to protect peopleagainst indirect contact.G - Earth fault protection with adjustable delayFunction protecting the plant against earth faults.U - Phase unbalance protection<strong>Protection</strong> function which intervenes when an excessive unbalance between thecurrents of the single phases protected by the circuit-breaker is detected.OT - Self-protection against overtemperature<strong>Protection</strong> function <strong>control</strong>ling the opening of the circuit-breaker when thetemperature inside the release can jeopardize its functioning.UV - Undervoltage protection<strong>Protection</strong> function which intervenes when the phase voltage drops below thepreset threshold.OV - Overvoltage protection<strong>Protection</strong> function which intervenes when the phase voltage exceeds thepreset threshold.RV - Residual voltage protection<strong>Protection</strong> which identifies anomalous voltages on the neutral conductor.RP - Reverse power protection<strong>Protection</strong> which intervenes when the direction of the active power is oppo-<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 41


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releasesto normal operation.UF - Under frequency protectionThis frequency protection detects the reduction of network frequency above theadjustable threshold, generating an alarm or opening the circuit.OF - Overfrequency protectionThis frequency protection detects the increase of network frequency above theadjustable threshold, generating an alarm or opening the circuit.M - Thermal memoryThanks to this function, it is possible to take into account the heating of acomponent so that the tripping is the quicker the less time has elapsed sincethe last one.R - <strong>Protection</strong> against rotor blockageFunction intervening as soon as conditions are detected, which could lead tothe block of the rotor of the protected motor during operation.Iinst - Very fast instantaneous protection against short-circuitThis particular protection function has the aim of maintaining the integrity of thecircuit-breaker <strong>and</strong> of the plant in case of high currents requiring delays lowerthan those guaranteed by the protection against instantaneous short-circuit. Thisprotection must be set exclusively by <strong>ABB</strong> SACE <strong>and</strong> cannot be excluded.Dual settingWith this function it is possible to program two different sets of parameters (LSIG)<strong>and</strong>, through an external comm<strong>and</strong>, to switch from one set to the other.K - Load <strong>control</strong>Thanks to this function, it is possible to engage/disengage individual loads onthe load side before the overload protection L trips.42 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releasesThe following table summarizes the types of electronic release <strong>and</strong> the functionsthey implement:EkipEkip-GEkip-NPR221PR222PR223PR231PR232PR331PR332PR333PR121PR122PR123Tmax XTTmax TT7/X1X1EmaxOnly with PR120/V for Emax <strong>and</strong> PR330/V for X1<strong>Protection</strong> functionsL (t=k/I 2 )LS1 (t=k)S1 (t=k/I 2 )S2 (t=k)D (t=k)I (t=k)G (t=k)G (t=k/I 2 )Gext (t=k)Gext (t=k/I 2 )Gext (Idn)Rc (t=k)U (t=k)OTUV (t=k)OV (t=k)RV (t=k)RP (t=k)UFOFIinstEF<strong>Protection</strong> against overloadSt<strong>and</strong>ard trip curve according to IEC 60255-3<strong>Protection</strong> against short-circuit with time delay<strong>Protection</strong> against short-circuit with time delay<strong>Protection</strong> against short-circuit with time delay<strong>Protection</strong> against directional short-circuit<strong>Protection</strong> against instantaneous short-circuit<strong>Protection</strong> against earth fault with adjustable delay<strong>Protection</strong> against earth fault with adjustable delay<strong>Protection</strong> against earth fault with adjustable delay<strong>Protection</strong> against earth fault with adjustable delay<strong>Protection</strong> against earth fault with adjustable delayResidual current protection<strong>Protection</strong> against phase unbalance<strong>Protection</strong> against temperature out of range<strong>Protection</strong> against undervoltage<strong>Protection</strong> against overvoltage<strong>Protection</strong> against residual voltage<strong>Protection</strong> against reverse active power<strong>Protection</strong> against underfrequency<strong>Protection</strong> against overfrequencyInstantantaneous self-protectionEarly Fault Detection <strong>and</strong> Prevention<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 43


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releases1.3.3 RESIDUAL CURRENT DEVICESThe residual current releases are associated with the circuit-breaker in order toobtain two main functions in a single device:- protection against overloads <strong>and</strong> short-circuits;- protection against indirect contacts (presence of voltage on exposed conductiveparts due to loss of insulation).Besides, they can guarantee an additional protection against the risk of firederiving from the evolution of small fault or leakage currents which are notdetected by the st<strong>and</strong>ard protections against overload.Residual current devices having a rated residual current not exceeding 30 mAare also used as a means for additional protection against direct contact incase of failure of the relevant protective means.Their logic is based on the detection of the vectorial sum of the line currentsthrough an internal or external toroid.This sum is zero under service conditions or equal to the earth fault current (I ∆)in case of earth fault.When the release detects a residual current different from zero, it opens thecircuit-breaker through an opening solenoid.As we can see in the picture the protection conductor or the equipotentialconductor have to be installed outside the eventual external toroid.Generic distribution system (IT, TT, TN)L1L2L3NPECircuit-breakerProtective conductorLoadOpeningsolenoidASDC008002F020144 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>The operating principle of the residual current release makes it suitable for thedistribution systems TT, IT (even if paying particular attention to the latter) <strong>and</strong>TN-S, but not in the systems TN-C. In fact, in these systems, the neutral isused also as protective conductor <strong>and</strong> therefore the detection of the residualcurrent would not be possible if the neutral passes through the toroid, since thevectorial sum of the currents would always be equal to zero.


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releasesOne of the main characteristics of a residual current release is its minimum ratedresidual current I ∆n. This represents the sensitivity of the release.According to their sensitivity to the fault current, the residual current circuitbreakersare classified as:- type AC: a residual current device for which tripping is ensured in case ofresidual sinusoidal alternating current, in the absence of a dc componentwhether suddenly applied or slowly rising;- type A: a residual current device for which tripping is ensured for residualsinusoidal alternating currents in the presence of specified residual pulsatingdirect currents, whether suddenly applied or slowly rising.- type B residual current device for which tripping is ensured for residual sinusoidalalternating currents in presence of specified residual pulsanting directcurrents whether suddenly applied or slowy rising, for residual directs mayresult from rectifying circuits.Form of residualcurrentCorrect functioning of residualcurrent devicesTypeAC A BSinusoidal acsuddenly applied+++slowly risingsuddenly appliedPulsating dcwith or without 0,006A++slowly risingSmooth dcIn presence of electrical apparatuses with electronic components (computers,photocopiers, fax etc.) the earth fault current might assume a non sinusoidalshape but a type of a pulsating unidirectional dc shape. In these cases it isnecessary to use a residual current release classified as type A.In presence of rectifying circuits (i.e. single phase connection with capacitiveload causing smooth direct current, three pulse star connection or six pulsebridge connection, two pulse connection line-to-line) the earth fault currentmight assume a unidirectional dc shape. In this case it is necessary to use aresidual current release classified as type B.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 45+ASDC008003F0201


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releasesIn order to fulfill the requirements for an adequate protection against earth faults<strong>ABB</strong> SACE has designed the following product categories:- Miniature circuit-breakers:• RCBOs(residual currentoperated circuit-breakers with integral overcurrentprotection) DS201, DS202C series with rated current from 1 A up to 40 A;• RCBOs (residual current operated circuit-breakers with integral overcurrentprotection) DS200 with rated cur-rent from 6A up to 63A;• RCBOs (residual current operated circuit-breakers with integral overcurrentprotection) DS800 with 125A rated current;• RCD blocks(residual current blocks) DDA 200 type to be coupled with thethermal magnetic circuit-breakers type S200 with rated current from 0.5A to 63 A;• RCD blocks (residual current blocks) DDA 60, DDA 70, DD 90 type to becoupled with the thermal magnetic circuit-breakers type S290 with ratedcurrent from 80 A to 100 A with C characteristic curve;• RCD blocks (residual current blocks) DDA 800 type to be coupled withthe thermal magnetic circuit-breakers type S800N <strong>and</strong> S800S with ratedcurrent up to 100 A. These blocks are available in two sizes: 63 A <strong>and</strong>100 A;• RCCBs (residual current circuit-breakers) F200 type, with rated currentfrom 16 A to 125 A.• RD3: residual current monitor for fixing on DIN rail.- Tmax XT moulded case circuit breakers:• RC Sel 200mm XT1 (with adjustable time of non trip): residual currentreleases can be installed in 200mm modules; it can be coupled with X1circuit breakers with a rated current up to 160A.• RC Sel XT1-XT3 (with adjustable time of non trip): residual current releasesto be coupled with circuit breakers XT1, XT3 with a rated current up to160A with XT1 <strong>and</strong> 250A with XT346 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releases• RC Inst XT1-XT3 (instantaneous): residual current releases to be coupledwith circuit breakers XT1, XT3 with a rated current up to 160A.• RC Sel XT2-XT4 (with adjustable time of non trip): residual current releasesto be coupled with circuit breakers XT2, XT4 with a rated current up to160A with XT2 <strong>and</strong> 250A with XT4• RC B Type XT3 (with adjustable time of non trip): residual current releasesto be coupled with circuit breaker XT3 with a rated current up to 225A• Electronic trip units Ekip LSIG for circuit breakers XT2 <strong>and</strong> XT4 with arated current from 10 to 250A.RC Sel 200mmXT1RC InstXT1-XT3RC SelXT1-XT3RC SelXT2-XT4RC B TypeXT3Type “L” shaped “L” shaped “L” shaped Placed below Placed belowTechnologyMicroprocessor - basedPrimary power supplyvoltage[V] 85...500 85...500 85...500 85...500 85...500Operating frequence [Hz] 45...66 45...66 45...66 45...66 45...66Self-supply n n n n nTest operation range 85...500 85...500 85...500 85...500 85...500Rated service current [A] up to 160up to 160-XT1 up to 160-XT1 up to 160-XT2up to 250-XT3 up to 250-XT3 up to 250-XT4up to 225Rated residual current trip [A]0.03-0.05-0.1-0.03-0.05-0.1- 0.03-0.05-0.1-0.03-0.1-0.3-0.03-0.05-0.1-0.2-0.3-0.5-1-0.3-0.5-1-3- 0.3-0.5-1-3-0.5-1-30.3-0.5-13-5-105-105-10Adjustable NON-trip timesettings et 2xI∆n[s]Instantaneous0.1-0.2-0.3-0.5-1-2-3InstantaneousInstantaneous Instantaneous Instantaneous0.1-0.2-0.3- 0.1-0.2-0.3- 0.1-0.2-0.3-0.5-1-2-3 0.5-1-2-3 0.5-1-2-3RC Sel 200mm RC Inst RC Sel RC Sel RC B Type Ekip LSIGInTypeA A A A B -XT1 16÷160 n n n - - -XT2 1.6÷160 - - - n - nXT3 63÷250 - n n - n (1) -XT4 16÷250 - - - n - n(1)Up to 225 A<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 47


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releases- Tmax T moulded case circuit breakers:• RC221 residual current releases to be coupled with circuit-brakers TmaxT1, T2, T3 with rated current from 16 A to 250A;• RC222 residual current releases to be coupled with circuit-breakers TmaxT1,T2,T3,T4,T5 with rated currents from 16A to 500A;• RC223 residual current releases to coupled with circuit-breaker Tmax T4with rated currents up to 250A;• electronic releases PR222DS/P, PR223 DS/P LSIG for circuit breakersT4, T5, T6 with rated current from 100A to 1000A;• electronic releases PR331, PR332 LSIG for the circuit breaker Tmax T7with rated currents from 800A to 1600A;• electronic release R332 with residual current integrated protection for thecircuit-breaker type Tmax T7 with rated uninterrupted current from 800Ato 1600A.RC221 RC222 RC223Circuit-breaker size T1-T2-T3 T1-T2-T3 T4 <strong>and</strong> T5 4p T4 4pType “L” shaped placed belowTechnologymicroprocessor-basedActionWith trip coilPrimary service voltage (1) [V] 85…500 85…500 85…500 110…500Operating frequence [Hz] 45…66 45…66 45…66 0-400-700-1000Self-supplyTest operation range (1) 85…500 85…500 85…500 110…500Rated service current [A] up to 250 A up to 250 A up to 500 A up to 250 ARated residual current trip [A]0.03-0.1-0.3 0.03-0.05-0.1-0.3 0.03-0.05-0.1 0.03-0.05-0.10.5-1-3 0.5-1-3-5-10 0.3-0.5-1-3-5-10 0.3-0.5-1Time limit for non-trip [s] IstantaneousIstantaneous - 0.1 Istantaneous - 0.1 Istantaneous -0- 0.1-0.2-0.3-0.5-1-2-3 -0.2-0.3-0.5-1-2-3 -0.2-0.3-0.5-1-2-3Tolerance over trip times ±20% ±20% ±20%(1)Operation up to 50 V phase-neutral (55 V for RC223).RC 221 RC 222 RC 223PR332LSIRcPR222LSIGPR223LSIGTypeInA-AC A-AC B A-AC - - -T1 16÷160 n n - - - - -T2 10÷160 n n - - - - -T3 63÷250 n n n (1) - - - -T4 100÷320 - n n (2) - n n -T5 320÷630 - n - - n n -T6 630÷1000 - - - - n n -T7 800÷1600 - - - n - - n(1)Up to 225 A(2)Up to 250 APR332LSIRc48 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices1.3 Types of releases- Emax air circuit breaker:• PR331, PR332, PR333 LSIG electronic releases for the circuit breakerEmax X1 with rated uninterrupted currents from 630A to 1600A;• Air circuit breaker equipped with electronic releases type PR121, PR122,PR123 LSIG for the circuit breaker Emax E1 to E6 with rated uninterruptedcurrents from 400A to 6300A.• PR332, PR333 electronic releases with residual current integrated protectionfor circuit-breaker Emax X1 with rated uninterrupted currents from630A to 1600A;• PR122 <strong>and</strong> PR123 electronic releases with residual current integratedprotection for circuit-breakers Emax E1 to E6 with rated uninterruptedcurrents from 400A to 6300APR332PR333LIRcPR122LIRcPR331PR332PR333LSIGPR121PR122PR123LSIGInType A-AC A-AC - -X1 400÷1600 n - n -E1 400÷1600 - n - nE2 400÷2000 - n - nE3 400÷3200 - n - nE4 1250÷4000 - - - nE6 3200÷6300 - - - nResidual current relay with external transformer<strong>ABB</strong> SACE circuit breaker can be combined also with the residual current relaysRCQ 020/A with separate toroid in order to fulfill the requirements when the<strong>installation</strong> conditions are particulary restrictive, such as with circuit breakersalready installed, limited space in the circuit breaker compartment etc.Thanks to the settings characteristics of the residual current <strong>and</strong> of the triptimes, the residual current relays with external transformer can be easily installedalso in the final stages of the plant; in particolar, by selecting the rated residualcurrent I∆n=0.03A with instantaneous tripping, the circuit-breaker guaranteesprotection against indirect contact <strong>and</strong> represents an additional measure againstdirect contact also in the presence of particulary high earth resistance values.Such residual current relays are of the type with indirect action: the openingcomm<strong>and</strong> given by the relay must cause the tripping of the circuit-breakerthrough a shunt opening release (to be provided by the user).Residual current relays SACE RCQ 020/APower supply voltage AC [V] 115-230…415Operating frequency [Hz] 45÷66TripThreshold adjustement I∆n [A] 0.03-0.05-0.1-0.3-0.5-1-3-5-10-30Trip time adjustement [s] Inst-0.1-0.2-0.3-0.5-0.7-1-2-3-5<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 49


2 General characteristics2.1 <strong>Electrical</strong> characteristics of circuit-breakersPro M compact miniature circuit-breakersThe following table shows an overview of the MCBs, for further details pleaserefer to the technical catalogue.Series S200 S200 M S200 P SN 201 L SN 201Characteristics B, C, D, K, Z B, C, D, K, Z B, C, D, K, Z B, C B, C, DRated current [A] 0.5 ≤ In≤ 630.5 ≤ In≤ 630.2 ≤ In≤ 2532 ≤ In≤ 4050 ≤ In≤ 632 ≤ In≤ 402 ≤ In≤ 40Breaking capacity [kA]Reference st<strong>and</strong>ard Nr. poles Ue [V]IEC 23-3/EN 60898 Icn 230/400 6 10 25 15 15 4.5 6IEC/EN 60947-2 Icu 1, 1P+N 133 20 25 2 40 25 25 10 15230 10 15 2 25 15 15 6 102, 3, 4 230 20 25 2 40 25 25400 10 15 2 25 15 152, 3, 4 500690Ics 1, 1P+N 133 15 18.7 2 20 18.7 18.7 6 10230 7.5 11.2 2 12.5 11.2 7.5 4.5 62, 3, 4 230 15 1 18.7 2 20 18.7 18.7400 7.5 11.2 2 12.5 11.2 7.52, 3, 4 500690IEC/EN 60947-2Icu 1, 1P+N 24 20Direct cuttent60 10 10 15 10 10 10 15T=I/R≤5ms for allseries, except S280 UC125250<strong>and</strong> S800-UC2 48 20whwre T=I/R


2 General characteristics2.1 <strong>Electrical</strong> characteristics of circuit-breakersSN 201 M S 280 S 280 UC S 290 S800S S800N S800CB, C B, C B, K, Z K, Z C. D, K B, C, D K KM UCB UCK B, C, D B, C, D, K2 ≤ In≤ 4080 ≤ In≤ 1000.2 ≤ In≤ 4050 ≤ In≤ 6380 ≤ In≤ 12510 ≤ In≤ 12510 ≤ In≤ 12520 ≤ In≤ 8010 ≤ In≤ 12510 ≤ In≤ 12510 ≤ In≤ 12510 ≤ In≤ 12510 6 10 25 20 1520 15 10 610 6 6 4.5 20 (15) 3 50 50 50 3610 10 6 25 50 50 50 36 256 6 4.5 20 (15) 3 50 50 50 36 2515 4 15 4 15 4 10 4 256 4 6 4 6 4 4.510 15 7.5 67.5 6 6 4.5 10 (7.5) 3 40 40 40 30 1810 7.5 6 12.5 40 40 40 30 186 6 4.5 10 (7.5) 3 40 40 40 30 1811 4 11 4 11 4 8 44 4 4 4 4 4 315 10 256 4.5 30 30 3050 50 20 1015 106 4.5 30 30 30 20 1050 5030 5 30 5 30 5 30 5 30 5 20 5 10 530 6 30 6 30 6 30 6 30 6 20 6 10 650 5015 10 12.56 4.5 30 30 30 20 1050 5015 106 4.5 30 30 30 20 1050 5030 5 30 5 30 5 30 5 30 5 20 5 10 530 6 30 6 30 6 30 6 30 6 20 6 10 650 50<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 51


2 General characteristicsTmax XT moulded-case circuit-breakersXT1Size [A] 160Poles [Nr.] 3, 4Rated service voltage, Ue (AC) 50-60Hz [V] 690(DC) [V] 500Rated insulation voltage, Ui [V] 800Rated impulse withst<strong>and</strong> voltage, Uimp [kV] 8Version Fixed, Plug-in 2Breaking capacities B C N S HRate ultimate short-circuit breaking capacity, IcuIcu @ 220-230V 50-60Hz (AC) [kA] 25 40 65 85 100Icu @ 380V 50-60Hz (AC) [kA] 18 25 36 50 70Icu @ 415V 50-60Hz (AC) [kA] 18 25 36 50 70Icu @ 440V 50-60Hz (AC) [kA] 15 25 36 50 65Icu @ 500V 50-60Hz (AC) [kA] 8 18 30 36 50Icu @ 525V 50-60Hz (AC) [kA] 6 8 22 35 35Icu @ 690V 50-60Hz (AC) [kA] 3 4 6 8 10Icu @ 250V (DC) 2 poles in series [kA] 18 25 36 50 70Icu @ 500V (DC) 2 poles in series [kA] 18 25 36 50 70Rate service short-circuit breaking capacity, IcsIcu @ 220-230V 50-60Hz (AC) [kA] 100% 100% 75% (50) 75% 75%Icu @ 380V 50-60Hz (AC) [kA] 100% 100% 100% 100% 75%Icu @ 415V 50-60Hz (AC) [kA] 100% 100% 100% 75% 50% (37.5)Icu @ 440V 50-60Hz (AC) [kA] 75% 50% 50% 50% 50%Icu @ 500V 50-60Hz (AC) [kA] 100% 50% 50% 50% 50%Icu @ 525V 50-60Hz (AC) [kA] 100% 100% 50% 50% 50%Icu @ 690V 50-60Hz (AC) [kA] 100% 100% 75% 50% 50%Icu @ 250V (DC) 2 poles in series [kA] 100% 100% 100% 75% 75%Icu @ 500V (DC) 2 poles in series [kA] 100% 100% 100% 75% 75%Rate short-circuit making capacity, IcmIcu @ 220-230V 50-60Hz (AC) [kA] 52.5 84 143 187 220Icu @ 380V 50-60Hz (AC) [kA] 36 52.5 75.6 105 154Icu @ 415V 50-60Hz (AC) [kA] 36 52.5 75.6 105 154Icu @ 440V 50-60Hz (AC) [kA] 30 52.5 75.6 105 143Icu @ 500V 50-60Hz (AC) [kA] 13.6 36 63 75.6 105Icu @ 525V 50-60Hz (AC) [kA] 9.18 13.6 46.2 73.6 73.5Icu @ 690V 50-60Hz (AC) [kA] 4.26 5.88 9.18 13.6 17Category of use (IEC 60947-2)AReference st<strong>and</strong>ard IEC 60947-2Isolation behaviournMounted on DIN rail DIN EN 50022Mechanical life [No. Operations] 25000[No. Hourly Operations] 240<strong>Electrical</strong> life @ 415 V (AC) [No. Operations] 8000[No. Hourly Operations] 120(1)90kA @ 690V only for XT4 160. Available shortly, please ask <strong>ABB</strong> SACE(2)XT1 plug in version only with In max = 125A2.1 <strong>Electrical</strong> characteristics of circuit-breakers52 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.1 <strong>Electrical</strong> characteristics of circuit-breakersXT2 XT3 XT4160 250 160/2503, 4 3, 4 3, 4690 690 690500 500 5001000 800 10008 8 8Fixed, Withdrawable, Plug-in Fixed, Plug-in Fixed, Withdrawable, Plug-inN S H L V N S N S H L V65 85 100 150 200 50 85 65 85 100 150 20036 50 70 120 200 36 50 36 50 70 120 15036 50 70 120 150 36 50 36 50 70 120 15036 50 65 100 150 25 40 36 50 65 100 15030 36 50 60 70 20 30 30 36 50 60 7020 25 30 36 50 13 20 20 25 45 50 5010 12 15 18 20 5 8 10 12 15 20 25 (90 1 )36 50 70 120 150 36 50 36 50 70 120 15036 50 70 120 150 36 50 36 50 70 120 150100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%100% 100% 100% 100% 100% 75% 50% (27) 100% 100% 100% 100% 100%100% 100% 100% 100% 100% 75% 50% (27) 100% 100% 100% 100% 100%100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%100% 100% 100% 100% 100% 75% 50% 100% 100% 100% 100% 100%100% 100% 100% 100% 75% 75% 50% 100% 100% 100% 100% 75% (20)100% 100% 100% 100% 100% 100% 75% 100% 100% 100% 100% 100%100% 100% 100% 100% 100% 100% 75% 100% 100% 100% 100% 100%143 187 220 330 440 105 187 143 187 220 330 44075.6 105 154 264 440 75.6 105 75.6 105 154 264 33075.6 105 154 264 330 75.6 105 75.6 105 154 264 33075.6 105 143 220 330 52.5 84 75.6 105 143 220 33063 75.6 105 132 154 40 63 63 75.6 105 132 15440 52.5 63 75.6 105 26 40 40 52.5 94.5 105 10517 24 30 36 40 7.65 13.6 17 24 84 40 52.5A A AIEC 60947-2 IEC 60947-2 IEC 60947-2n n nDIN EN 50022 DIN EN 50022 DIN EN 5002225000 25000 25000240 240 2408000 8000 8000120 120 120<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 53


2 General characteristicsTmax T moulded-case circuit-breakers2.1 <strong>Electrical</strong> characteristics of circuit-breakersTmax T1 1P Tmax T1 Tmax T2Rated uninterrupted cur rent, Iu [A] 160 160 160Poles [Nr] 1 3/4 3/4Rated service cur rent, Ue (AC) 50-60 Hz [V] 240 690 690(DC) [V] 125 500 500Rated impulse withst<strong>and</strong> voltage, Uimp [kV] 8 8 8Rated insulation voltage, Ui [V] 500 800 800Test voltage at industrial frequency for 1 min. [V] 3000 3000 3000Rated ultimate short-ci rcuit breaking capacity, Icu B B C N N S H L(AC) 50-60 Hz 220/230 V [kA] 25* 25 40 50 65 85 100 120(AC) 50-60 Hz 380/415 V [kA] – 16 25 36 36 50 70 85(AC) 50-60 Hz 440 V [kA] – 10 15 22 30 45 55 75(AC) 50-60 Hz 500 V [kA] – 8 10 15 25 30 36 50(AC) 50-60 Hz 690 V [kA] – 3 4 6 6 7 8 10(DC) 250 V - 2 poles in series [kA] 25 (at 125 V) 16 25 36 36 50 70 85(DC) 250 V - 3 poles in series [kA] – 20 30 40 40 55 85 100(DC) 500 V - 2 poles in series [kA] – – – – – – – –(DC) 500 V - 3 poles in series [kA] – 16 25 36 36 50 70 85(DC) 750 V - 3 poles in series [kA] – – – – – – – –Rated service short-ci rcuit breaking capacity, Ics(AC) 50-60 Hz 220/230 V [%Icu] 75% 100% 75% 75% 100% 100% 100% 100%(AC) 50-60 Hz 380/415 V [%Icu] – 100% 100% 75% 100% 100% 100% 75% (70 kA)(AC) 50-60 Hz 440 V [%Icu] – 100% 75% 50% 100% 100% 100% 75%(AC) 50-60 Hz 500 V [%Icu] – 100% 75% 50% 100% 100% 100% 75%(AC) 50-60 Hz 690 V [%Icu] – 100% 75% 50% 100% 100% 100% 75%Rated short-ci rcuit making capacity, Icm(AC) 50-60 Hz 220/230 V [kA] 52.5 52.5 84 105 143 187 220 264(AC) 50-60 Hz 380/415 V [kA] – 32 52.5 75.6 75.6 105 154 187(AC) 50-60 Hz 440 V [kA] – 17 30 46.2 63 94.5 121 165(AC) 50-60 Hz 500 V [kA] – 13.6 17 30 52.5 63 75.6 105(AC) 50-60 Hz 690 V [kA] – 4.3 5.9 9.2 9.2 11.9 13.6 17Opening time (415 V) [ms] 7 7 6 5 3 3 3 3Utilisation category (IEC 60947-2 ) A A AReference St<strong>and</strong>a rd IEC 60947-2 IEC 60947-2 IEC 60947-2Isolation behaviourInterchangeability – – –Versions F F F-PMechanical lif e [No. operations ] 25000 25000 25000[No. Hourly operations ] 240 240 240<strong>Electrical</strong> life @ 415 V AC [No. operations ] 8000 8000 8000[No. Hourly operations ] 120 120 120FPW= fixed circuit-breakers= plug-in circuit-breakers= withdrawable ci rcuit-breakers(*)The breaking capacity for settings In=16 A<strong>and</strong> In=20 A is 16 kA54 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.1 <strong>Electrical</strong> characteristics of circuit-breakersTmax T3 Tmax T4 Tmax T5 Tmax T6 Tmax T7250 250/320 400/630 630/800/100 0 800/1000/1250/16003/4 3/4 3/4 3/4 3/4690 690 690 690 690500 750 750 750 –8 8 8 8 8800 1000 1000 1000 10003000 3500 3500 3500 3500N S N S H L V N S H L V N S H L S H L V (6)50 85 70 85 100 200 200 70 85 100 200 200 70 85 100 200 85 100 200 20036 50 36 50 70 120 200 36 50 70 120 200 36 50 70 100 50 70 120 15025 40 30 40 65 100 180 30 40 65 100 180 30 45 50 80 50 65 100 13020 30 25 30 50 85 150 25 30 50 85 150 25 35 50 65 40 50 85 1005 8 20 25 40 70 80 20 25 40 70 80 20 22 25 30 30 42 50 6036 50 36 50 70 100 150 36 50 70 100 150 36 50 70 100 – – – –40 55 – – – – – – – – – – – – – – – – – –– – 25 36 50 70 100 25 36 50 70 100 20 35 50 65 – – – –36 50 – – – – – – – – – – – – – – – – – –– – 16 25 36 50 70 16 25 36 50 70 16 20 36 50 – – – –75% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 100% 100% 100% 100%75% 50% (27 kA) 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 100% 100% 100% 100%75% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 100% 100% 100% 100%75% 50% 100% 100% 100% 100% 100% 100% 100% 100% 100% (1) 100% (2) 100% 100% 100% 75% 100% 100% 75% 100%75% 50% 100% 100% 100% 100% 100% 100% 100% 100% (1) 100% (2) 100% (2) 75% 75% 75% 75% 100% 75% 75% 75%105 187 154 187 220 440 660 154 187 220 440 660 154 187 220 440 187 220 440 44075.6 105 75.6 105 154 264 440 75.6 105 154 264 440 75.6 105 154 220 105 154 264 33052.5 84 63 84 143 220 396 63 84 143 220 396 63 94.5 105 176 105 143 220 28640 63 52.5 63 105 187 330 52.5 63 105 187 330 52.5 73.5 105 143 84 105 187 2207.7 13.6 40 52.5 84 154 176 40 52.5 84 154 176 40 46 52.5 63 63 88.2 105 1327 6 5 5 5 5 5 6 6 6 6 6 10 9 8 7 15 10 8 8A A B (400 A) (3) - A (630 A) B (630A - 800A) (5) - A (1000A) B (7)IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2–F-P F-P-W F-P-W F-W (4) F-W25000 20000 20000 20000 10000240 240 120 120 608000 8000 (250 A) - 6000 (320 A) 7000 (400 A) - 5000 (630 A) 7000 (630A) - 5000 (800A) - 4000 (1000A) 2000 (S-H-L versions) - 3000 (V version)120 120 60 60 60(1)75% for T5 630(2)50% for T5 630(3)Icw = 5 kA(4)W version is not available on T6 1000 A(5)Icw = 7.6 kA (630 A) - 10 kA (800 A)(6)Only for T7 800/1000/1250 A(7) Icw = 20 kA (S,H,L versions) - 15 kA (V version)Notes: in the plug-in version of T2,T3,T5 630 <strong>and</strong>in the withdrawable version of T5 630 themaximum rated current available is deratedby 10% at 40 ϒC<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 55


2 General characteristics2.1 <strong>Electrical</strong> characteristics of circuit-breakersCommon dataSACE Emax air circuit-breakersVoltagesRated operational voltage Ue [V] 690 ~Rated insulation voltage Ui [V] 1000Rated impulse withst<strong>and</strong>voltage Uimp [kV] 12Service temperature [°C] -25....+70Storage temperature [°C] -40....+70Frequency f [Hz] 50 - 60Number of poles 3 - 4VersionFixed -Withdrawable(1) Without intentional delays(2) Performance at 600 V is100 kAPerformance levelsCurrents: rated uninterrupted current (at 40 ϒC) Iu[A][A][A][A][A][A][A]Neutral pole current-carrying capacity for 4-pole CBs[%Iu]Rated ultimate breaking capacity under short-circuit Icu220/230/380/400/415 V~ [kA]440 V~ [kA]500/525 V~ [kA]660/690 V~ [kA]Rated service breaking capacity under short-circuit Ics220/230/380/400/415 V~ [kA]440 V~ [kA]500/525 V~ [kA]660/690 V~ [kA]Rated short-time withst<strong>and</strong> current Icw (1s) [kA](3s)[kA]Rated making capacity under short-circuit (peak value) Icm220/230/380/400/415 V~ [kA]440 V~ [kA]500/525 V~ [kA]660/690 V~ [kA]Utilisation category (according to IEC 60947-2)Isolation behaviour (according to IEC 60947-2)Overcurrent protectionElectronic releases forACapplicationsOperating timesClosing time (max)[ms]Breaking time for IIcw (max)[ms]SACE Emax air circuit-breakersRated uninterrupted current (at 40 ϒC) Iu[A]Mechanical life with regular ordinary maintenance [No. operations x 1000]Operation frequency[Operations/hour]<strong>Electrical</strong> life (440 V~)[No. operations x 1000](690 V~)[No. operations x 1000]Operation frequency[Operations/hour]800X11250 160012.5 12.5 12.560 60 606 4 33 2 130 30 30E1 B-N800 1000-1250 160025 25 2560 60 6010 10 1010 8 830 30 3056 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.1 <strong>Electrical</strong> characteristics of circuit-breakersX1B N L630 630 630800 800 8001000 1000 10001250 1250 12501600 1600100 100 100BE1 E2 E3 E4 E6N800 8001000 10001250 12501600 1600100 100B N S LN S H V L S H V HV1600 1000 800 1250 2500 1000 800 800 2000 4000 3200 3200 4000 32002000 1250 1000 1600 3200 1250 1000 1250 25004000 4000 5000 40001600 12502000 160020001600200025003200125016002000250016002000250032006300 500063003200100 100 100 100 100 100 100 100 100 50 50 50 50 5042 65 15042 65 13042 50 10042 50 6042 5042 5042 5042 5042 65 85 13042 65 85 11042 55 65 8542 55 65 8565 75 100 130 13065 75 100 130 11065 75 100 100 8565 75 85 100 85(2)75 100 15075 100 15075 100 13075 85 (2) 100100 150100 150100 130100 10042 50 15042 50 13042 42 10042 42 4542 42 1542 5042 5042 5042 5042 5036 3642 65 85 1304242655585651106542 55 65 6542 55 65 1042 42 50 –65 75 85 100 13065 75 85 100 11065 75 85 85 6565 75 85 85 6565 75 75 85 1565 65 65 65 –75 100 15075 100 15075 100 13075 85 10075 100 10075 75 75100 125100 125100 100100 100100 10085 8588.2 143 33088.2 143 28688.2 121 22088.2 121 132B B A88.2 10588.2 10588.2 10588.2 105B B88.2 143 187 28688.2 143 187 24288.2 121 143 18788.2 121 143 187B B B A143 165 220 286 286143 165 220 286 242143 165 187 220 187143 165 187 220 187B B B B A165 220 330165 220 330165 220 286165 187 220B B B220 330220 330220 286220 220BB80 80 8070 70 7030 30 1280 8070 7030 3080 80 80 8070 70 70 7030 30 30 1280 80 80 80 8070 70 70 70 7030 30 30 30 1280 80 8070 70 7030 30 3080 8070 7030 30E2 B-N-S800 1000-1250 1600 200025 25 25 2560 60 60 6015 15 12 1015 15 10 830 30 30 30E2 L E3 N-S-H-V E3 L E4 S-H-V E6 H-V1250 160020 2060 604 33 220 20800 1000-1250 1600 2000 2500 3200 2000 2500 3200 4000 3200 4000 5000 630020 20 20 20 20 20 15 15 15 15 12 12 12 1260 60 60 60 60 60 60 60 60 60 60 60 60 6012 12 10 9 8 6 2 1.8 7 5 5 4 3 212 12 10 9 7 5 1.5 1.3 7 4 5 4 2 1.520 20 20 20 20 20 20 20 10 10 10 10 10 10<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 57


2 General characteristics2.1 <strong>Electrical</strong> characteristics of circuit breakersSACE Emax air circuit-breakers with full-size neutralconductorE4S/f E4H/f E6H/fRated uninterrupted current (at 40 °C) Iu [A] 4000 3200 4000[A] 4000 50006300Number of poles 4 4 4Rated operational voltage Ue [V ~] 690 690 690Rated ultimate short-circuit breaking capacity Icu220/230/380/400/415 V ~ [kA] 80 100 100440 V ~ [kA] 80 100 100500/525 V ~ [kA] 75 100 100660/690 V ~ [kA] 75 100 100Rated service short-circuit breaking capacity Ics220/230/380/400/415 V ~ [kA] 80 100 100440 V ~ [kA] 80 100 100500/525 V ~ [kA] 75 100 100660/690 V ~ [kA] 75 100 100Rated short-time withst<strong>and</strong> current Icw(1s) [kA] 75 85 100(3s) [kA] 75 75 85Rated short-circuit making capacity Icm220/230/380/400/415 V ~ [kA] 176 220 220440 V ~ [kA] 176 220 220500/525 V ~ [kA] 165 220 220660/690 V ~ [kA] 165 220 220Utilization category (in accordance with IEC 60947-2) B B BIsolation behavior (in accordance with IEC 60947-2) ■ ■ ■Overall dimensionsFixed: H = 418 mm - D = 302 mm L [mm] 746 746 1034Withdrawable: H = 461 - D = 396.5 mm L [mm] 774 774 1062Weight (circuit-breaker complete with releases <strong>and</strong> CT, not including accessories)Fixed [kg] 120 120 165Withdrawable (including fixed part) [kg] 170 170 25058 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2.2 Characteristic curves <strong>and</strong> thesoftware “Curves”2 General characteristics2.2.1 Curves 1.0The software “Curves”, which can be downloaded from our web sitehttp://bol.it.abb.com, is a tool dedicated to who works in the electrical engineeringfield.This program allows the visualization of :• I-t LLL: tripping characteristics for three-phase faults;• I-t LL: tripping characteristics for two-phase faults;• I-t LN: tripping characteristics for single-phase faults;• I-t LPE: tripping characteristics for phase-to-earth faults;• I-I 2 t LLL: specific let-through energy for three-phase faults;• I-I 2 t LL: specific let-through energy for two-phase faults;• I-I 2 t LN: specific let-through energy for single-phase faults;• I-I 2 t LPE: specific let-through energy for phase-to-earth faults;• Peak: current limitation curve;• Cable <strong>and</strong> fuse characteristic curves.Besides, other program features are the verifications of cable protection, ofhuman beings’ protection <strong>and</strong> of discrimination. The algorithms for the verificationof the cable protection are described in the international st<strong>and</strong>ards. Thealgorithms for the verification of discrimination are implemented in accordancewith the guidelines provided in <strong>ABB</strong> SACE Technical Application Papers,specifically “QT1: Low voltage selectivity with <strong>ABB</strong> circuit-breakers” (QT1 fromnow on). The software “Curves” displays tripping <strong>and</strong> limiting characteristicsaccording to the catalogues.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 59


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”2.2.2 Trip curves of thermomagnetic <strong>and</strong> magnetic only releasesThe overload protection function must not trip the circuit-breaker in 2 hoursfor current values which are lower than 1.05 times the set current, <strong>and</strong> musttrip within 2 hours for current values which are lower than 1.3 times the setcurrent.By “cold trip conditions” it is meant that the overload occurs when the circuitbreakerhas not reached the normal working temperature (no current flowsthrough the circuit-breaker before the anomalous condition occurs); on thecontrary “hot trip conditions” refers to the circuit-breaker having reached thenormal working temperature with the rated current flowing through, before theoverload current occurs. For this reason “cold trip conditions” times are alwaysgreater than “hot trip conditions” times.The protection function against short-circuit is represented in the time-currentcurve by a vertical line, corresponding to the rated value of the trip threshold I3.In accordance with the St<strong>and</strong>ard IEC 60947-2, the real value of this threshold iswithin the range 0.8·I3 <strong>and</strong> 1.2·I3. The trip time of this protection varies accordingto the electrical characteristics of the fault <strong>and</strong> the presence of other devices:it is not possible to represent the envelope of all the possible situations in asufficiently clear way in this curve; therefore it is better to use a single straightline, parallel to the current axis.All the information relevant to this trip area <strong>and</strong> useful for the sizing <strong>and</strong> coordinationof the plant are represented in the limitation curve <strong>and</strong> in the curvesfor the specific let-through energy of the circuit-breaker under short-circuitconditions.The following pages show some examples reporting the settings of thermomagneticreleases.To simplify the reading of these examples, the tolerance of the protection functionshas not been considered.For a proper setting it is necessary to consider the tolerances referred to thetype of thermomagnetic release used; for these information please refer to thetechnical catalogues.60 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”The following figure shows the time-current tripping curve of a circuit-breakerequipped with thermomagnetic release:10 4t [s]2h1h10 330’20’10’10 25’2’1’L10110 -1I10 -2 10 -1 1 10 10 2= cold trip conditionx I 1= hot trip condition<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 61


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”Overload protection (L)To set correctly the function L of the release is necessary to know the loadcurrent (Ib) <strong>and</strong> divide it for the rated current of the thermomagnetic releases,taking the setting available higher or equal to the value obtained.Setting L=I bI nBesides, in case of protection of a cable, it is necessary to comply with thefollowing relation :Ib < I1 < Iz where Iz is the conductor carrying capacity <strong>and</strong> I1 is the current seton the overload protection.Example:XT4N 250 TMA 200 with thermomagnetic release TMA. (with function L adjustablefrom 0.7 to 1 x In)Ib=170ASetting L=I b= 170 = 0.85I n200t [s] x I n1LIn 200AI1MAX MED MIN200A 175A 140AIMAXMEDMIN0.70.925 0.7750.8562 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”Short-circuit instantaneous protection (I)To set the magnetic function of the release is necessary to know the minimumvalue of the short-circuit current that we can have in the plant.The I3 thresold shall comply with following condition:I3 ≤ IkminI3=setting Ix InTo detect the setting it is necessary to divide the Ikmin by the rated currentof the releases <strong>and</strong> take the setting value immediately lower.Ik minSetting = I InExample:XT4N 250 TMA 200 with thermomagnetic release TMA with instantaneousfunction adjustable from 5 (=1000A) to 10 (=2000A).Ikmin=1800 AIkSetting =min = 1800 = 9I In 200It is possible to choose: 8.75 :I3=8.75x200=1750 ≤ 1800 ALIt [s] x I n10I3MAX MED MIN2000A 1500A 1000AIn 200AMAXMEDMIN58.75 6.257.5<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 63


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”Example of thermomagnetic release settingConsider a circuit-breaker type XT2 160 In 160 <strong>and</strong>, using the trimmer forthe thermal regulation, select the current threshold, for example at 144 A; themagnetic trip threshold, fixed at 10xln, is equal to 1600 A.Note that, according to the conditions under which the overload occurs, thatis either with the circuit-breaker at full working temperature or not, the trip ofthe thermal release varies considerably. For example, for an overload currentof 600 A, the trip time is between 6 <strong>and</strong> 30 s for hot trip, <strong>and</strong> between 30 <strong>and</strong>100 s for cold trip.For fault current values higher than 1600 A, the circuit-breaker trips instantaneouslythrough magnetic protection.XT2 160 - In 160 Time-current curvest [s]10 4 110 3100 s10 230 s6 s10110 -110 -2 10 -11010 2xI 14xI164 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.2.3 The functions of electronic releases2.2 Characteristic curves <strong>and</strong> the software “Curves”In the following pages the protection functions of the electronic releases forboth moulded-case as well as air circuit breakers are reported; as regards theavailability of the protection functions with the different releases, reference shallbe made to the table on page 43.The examples shown in these pages show how it is possible to set the electronicrelease by means of the dip-switch on the front of the circuit-breaker; thisoperation can be carried out also through the <strong>control</strong>s viewing the LED display(for the releases PR122-PR123-PR332-PR333) or electronically through thetest unit PR 010T or with SD-TESTBUS 2.To simplify the reading of the examples, the tolerance of the protection functionshas not been considered. For a correct setting it is necessary to takeinto consideration the tolerances relevant to the different protection functionsreferred to the electronic trip unit used; for this information please consult thetechnical catalogue.The figure below shows the time-current tripping curve of a circuit-breakerequipped with an electronic release having the protection functions LSIG whichare described in the following pages:t [s]1E4s1E3sL100s10sGS1sI0.1s1E-2s0.1kA 1kA 10kAx I [kA]<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 65


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”t [s] 10 4Overload protection (L function)10 3 1I110 210 1t110 -110 -2 10 -11 10 1 10 2x InThe application field of this protection function refers to all the <strong>installation</strong>s whichcan be subject to overloads - usually of low value but of long duration - whichare dangerous for the life of apparatus <strong>and</strong> cables.These currents usually occur in a sound circuit, where the line results to beoverloaded (this event is more likely than a real fault).The trip curve of this protection (which cannot be excluded) is defined by acurrent threshold I1 <strong>and</strong> by a trip time t1. More exactly :• I1 represents the current value beyond which the protection functioncomm<strong>and</strong>s the opening of the circuit-breaker according to an inversetime trip characteristic, where the time-current connection is given by therelationI 2 t = constant (constant specific let-through energy);• t1 represents the trip time of the protection, in seconds, correspondingto a well defined multiple of I1 <strong>and</strong> it is used to identify a defined curveamong those made available by the trip unit.As regards the settings available please consult the technical catalogues.66 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”To set properly L threshold, it is necessary to know the current required by theload (Ib), divide it by the In of the trip unit <strong>and</strong> take the setting immediately higherthan or equal to the value obtained :Setting L=I bI nBesides, in case of cable protection, the following relation shall be observedIb < I1 < Iz where Iz is the conductor carrying capacity <strong>and</strong> I1 is the currentvalue set for the overload protection.Example :XT2N 160, trip unit type Ekip LSI In=100, function L (I1=0.4 at 1 x In with step0.02) through manual setting.Ib= 85ASetting L=I b= 85 = 0.85I n100I1=0.86 is chosen.Through the manual setting, the dip-switches shall be positioned so that a coefficientequal to 0.86 is obtained; this coefficient multiplied by the rated current ofthe trip unit gives the required current value. The figure below shows the correctcombination of dip-switches to obtain the required multiplying factor:I1= 100 x (0.4*+0.02+0.04+0.08+0,32) = 86AThe trip time of L function for an overload current varies according to the typeof curve used.As regards the release considered in the example, the available curves are 4<strong>and</strong> each of them is characterized by the passage by a characteristic multiple(3xI1) to which a different trip time (t1=3s, 12s, 36s, 60s) corresponds; sincethese are curves with I 2 t=const, it is possible to identify multiples different from3xI1 after the setting of t1.Being a curve with I 2 t constant, the condition(3xI1) 2 x t1 =const =I 2 tmust be always verified.(*) 0.4 is the fixed value, which cannot be excluded<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 67


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”where the expression I 2 t represents the product of a generic fault current to thesquare <strong>and</strong> the time necessary to the protection to extinguish it.Assuming an overload current of 300A (Iol) <strong>and</strong> having set t1 at 3s, the followingresults :(3x86)(3xI1) 2 x t1 = Iol 2 x t t =2 x 3= 2.21s(300) 2At the same overload level (Iol)=300A, if t1 had been set at 36s, the trip timewould have been :(3xI1) 2 x t1 = Iol 2 x t t = (3x86)2 x 36= 26.62s(300) 21E3s100sCurve t1=36s26.62s10s2.21sCurve t1=3s1s0.1s1E-2kA 0.1kA 1kA 10kA 100kAThe time t1 shall be chosen keeping into consideration any co-ordination withcables or other devices either on the supply or the load side of the circuitbreakerunder consideration.tI4Gt4I1Lt1I2St2I3IILI1=In x (0.4 + Σ)0 0.020.040.080.160.323 3612 72t1 (s)I=3I168 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”Short-circuit protection with time delay (function S)t [s] 10 410 3 I210 210 1I 2 t=k1t2t=k10 -110 -2 10 -1 110 110 2x InThis protection function is used to introduce a trip time-delay in case of shortcircuit.S function is necessary when time-current discrimination is requiredso that the tripping is delayed more <strong>and</strong> more by approaching the supplysources.The trip curve of this protection (which can be excluded) is defined by a currentthreshold I2 <strong>and</strong> by a trip time t2. In details :• I2 represents the current value beyond which the protection functioncomm<strong>and</strong>s the opening of the circuit-breaker, according to one of thefollowing tripping characteristics:- with inverse time delay, where the link time-current is given by therelation I 2 t = k (constant let-through energy)- with definite time, where the trip time is given by the relationt=k (constant time); in this case the tripping time is equal for anyvalue of current higher than I2;• t2 represents the trip time of the protection, in seconds, in correspondencewith:- a well defined multiple of In for the tripping curve at I 2 t = k;- I2 for the tripping curve at t = k.As regards the availability of the settings with the different trip units, please refer to the technical catalogues.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 69


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”In order to adjust properly the function S of a circuit-breaker equipped with anelectronic trip unit it is necessary to divide the Ikmin value (the lowest shortcircuitcurrent among all the available ones) by the In value of the trip unit <strong>and</strong>then to take the setting value immediately lower.Ik minSetting = s InExample :XT4N 250 with trip unit Ekip LSIG In 250function S (I2=1-1.5-2-2.5-3-3.5-4.5-5.5-6.5-7-7.5-8-8.5-9-10 x In)Ikmin=900ASetting s=Ik min = 2000 = 8In 250then, the value 7.5 is to be chosen.As in the previous example, the figure shows the correct positioning of the dipswitches so that the required multiplying factor can be obtained:I2 = 250 x (2+5.5) = 1875 A < 2000 AThe time delay t2 of function S changes according to the selected characteristic:either t=constant or I 2 t=constant.By selecting t2=const, in case of short-circuit, all the overcurrents higher or equalto I2 (in this case 1875 A) shall be extinguished within the set time t2;instead, by selecting the characteristic curve with I 2 t=const, the same considerationsmade for the determination of the trip time t1 are valid, taking intoaccount the proper thresholds I2.tI4LGt4I1t1I2St2I3IIS I2=In x Σ0 11.525.5I=10Int2 (s)0.05 0.20.1 0.4L70 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


t [s]10 42 General characteristicsShort-circuit instantaneous protection (I function)2.2 Characteristic curves <strong>and</strong> the software “Curves”10 3 110 210 1I310 -110 -2 10 -1110 110 2x InThis function allows to have instantaneous protection in case of short-circuit.This protection is active for fault currents exceeding the set threshold I3; thetrip time (instantaneous) cannot be set.Function I can be excluded; the term “excludible” means that the trip thresholdof the current is increased in comparison with the maximum threshold whichcan be adjusted through st<strong>and</strong>ard settings.In order to set properly the threshold I, it is necessary to know the lowest shortcircuitcurrent of those which can occur at the <strong>installation</strong> point.The threshold I3 shall comply with the following relation:I3≤IminI3=setting Ix InAs regards the availability of the settings with the different trip units, please refer to the technicalcatalogues.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 71


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”To determine the value to be set, the Ikmin value shall be divided by the In value<strong>and</strong> the setting value immediately lower shall be taken:Setting I=IkminExample:XT4N 160 with trip unit Ekip LSIG In100function I (I3=1-1.5-2-2.5-3-3.5-4.5-5.5-6.5-7-7.5-8-8.5-9-10 x In)Ikmin=900 ASetting = Ikmin = 900 = 9l I n1008.5 is to be chosen.As in the previous example, the figure shows the correct positioning of the dipswitches so that the required multiplying factor can be obtained:I3 = 100 x (1+2+5.5) = 850 A < 900I ntGt4Lt1St2II I3=In x Σ0 11.525.5I4I1I2I3I72 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”t [s] 10 4Earth fault protection (function G)10 3 1I410 210 1t410 -1t=kI 2 t=k10 -2 10 -1 110 110 2x In<strong>Protection</strong> G can assess the vectorial sum of the currents flowing through thelive conductors (the three phases <strong>and</strong> the neutral).In a sound circuit, this sum is equal to zero, but in the presence of an earth fault,a part of the fault current returns to the source through the protective conductor<strong>and</strong>/or the earth, without affecting the live conductors. The trip curve of thisprotection (which can be excluded) is defined by a current threshold I4 <strong>and</strong> bya trip time t4. More precisely:• I4 represents the current value beyond which the protection functioncomm<strong>and</strong>s the opening of the circuit-breaker, according to one of thefollowing tripping characteristics:- with inverse time delay, where the link time-current is given by therelation I 2 t = k (constant let-through energy)- with definite time, where the trip time is given by the relationt=k(constant time); in this case the tripping time is equal for any valueof current higher than I4;• t4 represents the trip time of the protection, in seconds, in correspondencewith:- a well defined multiple of In for the tripping curve at I 2 t = k;- I4 for the tripping curve at t = k.As regards the availability of the settings with the different trip units, please refer to the technicalcatalogues.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 73


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”In order to set properly the current I4 <strong>and</strong> the time t4 of the function G, it isnecessary to comply with the requirements reported in the <strong>installation</strong> St<strong>and</strong>ard(see Chapter 4 of Part 2 - “<strong>Protection</strong> of human beings”).Example:XT4N 250 with trip unit Ekip LSIG In 250function G (I4=0.2-0.25-0.45-0.55-0.75-0.8-1 x In)Ik PE=120 Adistribution system: TN-S.In TN systems, a bolted fault to ground on the LV side usually generates a currentwith a value analogous to that of a short-circuit <strong>and</strong> the fault current flowingthrough the phase <strong>and</strong>/or the protection conductor (or the conductors) doesnot affect the earthing system at all.The relation concerning TN-S distribution systems Zs x Ia ≤ Uo can be expressedas follows:Ia ≤ Uo = Ik LPEZswhere:• Uo is the voltage phase-to-PE;• Zs is the fault ring impedance;• Ia is the trip current within the time delay established by the St<strong>and</strong>ard (seeChapter 4 of Part 2 - “<strong>Protection</strong> of human beings”).• Ik LPE= is the fault current phase-to-PETherefore, it is possible to affirm that the protection against indirect contacts isverified if the trip current Ia is lower than the fault current phase-PE (Ikl PE) which ispresent in correspondence with the exposed conductive part to be protected.Then:the setting 0.45 is selected.Setting G= Ik PE = 120 = 0.48I n25074 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”As in the previous example, the figure shows the correct positioning of the dipswitches so that the required multiplying factor can be obtained:I4 = 250 x (0.2+0.25) = 112,5 A < 120 AThe trip time t4 shall be chosen according to the provisions of the <strong>installation</strong>st<strong>and</strong>ards; with the trip unit under consideration, the available curves whichdefine t4 are with I 2 t constant; therefore, in order to define the trip time it isnecessary to apply the same considerations made for the determination of thetrip time t1, but taking into account the proper thresholds I4 <strong>and</strong> the relevantcharacteristic curves (t4).Assuming to use a release with trip time t4=constant, when the set threshold I4is reached <strong>and</strong> exceeded, the circuit-breaker shall trip within the set time t4.tI4LGt4I1t1I2St2I3IIG I4=In x Σ0 0.20.250.55t2 (s)0.1 0.40.2 0.8<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 75


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”<strong>Protection</strong> against directional short-circuit with adjustabletime-delay (function D)10 4t [s]10 3D10 210 1 10 -2 1 10 1 10 2110 -110 -1 0,2...0,8x InThis protection is very similar to function S with definite time. It allows to identify,besides the intensity, also the direction of the fault current <strong>and</strong> consequently tounderst<strong>and</strong> whether the fault is either on the supply or on the load side of thecircuit-breaker, thus excluding only the part of the <strong>installation</strong> affected by thefault. Its use is particularly suitable in the ring distribution systems <strong>and</strong> in the<strong>installation</strong>s with more supply lines in parallel.The adjustable current thresholds are in a range from 0.6 to 10xIn <strong>and</strong> the triptimes can be set within a range from 0.2 to 0.8 seconds.Function D can be excluded.76 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics<strong>Protection</strong> against unbalanced phase (function U)2.2 Characteristic curves <strong>and</strong> the software “Curves”10 40,05...6010 30,050,9Ut [s]10 26010 1 10 -1 1 10 10,5...6010,510 -110 -2x InThis protection makes the circuit-breaker open when an unbalanced phasecurrent exceeding the set threshold is detected.The possible settings are 5% to 90% of the rated current, <strong>and</strong> the trip timescan be set in the range from 0.5 to 60 s.The protection function U is used above all in the <strong>installation</strong>s with the presenceof rotary machines, where an unbalanced phase might cause unwanted effectson the same machines. Function U can be excluded.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 77


2 General characteristics<strong>Protection</strong> against undervoltage (function UV)2.2 Characteristic curves <strong>and</strong> the software “Curves”10 410 30,50,5...0,950,95UVt [s]10 210 15110 -110 -2 0,1...50.30.5 0.7 0.9 1.1 1.3x UnThis protection trips after the adjusted time (t8) has elapsed when the phasevoltage decreases below the set threshold U8.The voltage threshold can be set in the range from 0.5 to 0.95xUn <strong>and</strong> thetime threshold from 0.1 to 5 s.Function UV can be excluded.0,178 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics<strong>Protection</strong> against overvoltage (function OV)2.2 Characteristic curves <strong>and</strong> the software “Curves”10 41,05...1,210 31,051,2OVt [s]10 210 1510,1...510 -10,110 -2 11.05 1.1 1.15 1.2 1.251.3x UnThis protection trips after the set time (t9) has elapsed, when the phase voltageexceeds the set threshold U9.The voltage threshold can be set in the range from 1.05 to 1.2xUn <strong>and</strong> thetime threshold from 0.1 to 5 s.Function OV can be excluded.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 79


2 General characteristics<strong>Protection</strong> against residual voltage (function RV)2.2 Characteristic curves <strong>and</strong> the software “Curves”10 40,1...0,410 30,10,4RVt [s]10 23010 1 0.80,5...3010,510 -10 0.2 0.4 0.6 11.2x UnThe protection against residual voltage allows to detect the faults which causethe movements of the star centre in case of system with isolated neutral.This protection trips after the set time when the residual voltage exceeds thethreshold U10.This threshold can be set in a range from 0.1 to 0.4xUn <strong>and</strong> the time thresholdfrom 0.5s to 30s.Function RV can be excluded.80 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics<strong>Protection</strong> against reversal of power (function RP)2.2 Characteristic curves <strong>and</strong> the software “Curves”10 40,3...0,110 30,30,1RPt [s]10 22510 1 -0.3 -0.2 -0.1 00,5...2510,510 -1-0.4x PnThe protection against reversal of power is particularly suitable for protectionof large rotary machines (e.g. motors).Under certain conditions a motor may generate power instead of absorbing it.When the total reverse active power (sum of the power of the three phases)exceeds the set power threshold P11, the protection function trips after the settime-delay t11 causing the circuit-breaker opening<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 81


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”<strong>Protection</strong> against minimum frequency (function UF)This protection intervenes by generating an alarm or making the circuit-breakeropen after the adjusted time-delay (t9) when the frequency varies below theset threshold f12.It is used above all for <strong>installation</strong>s supplied by generators <strong>and</strong> co-generationplants.<strong>Protection</strong> against maximum frequency (function OF)This protection intervenes by generating an alarm or making the circuit-breakeropen after the adjusted time-delay (t10) when the frequency exceeds the setthreshold f13.It is used above all for <strong>installation</strong>s supplied by generators <strong>and</strong> co-generationplants.<strong>Protection</strong> against overtemperature (function OT)This protection allows signaling of the presence of anomalous temperatureswhich might cause malfunctioning of the electronic components of the tripunit.If the temperature reaches the first threshold, (70°C), the trip unit shall advisethe operator through the lightening up of the “warning” led; should the temperaturereach the second threshold (85°C), besides the lightening up of the“warning” <strong>and</strong> “alarm” leds, the circuit-breaker would be tripped (by enablingthe proper parameter).Overload protection with curves according to IEC60255-3This protection function against overload finds its application in the co-ordinationwith MV releases <strong>and</strong> fuses.In fact it is possible to obtain a co-ordination among the tripping curves ofthe circuit-breakers by getting nearer to the slopes of the tripping curves ofMV releases or fuses, so that time-current selectivity between LV <strong>and</strong> MV isobtained. Besides being defined by a current threshold I1 <strong>and</strong> by a trip timet1, the curves according to Std. IEC 60255 are defined by the parameters “K”<strong>and</strong> “a” which determine their slope.The parameters are the following:Curve typologyParameters A B CK 0.14 13.5 80.0a 0.02 1.0 2.0The curve L complying with Std. IEC 60255-3 is available both for the electronictrip units type PR332-PR333 for T7 <strong>and</strong> X1 series circuit-breakers, as well as forthe electronic trip units type PR122-PR123 for Emax series circuit-breakers.82 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristicsCurve Ak=0.14 alfa=0.022.2 Characteristic curves <strong>and</strong> the software “Curves”10 4t [s]10 310 210 1110 -1 10 -1 1 10 1 10 2x In<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 83


2 General characteristicsCurve Bk=13.5 alfa=12.2 Characteristic curves <strong>and</strong> the software “Curves”10 410 3t [s]10 210 1110 -1 10 -1 1 10 1 10 2x In84 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristicsCurve Ck=80 alfa=22.2 Characteristic curves <strong>and</strong> the software “Curves”10 410 3t [s]10 210 1 10 -1 1 10 1 10 2110 -1x In<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 85


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”Motor protectionL: motor protection function against overload according to the indications<strong>and</strong> classes defined by the Std. IEC 60947-4-110 5 3010 4hotcoldt [s]10 310 210A101201010A30201010A10 -1 1,0510 -1 11010 2x I 1Function L implemented on MP <strong>and</strong> Ekip M trip units protects the motor againstoverloads, according to the indications <strong>and</strong> the classes defined by the Std. IEC60947-4-1. The protection is based on a pre-defined thermal model, whichby simulating the copper <strong>and</strong> iron overtemperatures inside motors, allows tosafeguard properly the motor itself. The trip time-delay is set by selecting thetrip class defined in the above mentioned St<strong>and</strong>ard.The function is temperature-compensated <strong>and</strong> sensitive to the lack of phase.Function L, which cannot be excluded, can be set manually from a minimumof 0.4 to a maximum of 1x In. Besides, it is necessary to select the startingclass of the motor, which determines the trip time with a current equal to 7.2xIein compliance with the prescriptions of item 4.7.3 of the Std. IEC 60947-4-14.7.3. For further details see Chapter 2.3 of Part 2.86 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.2 Characteristic curves <strong>and</strong> the software “Curves”Motor protectionI: protection against short-circuit with instantaneous trip10 3 10 -16...136 1310 2t [s]10110 -110 -210 -3 11010 2I [kA]This protection function trips in case of phase-to-phase short-circuit. It is enoughthat one phase only exceeds the set threshold to cause the instantaneousopening of the circuit-breaker.The trip current can be set up to 13 times the rated current of the trip unit.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 87


2 General characteristicsMotor protectionR: <strong>Protection</strong> against rotor block2.2 Characteristic curves <strong>and</strong> the software “Curves”10 5 1010 4t [s]10 3310 24567810 1 107410 1 x I11110 -1 1,0510 -1 110 2Function R protects the motor against possible rotor block during operation.<strong>Protection</strong> R has the characteristics of protecting the motor in two differentways, according to whether the fault is present at start-up or whether it occursduring normal service of an already active plant.In the former case, protection R is linked to protection L for time selection aswell: in the presence of a fault during the start-up, protection R is inhibited fora time equal to the time set according to the trip class. Once this time hasbeen exceeded, protection R becomes active causing a trip after the set timet5. In the latter case, protection R is already active <strong>and</strong> the protection trippingtime shall be equal to the set value t5. This protection intervenes when at leastone of the phase current exceeds the established value <strong>and</strong> remains over thatthreshold for the fixed time t5.88 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristicsMotor protectionU: <strong>Protection</strong> against phase unbalance2.2 Characteristic curves <strong>and</strong> the software “Curves”10 510 4t [s]10 310 210 1 10 1 x I1110 -1 1,0510 -1 110 2Function U can be used in those cases where a particularly accurate <strong>control</strong> isneeded as regards phase lack/unbalance. This protection intervenes if the r.m.s.value of one or two currents drop below the level equal to 0.4 times the currentI1 set for protection L <strong>and</strong> remain below it for longer than 4 seconds.This protection can be excluded.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 89


2 General characteristics2.3 Limitation curvesA circuit-breaker in which the opening of the contacts occurs after the passageof the peak of the short-circuit current, or in which the trip occurs with the naturalpassage to zero, allows the system components to be subjected to highstresses, of both thermal <strong>and</strong> dynamic type. To reduce these stresses, currentlimitingcircuit-breakers have been designed (see Chapter 1.2 “Main definitions”),which are able to start the opening operation before the short-circuit current hasreached its first peak, <strong>and</strong> to quickly extinguish the arc between the contacts;the following diagram shows the shape of the waves of both the prospectiveshort-circuit current as well as of the limited short-circuit current.Ik1SDC008011F0001Prospectiveshort-circuit currentLimitedshort-circuit currenttThe following diagram shows the limit curve for Tmax XT2L160, In160 circuitbreaker.The x-axis shows the effective values of the symmetrical prospectiveshort-circuit current, while the y-axis shows the relative peak value. The limitingeffect can be evaluated by comparing, at equal values of symmetrical faultcurrent, the peak value corresponding to the prospective short-circuit current(curve A) with the limited peak value (curve B).90 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.3 Limitation curvesCircuit-breaker XT2L160 with thermomagnetic release In160 at 400 V, for afault current of 90 kA, limits the short-circuit peak to 14.6 kA only, with a remarkablereduction compared with the peak value in the absence of limitation(198 kA).Ip [kA]1000198 kACurve A10014.6 kA10Curve BIn=2011.00 10.00 100.001000.00x rms [kA]1SDC008012F0001Considering that the electro-dynamic stresses <strong>and</strong> the consequent mechanicalstresses are closely connected to the current peak, the use of current limitingcircuit-breakers allows optimum dimensioning of the components in an electricalplant. Besides, current limitation may also be used to obtain back-up protectionbetween two circuit-breakers in series.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 91


2 General characteristics2.3 Limitation curvesIn addition to the advantages in terms of design, the use of current-limitingcircuit-breakers allows, for the cases detailed by St<strong>and</strong>ard IEC 61439-1, theavoidance of short-circuit withst<strong>and</strong> verifications for switchboards. Clause8.2.3.1 of the St<strong>and</strong>ard “Circuits of ASSEMBLIES which are exempted fromthe verification of the short-circuit withst<strong>and</strong> strength” states that:“A verification of the short-circuit withst<strong>and</strong> strength is not required in thefollowing cases…For ASSEMBLIES protected by current-limiting devices having a cut-off currentnot exceeding 17 kA at the maximum allowable prospective short-circuit currentat the terminals of the incoming circuit of the ASSEMBLY...”The example in the previous page included among those considered by theSt<strong>and</strong>ard: if the circuit-breaker was used as a main breaker in a switchboardto be installed in a point of the plant where the prospective short-circuit currentis 90 kA, it would not be necessary to carry out the verification of short-circuitwithst<strong>and</strong>.92 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2.4 Specific let-through energy curvesI 2 t [10 6 A 2 s]100.002 General characteristicsIn case of short-circuit, the parts of a plant affected by a fault are subjected tothermal stresses which are proportional both to the square of the fault currentas well as to the time required by the protection device to break the current. Theenergy let through by the protection device during the trip is termed “specificlet-through energy” (I 2 t), measured in A 2 s. The knowledge of the value of thespecific let-through energy in various fault conditions is fundamental for thedimensioning <strong>and</strong> the protection of the various parts of the <strong>installation</strong>.The effect of limitation <strong>and</strong> the reduced trip times influence the value of thespecific let-through energy. For those current values for which the tripping ofthe circuit-breaker is regulated by the timing of the release, the value of thespecific let-through energy is obtained by multiplying the square of the effectivefault current by the time required for the protection device to trip; in othercases the value of the specific let-through energy may be obtained from thefollowing diagrams.The following is an example of the reading from a diagram of the specific letthroughenergy curve for a circuit-breaker type XT2L 160 In 20 at 400 V.The x-axis shows the symmetrical prospective short-circuit current, while they-axis shows the specific let-through energy values, expressed in MA 2 s.Corresponding to a short-circuit current equal to 90 kA, the circuit-breaker letsthrough a value of I 2 t equal to 0.218 MA 2 s.10.001.000.218 MA2s0.100.0190 kA1 10 100 1000xI rms [kA]1SDC008013F0001<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 93


2 General characteristics2.5 Temperature deratingSt<strong>and</strong>ard IEC 60947-2 states that the temperature rise limits for circuit-breakersworking at rated current must be within the limits given in the following table:Table 1 - Temperature rise limits for terminals <strong>and</strong> accessible partsDescription of part*Temperature rise limitsK- Terminal for external connections 80- Manual operating metallic 25means: non metallic 35- Parts intended tobe touched but not metallic 40h<strong>and</strong>-held: non metallic 50- Parts which neednot be touched for metallic 50normal operation: non metallic 60* No value is specified for parts other than those listed but no damage should be causedto adjacent parts of insulating materials.These values are valid for a maximum reference ambient temperature of 40°C,as stated in St<strong>and</strong>ard IEC 60947-1, clause 6.1.1.94 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.5 Temperature deratingWhenever the ambient temperature is other than 40°C, the value of the currentwhich can be carried continuously by the circuit-breaker is given in thefollowing tables:SACE Tmax XT circuit-breakers with thermomagnetic release30 °C 40 °C 50 °C 60 °C 70 °CIn [A] MIN MAX MIN MAX MIN MAX MIN MAX MIN MAXXT116 12 17 11,2 16 11 15 10 14 9 1320 15 21 14 20 13 19 12 18 11 1625 18 26 17,5 25 16 23 15 22 14 2032 24 34 22,4 32 21 30 20 28 18 2640 29 42 28 40 27 38 25 35 23 3350 37 53 35 50 33 47 31 44 28 4163 46 66 44,1 63 41 59 39 55 36 5180 59 84 56 80 53 75 49 70 46 65100 74 105 70 100 66 94 61 88 57 81125 92 131 87,5 125 82 117 77 109 71 102160 118 168 112 160 105 150 98 140 91 130XT21,6 1,2 1,7 1,1 1,6 1,1 1,5 1 1,4 0,9 1,32 1,5 2,2 1,4 2 1,3 1,9 1,2 1,7 1,1 1,62,5 1,8 2,6 1,8 2,5 1,6 2,3 1,5 2,2 1,4 23 2,5 3,5 2,1 3 2 2,8 1,8 2,6 1,6 2,34 2,9 4,2 2,8 4 2,6 3,7 2,5 3,5 2,2 3,26,3 4,6 6,6 4,4 6,3 4,1 5,9 3,9 5,5 3,6 5,18 5,9 8,4 5,6 8 5,3 7,5 4,9 7 4,6 6,510 7,4 10,5 7 10 6,5 9,3 6,1 8,7 5,7 8,112,5 9,2 13,2 8,8 12,5 8,2 11,7 7,6 10,9 7,1 10,116 11,9 17 11,2 16 10,5 15 9,8 14 9,1 1320 14,7 21 14 20 13,3 19 11,9 17 11,2 1632 23,8 34 22,4 32 21 30 19,6 28 18,2 2640 29,4 42 28 40 25,9 37 24,5 35 22,4 3250 37,1 53 35 50 32,9 47 30,1 43 28 4063 46,2 66 44,1 63 41,3 59 38,5 55 35,7 5180 58,8 84 56 80 52,5 75 49 70 45,5 65100 73,5 105 70 100 65,1 93 60,9 87 56,7 81125 92,4 132 87,5 125 81,9 117 76,3 109 70,7 101160 117,6 168 112 160 105 150 97,3 139 90,3 129<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 95


2 General characteristics2.5 Temperature derating30 °C 40 °C 50 °C 60 °C 70 °CIn [A] MIN MAX MIN MAX MIN MAX MIN MAX MIN MAXXT363 46 66 44 63 41 59 39 55 36 5180 59 84 56 80 53 75 48 69 45 64100 74 105 70 100 65 93 61 87 56 80125 92 132 88 125 81 116 76 108 70 100160 118 168 112 160 104 149 97 139 90 129200 148 211 140 200 130 186 121 173 113 161250 184 263 175 250 163 233 151 216 141 201XT416 12 17 11 16 10 14 9 13 8 1220 16 23 14 20 12 17 11 15 9 1325 19 27 18 25 16 23 15 21 13 1932 25 36 22 32 19 27 17 24 15 2140 30 43 28 40 26 37 24 34 21 3050 38 54 35 50 32 46 29 42 27 3963 47 67 44 63 41 58 37 53 33 4880 60 86 56 80 52 74 46 66 41 58100 74 106 70 100 67 95 60 85 53 75125 94 134 88 125 81 115 74 105 67 95160 118 168 112 160 105 150 96 137 91 130200 147 210 140 200 133 190 123 175 112 160225 168 241 158 225 146 208 133 190 119 170250 183 262 175 250 168 240 161 230 154 22096 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.5 Temperature deratingTmax T circuit-breakers with thermomagnetic release10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °CIn [A] MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAXT116 13 18 12 18 12 17 11 16 11 15 10 14 9 1320 16 23 15 22 15 21 14 20 13 19 12 18 11 1625 20 29 19 28 18 26 18 25 16 23 15 22 14 2032 26 37 25 35 24 34 22 32 21 30 20 28 18 2640 32 46 31 44 29 42 28 40 26 38 25 35 23 3350 40 58 39 55 37 53 35 50 33 47 31 44 28 4163 51 72 49 69 46 66 44 63 41 59 39 55 36 5180 64 92 62 88 59 84 56 80 53 75 49 70 46 65100 81 115 77 110 74 105 70 100 66 94 61 88 57 81125 101 144 96 138 92 131 88 125 82 117 77 109 71 102160 129 184 123 176 118 168 112 160 105 150 98 140 91 130T21,6 1,3 1,8 1,2 1,8 1,2 1,7 1,1 1,6 1 1,5 1 1,4 0,9 1,32 1,6 2,3 1,5 2,2 1,5 2,1 1,4 2 1,3 1,9 1,2 1,7 1,1 1,62,5 2 2,9 1,9 2,8 1,8 2,6 1,8 2,5 1,6 2,3 1,5 2,2 1,4 23,2 2,6 3,7 2,5 3,5 2,4 3,4 2,2 3,2 2,1 3 1,9 2,8 1,8 2,64 3,2 4,6 3,1 4,4 2,9 4,2 2,8 4 2,6 3,7 2,4 3,5 2,3 3,25 4 5,7 3,9 5,5 3,7 5,3 3,5 5 3,3 4,7 3 4,3 2,8 46,3 5,1 7,2 4,9 6,9 4,6 6,6 4,4 6,3 4,1 5,9 3,8 5,5 3,6 5,18 6,4 9,2 6,2 8,8 5,9 8,4 5,6 8 5,2 7,5 4,9 7 4,5 6,510 8 11,5 7,7 11 7,4 10,5 7 10 6,5 9,3 6,1 8,7 5,6 8,112,5 10,1 14,4 9,6 13,8 9,2 13,2 8,8 12,5 8,2 11,7 7,6 10,9 7,1 10,116 13 18 12 18 12 17 11 16 10 15 10 14 9 1320 16 23 15 22 15 21 14 20 13 19 12 17 11 1625 20 29 19 28 18 26 18 25 16 23 15 22 14 2032 26 37 25 35 24 34 22 32 21 30 19 28 18 2640 32 46 31 44 29 42 28 40 26 37 24 35 23 3250 40 57 39 55 37 53 35 50 33 47 30 43 28 4063 51 72 49 69 46 66 44 63 41 59 38 55 36 5180 64 92 62 88 59 84 56 80 52 75 49 70 45 65100 80 115 77 110 74 105 70 100 65 93 61 87 56 81125 101 144 96 138 92 132 88 125 82 117 76 109 71 101160 129 184 123 178 118 168 112 160 105 150 97 139 90 129<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 97


2 General characteristics2.5 Temperature derating10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °CIn [A] MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAXT363 51 72 49 69 46 66 44 63 41 59 38 55 35 5180 64 92 62 88 59 84 56 80 52 75 48 69 45 64100 80 115 77 110 74 105 70 100 65 93 61 87 56 80125 101 144 96 138 92 132 88 125 82 116 76 108 70 100160 129 184 123 176 118 168 112 160 104 149 97 139 90 129200 161 230 154 220 147 211 140 200 130 186 121 173 112 161250 201 287 193 278 184 263 175 250 163 233 152 216 141 201T420 19 27 18 24 16 23 14 20 12 17 10 15 8 1332 26 43 24 39 22 36 19 32 16 27 14 24 11 2150 37 62 35 58 33 54 30 50 27 46 25 42 22 3980 59 98 55 92 52 86 48 80 44 74 40 66 32 58100 83 118 80 113 74 106 70 100 66 95 59 85 49 75125 103 145 100 140 94 134 88 125 80 115 73 105 63 95160 130 185 124 176 118 168 112 160 106 150 100 104 90 130200 162 230 155 220 147 210 140 200 133 190 122 175 107 160250 200 285 193 275 183 262 175 250 168 240 160 230 150 220T5320 260 368 245 350 234 335 224 320 212 305 200 285 182 263400 325 465 310 442 295 420 280 400 265 380 250 355 230 325500 435 620 405 580 380 540 350 500 315 450 280 400 240 345T6630 520 740 493 705 462 660 441 630 405 580 380 540 350 500800 685 965 640 905 605 855 560 800 520 740 470 670 420 610Examples:Selection of a moulded-case circuit-breaker, with thermomagnetic release,for a load current of 160 A, at an ambient temperature of 60°C.From the table referring to SACE Tmax XT3, it can be seen that the mostsuitable breaker is the XT3 In 200, which can be set from 121 A to 173 A.98 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2.5 Temperature derating2 General characteristicsCircuit-breakers with electronic releaseup to 40°C 50°C 60°C 70°CImax (A) I1 Imax (A) I1 Imax (A) I1 Imax (A) I1XT2 fixed F 160 1 160 1 146 0,92 131 0,82XT4 fixed F 250 1 250 1 238 0,96 213 0,86T4 320fixedplug-inFC 320 1 294 0,92 269 0,84 243 0,76F 320 1 294 0,92 269 0,84 243 0,76R (HR) 320 1 294 0,92 269 0,84 243 0,76R (VR) 320 1 307 0,96 281 0,88 256 0,8FC 320 1 294 0,92 268 0,84 242 0,76F 320 1 294 0,92 268 0,84 242 0,76HR 320 1 294 0,92 268 0,84 242 0,76VR 320 1 307 0,96 282 0,88 256 0,8T5 400T5 630fixedplug-infixedplug-inFC 400 1 400 1 400 1 352 0,88F 400 1 400 1 400 1 352 0,88R (HR) 400 1 400 1 400 1 352 0,88R (VR) 400 1 400 1 400 1 368 0,92FC 400 1 400 1 368 0,92 336 0,84F 400 1 400 1 368 0,92 336 0,84R (HR) 400 1 400 1 368 0,92 336 0,84R (VR) 400 1 400 1 382 0,96 350 0,88FC 630 1 580 0,92 529 0,84 479 0,76F 630 1 580 0,92 529 0,84 479 0,76HR 630 1 580 0,92 529 0,84 479 0,76VR 630 1 605 0,96 554 0,88 504 0,80F 567 0.9 502 0,8 458 0,72 409 0,64HR 567 0.9 502 0,8 458 0,72 409 0,64VR 567 0.9 526 0,82 480 0,76 429 0,68CaptionF= Front flat terminalsFC= Front terminals for cablesHR= Rear flat horizontal terminalsVR= Rear flat vertical terminalsR= Rear terminalsEF= Front extendedFC Cu = Front terminals for copper cablesFC CuAl= Front terminals for CuAl cablesES= Front extended spread terminals<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 99


2 General characteristics2.5 Temperature deratingT6 630T6 800T6 1000fixedplug-infixedplug-infixedup to 40°C 50°C 60°C 70°CImax (A) I1 Imax (A) I1 Imax (A) I1 Imax (A) I1FC 630 1 630 1 598,1 1 567 0,9R (VR) 630 1 630 1 630 1 598,5 0,95R (HR) 630 1 630 1 567 0,9 504 0,8F 630 1 598,5 0,95 567 0,9 567 0,9VR 630 1 630 1 598,5 0,95 504 0,8HR 630 1 598,5 0,95 567 0,9 504 0,8FC 800 1 800 1 760 0,95 720 0,9R (VR) 800 1 800 1 800 1 760 0,95R (HR) 800 1 800 1 720 0,9 640 0,8F 800 1 760 0,95 720 0,9 640 0,8VR 800 1 800 1 760 0,95 720 0,9HR 800 1 760 0,95 720 0,9 640 0,8FC 1000 1 926 0,93 877 0,88 784 0,78R (HR) 1000 1 926 0,93 845 0,85 756 0,76R (VR) 1000 1 1000 1 913 0,92 817 0,82ES 1000 1 900 0,9 820 0,82 720 0,72T7 1000V versionT7 1250V versionT7 1250S-H-LversionT7 1600S-H-Lversionfixedplug-infixedplug-infixedplug-infixedplug-inVR 1000 1 1000 1 1000 1 894 0,89EF-HR 1000 1 1000 1 895 0,89 784 0,78VR 1000 1 1000 1 913 0,91 816 0,82EF-HR 1000 1 1000 1 895 0,89 784 0,78VR 1250 1 1201 0,96 1096 0,88 981 0,78EF-HR 1250 1 1157 0,93 1056 0,85 945 0,76VR 1250 1 1157 0,93 1056 0,85 945 0,76EF-HR 1250 1 1000 0,8 913 0,73 816 0,65VR 1250 1 1250 1 1250 1 1118 0,89EF-HR 1250 1 1250 1 1118 0,89 980 0,78VR 1250 1 1250 1 1141 0,91 1021 0,82EF-HR 1250 1 1250 1 1118 0,89 980 0,78VR 1600 1 1537 0,96 1403 0,88 1255 0,78EF-HR 1600 1 1481 0,93 1352 0,85 1209 0,76VR 1600 1 1481 0,93 1352 0,85 1209 0,76EF-HR 1600 1 1280 0,8 1168 0,73 1045 0,65CaptionF= Front flat terminalsFC= Front terminals for cablesHR= Rear flat horizontal terminalsVR= Rear flat vertical terminalsR= Rear terminalsEF= Front extendedFC Cu = Front terminals for copper cablesFC CuAl= Front terminals for CuAl cablesES= Front extended spread terminalsExample:Selection of a moulded-case circuit-breaker, with electronic release, in withdrawableversion with rear flat horizontal bar terminals, for a load currentequal to 720 A, with an ambient temperature of 50 °C. From the table referringto Tmax T6, it can be seen that the most suitable breaker is the T6 800, whichcan be set from 320 A to 760 A.100 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.5 Temperature deratingEmax X1 with horizontal rear terminalsTemperature X1 630 X1 800 X1 1000 X1 1250 X1 1600[°C] % [A] % [A] % [A] % [A] % [A]10 100 630 100 800 100 1000 100 1250 100 160020 100 630 100 800 100 1000 100 1250 100 160030 100 630 100 800 100 1000 100 1250 100 160040 100 630 100 800 100 1000 100 1250 100 160045 100 630 100 800 100 1000 100 1250 100 160050 100 630 100 800 100 1000 100 1250 97 155055 100 630 100 800 100 1000 100 1250 94 150060 100 630 100 800 100 1000 100 1250 93 1480Emax X1 with vertical rear terminalsTemperature X1 630 X1 800 X1 1000 X1 1250 X1 1600[°C] % [A] % [A] % [A] % [A] % [A]10 100 630 100 800 100 1000 100 1250 100 160020 100 630 100 800 100 1000 100 1250 100 160030 100 630 100 800 100 1000 100 1250 100 160040 100 630 100 800 100 1000 100 1250 100 160045 100 630 100 800 100 1000 100 1250 100 160050 100 630 100 800 100 1000 100 1250 100 160055 100 630 100 800 100 1000 100 1250 98 157060 100 630 100 800 100 1000 100 1250 95 1520Emax E1Temperature E1 800 E1 1000 E1 1250 E1 1600[°C] % [A] % [A] % [A] % [A]10 100 800 100 1000 100 1250 100 160020 100 800 100 1000 100 1250 100 160030 100 800 100 1000 100 1250 100 160040 100 800 100 1000 100 1250 100 160045 100 800 100 1000 100 1250 98 157050 100 800 100 1000 100 1250 96 153055 100 800 100 1000 100 1250 94 150060 100 800 100 1000 100 1250 92 147065 100 800 100 1000 99 1240 89 143070 100 800 100 1000 98 1230 87 1400<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 101


2 General characteristics2.5 Temperature deratingEmax E2Temperature E2 800 E2 1000 E2 1250 E2 1600 E2 2000[°C] % [A] % [A] % [A] % A] % [A]10 100 800 100 1000 100 1250 100 1600 100 200020 100 800 100 1000 100 1250 100 1600 100 200030 100 800 100 1000 100 1250 100 1600 100 200040 100 800 100 1000 100 1250 100 1600 100 200045 100 800 100 1000 100 1250 100 1600 100 200050 100 800 100 1000 100 1250 100 1600 97 194555 100 800 100 1000 100 1250 100 1600 94 188560 100 800 100 1000 100 1250 98 1570 91 182565 100 800 100 1000 100 1250 96 1538 88 176570 100 800 100 1000 100 1250 94 1510 85 1705Emax E3Temperature E3 800 E3 1000 E3 1250 E3 1600 E3 2000 E3 2500 E3 3200[C°] % [A] % [A] % [A] % [A] % [A] % [A] % [A]10 100 800 100 1000 100 1250 1001600 100 2000 100 2500100 320020 100 800 100 1000 100 1250 100 1600 100 2000 100 2500100 320030 100 800 100 1000 100 1250 100 1600 100 2000 100 2500100 320040 100 800 100 1000 100 1250 100 1600 100 2000 100 2500100 320045 100 800 100 1000 100 1250 100 1600 100 2000 100 2500100 320050 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 97 309055 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 93 297560 100 800 100 1000 100 1250 100 1600 100 2000 100 2500 89 286065 100 800 100 1000 100 1250 100 1600 100 2000 97 2425 86 274570 100 800 100 1000 100 1250 100 1600 100 2000 94 2350 82 2630102 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.5 Temperature deratingEmax E4Temperature E4 3200 E4 4000[°C] % [A] % [A]10 100 3200 100 400020 100 3200 100 400030 100 3200 100 400040 100 3200 100 400045 100 3200 100 400050 100 3200 98 390055 100 3200 95 379060 100 3200 92 368065 98 3120 89 357070 95 3040 87 3460Emax E6Temperature E6 3200 E6 4000 E6 5000 E6 6300[°C] % [A] % [A] % [A] % [A]10 100 3200 100 4000 100 5000 100 630020 100 3200 100 4000 100 5000 100 630030 100 3200 100 4000 100 5000 100 630040 100 3200 100 4000 100 5000 100 630045 100 3200 100 4000 100 5000 100 630050 100 3200 100 4000 100 5000 100 630055 100 3200 100 4000 100 5000 98 619060 100 3200 100 4000 98 4910 96 607065 100 3200 100 4000 96 4815 94 585070 100 3200 100 4000 94 4720 92 5600<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 103


2 General characteristics2.5 Temperature deratingThe following table lists examples of the continuous current carrying capacityfor circuit-breakers installed in a switchboard with the dimensions indicatedbelow. These values refer to withdrawable switchgear installed in non segregatedswitchboards with a protection rating up to IP31, <strong>and</strong> following dimensions:2000x400x400 (HxLxD) for X1, 2300x800x900 (HxLxD) for X1 - E1 - E2 - E3;2300x1400x1500 (HxLxD) for E4 - E6.The values refer to a maximum temperature at the terminals of 120 °C.For withdrawable circuit-breakers with a rated current of 6300 A, the use ofvertical rear terminals is recommended.For switchboards with the following dimensions (mm): 2000x400x400Vertical terminalsHorizontal <strong>and</strong> front terminalsTypeIu Continuous capacity Busbars section Continuous capacity Busbars section[A][A][mm 2 ][A][mm 2 ]35°C 45°C 55°C 35°C 45°C 55°CX1B/N/L 06 630 630 630 630 2x(40x5) 630 630 630 2x(40x5)X1B/N/L 08 800 800 800 800 2x(50x5) 800 800 800 2x(50x5)X1B/N/ 10 1000 1000 1000 1000 2x(50x8) 1000 1000 1000 2x(50x10)X1L 10 1000 1000 1000 960 2x(50x8) 1000 950 890 2x(50x10)X1B/N/ 12 1250 1250 1250 1250 2x(50x8) 1250 1250 1200 2x(50x10)X1L 12 1250 1250 1205 1105 2x(50x8) 1250 1125 955 2x(50x10)X1B/N 16 1600 1520 1440 1340 2x(50x10) 1400 1330 1250 3x(50x8)For switchboards with the following dimensions (mm): 2300x800x900Vertical terminalsHorizontal <strong>and</strong> front terminalsTypeIu Continuous capacity Busbars section Continuous capacity Busbars section[A][A][mm 2 ][A][mm 2 ]35°C 45°C 55°C 35°C 45°C 55°CX1B/N/L 06 630 630 630 630 2x(40x5) 630 630 630 2x(40x5)X1B/N/L 08 800 800 800 800 2x(50x5) 800 800 800 2x(50x5)X1B/N/L 10 1000 1000 1000 1000 2x(50x8) 1000 1000 1000 2x(50x10)X1L 10 1000 1000 1000 1000 2x(50x8) 1000 960 900 2x(50x10)X1B/N/L 12 1250 1250 1250 1250 2x(50x8) 1250 1250 1200 2x(50x10)X1L 12 1250 1250 1250 1110 2x(50x8) 1250 1150 960 2x(50x10)X1B/N 16 1600 1600 1500 1400 2x(50x10) 1460 1400 1300 3x(50x8)104 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.5 Temperature deratingVertical terminalsHorizontal <strong>and</strong> front terminalsTypeIu Continuous capacity Busbars section Continuous capacity Busbars section[A][A][mm 2 ][A][mm 2 ]35°C 45°C 55°C 35°C 45°C 55°CE1B/N 08 800 800 800 800 1x(60x10) 800 800 800 1x(60x10)E1B/N 10 1000 1000 1000 1000 1x(80x10) 1000 1000 1000 2x(60x8)E1B/N 12 1250 1250 1250 1250 1x(80x10) 1250 1250 1200 2x(60x8)E1B/N 16 1600 1600 1600 1500 2x(60x10) 1550 1450 1350 2x(60x10)E2S 08 800 800 800 800 1x(60x10) 800 800 800 1x(60x10)E2N/S 10 1000 1000 1000 1000 1x(60x10) 1000 1000 1000 1x(60x10)E2N/S 12 1250 1250 1250 1250 1x(60x10) 1250 1250 1250 1x(60x10)E2B/N/S 16 1600 1600 1600 1600 2x(60x10) 1600 1600 1530 2x(60x10)E2B/N/S 20 2000 2000 2000 1800 3x(60x10) 2000 2000 1750 3x(60x10)E2L 12 1250 1250 1250 1250 1x(60x10) 1250 1250 1250 1x(60x10)E2L 16 1600 1600 1600 1500 2x(60x10) 1600 1500 1400 2x(60x10)E3H/V 08 800 800 800 800 1x(60x10) 800 800 800 1x(60x10)E3S/H 10 1000 1000 1000 1000 1x(60x10) 1000 1000 1000 1x(60x10)E3S/H/V 12 1250 1250 1250 1250 1x(60x10) 1250 1250 1250 1x(60x10)E3S/H/V 16 1600 1600 1600 1600 1x(100x10) 1600 1600 1600 1x(100x10)E3S/H/V 20 2000 2000 2000 2000 2x(100x10) 2000 2000 2000 2x(100x10)E3N/S/H/V 25 2500 2500 2500 2500 2x(100x10) 2500 2450 2400 2x(100x10)E3N/S/H/V 32 3200 3200 3100 2800 3x(100x10) 3000 2880 2650 3x(100x10)E3L 20 2000 2000 2000 2000 2x(100x10) 2000 2000 1970 2x(100x10)E3L 25 2500 2500 2390 2250 2x(100x10) 2375 2270 2100 2x(100x10)E4H/V 32 3200 3200 3200 3200 3x(100x10) 3200 3150 3000 3x(100x10)E4S/H/V 40 4000 4000 3980 3500 4x(100x10) 3600 3510 3150 6x(60x10)E6V 32 3200 3200 3200 3200 3x(100x10) 3200 3200 3200 3x(100x10)E6H/V 40 4000 4000 4000 4000 4x(100x10) 4000 4000 4000 4x(100x10)E6H/V 50 5000 5000 4850 4600 6x(100x10) 4850 4510 4250 6x(100x10)E6H/V 63 6300 6000 5700 5250 7x(100x10) - - - -Note: the reference temperature is the ambient temperatureExamples:Selection of an air circuit-breaker, with electronic release, in withdrawable version,with vertical terminals, for a load current of 2700 A, with a temperature of55 °C outside of the IP31 switchboard.From the tables referring to the current carrying capacity inside the switchboardfor Emax circuit-breaker (see above), it can be seen that the most suitablebreaker is the E3 3200, with busbars section 3x(100x10) mm 2 , which can beset from 1280 A to 2800 A.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 105


2 General characteristics2.6 Altitude deratingFor <strong>installation</strong>s carried out at altitudes of more than 2000 m above sea level,the performance of low voltage circuit-breakers is subject to a decline.Basically there are two main phenomena:• the reduction of air density causes a lower efficiency in heat transfer. Theallowable heating conditions for the various parts of the circuit-breaker canonly be followed if the value of the rated uninterrupted current is decreased;• the rarefaction of the air causes a decrease in dielectric rigidity, so the usualisolation distances become insufficient. This leads to a decrease in the maximumrated voltage at which the device can be used.The correction factors for the different types of circuit-breakers, both mouldedcase<strong>and</strong> air circuit-breakers, are given in the following table:Rated operational voltage Ue [V]Altitude 2000[m] 3000[m] 4000[m] 5000[m]Tmax XT 690 600 540 470Tmax T* 690 600 500 440Emax 690 600 500 440Rated uninterrupted current Iu [A]Altitude 2000[m] 3000[m] 4000[m] 5000[m]Tmax XT 100% 98% 93% 90%Tmax T 100% 98% 93% 90%Emax 100% 98% 93% 90%*Excluding Tmax T1P106 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.7 <strong>Electrical</strong> characteristics of switch disconnectorsA switch disconnector as defined by the st<strong>and</strong>ard IEC 60947-3 is a mechanicalswitching device which, when in the open position, carries out a disconnectingfunction <strong>and</strong> ensures an isolating distance (distance between contacts) sufficientto guarantee safety. This safety of disconnection must be guaranteed <strong>and</strong>verified by the positive operation: the operating lever must always indicate theactual position of the mobile contacts of the device.The mechanical switching device must be able to make, carry <strong>and</strong> break currentsin normal circuit conditions, including any overload currents in normal service,<strong>and</strong> to carry, for a specified duration, currents in abnormal circuit conditions,such as, for example, short-circuit conditions.Switch disconnectors are often used as:• main sub-switchboard devices;• switching <strong>and</strong> disconnecting devices for lines, busbars or load units;• bus-tie.The switch disconnector shall ensure that the whole plant or part of it is notlive, safely disconnecting from any electrical supply. The use of such a switchdisconnector allows, for example, personnel to carry out work on the plantwithout risks of electrical nature.Even if the use of a single pole devices side by side is not forbidden, thest<strong>and</strong>ards recommend the use of multi-pole devices so as to guarantee thesimultaneous isolation of all poles in the circuit.The specific rated characteristics of switch disconnectors are defined by thest<strong>and</strong>ard IEC 60947-3, as detailed below:• Icw [kA]: rated short-time withst<strong>and</strong> current:is the current that a switch is capable of carrying, without damage, in theclosed position for a specific duration<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 107


2 General characteristics2.7 <strong>Electrical</strong> characteristics of switch disconnectors• Icm [kA]: rated short-circuit making capacity:is the maximum peak value of a short-circuit current which the switch disconnectorcan close without damages. When this value is not given bythe manufacturer it must be taken to be at least equal to the peak currentcorresponding to Icw. It is not possible to define a breaking capacity Icu [kA]since switch disconnectors are not required to break short-circuit currents• utilization categories with alternating current AC <strong>and</strong> with direct currentDC:define the kind of the conditions of using which are represented by two lettersto indicate the type of circuit in which the device may be installed (AC foralternating current <strong>and</strong> DC for direct current), with a two digit number for thetype of load which must be operated, <strong>and</strong> an additional letter (A or B) whichrepresents the frequency in the using.With reference to the utilization categories, the product st<strong>and</strong>ard defines thecurrent values which the switch disconnector must be able to break <strong>and</strong> makeunder abnormal conditions.The characteristics of the utilization categories are detailed in Table 1 below.The most dem<strong>and</strong>ing category in alternating current is AC23A, for which thedevice must be capable of connecting a current equal to 10 times the ratedcurrent of the device, <strong>and</strong> of disconnecting a current equal to 8 times the ratedcurrent of the device.From the point of view of construction, the switch disconnector is a very simpledevice. It is not fitted with devices for overcurrent detection <strong>and</strong> the consequentautomatic interruption of the current. Therefore the switch disconnector cannotbe used for automatic protection against overcurrent which may occur in thecase of failure, protection must be provided by a coordinated circuit-breaker.The combination of the two devices allows the use of switch disconnectors insystems in which the short-circuit current value is greater than the electrical parameterswhich define the performance of the disconnector (back-up protectionsee Chapter 3.4. This is valid only for Isomax <strong>and</strong> Tmax switch-disconnectors.For the Emax/MS air disconnectors, it must be verified that the values for Icw<strong>and</strong> Icm are higher to the values for short-circuit in the plant <strong>and</strong> correspondentpeak, respectively.108 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristicsTable1: Utilization categories2.7 <strong>Electrical</strong> characteristics of switch disconnectorsNatureof currentUtilization categoryFrequentoperationNon-frequentoperationUtilization categoriesTypical applicationsAC-20A AC-20B Connecting <strong>and</strong> disconnecting under no-load conditionsAlternatingCurrentAC-21A AC-21B Switching of resistive loads including moderate overloadsAC-22AAC-22BSwitching of mixed resistive <strong>and</strong> inductive loads, includingmoderate overloadAC-23A AC-23B Switching of motor loads or other highly inductive loadsDC-20A DC-20B Connecting <strong>and</strong> disconnecting under no-load conditionsDirectCurrentDC-21A DC-21B Switching of resistive loads including moderate overloadsDC-22ADC-22BSwitching of mixed resistive <strong>and</strong> inductive loads, includingmoderate overload (e.g. shunt motors)DC-23A DC-23B Switching of highly inductive loads<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 109


2 General characteristics2.7 <strong>Electrical</strong> characteristics of switch disconnectorsTables 2, 3 <strong>and</strong> 4 detail the main characteristics of the disconnectors.Table 2: SACE Tmax XT switch disconnectorsSize[A]Rated operating current in class AC21, Ie[A]Rated operating current in class AC22, Ie[A]Rated operating current in class AC23, Ie[A]Poles[Nr.]Rated service voltage, Ue (AC) 50-60Hz [V](DC)[V]Rated insulation voltage, Ui[V]Rated impulse withst<strong>and</strong> voltage, Uimp[kV]Test voltage at industrial frequency for 1 min[V]Rated breaking capacity in short-circuit, Icm (Min) Disconnector only[kA](Max) With automatic[kA]Circuit-breaker on supply side Rated short-time withst<strong>and</strong> current for 1s, Icw [kA]VersionsTable 3: Tmax T switch disconnectorsTmax T1DConventional thermal current, Ith [A] 160Rated service current in category AC22, Ie [A] 160Rated service current in category AC23, Ie [A] 125Poles [Nr.] 3/4Rated service voltage, Ue (AC) 50-60 Hz [V] 690(DC) [V] 500Rated impulse withst<strong>and</strong> voltage, Uimp [kV] 8Rated insulation voltage, Ui [V] 800Test voltage at industrial frequency for 1 minute [V] 3000Rated short-circuit making capacity, Icm (min) switch-disconnector only [kA] 2.8(max) with circuit-breaker on supply side [kA] 187Rated short-time withst<strong>and</strong> current for 1s, Icw [kA] 2Reference St<strong>and</strong>ard IEC 60947-3VersionsFTerminals FC Cu - EF -FC CuAlMechanical life [No. operations] 25000[No. Hourly operations] 120Weight fixed 3/4 poles [kg] 0.9/1.2plug-in 3/4 poles [kg] –withdrawable 3/4 poles [kg] –Tmax T3D2502502003/4690500880030005.31053.6IEC 60947-3F - PF-FC CuAl-FC Cu-EF-ES-R250001201.5/22.1/3.7–110 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.7 <strong>Electrical</strong> characteristics of switch disconnectorsTmax XT1D Tmax XT3D Tmax XT4D160 250 250160 250 250160 250 250125 200 2003,4 3,4 3,4690 690 690500 500 500800 800 8008 8 83000 3000 30002,8 5,3 5,3187 105 1052 3,6 3,6Fixed / Plug-in Fixed / Plug-in Fixed / Withdrawable / Plug-inTmax T4D Tmax T5D Tmax T6D Tmax T7D250/320 400/630 630/800/1000 1000/1250/1600250/320 400/630 630/800/1000 1000/1250/1600250 400 630/800/800 1000/1250/12503/4 3/4 3/4 3/4690 690 690 690750 750 750 75088 8 8800 800 1000 10003000 3000 3500 30005.3 11 30 52.5440 440 440 4403.6 6 15 20IEC 60947-3 IEC 60947-3 IEC 60947-3 IEC 60947-3F - P -W F - P -W F-W F-WF-FC CuAl-FC Cu-EF-ES-R-MC-HR-VRF-FC CuAl-FC Cu-EF-ES-R-HR-VRF-FC CuAl-EF-ES-R-RCF-EF-ES-FC CuAlHR/VR20000 20000 20000 10000120 120 120 602.35/3.05 3.25/4.15 9.5/12 9.7/12.5(manual)/11/14(motorizable)3.6/4.65 5.15/6.65 – –3.85/4.9 5.4/6.9 12.1/15.1 29.7/39.6(manual)/32/42.6(motorizable)KEY TO VERSIONSF = FixedP = Plug-inW = WithdrawableKEY TO TERMINALSF = FrontEF = Extended frontES = Extended spreaded frontFC CuAl = Front for copper or aluminium cablesR = Rear threadedRC = Rear for copper or aluminium cablesHR = Rear horizontal flat barVR = Rear vertical flat bar<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 111


2 General characteristics2.7 <strong>Electrical</strong> characteristics of switch disconnectorsTable 4: Emax switch disconnectorsX1B/MS E1B/MS E1N/MS E2B/MSE2N/MSRated uninterrupted current [A] 1000 800 800 1600 1000(a 40 °C) Iu [A] 1250 1000 1000 2000 1250[A] 1600 1250 1250 1600[A] 1600 1600 2000[A][A]Rated operational voltage Ue [V ~] 690 690 690 690 690[V –] 250 250 250 250 250Rated insulation voltage Ui [V ~] 1000 1000 1000 1000 1000Rated impulse withst<strong>and</strong>voltage Uimp [kV] 12 12 12 12 12Rated short-timewithst<strong>and</strong> current Icw (1s) [kA] 42 42 50 (1) 42 55(3s) [kA] 36 36 42 42Rated short-circuit makingcapacity (peak value) Icm220/230/380/400/415/440 V ~ [kA] 88.2 88.2 105 88.2 121500/660/690 V ~ [kA] 88.2 88.2 105 88.2 121Note: the breaking capacity I cu, at the maximum rated use voltage, by means of externalprotection relay, with 500 ms maximum timing, is equal to the value of I cw(1s).112 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


2 General characteristics2.7 <strong>Electrical</strong> characteristics of switch disconnectorsE2S/MS E3N/MS E3S/MS E3V/MS E4S/fMS E4S/MS E4H/fMS E4H/MS E6H/MS E6H/f MS1000 2500 1000 800 4000 4000 3200 3200 4000 40001250 3200 1250 1250 4000 4000 5000 50001600 1600 1600 6300 63002000 2000 20002500 26003200 3200690 690 690 690 690 690 690 690 690 690250 250 250 250 250 250 250 250 250 2501000 1000 1000 1000 1000 1000 1000 1000 1000 100012 12 12 12 12 12 12 12 12 1265 65 75 85 75 75 85 100 (2) 100 10042 65 65 65 75 75 75 75 85 85187 143 165 187 165 165 187 220 220 220143 143 165 187 165 165 187 220 220 220(1)I cw=36kA@690V.(2)I cw=85kA@690V.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 113


3.1 <strong>Protection</strong> coordination3 <strong>Protection</strong> coordinationThe design of a system for protecting an electric network is of fundamentalimportance both to ensure the correct economic <strong>and</strong> functional operation ofthe <strong>installation</strong> as a whole <strong>and</strong> to reduce to a minimum any problem causedby anomalous operating conditions <strong>and</strong>/or malfunctions.The present analysis discusses the coordination between the different devicesdedicated to the protection of zones <strong>and</strong> specific components with a view to:• guaranteeing safety for people <strong>and</strong> <strong>installation</strong> at all times;• identifying <strong>and</strong> rapidly excluding only the zone affected by a problem, insteadof taking indiscriminate actions <strong>and</strong> thus reducing the energy available to therest of the network;• containing the effects of a malfunction on other intact parts of the network(voltage dips, loss of stability in the rotating machines);• reducing the stress on components <strong>and</strong> damage in the affected zone;• ensuring the continuity of the service with a good quality feeding voltage;• guaranteeing an adequate back-up in the event of any malfunction of theprotective device responsible for opening the circuit;• providing staff <strong>and</strong> management systems with the information they need torestore the service as rapidly as possible <strong>and</strong> with a minimal disturbance tothe rest of the network;• achieving a valid compromise between reliability, simplicity <strong>and</strong> costeffectiveness.To be more precise, a valid protection system must be able to:• underst<strong>and</strong> what has happened <strong>and</strong> where it has happened, discriminatingbetween situations that are anomalous but tolerable <strong>and</strong> faults within a givenzone of influence, avoiding unnecessary tripping <strong>and</strong> the consequentunjustified disconnection of a sound part of the system;• take action as rapidly as possible to contain damage (destruction, acceleratedageing, ...), safeguarding the continuity <strong>and</strong> stability of the power supply.The most suitable solution derives from a compromise between these twoopposing needs-to identify precisely the fault <strong>and</strong> to act rapidly - <strong>and</strong> is definedin function of which of these two requirements takes priority.Over-current coordinationInfluence of the network’s electrical parameters (rated current <strong>and</strong>short-circuit current)The strategy adopted to coordinate the protective devices depends mainlyon the rated current (I n) <strong>and</strong> short-circuit current (I k) values in the consideredpoint of network.Generally speaking, we can classify the following types of coordination:• current discrimination;• time (or time-current) discrimination;• zone (or logical) discrimination;• energy discrimination;• back-up.114 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.1 <strong>Protection</strong> coordinationDefinition of discriminationThe over-current discrimination is defined in the St<strong>and</strong>ards as “coordinationof the operating characteristics of two or more over-current protective devicessuch that, on the incidence of over-currents within stated limits, the device intendedto operate within these limits does so, while the others do not operate”(IEC 60947-1, def. 2.5.23);It is possible to distinguish between:• total discrimination, which means “over-current discrimination such that, inthe case of two over-current protective devices in series, the protective deviceon the load side provides protection without tripping the other protectivedevice” (IEC 60947-2, def. 2.17.2);• partial discrimination, which means “over-current discrimination such that, inthe case of two over-current protective devices in series, the protective deviceon the load side provides protection up to a given over-current limit withouttripping the other” (IEC 60947-2, def. 2.17.3); this over-current threshold iscalled “discrimination limit current I s” (IEC 60947-2, def. 2.17.4).Current discriminationThis type of discrimination is based on the observation that the closer the faultcomes to the network’s feeder, the greater the short-circuit current will be. Wecan therefore pinpoint the zone where the fault has occurred simply by calibratingthe instantaneous protection of the device upstream to a limit value higher thanthe fault current which causes the tripping of the device downstream.We can normally achieve total discrimination only in specific cases where thefault current is not very high (<strong>and</strong> comparable with the device’s rated current) orwhere a component with high impedance is between the two protective devices(e.g. a transformer, a very long or small cable...) giving rise to a large differencebetween the short-circuit current values.This type of coordination is consequently feasible mainly in final distributionnetworks (with low rated current <strong>and</strong> short-circuit current values <strong>and</strong> a highimpedance of the connection cables).The devices’ time-current tripping curves are generally used for the study.This solution is:• rapid;• easy to implement;• <strong>and</strong> inexpensive.On the other h<strong>and</strong>:• the discrimination limits are normally low;• increasing the discrimination levels causes a rapid growing of the device sizes.The following example shows a typical application of current discrimination basedon the different instantaneous tripping threshold values of the circuit-breakersconsidered.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 115


3 <strong>Protection</strong> coordination3.1 <strong>Protection</strong> coordinationUUr = 400VWith a fault current value at the defined point equal to 1000 A, an adequatecoordination is obtained by using the considered circuit-breakers as verified inthe tripping curves of the protection devices.The discrimination limit is given by the minimum magnetic threshold of thecircuit-breaker upstream, XT1B160 In160.[s] 10 410 3Time-current curvesXT1B 160 In16010 2XT1B160In40Cable10 1 1XT1B160In160XT1D 160XT1B 160 In4010 -110 -210 -210 -1 1 10 1I [kA]1SDC008014F0001Ik=1kATime discriminationThis type of discrimination is an evolution from the previous one. The settingstrategy is therefore based on progressively increasing the current thresholds<strong>and</strong> the time delays for tripping the protective devices as we come closer to thepower supply source. As in the case of current discrimination, the study is basedon a comparison of the time-current tripping curves of the protective devices.This type of coordination:• is easy to study <strong>and</strong> implement;• is relatively inexpensive;• enables to achieve even high discrimination levels, depending on the I cwof theupstream device;• allows a redundancy of the protective functions <strong>and</strong> can send valid informationto the <strong>control</strong> system,but has the following disadvantages:• the tripping times <strong>and</strong> the energy levels that the protective devices (especiallythose closer to the sources) let through are high, with obvious problems concerningsafety <strong>and</strong> damage to the components even in zones unaffected bythe fault;116 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.1 <strong>Protection</strong> coordination• it enables the use of current-limiting circuit-breakers only at levels hierarchicallylower down the chain; the other circuit-breakers have to be capable ofwithst<strong>and</strong>ing the thermal <strong>and</strong> electro-dynamic stresses related to the passageof the fault current for the intentional time delay. Selective circuit-breakers,often air type, have to be used for the various levels to guarantee a sufficientlyhigh short-time withst<strong>and</strong> current;• the duration of the disturbance induced by the short-circuit current on thepower supply voltages in the zones unaffected by the fault can cause problemswith electronic <strong>and</strong> electro-mechanical devices (voltage below theelectromagnetic releasing value);• the number of discrimination levels is limited by the maximum time that thenetwork can st<strong>and</strong> without loss of stability.The following example shows a typical application of time discrimination obtainedby setting differently the tripping times of the different protection devices.Electronic release:E4S 4000 PR121-LSI In4000E3N 2500 PR121-LSI In2500T7H 1600 PR332-LI In1600L (Long delay)Setting: 0.93Curve: 36sSetting: 1Curve: 24sSetting: 1Curve: 18sS (Short delay)Setting: 10Curve: 0.5sSetting: 10Curve: 0.2sI (IST)OffOffSetting: 10UUr = 15000 VTime-current curvesSr = 2500 kVAUr2 = 400 Vu k % = 6%[s] 10 410 3E4S 4000 PR121-LSI In400010 2E4S400010 1E3N 2500 PR121-LSI In25001T7H 1600 PR332-LI In1600I k =60kA10 -110 -2T7H16001 10 1E3N250010 2 10 3I [kA]1SDC008015F0001<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 117


3 <strong>Protection</strong> coordination3.1 <strong>Protection</strong> coordinationZone (or logical) discriminationThe zone discrimination is available with MCCB (T4 L-T5 L-T6 L with PR223-EF)<strong>and</strong> ACB (with PR332/P - PR333/P - PR122 - PR 123).This type of coordination is implemented by means of a dialogue betweencurrent measuring devices that, when they ascertain that a setting thresholdhas been exceeded, give the correct identification <strong>and</strong> disconnection only ofthe zone affected by the fault.In practice, it can be implemented in two ways:• the releases send information on the preset current threshold that has beenexceeded to the supervisor system <strong>and</strong> the latter decides which protectivedevice has to trip;• in the event of current values exceeding its setting threshold, each protectivedevice sends a blocking signal via a direct connection or bus to the protectivedevice higher in the hierarchy (i.e. upstream with respect to the direction ofthe power flow) <strong>and</strong>, before it trips, it makes sure that a similar blocking signalhas not arrived from the protective device downstream; in this way, only theprotective device immediately upstream of the fault trips.The first mode foresees tripping times of about one second <strong>and</strong> is used mainlyin the case of not particularly high short-circuit currents where a power flow isnot uniquely defined.The second mode enables distinctly shorter tripping times: with respect to atime discrimination coordination, there is no longer any need to increase theintentional time delay progressively as we move closer to the source of the powersupply. The maximum delay is in relation to the time necessary to detect anypresence of a blocking signal sent from the protective device downstream.Advantages:• reduction of the tripping times <strong>and</strong> increase of the safety level;• reduction of both the damages caused by the fault as well of the disturbancesin the power supply network;• reduction of the thermal <strong>and</strong> dynamic stresses on the circuit-breakers <strong>and</strong> onthe components of the system;• large number of discrimination levels;• redundancy of protections: in case of malfunction of zone discrimination, thetripping is ensured by the settings of the other protection functions of thecircuit-breakers. In particular, it is possible to adjust the time-delay protectionfunctions against short-circuit at increasing time values, the closer they are tothe network’s feeder.Disadvantages:• higher costs;• greater complexity of the system (special components, additional wiring,auxiliary power sources, ...).This solution is therefore used mainly in systems with high rated current <strong>and</strong>high short-circuit current values, with precise needs in terms of both safety<strong>and</strong> continuity of service: in particular, examples of logical discrimination canbe often found in primary distribution switchboards, immediately downstreamof transformers <strong>and</strong> generators <strong>and</strong> in meshed networks.118 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.1 <strong>Protection</strong> coordinationZone selectivity with EmaxAE4S 4000PR123/POUTINBE3N 2500PR123/POUTINX1N 1000PR333/PCOUTINIkDX1N 800PR332/POUTINX1N 800PR332/PEOUTIN1SDC200559F0001The example above shows a plant wired so as to guarantee zone selectivity withEmax CB equipped with PR332/P-PR333/P-PR122/P-PR123/P releases.Each circuit-breaker detecting a fault sends a signal to the circuit-breaker immediatelyon the supply side through a communication wire; the circuit-breakerthat does not receive any communication from the circuit-breakers on the loadside shall launch the opening comm<strong>and</strong>.In this example, with a fault located in the indicated point, the circuit-breakersD <strong>and</strong> E do not detect the fault <strong>and</strong> therefore they do not communicate withthe circuit-breaker on the supply side (circuit-breaker B), which shall launch theopening comm<strong>and</strong> within the selectivity time set from 40 to 200 ms.To actuate correctly zone selectivity, the following settings are suggested:SIGSelectivity timet 2≥ selectivity time + 70 msI 3= OFFt 4≥ selectivity time + 70 mssame settings for each circuit-breaker<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 119


3 <strong>Protection</strong> coordination3.1 <strong>Protection</strong> coordinationZone selectivity for circuit-breakers type Tmax (T4L-T5L-T6L) withPR223 EF releasesAT5L 630 PR223/EFOUTINOUTOUTT4L 250 PR223/EF IN T4L 250 PR223/EF IN T4L 250 PR223/EFB C DIkOUTIN1SDC200560F0001The example above shows a plant wired through an interlocking protocol (Interlocking,IL), so as to guarantee zone selectivity through PR223 EF release.In case of short-circuit, the circuit-breaker immediately on the supply side of thefault sends through the bus a block signal to the protection device hierarchicallyhigher <strong>and</strong> verifies, before tripping, that an analogous block signal has not beensent by the protection on the load side.In the example in the figure, the circuit-breaker C, immediately on the supply sideof the fault, sends a block signal to the circuit-breaker A, which is hierarchicallyhigher. If, as in the given example, no protection on the load side is present,the circuit-breaker C shall open in very quick times since it has received noblock signal.Everything occurs in shorter times (10 to 15ms) than in the case of zone selectivitywith the Emax series air circuit-breaker (40 to 200ms), thus subjecting theplant to lower electrodynamic stresses, <strong>and</strong> with a consequent cost reductionfor the plant.120 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.1 <strong>Protection</strong> coordinationEnergy discriminationEnergy coordination is a particular type of discrimination that exploits thecurrent-limiting characteristics of moulded-case circuit-breakers. It is importantto remember that a current-limiting circuit-breaker is “a circuit-breaker with abreak time short enough to prevent the short-circuit current reaching its otherwiseattainable peak value” (IEC 60947-2, def. 2.3).In practice, <strong>ABB</strong> SACE moulded-case circuit-breakers SACE Tmax XT <strong>and</strong> Tmax Tseries, under short-circuit conditions, are extremely rapid (tripping times ofabout some milliseconds) <strong>and</strong> therefore it is impossible to use the time-currentcurves for the coordination studies.The phenomena are mainly dynamic (<strong>and</strong> therefore proportional to the squareof the instantaneous current value) <strong>and</strong> can be described by using the specificlet-through energy curves.In general, it is necessary to verify that the let-through energy of the circuitbreakerdownstream is lower than the energy value needed to complete theopening of the circuit-breaker upstream.This type of discrimination is certainly more difficult to consider than the previousones because it depends largely on the interaction between the two devicesplaced in series <strong>and</strong> dem<strong>and</strong>s access to data often unavailable to the enduser. Manufacturers provide tables, rules <strong>and</strong> calculation programs in whichthe minimum discrimination limits are given between different combinations ofcircuit- breakers.Advantages:• fast breaking, with tripping times which reduce as the short-circuit currentincreases;• reduction of the damages caused by the fault (thermal <strong>and</strong> dynamic stresses),of the disturbances to the power supply system, of the costs...;• the discrimination level is no longer limited by the value of the short-timewithst<strong>and</strong> current I cwwhich the devices can withst<strong>and</strong>;• large number of discrimination levels;• possibility of coordination of different current-limiting devices (fuses, circuitbreakers,..)even if they are positioned in intermediate positions along thechain.Disadvantage:• difficulty of coordination between circuit-breakers of similar sizes.This type of coordination is used above all for secondary <strong>and</strong> final distributionnetworks, with rated currents below 1600A.Back-up protectionThe back-up protection is an “over-current coordination of two over-currentprotective devices in series where the protective device, generally but not necessarilyon the supply side, effects the over-current protection with or withoutthe assistance of the other protective device <strong>and</strong> prevents any excessive stresson the latter” (IEC 60947-1, def. 2.5.24).Besides, IEC 60364-4-43, 434.5.1 states: “… A lower breaking capacity isadmitted if another protective device having the necessary breaking capacityis installed on the supply side. In that case, characteristics of the devices, mustbe co-ordinated so that the energy let through by these two devices does notexceed that which can be withstood without damage by the device on the loadside <strong>and</strong> the conductors protected by these devices.”<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 121


3 <strong>Protection</strong> coordination3.1 <strong>Protection</strong> coordinationAdvantages:• cost-saving solution;• extremely rapid tripping.Disadvantages:• extremely low discrimination values;• low service quality, since at least two circuit-breakers in series have to trip.Coordination between circuit-breaker <strong>and</strong> switchdisconnectorThe switch disconnectorThe switch disconnectors derive from the corresponding circuit-breakers, ofwhich they keep the overall dimensions, the fixing systems <strong>and</strong> the possibility ofmounting all the accessories provided for the basic versions. They are deviceswhich can make, carry <strong>and</strong> break currents under normal service conditions ofthe circuit.They can also be used as general circuit-breakers in sub-switchboards, as busties,or to isolate <strong>installation</strong> parts, such as lines, busbars or groups of loads.Once the contacts have opened, these switches guarantee isolation thanks totheir contacts, which are at the suitable distance to prevent an arc from strikingin compliance with the prescriptions of the st<strong>and</strong>ards regarding aptitude toisolation.<strong>Protection</strong> of switch disconnectorsEach switch disconnector shall be protected by a coordinated device whichsafeguards it against overcurrents, usually a circuit-breaker able to limit theshort-circuit current <strong>and</strong> the let-through energy values at levels acceptable forthe switch-disconnector.As regards overload protection, the rated current of the circuit-breaker shall belower than or equal to the size of the disconnector to be protected.Regarding SACE Tmax XT <strong>and</strong> Tmax T series switch disconnectors thecoordination tables show the circuit-breakers which can protect them againstthe indicated prospective short-circuit currents values.Regarding Emax series switch disconnectors it is necessary to verify that theshort-circuit current value at the <strong>installation</strong> point is lower than the short-timewithst<strong>and</strong> current I cwof the disconnector, <strong>and</strong> that the peak value is lower thanthe making current value (I cm).122 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3.2 Discrimination tables3 <strong>Protection</strong> coordinationThe tables below give the selectivity values of short-circuit currents (in kA) betweenpre-selected combinations of circuit-breakers, for voltages from 230/240 to415 V, according annex A of IEC 60947-2. The tables cover the possible combinationsof <strong>ABB</strong> SACE Emax air circuit-breakers series, SACE Tmax XT <strong>and</strong>Tmax T moulded-case circuit-breakers series <strong>and</strong> the series of <strong>ABB</strong> modularcircuit-breakers. The values are obtained following particular rules which, if notrespected, may give selectivity values which in some cases may be much lowerthan those given. Some of these guidelines are generally valid <strong>and</strong> are indicatedbelow; others refer exclusively to particular types of circuit-breakers <strong>and</strong> will besubject to notes below the relevant table.General rules:• the function l of electronic releases of upstream breakers must be excluded(l3 in OFF);• the magnetic trip of thermomagnetic (TM) or magnetic only (MA-MF) breakerspositioned upstream must be ≥ 10·I n<strong>and</strong> set to the maximum threshold;• it is fundamentally important to verify that the settings adopted by the userfor the electronic <strong>and</strong> thermomagnetic releases of breakers positioned eitherupstream or downstream result in time-current curves properly spaced.Notes for the correct reading of the coordination tables:The limit value of selectivity is obtained considering the lower among the givenvalue, the breaking capacity of the CB on the supply side <strong>and</strong> the breakingcapacity of the CB on the load side.The letter T indicates total selectivity for the given combination, the correspondingvalue in kA is obtained considering the lower of the downstream <strong>and</strong> upstreamcircuit-breakers’ breaking capacities (Icu).The following tables show the breaking capacities at 415Vac for SACE Emax,SACE Tmax XT <strong>and</strong> Tmax T circuit-breakers.Tmax XT @ 415V acVersion Icu [kA]B 18C 25N 36S 50H 70L 120V 150Tmax T @ 415V acVersion Icu [kA]B 16C 25N 36S 50H 70L (for T2) 85L (for T4-T5-T7) 120L (for T6) 100V (for T7) 150V 200Emax @ 415V acVersion Icu [kA]B 42N 65*S 75**H 100L 130***V 150***** For Emax E1 version N Icu=50kA** For Emax E2 version S Icu=85kA*** For Emax X1 version L Icu=150kA**** For Emax E3 version V Icu=130kAKeysFor MCCB (Moulded-case circuit-breaker)ACB (Air circuit-breaker)TM = thermomagnetic release– TMD (Tmax)– TMA (Tmax)M = magnetic only release– MF (Tmax)– MA (Tmax)EL = elettronic releaseFor MCB (Miniature circuit-breaker):B = charatteristic trip (I3=3...5In)C = charatteristic trip (I3=5...10In)D = charatteristic trip (I3=10...20In)K = charatteristic trip (I3=8...14In)Z = charatteristic trip (I3=2...3In)<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 123


3 <strong>Protection</strong> coordination3.2 Discrimination tablesExample:From the selectivity table on page 154 it can be seen that breakers E2N1250<strong>and</strong> T5H400,correctly set, are selective up to 55kA (higher than the short-circuitcurrent at the busbar).From the selectivity table on page 149 it can be seen that, between T5H400<strong>and</strong> XT1N160 In125, the total sectivity is granted; as aleady specified on page123 this means selectivity up to the breaking capacity of XT1N <strong>and</strong> thereforeup to 36 kA (higher than the short-circuit current at the busbar).UUr = 400Vt [s]Time-current curves10 4 E2N1250 In125010 3E2N 1250 In125010 2Cable10 1 1I k =50kAXT1N160 In125T5H400CableI k =22kA10 -1 1T5H400 In40010 -110 -2 10 1 22kA50kA I [kA]1SDC008016F0001XT1N160 In125From the curves it is evident that between breakers E2N1250 <strong>and</strong> T5H400 timediscrimination exists, while between breakers T5H400 <strong>and</strong> XT1N160 there isenergy discrimination.124 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.2 Discrimination tablesIndex of discrimination tablesMCB-MCB (230/240V)............................................................................................ 126MCCB (415V)-MCB (240V)..................................................................................... 128MCB-MCB (415V)MCB-S2..B......................................................................................................... 130MCB-S2..C......................................................................................................... 130MCB-S2..D......................................................................................................... 132MCB-S2..K.......................................................................................................... 132MCB-S2..Z.......................................................................................................... 134MCCB-MCB (415V)MCCB-S800....................................................................................................... 136MCCB-S2..B....................................................................................................... 138MCCB-S2..C....................................................................................................... 140MCCB-S2..D....................................................................................................... 142MCCB-S2..K....................................................................................................... 144MCCB-S2..Z....................................................................................................... 146MCCB-MCCB (415V)MCCB-XT1.......................................................................................................... 148MCCB-XT2.......................................................................................................... 150MCCB-XT3.......................................................................................................... 152MCCB-XT4.......................................................................................................... 152MCCB-T5............................................................................................................ 153MCCB-T6............................................................................................................ 153ACB-MCCB (415V)................................................................................................. 154MCCB-MCCB (400/415V)....................................................................................... 155<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 125


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCB - SN @ 230/240 VSupply s. 2 S290 S800 N-SLoad s. 1 Char. C D BI cu[kA] 15 36-50I n[A] 80 100 125 80 100 32 40 50 63 80 100 1252 T T T T T 0,43 3 0,6 1,3 4 T T T4 5 T T T T 0,45 0,8 1,5 2,5 4 T6 4,5 5 T 5,5 T 0,6 1,2 1,6 2,6 3,810 4 4,5 5 5 5 0,5 1,1 1,4 2 3SN201L B, C 6 16 2,5 3,5 3,5 4 4,5 0,8 1,2 1,7 2,520 1,5 2,5 2,5 3 4,5 1 1,5 2,125 0,5 0,5 1,5 2 4 1,3 1,832 0,5 0,5 0,5 1,5 3,5 1,1 1,740 0,5 0,5 0,5 1,5 3,5 1,62 6 8 9 7 8 0,43 3 0,6 1,3 4 9 T T4 5 6 7,5 6 7 0,45 0,8 1,5 2,5 4 7,36 4,5 5 6 5,5 6 0,6 1,2 1,6 2,6 3,810 4 4,5 5 5 5 0,5 1,1 1,4 2 3SN201 B, C, D 10 16 2,5 3,5 3,5 4 4,5 0,8 1,2 1,7 2,520 1,5 2,5 2,5 3 4,5 1 1,5 2,125 0,5 0,5 1,5 2 4 1,3 1,832 0,5 0,5 0,5 1,5 3,5 1,1 1,740 0,5 0,5 0,5 1,5 3,5 1,62 6 8 9 7 8 0,43 3 0,6 1,3 4 9 T T4 5 6 7,5 6 7 0,45 0,8 1,5 2,5 4 7,36 4,5 5 6 5,5 6 0,6 1,2 1,6 2,6 3,810 4 4,5 5 5 5 0,5 1,1 1,4 2 3SN201M B, C 10 16 2,5 3,5 3,5 4 4,5 0,8 1,2 1,7 2,520 1,5 2,5 2,5 3 4,5 1 1,5 2,125 0,5 0,5 1,5 2 4 1,3 1,832 0,5 0,5 0,5 1,5 3,5 1,1 1,740 0,5 0,5 0,5 1,5 3,5 1,61Load side circuit-breaker 1P+N (230/240 V)2For networks 230/240 V AC ⇒ two poles circuit-breaker (phase + neutral)For networks 400/415 V AC ⇒ four poles circuit-breaker (load side circuit branched between onephase <strong>and</strong> the neutral)3Only for curve B126 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3.2 Discrimination tables3 <strong>Protection</strong> coordinationS800 N-SS800 N-SCD36-50 36-5025 32 40 50 63 80 100 125 25 32 40 50 63 80 100 1250,4 3 0,55 1,2 3 T T T T 1,3 4,1 T T T T T T0,43 0,75 1,3 2,1 3,9 T T 0,8 1,6 3 5,4 T T T T0,55 1,1 1,5 2,5 3,6 5,5 0,6 1,3 2 3,2 3,9 T T T0,45 1 1,3 1,9 2,8 4,2 0,5 1,2 1,65 2,6 3,1 T T T0,75 1,1 1,6 2,3 3,6 0,9 1,4 1,8 2,6 5 T T0,9 1,4 1,9 3,3 1,3 1,6 2,2 4,2 5,4 T1,2 1,6 2,7 1,5 1,9 3,5 4,5 T1 1,5 2,5 1,8 2,8 4,2 5,51,4 2,1 1,7 2,7 4 50,4 3 0,55 1,2 3 6,6 T T T 1,3 4,1 T T T T T T0,43 0,75 1,3 2,1 3,9 6,6 T 0,8 1,6 3 5,4 7,6 T T T0,55 1,1 1,5 2,5 3,6 5,5 0,6 1,3 2 3,2 3,9 8 T T0,45 1 1,3 1,9 2,8 4,2 0,5 1,2 1,65 2,6 3,1 6,2 8,6 T0,75 1,1 1,6 2,3 3,6 0,9 1,4 1,8 2,6 5 6,3 8,80,9 1,4 1,9 3,3 1,3 1,6 2,2 4,2 5,4 7,61,2 1,6 2,7 1,5 1,9 3,5 4,5 6,61 1,5 2,5 1,8 2,8 4,2 5,51,4 2,1 1,7 2,7 4 50,4 3 0,55 1,2 3 6,6 T T T 1,3 4,1 T T T T T T0,43 0,75 1,3 2,1 3,9 6,6 T 0,8 1,6 3 5,4 7,6 T T T0,55 1,1 1,5 2,5 3,6 5,5 0,6 1,3 2 3,2 3,9 8 T T0,45 1 1,3 1,9 2,8 4,2 0,5 1,2 1,65 2,6 3,1 6,2 8,6 T0,75 1,1 1,6 2,3 3,6 0,9 1,4 1,8 2,6 5 6,3 8,80,9 1,4 1,9 3,3 1,3 1,6 2,2 4,2 5,4 7,61,2 1,6 2,7 1,5 1,9 3,5 4,5 6,61 1,5 2,5 1,8 2,8 4,2 5,51,4 2,1 1,7 2,7 4 5<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 127


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB @ 415 V 4p - SN @ 240 VSupply s. XT1 160VersionReleaseB, C, N, S, HLoad s. Char. I cu [kA] I n [A] 16 20 25 32 40 50 63 80 100 125 2 125 160 2 160 16 20 25 32SN201L B, C 6SN201 B, C, D 10SN201M B, C 10Supply side circuit-breaker 4P (load side circuit branched between one phase <strong>and</strong> the neutral)Load side circuit-breaker 1P+N (230/240)1Value valid only for magnetic only supply side circuit-breaker2Value valid also with neutral 50%TM≤4 T T T T T T T T T T T T T T T T T6 T T T T T T T T T T T T T T T T T10 3 3 3 4,5 T T T T T T T 3 1 3 316 3 4,5 5 T T T T T T 3 120 3 5 T T T T T T 3 125 5 T T T T T T32 T T T T T T40 T T T T T≤4 T T T T T T T T T T T T T T T T T6 6 6 6 6 6 6 T T T T T T T T T T T10 3 3 3 4,5 7,5 8,5 T T T T T 3 1 3 316 3 4,5 5 7,5 T T T T T 3 120 3 5 6 T T T T T 3 125 5 6 T T T T T32 6 7,5 T T T T40 7,5 T T T T≤4 T T T T T T T T T T T T T T T T T6 6 6 6 6 6 6 12 T T T T T T T T T T10 3 3 3 4,5 7,5 8,5 T T T T T 3 1 3 316 3 4,5 5 7,5 T T T T T 3 120 3 5 6 T T T T T 3 125 5 6 T T T T T32 6 T T T T T40 T T T T T128 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3.2 Discrimination tables3 <strong>Protection</strong> coordinationXT2 160 XT3 250N, S, H, L, V N, STM EL TM40 50 63 80 100 125 2 125 160 2 160 10 25 63 100 160 63 80 100 125 2 125 160 2 160 200 2 200 250 2 250T T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T3 4,5 T T T T T T T T T T T T T T T T T T T T T T3 4,5 5 T T T T T T T T T 5 T T T T T T T T T T3 5 T T T T T T T T T 5 T T T T T T T T T T3 1 5 T T T T T T T T T 5 T T T T T T T T T T3 1 T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T3 4,5 7,5 8,5 T T T T T T T T T 7,5 8,5 T T T T T T T T T3 4,5 5 7,5 T 7,5 T T T T T T 5 7,5 T 7,5 T T T T T T T3 5 6 T 6 T T T T T T 5 6 T 6 T T T T T T T3 1 5 6 T 6 T T T T T T 5 6 T 6 T T T T T T T3 1 6 7,5 6 T T T T T T 6 7,5 6 T T T T T T T6 1 7,5 T T T T T 6 1 7,5 T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T3 4,5 7,5 8,5 T T T T T T T T T 7,5 8,5 T T T T T T T T T3 4,5 5 7,5 T 7,5 T T T T T T 5 7,5 T 7,5 T T T T T T T3 5 6 T 6 T T T T T T 5 6 T 6 T T T T T T T3 1 5 6 T 6 T T T T T T 5 6 T 6 T T T T T T T3 1 6 7,5 6 T T T T T T 6 7,5 6 T T T T T T T6 1 7,5 T T T T T 6 1 7,5 T T T T T T T<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 129


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCB - S2.. B @ 415 VLoad s.Supply s. S290 S800N-SChar. D BBI cu [kA] 15 36-5010 15 25 I n [A] 80 100 40 50 63 80 100 125- - - ≤2- - - 3- - - 4S200 S200M S200P 6 10,5 T 0,4 0,5 0,7 1 1,5 2,6S200 S200M S200P 8 10,5 T 0,4 0,6 0,7 1 1,4S200 S200M S200P 10 5 8 0,4 0,6 0,7 1 1,4S200 S200M S200P 13 4,5 7 0,5 0,7 0,9 1,3S200 S200M S200P 16 4,5 7 0,7 0,9 1,3S200 S200M S200P 20 3,5 5 0,9 1,3S200 S200M S200P 25 3,5 5 0,9 1,3S200 S200M-S200P - 32 4,5 0,8 1,1S200 S200M-S200P - 40 0,8 1,1S200 S200M-S200P - 50 1S200 S200M-S200P - 63 0,9MCB - S2.. C @ 415 VLoad s.Supply s. S290 S800N-SChar. D BCI cu [kA] 15 36-5010 15 25 I n [A] 80 100 32 40 50 63 80 100 125S200 S200M S200P ≤2 T T 0,7 1,3 T T T T TS200 S200M S200P 3 T T 0,6 0,7 1,1 2,6 8,8 TS200 S200M S200P 4 T T 0,6 0,7 1 1,7 3,1 7S200 S200M S200P 6 10,5 T 0,4 0,5 0,7 1 1,5 2,6S200 S200M S200P 8 10,5 T 0,4 0,6 0,7 1 1,4S200 S200M S200P 10 5 8 0,4 0,6 0,7 1 1,4S200 S200M S200P 13 4,5 7 0,5 0,7 0,9 1,3S200 S200M S200P 16 4,5 7 0,7 0,9 1,3S200 S200M S200P 20 3,5 5 0,9 1,3S200 S200M S200P 25 3,5 5 0,9 1,3S200 S200M-S200P - 32 4,5 0,8 1,1S200 S200M-S200P - 40 0,8 1,1S200 S200M-S200P - 50 1S200 S200M-S200P - 63 0,9130 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3.2 Discrimination tables3 <strong>Protection</strong> coordinationS800N-SS800N-SCD36-50 36-5040 50 63 80 100 125 25 32 40 50 63 80 100 1250,4 0,5 0,7 1 1,5 2,6 0,5 1 1,2 2 2,8 9,9 21,3 T0,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,40,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,40,5 0,7 0,9 1,3 0,4 0,6 0,8 1,1 1,4 2,5 3,3 5,60,7 0,9 1,3 0,6 0,8 1,1 1,4 2,5 3,3 5,60,9 1,3 0,8 1,1 1,3 2,3 3 4,70,9 1,3 0,8 1,1 1,3 2,3 3 4,70,8 1,1 0,9 1,1 1,9 2,4 3,70,8 1,1 1,1 1,9 2,4 3,71 1,5 1,9 2,30,9 1,7 2,3S800N-SS800N-SCD36-50 36-5032 40 50 63 80 100 125 25 32 40 50 63 80 100 1250,7 1,3 T T T T T T T T T T T T T0,6 0,7 1,1 2,6 8,8 T 0,7 2,2 4,4 T T T T T0,6 0,7 1 1,7 3,1 7 0,7 1,3 2,2 4,4 7,7 T T T0,4 0,5 0,7 1 1,5 2,6 0,5 1 1,2 2 2,8 9,9 22 T0,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,40,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,40,5 0,7 0,9 1,3 0,4 0,6 0,8 1,1 1,4 2,5 3,3 5,60,7 0,9 1,3 0,6 0,8 1,1 1,4 2,5 3,3 5,60,9 1,3 0,8 1,1 1,3 2,3 3 4,70,9 1,3 0,8 1,1 1,3 2,3 3 4,70,8 1,1 0,9 1,1 1,9 2,4 3,70,8 1,1 1,1 1,9 2,4 3,71 1,5 1,9 2,30,9 1,7 2,3<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 131


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCB - S2.. D @ 415 VLoads.Supply s. S290 S800N-SChar. D BDI cu [kA] 15 36-5010 15 25 I n [A] 80 100 32 40 50 63 80 100 125S200 - S200P ≤2 T T 0,5 0,7 2,1 T T T TS200 - S200P 3 T T 0,5 0,7 1,2 2,5 8,6 TS200 - S200P 4 T T 0,4 0,7 1 1,7 3 7,7S200 - S200P 6 10,5 T 0,6 0,8 1,2 2 3,6S200 - S200P 8 10,5 T 0,7 0,9 1,3 2S200 - S200P 10 5 8 0,9 1,3 2S200 - S200P 13 3 5 1 1,5S200 - S200P 16 3 5 1,5S200 - S200P 20 3 5S200 - S200P 25 4S200 S200P - 32S200 S200P - 40S200 S200P - 50S200 S200P - 63MCB - S2.. K @ 415 VLoads.Supply s. S290 S800N-SChar. D BKI cu [kA] 15 36-5010 15 25 I n [A] 80 100 32 40 50 63 80 100 125S200 - S200P ≤2 T T 0,5 0,7 2,1 T T T TS200 - S200P 3 T T 0,5 0,7 1,2 2,5 8,6 TS200 - S200P 4 T T 0,4 0,7 1 1,7 3 7,7S200 - S200P 6 10,5 T 0,6 0,8 1,2 2 3,6S200 - S200P 8 10,5 T 0,7 0,9 1,3 2S200 - S200P 10 5 8 0,9 1,3 2- - S200P 13 3 5 1 1,5S200 - S200P 16 3 5 1,5S200 - S200P 20 3 5S200 - S200P 25 4S200 S200P - 32S200 S200P - 40S200 S200P - 50S200 S200P - 63132 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3.2 Discrimination tables3 <strong>Protection</strong> coordinationS800N-SCS800N-S36-50 36-5032 40 50 63 80 100 125 25 32 40 50 63 80 100 1250,5 0,7 2,1 T T T T 2,3 T T T T T T T0,5 0,7 1,2 2,5 8,6 T 0,7 1,3 4,4 T T T T T0,4 0,7 1 1,7 3 7,7 0,7 1 2,2 4,4 7,7 T T T0,6 0,8 1,2 2 3,6 0,6 0,8 1,5 2,5 3,6 12,1 24,2 T0,7 0,9 1,3 2 0,5 0,7 1,1 1,5 2 4 5,5 9,90,9 1,3 2 0,5 0,7 1,1 1,5 2 4 5,5 9,91 1,5 0,6 0,9 1,2 1,5 2,6 3,4 5,21,5 0,9 1,2 1,5 2,6 3,4 5,2D0,9 1,1 1,8 2,2 3,21,1 1,8 2,2 3,21,7 2 2,91,9 2,62,2S800N-SCS800N-S36-50 36-5032 40 50 63 80 100 125 25 32 40 50 63 80 100 1250,5 0,7 2,1 T T T T 2,3 T T T T T T T0,5 0,7 1,2 2,5 8,6 T 0,7 1,3 4,4 T T T T T0,4 0,7 1 1,7 3 7,7 0,7 1 2,2 4,4 7,7 T T T0,6 0,8 1,2 2 3,6 0,6 0,8 1,5 2,5 3,6 12,1 24,2 T0,7 0,9 1,3 2 0,5 0,7 1,1 1,5 2 4 5,5 9,90,9 1,3 2 0,5 0,7 1,1 1,5 2 4 5,5 9,91 1,5 0,6 0,9 1,2 1,5 2,6 3,4 5,21,5 0,9 1,2 1,5 2,6 3,4 5,2D0,9 1,1 1,8 2,2 3,21,1 1,8 2,2 3,21,7 2 2,91,9 2,62,2<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 133


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCB - S2.. Z @ 415 VLoad s.Supply s. S290 S800N-SChar. D BZI cu [kA] 15 36-5010 15 25 I n [A] 80 100 32 40 50 63 80 100 125S200 - S200P ≤2 T T 0,7 1,3 T T T T TS200 - S200P 3 T T 0,6 0,7 1,1 2,6 8,8 TS200 - S200P 4 T T 0,6 0,7 1 1,7 3,1 7S200 - S200P 6 10,5 T 0,4 0,5 0,7 1 1,5 2,6S200 - S200P 8 10,5 T 0,4 0,6 0,7 1 1,4S200 - S200P 10 5 8 0,4 0,6 0,7 1 1,4- - S200P 13 4,5 7 0,7 0,9 1,3S200 - S200P 16 4,5 7 0,7 0,9 1,3S200 - S200P 20 3,5 5 0,9 1,3S200 - S200P 25 3,5 5 0,9 1,3S200 S200P - 32 3 4,5 0,8 1,1S200 S200P - 40 3 4,5 0,8 1,1S200 S200P - 50 3 1S200 S200P - 63 0,9134 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3.2 Discrimination tables3 <strong>Protection</strong> coordinationS800N-SS800N-SCD36-50 36-5032 40 50 63 80 100 125 25 32 40 50 63 80 100 1250,7 1,3 T T T T T T T T T T T T T0,6 0,7 1,1 2,6 8,8 T 0,7 2,2 4,4 T T T T T0,6 0,7 1 1,7 3,1 7 0,7 1,3 2,2 4,4 7,7 T T T0,4 0,5 0,7 1 1,5 2,6 0,5 1 1,2 2 2,8 9,9 22 T0,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,40,4 0,6 0,7 1 1,4 0,4 0,6 0,8 1,1 1,4 2,8 3,9 7,40,7 0,9 1,3 0,6 0,8 1,1 1,4 2,5 3,3 5,60,7 0,9 1,3 0,6 0,8 1,1 1,4 2,5 3,3 5,60,9 1,3 0,8 1,1 1,3 2,3 3 4,70,9 1,3 0,8 1,1 1,3 2,3 3 4,70,8 1,1 0,9 1,1 1,9 2,4 3,70,8 1,1 1,1 1,9 2,4 3,71 1,5 1,9 2,30,9 1,7 2,3<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 135


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - S800 @ 415 VSupply s. XT1 160 XT3 250Version B, C, N, S, H N, SRelease TM TMLoad s. Char. Icu [kA] In [A] 25 32 40 50 63 80 100 125 160 63 80 100 125 160 200 250S800NS800SBCDBCDK365010 4,5 4,5 4,5 4,5 8 10 20 1 25 1 T 8 10 20 1 25 1 T T T13 4,5 4,5 4,5 7,5 10 15 25 1 T 7,5 10 15 25 1 T T T16 4,5 4,5 7,5 10 15 25 1 T 7,5 10 15 25 1 T T T20 4,5 7,5 10 15 25 1 T 7,5 10 15 25 1 T T T25 6 10 15 20 1 T 6 10 15 20 1 T T T32 7,5 10 20 1 T 7,5 10 20 1 T T T40 10 20 1 T 10 20 1 T T T50 15 T 15 T T T63 T T T T80 T 2 T T100 T125 T 210 4,5 4,5 4,5 4,5 8 10 20 1 25 1 T 8 10 20 1 25 1 36 36 T13 4,5 4,5 4,5 7,5 10 15 25 1 T 7,5 10 15 25 1 36 36 T16 4,5 4,5 7,5 10 15 25 1 T 7,5 10 15 25 1 36 36 T20 4,5 7,5 10 15 25 1 T 7,5 10 15 25 1 36 36 T25 6 10 15 20 1 T 6 10 15 20 1 36 36 T32 7,5 10 20 1 T 7,5 10 20 1 36 36 T40 10 20 1 T 10 20 1 36 36 T50 15 T 15 36 36 T63 T 36 36 T80 T 2 36 T100 T125 T 21Select the lowest value between what is indicated <strong>and</strong> the breaking capacity of the supply sidecircuit-breaker2Value valid only with S800N/S B or C characteristic136 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB-S800 @ 415 VSupply s. XT4 T4 - T5VersionN, S, H, L, VRelease TM EL ELLoad s. Carat. I cu [kA] In [A] 20 25 32 40 50 63 80 100 125 160 200÷250 40÷63 100÷250 100÷63010 6,5 6,5 6,5 6,5 6,5 6,5 11 T T T T 6,5 T T13 6,5 5 6,5 6,5 6,5 6,5 11 T T T T 6,5 T T16 5 6,5 6,5 6,5 6,5 11 T T T T 6,5 T T20 6,5 1 6,5 6,5 6,5 11 T T T T 6,5 T T25 6,5 6,5 6,5 11 T T T T 6,5 T TB 36-5032 6,5 6,5 8 T T T T 6,5 T T40 5 1 6,5 T T T T T T50 5 1 7,5 T T T T T63 5 1 7 T T T T80 T 1 T T T 2 T 2100 T 1 T T 2 T 2125T 2 3 T 2 310 6,5 6,5 6,5 6,5 6,5 6,5 11 T T T T 6,5 T T13 6,5 5 6,5 6,5 6,5 6,5 11 T T T T 6,5 T T16 5 1 5 6,5 6,5 6,5 6,5 11 T T T T 6,5 T T20 6,5 1 6,5 6,5 6,5 11 T T T T 6,5 T T25 6,5 6,5 6,5 11 T T T T 6,5 T TC 36-5032 6,5 6,5 8 T T T T 6,5 T T40 6,5 T T T T T T50 5 1 7,5 T T T T T63 6,5 1 7 T T T T80 6,5 1 6,5 T T 2 T 2100 5 1 6,5 T 2 T 2S800N/SD 36-50K 36-50125T 2 3 T 2 310 6,5 6,5 6,5 6,5 6,5 6,5 11 T T T T 6,5 T T13 6,5 5 6,5 6,5 6,5 6,5 11 T T T T 6,5 T T16 6,5 6,5 6,5 11 T T T T 6,5 T T20 11 T T T T T T25 11 T T T T T T32 T T T T T T40 T T T T T50 T T T T63 T T T80 T 2 T 2100 T 2 T 2125T 2 3 T 2 310 6,5 1 6,5 6,5 6,5 6,5 11 T T T T 6,5 T T13 5 1 5 1 6,5 6,5 6,5 11 T T T T 6,5 T T16 6,5 6,5 11 T T T T 6,5 T T20 6,5 6,5 11 T T T T 6,5 T T25 6,5 1 11 1 T T T T T T32 8 1 T 1 T T T T T40 6,5 1 T 1 T 1 T T T T50 7,5 1 T 1 T 1 T T T63 7 1 T 1 T 1 T T80 T 1 T 1 T 2 T 2100 7 1 T 2 T 2125 6,5 1T 2 3 T 2 31Value valid only for magnetic only supply side circuit-breaker (for In = 50 A, please consider MA52circuit-breaker)2For T4 In = 100 A, value valid only for magnetic only supply3For T4 In = 160 A, value valid only for magnetic only supply<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 137


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - S2.. B @ 415 VSupply s. XT2 XT1 - XT2 XT1 - XT2 - XT3 XT3VersionB, C, N, S, H, L, VChar. I cu [kA] Release TM10 15 25 In [A] 12,5 16 20 25 32 40 50 63 80 100 125 160 200 250S200 S200M S200P 6 5,5 1 5,5 5,5 5,5 5,5 5,5 5,5 10,5 T T T T T TS200 S200M S200P 10 3 1 3 3 3 4,5 7,5 8,5 17 T T T TS200 S200M S200P 13 3 1 3 3 4,5 7,5 7,5 12 20 T T TS200 S200M S200P 16 3 1 3 4,5 5 7,5 12 20 T T TS200 S200M S200P 20 3 1 3 5 6 10 15 T T TS200 S200M S200P 25 3 1 5 6 10 15 T T TLoad s. B S200 S200M-S200P - 32 3 1 6 7,5 12 T T TS200 S200M-S200P - 40 5,5 1 7,5 12 T T TS200 S200M-S200P - 50 3 1 5 2 7,5 10,5 T TS200 S200M-S200P - 63 5 2 6 3 10,5 T T- - - 80- - - 100- - - 1251Value valid only for XT2 magnetic only supply side circuit-breaker2Value valid only for XT2-XT3 magnetic only supply side circuit-breaker3Value valid only for XT3 magnetic only supply side circuit-breaker4Value valid only for XT4 magnetic only supply side circuit-breaker138 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.2 Discrimination tablesXT4 T5 XT2 XT4 T4 T5B, C, N, S, H, L, VTMEL20 25 32 40 50 63 80 100 125 160 200 225 250 320÷500 25 63 100 160 40 63 100, 160 250 320 320÷6307,5 4 7,5 7,5 7,5 7,5 10,5 T T T T T T T T T T T T T T T T T T5 4 5 5 5 6,5 7,5 9 T T T T T T T T T T T T T T T T T5 5 5 6,5 7,5 8 T T T T T T T T T T T T T T T T T3 5 5 6,5 7,5 8 T T T T T T T T T T T T T T T T5 5 5 7,5 T T T T T T T T T T T T T T T T5 5 7,5 T T T T T T T T T T T T T T T5 4 5 7,5 T T T T T T T T T T T T T T T6,5 T T T T T T T T T T T T T5 4 T T T T T T T 10,5 10,5 T T T TT 4 T 4 T T T T T 10,5 T T T T<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 139


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - S2.. C @ 415 VLoad s.Supply s. XT2 XT1 - XT2 XT1 - XT2 - XT3 XT3VersionB, C, N, S, H, L, VChar. I cu [kA] Release TMC10 15 25 I n [A] 12,5 16 20 25 32 40 50 63 80 100 125 160 200 250S200 S200M S200P ≤2 T T T T T T T T T T T T T TS200 S200M S200P 3 T T T T T T T T T T T T T TS200 S200M S200P 4 T T T T T T T T T T T T T TS200 S200M S200P 6 5,5 1 5,5 5,5 5,5 5,5 5,5 5,5 10,5 T T T T T TS200 S200M S200P 8 5,5 5,5 5,5 5,5 5,5 10,5 T T T T T TS200 S200M S200P 10 3 1 3 3 3 4,5 7,5 8,5 17 T T T TS200 S200M S200P 13 3 1 3 3 4,5 7,5 7,5 12 20 T T TS200 S200M S200P 16 3 1 3 4,5 5 7,5 12 20 T T TS200 S200M S200P 20 3 1 3 5 6 10 15 T T TS200 S200M S200P 25 3 1 5 6 10 15 T T TS200 S200M-S200P - 32 3 1 6 7,5 12 T T TS200 S200M-S200P - 40 5,5 1 7,5 12 T T TS200 S200M-S200P - 50 3 1 5 2 7,5 10,5 T TS200 S200M-S200P - 63 5 2 6 3 10,5 T T- S290 - 80 10 15- S290 - 100 7,5 3 15- S290 - 125 7,5 31Value valid only for XT2 magnetic only supply side circuit-breaker2Value valid only for XT2-XT3 magnetic only supply side circuit-breaker3Value valid only for XT3 magnetic only supply side circuit-breaker4Value valid only for XT4 magnetic only supply side circuit-breaker5Value valid only for XT4 In160 supply side circuit-breaker140 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.2 Discrimination tablesTMXT4 T5 XT2 XT4 T4 T5B, C, N, S, H, L, V20 25 32 40 50 63 80 100 125 160 200 225 250 320÷500 10 25 63 100 160 40 63 100, 160 250 320 320÷630T T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T T7,5 7,5 7,5 7,5 7,5 10,5 T T T T T T T T T T T T T T T T T T7,5 7,5 7,5 7,5 7,5 10,5 T T T T T T T T T T T T T T T T T T5 5 5 5 6,5 7,5 9 T T T T T T T T T T T T T T T T T5 5 5 6,5 7,5 8 T T T T T T T T T T T T T T T T T3 5 5 6,5 5 8 T T T T T T T T T T T T T T T T5 5 5 7,5 T T T T T T T T T T T T T T T T5 5 7,5 T T T T T T T T T T T T T T T5 4 5 7,5 T T T T T T T T T T T T T T T6,5 T T T T T T T T T T T T T5 4 T T T T T T T 10,5 10,5 T T T TT 4 T 4 T T T T T 10,5 T T T T5 11 T T T 4 T 5 T T T5 4 8 T T T 4 12 4 T T T8 4 12 4 12 T 4 T T TEL<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 141


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - S2.. D @ 415 VLoad s.Supply s. XT2 XT1 - XT2 XT1 - XT2 - XT3 XT3VersionB, C, N, S, H, L, VChar. I cu [kA] Release TM10 15 25 I n [A] 12,5 16 20 25 32 40 50 63 80 100 125 160 200 250S200 S200M S200P ≤2 T T T T T T T T T T T T T TS200 S200M S200P 3 T T T T T T T T T T T T T TS200 S200M S200P 4 T T T T T T T T T T T T T TS200 S200M S200P 6 5,5 1 5,5 5,5 5,5 5,5 5,5 5,5 10,5 T T T T T TS200 S200M S200P 8 5,5 5,5 5,5 5,5 5,5 10,5 12 T T T T TS200 S200M S200P 10 3 1 3 3 3 3 5 8,5 17 T T T TS200 S200M S200P 13 2 1 2 2 3 5 8 13,5 T T TS200 S200M S200P 16 2 1 2 2 3 5 8 13,5 T T TD S200 S200M S200P 20 2 1 2 3 4,5 6,5 11 T T TS200 S200M S200P 25 2 1 2,5 4 6 9,5 T T TS200 S200M-S200P - 32 4 6 9,5 T T TS200 S200M-S200P - 40 3 1 5 2 8 T T TS200 S200M-S200P - 50 2 1 3 2 5 9,5 T TS200 S200M-S200P - 63 3 2 5 3 9,5 T T- S290 - 80 4 3 10 15- S290 - 100 4 3 7,5 3 15- - - 1251Value valid only for XT2 magnetic only supply side circuit-breaker2Value valid only for XT2-XT3 magnetic only supply side circuit-breaker3Value valid only for XT3 magnetic only supply side circuit-breaker4Value valid only for XT4 magnetic only supply side circuit-breaker5Value valid only for XT4 In160 supply side circuit-breaker142 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.2 Discrimination tablesTMXT4 T5 XT2 XT4 T4 T5B, C, N, S, H, L, V20 25 32 40 50 63 80 100 125 160 200 225 250 320÷500 10 25 63 100 160 40 63 100, 160 250 320 320÷630T T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T T7,5 7,5 7,5 7,5 7,5 7,5 T T T T T T T T T T T T T T T T T T7,5 7,5 7,5 7,5 7,5 7,5 T T T T T T T T T T T T T T T T T T5 4 5 5 5 5 6 9 T T T T T T T T T T T T T T T T T5 4 5 4 5 5,5 T T T T T T T T T T T T T T T T5 4 4 5 5,5 T T T T T T T T T T T T T T T T5 4 4 4 5 5 T T T T T T T T T T T T T T T T4 4 4 4 4,5 T T T T T T T T T T T T T T T5 4 4,5 4 T T T T T T T T T T T T T T T4,5 4 T T T T T T T T T T T T TT 4 T T T T T T 9,5 9,5 T T T TT 4 T 4 T T T T 9,5 T T T T5 11 T T T 4 T 5 T T T8 T T T 4 12 5 T T TEL<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 143


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - S2.. K @ 415 VLoad s.Supply s. XT2 XT1 - XT2 XT1 - XT2 - XT3 XT3VersionB, C, N, S, H, L, VChar. I cu [kA] Release TMK10 15 25 I n [A] 12,5 16 20 25 32 40 50 63 80 100 125 160 200 250S200 S200M S200P ≤2 T T T T T T T T T T T T T TS200 S200M S200P 3 T T T T T T T T T T T T T TS200 S200M S200P 4 T T T T T T T T T T T T T TS200 S200M S200P 6 5,5 1 5,5 5,5 5,5 5,5 5,5 5,5 10,5 T T T T T TS200 S200M S200P 8 5,5 5,5 5,5 5,5 5,5 10,5 12 T T T T TS200 S200M S200P 10 3 1 3 3 3 3 5 8,5 17 T T T TS200 S200M S200P 13 2 1 3 3 5 7,5 10 13,5 T T TS200 S200M S200P 16 2 1 3 3 4,5 7,5 10 13,5 T T TS200 S200M S200P 20 2 1 3 3,5 5,5 6,5 11 T T TS200 S200M S200P 25 2 1 3,5 5,5 6 9,5 T T TS200 S200M-S200P - 32 4,5 6 9,5 T T TS200 S200M-S200P - 40 3 1 5 8 T T TS200 S200M-S200P - 50 2 1 3 2 6 9,5 T TS200 S200M-S200P - 63 3 2 5 3 9,5 T T- S290 - 80 4 3 10 15- S290 - 100 4 3 7,5 3 15- - - 1251Value valid only for XT2 magnetic only supply side circuit-breaker2Value valid only for XT2-XT3 magnetic only supply side circuit-breaker3Value valid only for XT3 magnetic only supply side circuit-breaker4Value valid only for XT4 magnetic only supply side circuit-breaker5Value valid only for XT4 In160 supply side circuit-breaker144 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.2 Discrimination tablesTMXT4 T5 XT2 XT4 T4 T5B, C, N, S, H, L, V20 25 32 40 50 63 80 100 125 160 200 225 250 320÷500 10 25 63 100 160 40 63 100, 160 250 320 320÷630T T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T T7,5 7,5 7,5 7,5 7,5 8 T T T T T T T T T T T T T T T T T T7,5 4 7,5 7,5 7,5 7,5 8 T T T T T T T T T T T T T T T T T T5 4 5 5 5 7,5 9 T T T T T T T T T T T T T T T T T5 4 5 5 5 7,5 8 T T T T T T T T T T T T T T T T T5 4 5 4 5 6 8 T T T T T T T T T T T T T T T T5 6 6 T T T T T T T T T T T T T T T T5 4 5,5 4 6 4 T T T T T T T T T T T T T T T5 4 5 4 6 4 T 4 T T T T T T T T T T T T T T5 4 5,5 4 T 4 T 4 T T T T T T T T T T T5 4 T 4 T 4 T 4 T T T T 9,5 9,5 T T T TT 4 T 4 T 4 T T T T 9,5 T T T T5 11 T T T 4 T 5 T T T5 4 8 T T T 4 12 5 T T TEL<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 145


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - S2.. Z @ 415 VLoad s.Supply s. XT2 XT1 - XT2 XT1 - XT2 - XT3 XT3VersionB, C, N, S, H, L, VChar. I cu [kA] Release TMZ10 15 25 I n [A] 12,5 16 20 25 32 40 50 63 80 100 125 160 200 250S200 S200M S200P ≤2 T T T T T T T T T T T T T TS200 S200M S200P 3 T T T T T T T T T T T T T TS200 S200M S200P 4 T T T T T T T T T T T T T TS200 S200M S200P 6 5,5 1 5,5 5,5 5,5 5,5 5,5 5,5 10,5 T T T T T TS200 S200M S200P 8 5,5 5,5 5,5 5,5 5,5 10,5 T T T T T TS200 S200M S200P 10 3 1 3 3 3 4,5 8 8,5 17 T T T TS200 S200M S200P 16 3 1 3 4,5 5 7,5 12 20 T T TS200 S200M S200P 20 3 1 3 5 6 10 15 T T TS200 S200M S200P 25 3 1 5 6 10 15 T T TS200S200S200S200S200M-S200PS200M-S200PS200M-S200PS200M-S200P- - - 80- - - 100- - - 125- 32 3 1 6 7,5 12 T T T- 40 5,5 1 7,5 12 T T T- 50 4 1 5 2 7,5 10,5 T T- 63 5 2 6 3 10,5 T T1Value valid only for XT2 magnetic only supply side circuit-breaker2Value valid only for XT2-XT3 magnetic only supply side circuit-breaker3Value valid only for XT3 magnetic only supply side circuit-breaker4Value valid only for XT4 magnetic only supply side circuit-breaker146 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.2 Discrimination tablesXT4 T5 XT2 XT4 T4 T5B, C, N, S, H, L, VTMEL20 25 32 40 50 63 80 100 125 160 200 225 250 320÷500 10 25 63 100 160 40 63 100, 160 250 320 320÷630T T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T TT T T T T T T T T T T T T T T T T T T T T T T T T7,5 7,5 7,5 7,5 7,5 7,5 T T T T T T T T T T T T T T T T T T7,5 7,5 7,5 7,5 7,5 7,5 T T T T T T T T T T T T T T T T T T5 7,5 5 5 6,5 6,5 9 T T T T T T T T T T T T T T T T T7,5 4 4,5 5 6,5 6,5 8 T T T T T T T T T T T T T T T T5 5 5 6,5 T T T T T T T T T T T T T T T T5 5 6,5 T T T T T T T T T T T T T T T5 5 6,5 T T T T T T T T T T T T T T T5 4 5 T T T T T T T T T T T T T3,5 4 T T T T T T T 10,5 10,5 T T T TT 4 T T T T T T 10,5 T T T T<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 147


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - XT1 @ 415 VVersionSupply s. XT1 XT2 XT3 XT4B, CN, SHN, S, H, L, V N, S N, S, H, L, VRelease TM TM,M EL TM, M TMSize 160 160 250 160 250Load s. I n [A] 160 160 25 63 100 160 160 200 250 63 80 100 125 160 200 225 250XT1BTM 16016 3 3 3 3 3 3 4 5 10 10 10 10 10 10 10 10B, C 20 3 3 3 3 3 3 4 5 10 10 10 10 10 10 10 10B, C, NB, C, NS, H25 3 3 3 3 3 3 4 5 10 10 10 10 10 10 10 1032 3 3 3 3 3 4 5 10 10 10 10 10 10 1040 3 3 3 3 3 4 5 10 10 10 10 10 1050 3 3 3 3 3 4 5 10 1 10 10 10 10 1063 3 3 3 3 4 5 10 1 10 10 10 1080 3 4 5 10 10 10 10100 5 10 1 10 10 10125 10 1 10 1 101601Value valid only for magnetic only supply side circuit-breaker2Value valid only for PR232/P, PR331/P <strong>and</strong> PR332/P trip units3Available only with Iu ≤ 1250A148 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.2 Discrimination tablesXT4 T4 T5 T6 T7N, S, H, L, VN, S,H,L, VN, S, H, L, V N, S, H, L S, H, L, V 3EL TM EL TM, M EL EL250 320 400 630 400 630 630 800 630 800 1000 800 1000 1250 1600100 160 250 320 320 400 500 320 400 630 630 800 630 800 1000 800 2 1000 2 1250 2 1600 210 10 10 10 36 36 36 36 36 36 T T T T T T T T T10 10 10 10 36 36 36 36 36 36 T T T T T T T T T10 10 10 10 36 36 36 36 36 36 T T T T T T T T T10 10 10 10 36 36 36 36 36 36 T T T T T T T T T10 10 10 10 36 36 36 36 36 36 T T T T T T T T T10 10 10 10 36 36 36 36 36 36 T T T T T T T T T10 10 10 10 36 36 36 36 36 36 T T T T T T T T T10 10 10 36 36 36 36 36 36 T T T T T T T T T10 10 10 36 36 36 36 36 36 T T T T T T T T T10 10 36 36 36 36 36 36 T T T T T T T T T10 10 36 36 36 36 36 36 T T T T T T T T T<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 149


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - XT2 @ 415 VVersionSupply s. XT1 XT2 XT3 XT4B, CN, SHN, S, H, L, V N, S N, S, H, L, VRelease TM TM,M EL TM, M TM, MSize 160 160 250 160 250Load s. In [A] 160 160 25 63 100 160 160 200 250 50 63 80 100 125 160 200 225 250XT2NSHLVTM 160EL 1601,6-2,5 T T T T T T T T T 85 85 85 85 85 85 85 85 853,2 T T T T T T T T T 85 85 85 85 85 85 85 85 854-5 T T T T T T T T T 85 85 85 85 85 85 85 85 856,3 10 10 10 10 10 10 10 15 40 85 85 85 85 85 85 85 85 858 10 10 10 10 10 10 10 15 40 85 85 85 85 85 85 85 85 8510 10 10 10 10 10 10 10 15 40 85 85 85 85 85 85 85 85 8512,5 3 3 3 3 3 3 4 5 85 85 85 85 85 85 85 85 8516 3 3 3 3 3 3 4 5 70 70 70 70 70 70 7020 3 3 3 3 3 3 4 5 55 1 55 55 55 55 55 5525 3 3 3 3 3 3 4 5 50 1 50 50 50 50 50 5032 3 3 3 3 3 4 5 50 1 50 50 50 50 50 5040 3 3 3 3 3 4 5 50 1 50 1 50 50 50 50 5050 3 3 3 3 3 4 5 50 1 50 1 50 50 50 50 5063 3 3 3 3 4 5 50 1 50 1 50 1 50 50 50 5080 3 3 1 4 5 50 1 50 1 50 1 50 50 50100 4 5 50 1 50 1 50 1 50 1 50125 50 1 50 1 50 1 50160 50 1 50 1 5010 3 4 50 50 50 50 50 50 50 50 5025 3 4 50 50 50 50 50 50 50 5063 3 4 50 50 50 50100 3 4 50160 3 4 501Value valid only for magnetic only supply side circuit-breaker2Value valid only for PR232/P, PR331/P <strong>and</strong> PR332/P trip units3Available only with Iu ≤ 1250A150 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.2 Discrimination tablesXT4 T4 T5 T6 T7N, S, H, L, VN,S,H,L, VN, S, H, L, V N, S, H, L S, H, L, V 3EL EL TM EL TM, M EL EL160 250 320 400 630 400 630 630 800 630 800 1000 800 1000 1250 160040 63 100 160 250 320 320 400 500 320 400 630 630 800 630 800 1000 800 2 1000 2 1250 2 1600 285 85 85 85 85 85 T T T T T T T T T T T T T T T85 85 85 85 85 85 T T T T T T T T T T T T T T T85 85 85 85 85 85 T T T T T T T T T T T T T T T85 85 85 85 85 85 T T T T T T T T T T T T T T T85 85 85 85 85 85 T T T T T T T T T T T T T T T85 85 85 85 85 85 T T T T T T T T T T T T T T T85 85 85 85 85 85 T T T T T T T T T T T T T T T70 70 70 70 T T T T T T T T T T T T T T T55 55 55 55 T T T T T T T T T T T T T T T50 50 50 50 T T T T T T T T T T T T T T T50 50 50 50 T T T T T T T T T T T T T T T50 50 50 50 T T T T T T T T T T T T T T T50 50 50 50 T T T T T T T T T T T T T T T50 50 50 50 T T T T T T T T T T T T T T T50 50 50 50 T T T T T T T T T T T T T T T50 50 50 T T T T T T T T T T T T T T T50 50 50 T T T T T T T T T T T T T T T50 50 T T T T T T T T T T T T T T T50 50 50 50 50 50 T T T T T T T T T T T T T T T50 50 50 50 50 T T T T T T T T T T T T T T T50 50 50 T T T T T T T T T T T T T T T50 50 T T T T T T T T T T T T T T T50 50 T T T T T T T T T T T T T T T<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 151


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - XT3 @ 415 VVersionSupply s. XT3 XT4 XT4 T4N, S N, S, H, L, V N, S, H, L, VN, S,H, L, VRelease TM, M TM, M EL ELSize 250 160 250 160 250 320Load s. I n [A] 160 200 250 125 160 200 225 250 100 160 250 320XT3100 4 1 5 7 1 7 1 7 1 7 7 7 7NS TM 250 125 7 1 7 1 7 7160 7 763 3 4 5 7 1 7 7 7 7 7 7 7 780 3 1 4 5 7 1 7 7 7 7 7 7MCCB - XT4 - T4 @ 415 V200 72501Value valid only for magnetic only supply side circuit-breaker2Value valid only for PR232/P, PR331/P <strong>and</strong> PR332/P trip units3Available only with Iu ≤ 1250AVersionSupply s. T5 T6 T7N, S, H, L, V N, S, H, L S, H, L, V 1Release TM EL TM, M EL EL152 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>Size 400 630 400 630 630 800 630 800 1000 800 1000 1250 1600Load s. In [A] 320 400 500 320 400 630 630 800 630 800 1000 800 2 1000 2 1250 2 1600 2XT4NSHLVTMEL16025016016 T T T T T T T T T T T T T T T20 T T T T T T T T T T T T T T T25 T T T T T T T T T T T T T T T32 T T T T T T T T T T T T T T T40 T T T T T T T T T T T T T T T50 T T T T T T T T T T T T T T T63 T T T T T T T T T T T T T T T80 T T T T T T T T T T T T T T T100 50 T 50 50 T T T T T T T T T T125 T 50 50 T T T T T T T T T T160 T 50 50 T T T T T T T T T T200 T 50 50 T T T T T T T T T T225 T 50 T T T T T T T T T T250 T 50 T T T T T T T T T T40 50 50 T 50 50 T T T T T T T T T T63 50 50 T 50 50 T T T T T T T T T T100 50 50 T 50 50 T T T T T T T T T T160 50 50 T 50 50 T T T T T T T T T T250 250 T 50 T T T T T T T T T TT4 320 320 50 T T T T T T T T T T1Available only with Iu ≤ 1250A2Value valid only for PR232/P, PR331/P <strong>and</strong> PR332/P trip units


3 <strong>Protection</strong> coordination3.2 Discrimination tablesT5 T6 T7N, S, H, L, V N, S, H, L S, H, L, V 3TM EL TM, M EL EL400 630 400 630 630 800 630 800 1000 800 1000 1250 1600320 400 500 320 400 630 630 800 630 800 1000 800 2 1000 2 1250 2 1600 225 25 25 25 25 25 T T T T T T T T T25 25 25 25 25 25 T T T T T T T T T25 25 25 25 25 25 40 T 40 T T T T T T20 20 20 20 20 20 36 T 36 T T T T T T20 20 20 20 36 T 36 T T T T T T20 20 20 30 T 30 T T T T T T20 20 20 30 40 30 40 40 T T T TMCCB - T5 @ 415 VSupply s. T6 T7Version N, S, H, L S, H, L, V 1Release TM, M EL ELSize 630 800 630 800 1000 800 1000 1250 1600Load s. I n [A] 630 800 630 800 1000 800 2 1000 2 1250 2 1600 2T5NSHLVTMEL400320 30 30 30 30 30 T T T T400 30 30 30 T T T T630 500 30 30 T T T T400320 30 30 30 30 30 T T T T400 30 30 30 30 30 T T T T630 630 30 T T T T1Available only with Iu ≤ 1250A2Value valid only for PR232/P, PR331/P <strong>and</strong> PR332/P trip unitsMCCB - T6 @ 415 VSupply s.Version S, H, L, V 1ReleaseT7ELSize 800 1000 1250 1600Load s. I n [A] 800 2 1000 2 1250 2 1600 2T6NSHLVTMEL630 630 40 40800 800 40 40630 630 40 40 40 40800 800 40 40 40 401000 1000 40 401Available only with Iu ≤ 1250A, maximum selectivity value is: 15kA2Value valid only for PR232/P, PR331/P <strong>and</strong> PR332/P trip units<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 153


3 <strong>Protection</strong> coordination3.2 Discrimination tablesACB - MCCB @ 415 VLoads.XT1XT2Supply s. X1 E1 E2 E3 E4 E6Version B N L B N B N S L 1 N S H V L 1 S H V H VBRelease EL EL EL EL ELSize 800 800 800 800 800 1600 1000 800 1250 2500 1000 800 800 2000 4000 3200 3200 4000 32001000 1000 1000 1000 1000 2000 1250 1000 1600 3200 1250 1000 1000 2500 4000 4000 5000 40001250 1250 1250 1250 1250 1600 1250 1600 1250 1250 6300 50001600 1600 1600 1600 2000 1600 2000 1600 1600 63002000 2500 2000 20003200 2500 25003200 3200N TM 160 T T T T T T T T T T T T T T T T T T T154 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>T T T T T T T T T T T T T T T T T T TC T T T T T T T T T T T T T T T T T T TS T 42 T T T T T T T T T T T T T T T T TH T 42 T T T T 55 65 T T T T T T T T T T TNT T T T T T T T T T T T T T T T T T TS T 42 T T T T T T T T T T T T T T T T TH TM,EL 160 T 42 T T T T 55 65 T T T T T T T T T T TL T 42 T T T T 55 65 100 T T 75 85 100 T T 100 T 100V T 42 T T T T 55 65 100 T T 75 85 100 T T 100 T 100XT3 N T T T T T T T T T T T T T T T T T T TTM 250S T 42 T T T T T T T T T T T T T T T T TXT4T4T5T6T7NT T T T T T T T T T T T T T T T T T TSTM,EL 160T 42 T T T T T T T T T T T T T T T T TH T 42 T T T T 55 65 T T T T T T T T T T T250L T 42 T T T T 55 65 100 T T 75 85 100 T T 100 T 100V T 42 T T T T 55 65 100 T T 75 85 100 T T 100 T 100NT T T T T T T T T T T T T T T T T T TS T 42 T T T T T T T T T T T T T T T T TH TM,EL 320 T 42 T T T T 55 65 T T T T T T T T T T TL T 42 T T T T 55 65 100 T T 75 85 100 T T 100 T 100V T 42 T T T T 55 65 100 T T 75 85 100 T T 100 T 100NT T T T T T T T T T T T T T T T T T TSTM,EL 400T 42 T T T T T T T T T T T T T T T T TH T 42 T T T T 55 65 T T T T T T T T T T T630L T 42 T T T T 55 65 100 T T 75 85 100 T T 100 T 100V T 42 T T T T 55 65 100 T T 75 85 100 T T 100 T 100NT T 15 T T T T T T T T T T T T T T T TS630T 42 15 T T T T T T T T T T T T T T T TTM,EL 800H1000T 42 15 T T T 55 65 T T T T T T T T T T TL T 42 15 T T T 55 65 T T T 75 85 T T T T T TST80042 15 T T T T T T T T T T T T T T T TH 1000 T 42 15 T T T 55 65 T T T T T T T T T T TELL 1250 T 42 15 T T T 55 65 100 T T 75 85 100 T T 100 T 100V 2 1600T 42 15 T T T 55 65 100 T T 75 85 100 T T 100 T 100Table valid for Emax circuit-breaker only with PR121/P, PR122/P <strong>and</strong> PR123/P releases1Emax L circuit-breaker only with PR122/P <strong>and</strong> PR123/P releases2Available only with Iu ≤ 1250A


3 <strong>Protection</strong> coordination3.2 Discrimination tablesMCCB - Tmax XT1, XT2 @ 400/415 VVersion1Release in auxiliary power supply <strong>and</strong> trip delayed parameter set ON2Select the lowest value between what is indicated <strong>and</strong> the breaking capacity of the supply sidecircuit-breakerSupply s. T4 T5 T6Release PR223EF 1 PR223EFSize 250 320 400 630 800Load s. In [A] 160 250 320 320 400 630 630 800XT1 B, C, N TM 160XT2 N,S,H,L TM, EL 16016-100 50 50 50 50 50 50 T T125 50 50 50 50 50 T T160 50 50 50 50 50 T T10-100 75 2 75 2 75 2 85 85 85 85 85125 75 2 75 2 85 85 85 85 85160 75 2 75 2 85 85 85 85 85LMCCB - Tmax T4, T5, T6 @ 400/415 VSupply s. T4 T5 T6VersionLReleasePR223EFSize 250 320 400 630 800Load s. In [A] 250 320 320 400 630 630 800160 T T T T T T T250T4 L PR223EF250 T T T T T T T320 320 T T T T T T320 T T T T T400T5 L PR223EF400 T T T T630 630 T T T630 630 T TT6 L PR223EF800 800 TTable valid for release with auxiliary power supply connected through a shielded twisted-pair wire<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 155


3 <strong>Protection</strong> coordination3.3 Back-up tablesThe tables shown give the short-circuit current value (in kA) for which the backupprotection is verified for the chosen circuit-breaker combination, at voltagesfrom 240 up to 415 V. These tables cover all the possible combinations between<strong>ABB</strong> SACE moulded-case circuit-breakers Tmax XT/Tmax T <strong>and</strong> those betweenthe above mentioned circuit-breakers <strong>and</strong> <strong>ABB</strong> MCBs.Notes for a correct interpretation of the coordinationtables:Tmax XT @ 415V acVersion Icu [kA]B 18C 25N 36S 50H 70L 120V 150Tmax @ 415V acVersion Icu [kA]B 16C 25N 36S 50H 70L (for T2) 85L (for T4-T5) 120L (for T6) 100V (for T7) 150V 200Emax @ 415V acVersion Icu [kA]B 42N 65*S 75**H 100L 130***V 150***** For Emax E1 version N Icu=50kA** For Emax E2 version S Icu=85kA*** For Emax X1 version L Icu=150kA**** For Emax E3 version V Icu=130kAKeysFor MCCB (Moulded-case circuit-breaker)ACB (Air circuit-breaker)TM = thermomagnetic release– TMD (Tmax)– TMA (Tmax)M = magnetic only release– MF (Tmax)– MA (Tmax)EL = elettronic releaseFor MCB (Miniature circuit-breaker):B = charateristic trip (I3=3...5In)C = charateristic trip (I3=5...10In)D = charateristic trip (I3=10...20In)K = charateristic trip (I3=8...14In)Z = charateristic trip (I3=2...3In)156 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.3 Back-up tablesExample:From the coordination table on page 161 the following conclusion is derived:the circuit-breakers type T5H <strong>and</strong> XT1N are coordinated in back-up protectionup to a value of 65 kA (higher than the short-circuit current measured at the<strong>installation</strong> point), although the maximum breaking capacity of XT1N, at 415V, is 36 kA.UUr = 400VT5HCable1SDC008017F0001XT1N160I k = 60kAMCB - MCB @ 240 V (Two-pole circuit-breakers)Supply s. S200 S200M S200P S280 S290 S800Char. B-C B-C B-C B-C C B-CLoad s. Icu [kA] 20 25 40 25 20 25 100In [A] 0,5..63 0,5..63 0,5..25 32..63 80, 100 80..125 10..125SN201L B,C 6 2..40 20 25 40 25 15 15 100SN201 B,C,D 10 2..40 20 25 40 25 15 15 100SN201M B,C 10 2..40 20 25 40 25 15 15 100S200 B,C,K,Z 20 0,5..63 25 40 25 100S200M B,C 25 0,5..63 40 100S200PB,C,D,K,ZS280 B,C 20 80, 100S290 C,D 25 80..12540 0,5..25 10025 32..63 100<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 157


3 <strong>Protection</strong> coordination3.3 Back-up tablesMCCB @ 415 V - MCB @ 240 VSupply s. 1 XT1 XT2 XT3 XT1 XT2 XT3 XT1 XT2Version B C N S H L VLoad s. Carat. In [A] Icu [kA] 18 25 36 50 70 120 200SN201LSN201SN201NB,CB,C,DB,C2..2518 18 18 20 18 20 18 20 20 206101032..40 10 18 10 18 10 18 10 18 18 182..25252525 25 2510 18 18 18 18 18 18 1832..40 18 18 18 18 182..25252525 25 2510 18 16 18 18 18 18 1832..40 18 18 18 18 181Supply side circuit-breaker 4P (load side circuit branched between one phase <strong>and</strong> the neutral)MCB - MCB @ 415 VSupply s. S200 S200M S200P S280 S290 S800N S800SChar. B-C B-C B-C B-C C B-C-D B-C-D-KLoad s. Icu [kA] 10 15 25 15 6 15 36 50I n [A] 0,5..63 0,5..63 0,5..25 32..63 80, 100 80..125 25..125 25..125S200 B,C,K,Z 10 0,5..63 15 25 15 15 36 50S200M B,C 15 0,5..63 25 36 50S200PB,C,D,K,ZS280 B,C 6 80, 100S290 C,D 15 80..125S800N B,C,D 36 25..125S800S B,C,D,K 50 25..12525 0,5..25 36 5015 32..63 36 50158 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.3 Back-up tablesMCCB - MCB @ 415 VSupply s. XT1 XT2 XT3 XT4 XT1 XT2 XT3 XT4 XT1 XT2 XT4 XT2 XT4 XT2 XT4Version B C N S H L VLoad s. Carat. In [A] Icu [kA] 18 25 36 50 70 120 150S200S200MS200PB,C,K,ZB,C,D,K,ZB,C,D,K,Z0,5..1010 18 25 30 36 36 36 30 36 40 40 30 40 40 40 40 40 4013..63 16 160,5..1015 18 25 30 36 36 36 30 50 40 40 30 70 40 85 40 85 4013..63 25 25 60 60 600,5..1030 36 36 36 30 50 40 40 30 70 40 85 40 85 402513..25 30 36 30 36 30 50 30 40 30 60 40 60 40 60 4032..63 15 18 25 30 36 25 36 30 50 25 40 30 60 40 60 40 60 40S280 B,C 80, 100 6 18 16 16 36 16 30 16 36 16 30 16 36 30 36 30 36 30S290 C,D 80..125 15 18 25 30 36 30 30 30 50 30 30 30 70 30 85 30 85 30S800N B,C,D 10..125 36 70 70 85 120 85 150S800S B,C,D,K 10..125 50 70 70 85 120 85 150<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 159


3 <strong>Protection</strong> coordination3.3 Back-up tablesMCCB - MCCB @ 415 VSupply s. XT1 XT2 XT3 XT4 T5 T6 XT1 XT2 XT3 XT4 T5 T6 T7Version C N SLoad s. Carat. Icu [kA] 25 36 50XT1 B 16 25 36 36 36 36 30 30 36 50 50 50 36 36 36XT1 C 25 36 36 36 36 36 36 40 50 50 50 50 50 50XT150 50 50 50 50 50 50XT2 50 50 50 50 50 50XT3 50 50 50 50 50N 36XT4 50 50 50 40T5 50 50 50T6 50 40XT1XT2XT3XT4S 50T5T6XT1XT2XT4H 70T5T6XT2XT4T5L851201120 kA per T7160 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3 <strong>Protection</strong> coordination3.3 Back-up tablesXT1 XT2 XT4 T5 T6 T7 XT2 XT4 T5 T6 T7 XT2 XT4 T5H L V70 120 100 1 150 20040 70 50 40 40 40 70 65 50 50 70 70 7050 70 65 65 65 50 70 70 70 70 50 70 70 7065 70 65 65 65 50 70 70 70 70 70 70 70 7070 65 65 65 65 100 100 100 85 85 120 120 12065 65 65 50 100 100 100 50 120 12065 65 65 50 100 100 65 65 120 12065 65 50 100 85 65 12065 40 70 5070 70 70 70 70 70 70 70 70 70 70 70 70 7070 70 70 70 100 100 100 85 85 150 130 13070 70 70 100 100 100 150 15070 70 70 70 100 100 85 85 150 15070 70 70 100 85 85 15070 85 85120 120 120 85 85 150 150 150120 120 100 100 150 150120 100 100 180 180100 85150 150 150150 150200<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 161


3.4 Coordination tables between circuitbreakers<strong>and</strong> switch disconnectors3 <strong>Protection</strong> coordinationThe tables shown give the values of the short-circuit current (in kA) for whichback-up protection is verified by the pre-selected combination of circuit-breaker<strong>and</strong> switch disconnector, for voltages between 380 <strong>and</strong> 415 V. The tables coverthe possible combinations of moulded-case circuit-breakers in the <strong>ABB</strong> SACETmax series, with the switch disconnectors detailed above.Supply S. Version IcuXT1XT2XT3XT4T4T5T6T7Load S. XT1D XT3D XT4D T4DIcw [kA] 2 3,6 3,6 3,6B 18 18 18 18 18 18 18 18 18C 25 25 25 25 25 25 25 25 25N 36 160 36 36 36 36 36 36 36 36S 50 50 50 50 50 50 50 50 50H 70 70 70 70 70 70 70 70 70N 36 36 36 36 36 36 36 36 36S 50 50 50 50 50 50 50 50 50H 70 160 70 70 70 70 70 70 70 70L 120 120 120 120 120 120 120 120 120V 200 150 150 150 150 150 150 150 150N 36 36 36 36 36 36 36 36250S 50 50 50 50 50 50 50 50N 36 36 36 36 36 36 36 36S 50 50 50 50 50 50 50 50H 7016025070 70 70 70 70 70 70L 120 120 120 120 120 120 120 120V 150 150 150 150 150 150 150 150N 36 36 1 36 1 36 36 36 36 36S 50 50 1 50 1 50 50 50 50 50H 70 32070 1 70 1 70 70 70 70 70L 120 120 1 120 1 120 120 120 120 120V 200 200 1 200 1 200 200 200 200 200N 36 36 1 36 36 36S 50 50 1 50 50 50400H 70 70 1 70 70 70630L 120 120 1 120 120 120V 200 200 1 200 200 200N 36 36 1 36 1S 5063050 1 50 1800H 70100070 1 70 1L 100 100 1 100 1S 50H 70L 120V 2 150IuIth8001000125016001Value valid only with I1 (MCCB)


3.4 Coordination tables between circuit-breakers <strong>and</strong> switch disconnectors3 <strong>Protection</strong> coordinationNotes for the correct reading of the coordination tables:T7D201000 1250 160018 18 1825 25 2536 36 3650 50 5070 70 7036 36 3650 50 5070 70 70120 120 120150 150 15036 36 3650 50 5036 36 3650 50 5070 70 70120 120 120150 150 15036 36 3650 50 5070 70 70120 120 120200 200 20036 36 3650 50 5070 70 70120 120 120200 200 20036 36 3650 50 5070 70 70100 100 10050 50 5070 70 70120 120 120150 2 150 2 150 21SDC008037F0201Tmax XT @ 415V acVersion Icu [kA]B 18C 25N 36S 50H 70L 120V 150Tmax @ 415V acVersion Icu [kA]B 16C 25N 36S 50H 70L (for T2) 85L (for T4-T5) 120L (for T6) 100V (for T7) 150V 200<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 163


3.4 Coordination tables between circuit-breakers <strong>and</strong> switch disconnectors3 <strong>Protection</strong> coordinationExample:From the coordination table on page 162-163 it can be seen that circuit-breakerXT2S160 is able to protect the switch disconnector XT1D160 up to a shortcircuitcurrent of 50 kA (higher than the short-circuit current at the <strong>installation</strong>point). Overload protection is also verified, as the rated current of the breakeris not higher than the size of the disconnector.UUr = 400VXT2S160CableXT1D 1601SDC008018F0001I k = 40kA164 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


3.4 Coordination tables between circuit-breakers <strong>and</strong> switch disconnectors3 <strong>Protection</strong> coordinationExample:For the correct selection of the components, the disconnector must beprotected from overloads by a device with a rated current not greaterthan the size of the disconnector, while in short-circuit conditions it mustbe verified that:I cw≥ I kI cm≥ I p.Therefore, with regard to the electrical parameters of the single devices,Emax E2N1250/MS disconnector is selected, <strong>and</strong> a E2N1250 breaker.That is:I cw(E2N /MS) = 55 kA > 45 kAI cm(E2N /MS) = 143 kA > 100 kA.UUr = 400VE2N1250CableE2N1250 /MS1SDC008019F0001I k =45 kAI p =100 kA<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 165


4.1 Direct current networks4 Special applicationsMain applications of direct current:• Emergency supply or auxiliary services:the use of direct current is due to the need to employ a back-up energy sourcewhich allows the supply of essential services such as protection services,emergency lighting, alarm systems, hospital <strong>and</strong> industrial services, dataprocessingcentres etc., using accumulator batteries, for example.• <strong>Electrical</strong> traction:the advantages offered by the use of dc motors in terms of regulation <strong>and</strong> ofsingle supply lines lead to the widespread use of direct current for railways,underground railways, trams, lifts <strong>and</strong> public transport in general.• Particular industrial <strong>installation</strong>s:there are some electrolytic process plants <strong>and</strong> applications which have aparticular need for the use of electrical machinery.Typical uses of circuit-breakers include the protection of cables, devices <strong>and</strong>the operation of motors.Considerations for the interruption of direct currentDirect current presents larger problems than alternating current does in termsof the phenomena associated with the interruption of high currents. Alternatingcurrents have a natural passage to zero of the current every half-cycle, whichcorresponds to a spontaneous extinguishing of the arc which is formed whenthe circuit is opened.This characteristic does not exist in direct currents, <strong>and</strong> furthermore, in order toextinguish the arc, it is necessary that the current lowers to zero.The extinguishing time of a direct current, all other conditions being equal, isproportional to the time constant of the circuit T = L/R.It is necessary that the interruption takes place gradually, without a suddenswitching off of the current which could cause large over-voltages. This canbe carried out by extending <strong>and</strong> cooling the arc so as to insert an ever higherresistance into the circuit.The energetic characteristics which develop in the circuit depend upon thevoltage level of the plant <strong>and</strong> result in the <strong>installation</strong> of breakers according toconnection diagrams in which the poles of the breaker are positioned in series toincrease their performance under short-circuit conditions. The breaking capacityof the switching device becomes higher as the number of contacts which openthe circuit increases <strong>and</strong>, therefore, when the arc voltage applied is larger.This also means that when the supply voltage of the <strong>installation</strong> rises, so mustthe number of current switches <strong>and</strong> therefore the poles in series.166 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.1 Direct current networksCalculation of the short-circuit current of an accumulator batteryThe short-circuit current at the terminals of an accumulator battery may besupplied by the battery manufacturer, or may be calculated using the followingformula:I k= U MaxR iwhere:• U Maxis the maximum flashover voltage (no-load voltage);• R iis the internal resistance of the elements forming the battery.The internal resistance is usually supplied by the manufacturer, but may becalculated from the discharge characteristics obtained through a test such asdetailed by IEC 60896 – 1 or IEC 60896 – 2.For example, a battery of 12.84 V <strong>and</strong> internal resistance of 0.005 Ω gives ashort-circuit current at the terminals of 2568 A.Under short-circuit conditions the current increases very rapidly in the initialmoments, reaches a peak <strong>and</strong> then decreases with the discharge voltage ofthe battery. Naturally, this high value of the fault current causes intense heatinginside the battery, due to the internal resistance, <strong>and</strong> may lead to explosion.Therefore it is very important to prevent <strong>and</strong> / or minimize short-circuit currentsin direct currents systems supplied by accumulator batteries.Criteria for the selection of circuit-breakersFor the correct selection of a circuit-breaker for the protection of a direct currentnetwork, the following factors must be considered:1. the load current, according to which the size of the breaker <strong>and</strong> the settingfor the thermo-magnetic over-current release can be determined;2. the rated plant voltage, according to which the number of poles to be connectedin series is determined, thus the breaking capacity of the device canalso be increased;3. the prospective short-circuit current at the point of <strong>installation</strong> of the breakerinfluencing the choice of the breaker;4. the type of network, more specifically the type of earthing connection.Note: in case of using of four pole circuit-breakers, the neutral must be at 100%Direct current network typesDirect current networks may be carried out:• with both polarities insulated from earth;• with one polarity connected to earth;• with median point connected to earth.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 167


4 Special applications4.1 Direct current networksNetwork with both polarities insulated from earthabUcR1SDC008020F0001• Fault a: the fault, with negligible impedance, between the two polarities setsup a short-circuit current to which both polarities contribute to the full voltage,according to which the breaking capacity of the breaker must be selected.• Fault b: the fault between the polarity <strong>and</strong> earth has no consequences fromthe point of view of the function of the <strong>installation</strong>.• Fault c: again, this fault between the polarity <strong>and</strong> earth has no consequencesfrom the point of view of the function of the <strong>installation</strong>.In insulated networks it is necessary to install a device capable of signalling thepresence of the first earth fault in order to eliminate it. In the worst conditions,when a second earth fault is verified, the breaker may have to interrupt theshort-circuit current with the full voltage applied to a single polarity <strong>and</strong> thereforewith a breaking capacity which may not be sufficient.In networks with both polarities insulated from earth it is appropriate to dividethe number of poles of the breaker necessary for interruption on each polarity(positive <strong>and</strong> negative) in such a way as to obtain separation of the circuit.Diagrams to be used are as follows:- MCBs type S800 UC - S280 UCINSULATED NETWORKRated voltage (Un) ≤ 500 ≤ 750INSULATED NETWORKRated voltage (Un) ≤ 440+ - +-+-<strong>Protection</strong>+isolation function1 32 412345678<strong>Protection</strong>+isolation function12345678S800S UC In = 10…125 A 50 50S280UCIn = 0,5…2 A 50In = 3…40 A 6In = 50…63 A 4,5168 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.1 Direct current networks- MCCBs type Tmax XTRated voltage(Un)INSULATED NETWORK*≤ 250 ≤ 500+ -+ -<strong>Protection</strong>+isolation functionLOADLOADXT1XT2XT3XT4B 18 18C 25 25N 36 36S 50 50H 70 70N 36 36S 50 50H 70 70L 120 120V 150 150N 36 36S 50 50N 36 36S 50 50H 70 70L 120 120V 150 150* with these typologies of pole connection the possibility of a double fault to earth isconsidered unlikely.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 169


4 Special applications4.1 Direct current networks- MCCBs type Tmax TINSULATED NETWORKRated voltage (Un) ≤ 250 ≤ 500 ≤ 750+ -+ -+ -+ -+ -<strong>Protection</strong>+isolation functionLOADLOADLOADLOADLOADT1160T2160T3250T4250/320T5400/630T6630/800B 16 20 16C 25 30 25N 36 40 36N 36 40 36S 50 55 50H 70 85 70L 85 100 85N 36 40 36S 50 55 50N 36 25 16S 50 36 25H 70 50 36L 100 70 50V 150 100 70N 36 20 16S 50 35 20H 70 50 36L 100 65 50The positive pole (+) can be inverted with the negative pole (-).* with these typologies of pole connection the possibility of a double fault to earth isconsidered unlikely.170 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.1 Direct current networks- ACBs type EmaxINSULATED NETWORK (1)Rated voltage (Un) ≤ 500 ≤ 750 ≤ 1000+LOADLOAD-LOAD-LOADLOAD-+ LOAD+ -+ LOAD+ -Isolation n n n n<strong>Protection</strong> n n n nPR122/DC n n n nPR123/DC n n n nIcu (2) (kA) (kA) (kA) (kA)E2E3E4E68001000B35 25 25 2512501600N 1600 50 25 40 2580010001250N60 40 50 351600200025001600H 200065 (3) 40 50 40250016002000S75 65 65 5025003200H 3200 100 65 65 653200H 4000100 65 65 655000(1)the possibility of a double earth fault is considered negligible with this type of poleconnections.(2)Icu with L/R = 15ms according to IEC 60946-2 St<strong>and</strong>ard. For Icu with L/R = 5ms <strong>and</strong>L/R = 30ms, ask <strong>ABB</strong>.(3)85kA only if supplied from lower terminals.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 171


4 Special applications4.1 Direct current networksNetwork with one polarity connected to earthabUcR1SDC008026F0001• Fault a: the fault between the two polarities sets up a short-circuit current towhich both polarities contribute to the full voltage U, according to which thebreaking capacity of the breaker is selected.• Fault b: the fault on the polarity not connected to earth sets up a currentwhich involves the over-current protection according to the resistance of theground.• Fault c: the fault between the polarity connected to earth <strong>and</strong> earth has noconsequences from the point of view of the function of the <strong>installation</strong>.In a network with one polarity connected to earth, all the poles of the breakernecessary for protection must be connected in series on the non-earthedpolarity. If isolation is required, it is necessary to provide another breaker poleon the earthed polarity.Diagrams to be used with circuit isolation are as follows:+ -12NETWORK WITH ONE POLARITY EARTHEDRated voltage (Un) ≤ 250 ≤ 500 ≤ 750<strong>Protection</strong> function- MCBs type S800 UC - S280 UC1234+ -1234+ -56S800S UC In = 10…125 A 50 50 50NETWORK WITH ONE POLARITY EARTHEDRated voltage (Un) ≤ 220 ≤ 440+ -+ -<strong>Protection</strong> function121234<strong>Protection</strong>+isolation function+ -1234S280 UCIn = 0,5…2 A 50 50 50In = 3…40 A 6 10 6In = 50…63 A 4,5 6 4,5172 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.1 Direct current networks- MCCBs type Tmax XTRated voltage(Un)NETWORK WITH ONE POLARITY EARTHED≤ 250 ≤ 500+ -+ -<strong>Protection</strong>+isolation functionLOAD+ -LOAD+ -<strong>Protection</strong>functionLOADLOADXT1XT2XT3XT4B 18 18C 25 25N 36 36S 50 50H 70 70N 36 36S 50 50H 70 70L 120 120V 150 150N 36 36S 50 50N 36 36S 50 50H 70 70L 120 120V 150 150<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 173


4 Special applications4.1 Direct current networks- MCCBs type Tmax TNETWORK WITH ONE POLARITY EARTHEDRatedvoltage (Un)≤ 250 ≤ 500 ≤ 750+ -+ -+ -+ -+ -<strong>Protection</strong>+isolation functionLOADLOADLOAD LOAD LOAD+ -+ -+ -+ -+ -<strong>Protection</strong>functionLOADLOADLOADLOADLOADT1160T2160T3250T4250/320T5400/630T6630/800B 16 20 16C 25 30 25N 36 40 36N 36 40 36S 50 55 50H 70 85 70L 85 100 85N 36 40 36S 50 55 50N 36 25 16S 50 36 25H 70 50 36L 100 70 50V 150 100 70N 36 20 16S 50 35 20H 70 50 36L 100 65 50174 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.1 Direct current networks- ACBs type EmaxNETWORK WITH EARTHED NEGATIVE POLARITY (1)Rated voltage (Un) ≤ 500 (2)+abLOADLOAD-LOAD-+ LOAD+ -Isolation n n<strong>Protection</strong> n nPR122/DC n nPR123/DC n ntype of fault a b a bpoles in series affected by the fault 3 2 4 3Icu (3) (kA) (kA) (kA) (kA)E2E3E4E68001000B35 20 35 3512501600N 1600 50 25 50 5080010001250N60 30 60 601600200025001600H 200065 (4) 40 65 (4) 65 (4)250016002000S100 50 100 10025003200H 3200 100 65 100 1003200H 4000100 65 100 1005000(1) for networks with positive earthed polarity, ask <strong>ABB</strong>.(2) for higher voltages, ask <strong>ABB</strong>.(3) Icu with L/R = 15ms according to IEC 60946-2 St<strong>and</strong>ard. For Icu with L/R = 5ms <strong>and</strong> L/R = 30ms,ask <strong>ABB</strong>.(4) 85kA only if supplied from lower terminals.Earthing shall be carried out on the supply side of the circuit-breaker.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 175


4 Special applications4.1 Direct current networksNetwork with the median point connected to earthabUcR1SDC008034F0001• Fault a: the fault between the two polarities sets up a short-circuit current towhich both polarities contribute to the full voltage U, according to which thebreaking capacity of the breaker is selected.• Fault b: the fault between the polarity <strong>and</strong> earth sets up a short-circuit currentless than that of a fault between the two polarities, as it is supplied by a voltageequal to 0.5 U.• Fault c: the fault in this case is analogous to the previous case, but concernsthe negative polarity.With network with the median point connected to earth the breaker must beinserted on both polarities.Diagrams to be used are as follows:- MCBs type S280 UCNETWORK WITH THE MIDDLE POINT CONNECTED TO EARTHRatedvoltage (Un)≤ 220+ -<strong>Protection</strong>+isolation function1234+ -S280 UCIn = 0,5…2 A 50In = 3…40 A 10In = 50…63 A 6176 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.1 Direct current networks- MCCBs type Tmax XTRated voltage(Un)<strong>Protection</strong>+isolation functionNETWORK WITH THE MIDDLE POINT CONNECTED TO EARTH≤ 250 ≤ 500+ -+ -LOADLOADXT1XT2XT3XT4B 18 18C 25 25N 36 36S 50 50H 70 70N 36 36S 50 50H 70 70L 120 120V 150 150N 36 36S 50 50N 36 36S 50 50H 70 70L 120 120V 150 150<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 177


4 Special applications4.1 Direct current networks- MCCBs type Tmax TRatedvoltage (Un)NETWORK WITH THE MIDDLE POINT CONNECTED TO EARTH≤ 250* ≤ 500** ≤ 750+ -+ -+ -<strong>Protection</strong>+isolation functionLOADLOADLOADT1160B 20 16C 30 25N 40 36N 40 36T2160S 55 50H 85 70L 100 85T3250T4250/320T5400/630N 40 36S 55 50N 36 25 16S 50 36 25H 70 50 36L 100 70 50V 100 100 70N 36 20 16T6630/800S 50 35 20H 70 50 36L 100 65 50* for the use of three-phase circuit-breakers please ask <strong>ABB</strong>** for the use of three-phase circuit-breakers (T4-T5-T6) please ask <strong>ABB</strong>178 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.1 Direct current networks- ACBs type EmaxNETWORK WITH THE MID-POINT EARTHEDRated voltage (Ue) ≤ 500 ≤ 500 ≤ 750 ≤ 1000+abLOADLOAD-LOAD LOAD LOAD- 22c+ LOAD+ -PR122/DC - - - -PR123/DC n n n ntype of fault a b c a b c a b c a b cpoles in series affected by the fault 3 2 (U/2) 1 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2) 4 2 (U/2) 2 (U/2)Icu (1) kA kA kA kA8001000B35 35 18 35 35 35 25 25 25 25 25 25E212501600N 1600 50 50 25 50 50 50 40 40 40 25 25 25N8001000125060 60 30 60 60 60 50 50 50 35 35 3516002520002500H16002000250065 (2) 65 40 65 (2) 65 (2) 65 (2) 50 50 50 40 40 40S1600200075 75 35 75 75 75 65 65 65 50 50 50E425003200H 3200 100 100 50 100 100 100 65 65 65 65 65 65E6 H320040005000100 100 65 100 100 100 65 65 65 65 65 65(1)Icu with L/R = 15ms according to IEC 60946-2 St<strong>and</strong>ard. For Icu with L/R = 5ms <strong>and</strong> L/R = 30ms,ask <strong>ABB</strong>.(2) 85kA only if supplied from below.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 179


4 Special applications4.1 Direct current networksUse of switching devices in direct currentParallel connection of breaker polesAccording to the number of poles connected in parallel, the coefficients detailedin the following table must be applied:Table 1: Correction factor for poles connected in parallelnumber of poles in parallel 2 3 4 (neutral 100%)reduction factor of dc carrying capacity 0.9 0.8 0.7breaker current carrying capacity 1.8xIn 2.4xIn 2.8xInThe connections which are external from the breaker terminals must be carriedout by the user in such a way as to ensure that the connection is perfectlybalanced.The following table shows the connections of poles in parallel with the relevantderating <strong>and</strong> performances under short-circuit conditions referred to theadopted network typology.INSULATED NETWORKconnection of the poles inparallel+ -LOADelectrical characteristicsTo obtain such connection it is necessary to use a four-pole circuit-breakerwith the neutral conductor at 100%.With a CB type T6 800, the available settings are:- maximum line current = 1440 A- istantaneous tripping = 14400 A(±20% tolerance)This application can be obtained with an <strong>installation</strong> voltage not exceeding500Vd.c.The breaking capacities are (according to the different versions):N= 36kA with Un< 250Vd.c. - 20kA with Un< 500Vd.c.S= 50kA with Un< 250Vd.c. - 35kA with Un< 500Vd.c.H= 70kA with Un< 250Vd.c. - 50kA with Un< 500Vd.c.L= 100kA with Un< 250Vd.c. - 65kA with Un< 500Vd.c.NETWORK WITH ONE POLARITY EARTHEDprotection function withoutinsulation function+ -LOADelectrical characteristicsTo obtain such connection it is necessary to use a four-pole circuit-breakerwith the neutral conductor at 100%.With a CB type T6 800, the available settings are:- maximum line current = 1440 A- istantaneous tripping = 12960 A(±20% tolerance)This application can be obtained with an <strong>installation</strong> voltage not exceeding500Vd.c.The breaking capacities are (according to the different versions):N= 36kA with Un< 250Vd.c. - 20kA with Un< 500Vd.c.S= 50kA with Un< 250Vd.c. - 35kA with Un< 500Vd.c.H= 70kA with Un< 250Vd.c. - 50kA with Un< 500Vd.c.L= 100kA with Un< 250Vd.c. - 65kA with Un< 500Vd.c.180 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.1 Direct current networksBehaviour of thermal releasesAs the functioning of these releases is based on thermal phenomena arisingfrom the flowing of current, they can therefore be used with direct current, theirtrip characteristics remaining unaltered.Behaviour of magnetic releasesThe values of the trip thresholds of ac magnetic releases, used for direct current,must be multiplied by the following coefficient (k m), according to the breaker<strong>and</strong> the connection diagram:Table 2: k mcoefficientConnectionmodality+ -Circuit-breakerXT1 XT2 XT3 XT4 T1 T2 T3 T4 T5 T61.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.1 1.1LOAD+ -1 1.15 1.15 1.15 1 1.15 1.15 1.15 1 1LOAD+ -1 1.15 1.15 1.15 1 1.15 1.15 1.15 1 1LOAD+ -- - - - - - - 1 0.9 0.9LOAD+ -- - - - - - - 1 0.9 0.9LOAD+ -- - - - - - - 1 0.9 0.9LOAD+ -- - - - - - - - - 1LOAD+-- - - - - - - - - 0.9LOAD<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 181


4 Special applications4.1 Direct current networksExampleData:• Direct current network connected to earth;• Rated voltage Ur = 250 V;• Short-circuit current Ik = 32 kA• Load current Ib = 230 AUsing Table of page 173, it is possible to select the Tmax XT3N250 In = 250A three pole breaker, using the connection shown (two poles in series for thepolarity not connected to earth <strong>and</strong> one poles in series for the polarity connectedto earth).From km coefficient Table corresponding to the diagram select, <strong>and</strong> with breakerSACE Tmax XT3, it risults k m=1.15; therefore the nominal magnetic trip willoccur at 2875 A (taking into account the tolerance, the trip will occur between2300 A <strong>and</strong> 3450 A).182 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.2 Networks at particular frequencies: 400 Hz <strong>and</strong> 16 2/3 HzSt<strong>and</strong>ard production breakers can be used with alternating currents with frequenciesother than 50/60 Hz (the frequencies to which the rated performanceof the device refer, with alternating current) as appropriate derating coefficientsare applied.4.2.1 400 Hz networksAt high frequencies, performance is reclassified to take into account phenomenasuch as:• the increase in the skin effect <strong>and</strong> the increase in the inductive reactancedirectly proportional to the frequency causes overheating of the conductorsor the copper components in the breaker which normally carry current;• the lengthening of the hysteresis loop <strong>and</strong> the reduction of the magneticsaturation value with the consequent variation of the forces associated withthe magnetic field at a given current value.In general these phenomena have consequences on the behaviour of boththermo-magnetic releases <strong>and</strong> the current interrupting parts of the circuitbreaker.To protect 400 Hz networks <strong>ABB</strong> SACE has developed a new series of electronictrip units, Ekip LS/E, LSI <strong>and</strong> LSIG: the are available for circuit-breakerstype SACE Tmax XT.The following tables refer to circuit-breakers with thermomagnetic releases, witha breaking capacity lower than 36 kA. This value is usually more than sufficientfor the protection of <strong>installation</strong>s where such a frequency is used, normallycharacterized by rather low short-circuit currents.As can be seen from the data shown, the tripping threshold of the thermalelement (l n) decreases as the frequency increases because of the reduced conductivityof the materials <strong>and</strong> the increase of the associated thermal phenomena;in general, the derating of this performance is generally equal to 10%.Vice versa, the magnetic threshold (l 3) increases with the increase in frequency.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 183


T1B 160T1C 160T1N 1604 Special applicationsTable 1: Tmax performance T1 16-63 A TMDI1 (400Hz)4.2 Networks at particular frequenciesMIN MED MAX I3 (50Hz) K m I3 (400Hz)In16 10 12 14 500 2 1000In20 12 15 18 500 2 1000In25 16 19 22 500 2 1000In32 20 24.5 29 500 2 1000In40 25 30.5 36 500 2 1000In50 31 38 45 500 2 1000In63 39 48 57 630 2 1260K m= Multiplier factor of I3 due to the induced magnetic fieldsI3Trip curvesthermomagnetic releaseT1 B/C/N 160In 16 to 63 ATMD1000t [s]1001010.10.010.1 110100In=16 I3=1000 AIn=20 I3=1000 AIn=25 I3=1000 AIn=32 I3=1000 AIn=40 I3=1000 AIn=50-63 I3=1000 A1000I1184 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


T1B 160T1C 160T1N 160In804 Special applications4.2 Networks at particular frequenciesTable 2: Tmax performance T1 80 A TMDI1 (400Hz)I3MIN MED MAX I3 (50Hz) K m I3 (400Hz)50 61 72 800 2 1600K m= Multiplier factor of I3 due to the induced magnetic fieldsTrip curvesthermomagnetic releaseT1 B/C/N 160In 80 ATMD1000t [s]1001010.1In=80 I 3=1600 A0.010.1 110100I1<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 185


4 Special applicationsTable 3: Tmax performance T2 1.6-80 A TMD4.2 Networks at particular frequenciesI1 (400Hz)I3T2N 160 MIN MED MAX I3 (50Hz) K m I3 (400Hz)In1.6 1 1.2 1.4 16 1.7 27.2In2 1.2 1.5 1.8 20 1.7 34In2.5 1.5 1.9 2.2 25 1.7 42.5In3.2 2 2.5 2.9 32 1.7 54.4In4 2.5 3 3.6 40 1.7 68In5 3 3.8 4.5 50 1.7 85In6.3 4 4.8 5.7 63 1.7 107.1In8 5 6.1 7.2 80 1.7 136In10 6.3 7.6 9 100 1.7 170In12.5 7.8 9.5 11.2 125 1.7 212.5In16 10 12 14 500 1.7 850In20 12 15 18 500 1.7 850In25 16 19 22 500 1.7 850In32 20 24.5 29 500 1.7 850In40 25 30.5 36 500 1.7 850In50 31 38 45 500 1.7 850In63 39 48 57 630 1.7 1071In80 50 61 72 800 1.7 1360Trip curvesK m= Multiplier factor of I3 due to the induced magnetic fieldsthermomagnetic releaseT2N 1601000In 1.6 to 80 ATMDt [s]1001010.1In=16 I3=850 AIn=20 I3=850 AIn=25 I3=850 AIn=32 I3=850 AIn=40 I3=850 AIn=1.6 to 12.5 I3=17xInIn=50 to 80 I3=17xIn0.010.1 110100186 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>1000I1


T2N 1604 Special applicationsTable 4: Tmax performance T2 16-160 A TMGI1 (400Hz)4.2 Networks at particular frequenciesMIN MED MAX I3 (50Hz) K m I3 (400H z)In16 10 12 14 160 1,7 272In25 16 19 22 160 1,7 272In40 25 30,5 36 200 1,7 340In63 39 48 57 200 1,7 340In80 50 61 72 240 1,7 408In100 63 76,5 90 300 1,7 510In125 79 96 113 375 1,7 637,5In160 100 122 144 480 1,7 816I3Trip curvesthermomagnetic releaseT2N 16010000In 16 to 160 ATMG1000t [s]1001010.1In=16 I3=272 AIn=25 I3=272 AIn=40 I3=340 AIn=63 I3=340 AIn=80√160 I3=5.1xIn0.010.1 110100I1<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 187


4 Special applications4.2 Networks at particular frequenciesTable 5: Tmax performance T3 63-250 A TMGI1 (400Hz)I3 (Low magnetic setting)T3N 250 MIN MED MAX I3 (50Hz) K m I3 (400Hz)In63 39 48 57 400 1.7 680In80 50 61 72 400 1.7 680In100 63 76.5 90 400 1.7 680In125 79 96 113 400 1.7 680In160 100 122 144 480 1.7 816In200 126 153 180 600 1.7 1020In250 157 191 225 750 1.7 1275K m= Multiplier factor of I3 due to the induced magnetic fieldsTrip curvesthermomagnetic releaseT3N 250In 63 to 250 ATMG1000t [s]1001010.1In=63 I3=680 AIn=80 I3=680 AIn=100 I3=680 AIn=125 I3=680 AIn=160,200,250 I3=5.1xIn0.010.1 1101001000I1188 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.2 Networks at particular frequenciesTable 6: Tmax performance T3 63-125 A TMDI1 (400Hz)I3T3N 250 MIN MED MAX I3 (50Hz) K m I3 (400Hz)In63 39 48 57 630 1.7 1071In80 50 61 72 800 1.7 1360In100 63 76.5 90 1000 1.7 1700In125 79 96 113 1250 1.7 2125K m= Multiplier factor of I3 due to the induced magnetic fieldsTrip curvesthermomagnetic releaseT3N 250In 63 to 125 ATMD1000t [s]1001010.1In=63 to 125 I3=17xIn0.010.1 1101001000I1<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 189


4 Special applicationsTable 7: Tmax performance T4 20-50 A TMDI1 (400Hz)4.2 Networks at particular frequenciesT4N 250 MIN MED MAX I3 (50Hz) K m I3 (400Hz)In20 12 15 18 320 1.7 544In32 20 24.5 29 320 1.7 544In50 31 38 45 500 1.7 850K m= Multiplier factor of I3 due to the induced magnetic fieldsI3Trip curvesthermomagnetic releaseT4N 250In 20 to 50 ATMD100001000t [s]1001010.1In=20 I3=544 AIn=32;50 I3=17xIn0.010.1 1101001000I1190 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.2 Networks at particular frequenciesTable 8: Tmax performance T4N 80-250 A TMAI1 (400Hz)I3 setting (MIN=5xIn)T4N 250/320 MIN MED MAX I3 @ 5xIn (50Hz) K m I3 @ 5xIn (400Hz)In80 50 61 72 400 1.7 680In100 63 76.5 90 500 1.7 850In125 79 96 113 625 1.7 1060In160 100 122 144 800 1.7 1360In200 126 153 180 1000 1.7 1700In250 157 191 225 1250 1.7 2125K m= Multiplier factor of I3 due to the induced magnetic fieldsTrip curvesthermomagnetic releaseT4N 250/320In 80 to 250 ATMA100001000t [s]1001010.1In=80 to 320 I3=8.5xIn0.010.1 110100I1<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 191


4 Special applicationsTable 9: Tmax performance T5N 320-500 A TMAK m= Multiplier factor of I3 due to the induced magnetic fields4.2 Networks at particular frequenciesI1 (400Hz)I3 setting (MIN=5xIn)T5N400/630 MIN MED MAX I3 @ 5xIn(50Hz) K m I3 @ 5xIn (400)HzIn320 201 244 288 1600 1.5 2400In400 252 306 360 2000 1.5 3000In500 315 382 450 2500 1.5 3750Trip curvesthermomagnetic releaseT5 N 400/630In 320 to 500 ATMA100001000t [s]1001010.1In=320 to In500 I3=7.5xIn0.010.1 110100I1192 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applicationsTable 10: Tmax performance T5N 320-500 A TMG4.2 Networks at particular frequenciesI1 (400Hz)I3 setting (2.5…5xIn)T5N 400/630 MIN MED MAX I3 @ 2.5..5xIn(50Hz) K m I3 @ 2.5..5xIn (400Hz)In320 201 244 288 800...1600 1.5 1200...2400In400 252 306 360 1000...2000 1.5 1500...3000In500 315 382 450 1250...2500 1.5 1875...3750K m= Multiplier factor of I3 due to the induced magnetic fieldsTrip curvesthermomagnetic releaseT5N 400/630In 320 to 500 ATMG100001000t [s]1001010.1In=320 to 500 I3=3.75..7.5xIn0.010.1 110100I1<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 193


4 Special applicationsTable 11: Tmax performance T6N 630 A TMA4.2 Networks at particular frequenciesT6N630In630I1 (400Hz)I3 = 5√10In (set I3=5In)K mMIN MED MAX I3 (50Hz) I3 (400Hz)397 482 567 3150 1.5 4725K m= Multiplier factor of I3 due to the induced magnetic fieldsTrip curvesthermomagnetic releaseT6N 630In 630 ATMA10 4t [s]10 310 210 1 10 1 In=630 I3=7.5xIn110 -110 -2 10 -1 1 1,05 10 2I1194 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applicationsTable 12: Tmax performance T6N 800 A TMA4.2 Networks at particular frequenciesT6N 800In800I1 (400Hz)I3 = 5-10In (set I3=5In)MIN MED MAX I3 (50Hz) K m I3 (400Hz)504 602 720 4000 1.5 6000K m= Multiplier factor of I3 due to the induced magnetic fieldsTrip curvesthermomagnetic releaseT6N 800In 800 ATMA100001000t [s]1001010.1In=800 I3=7.5xIn0.010.1 110100I1<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 195


4.2 Networks at particular frequencies4 Special applications4.2.2 16 2/3 Hz networksSingle phase distribution with a frequency of 16 2/3 Hz was developed forelectrical traction systems as an alternative to three phase 50 Hz systems, <strong>and</strong>to direct current systems.At low frequencies the thermal tripping threshold is not subject to any derating,while the magnetic threshold requires a correction coefficient k m, as detailedin table 2.The Tmax series thermomagnetic moulded-case circuit-breakers are suitable foruse with frequencies of 16 2/3 Hz; the electrical performance <strong>and</strong> the relevantconnection diagrams are shown below.Table 1: Breaking capacity [kA]Rated currentBreaking capacity [kA]Circuit-breaker [A] 250 V 500 V 750 V 1000 V (1)T1B160 16 ÷160 16 (2P) 20 (3P) 16 (3P) - -T1C160 25 ÷ 160 25 (2P) 30 (3P) 25 (3P) - -T1N160 32 ÷ 160 36 (2P) 40 (3P) 36 (3P) - -T2N160 1.6 ÷ 160 36 (2P) 40 (3P) 36 (3P) - -T2S160 1.6 ÷ 160 50 (2P) 55 (3P) 50 (3P) - -T2H160 1.6 ÷ 160 70 (2P) 85 (3P) 70 (3P) - -T2L160 1.6 ÷ 160 85 (2P) 100 (3P) 85 (3P) 50 (4P) (2) -T3N250 63 ÷ 250 36 (2P) 40 (3P) 36 (3P) - -T3S250 63 ÷ 250 50 (2P) 55 (3P) 50 (3P) - -T4N250/320 20 ÷ 250 36 (2P) 25 (2P) 16 (3P) -T4S250/320 20 ÷ 250 50 (2P) 36 (2P) 25 (3P) -T4H250/320 20 ÷ 250 70 (2P) 50 (2P) 36 (3P) -T4L250/320 20 ÷ 250 100 (2P) 70 (2P) 50 (3P) -T4V250/320 20 ÷ 250 150 (2P) 100 (2P) 70 (3P) -T4V250 32 ÷ 250 40 (4P)T5N400/630 320 ÷ 500 36 (2P) 25 (2P) 16 (3P) -T5S400/630 320 ÷ 500 50 (2P) 36 (2P) 25 (3P) -T5H400/630 320 ÷ 500 70 (2P) 50 (2P) 36 (3P) -T5L400/630 320 ÷ 500 100 (2P) 70 (2P) 50 (3P) -T5V400/630 320 ÷ 500 150 (2P) 100 (2P) 70 (3P) -T5V400/630 400 ÷ 500 40 (4P)T6N630/800 630 ÷ 800 36 (2P) 20 (2P) 16 (3P) -T6S630/800 630 ÷ 800 50 (2P) 35 (2P) 20 (3P) -T6 H630/800 630 ÷ 800 70 (2P) 50 (2P) 36 (3P) -T6 L630/800 630 ÷ 800 100 (2P) 70 (2P) 50 (3P) 40 (4P)(1)1000V version circuit-breakers in dc, with neutral at 100%.(2)Circuit-breakers with neutral at 100%.196 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.2 Networks at particular frequenciesTable 2: k mfactorDiagram A Diagram B-C Diagram D-E-FT1 1 1 -T2 0.9 0.9 0.9T3 0.9 0.9 -T4 0.9 0.9 0.9T5 0.9 0.9 0.9T6 0.9 0.9 0.9Table 3: Possible connections according to the voltage, the type ofdistribution <strong>and</strong> the type of faultNeutral not Neutralgrounded grounded*L-N fault L-E fault250 V 2 poles in series A1 A2 B2250 V 3 poles in series** B1 B2, C B3500 V 2 poles in series A1 A2, B2 B2, C500 V 3 poles in series** B1 B2, C C750 V 3 poles in series B1 B2, C C750 V 4 poles in series*** E-F E1, D E11000 V 4 poles in series E-F E1, C3 E1* In the case of the onlypossible faults being L-Nor L-E (E=Earth) with nonsignificantimpedance, usethe diagrams shown. If bothfaults are possible, use thediagrams valid for L-E fault.** T1, T2, T3 only,*** T2 onlyConnection diagramsDiagram A1Configuration with two poles in series (without neutral connected to earth)• Interruption for phase to neutral fault: 2 poles in series• Interruption for phase to earth fault: not considered(The <strong>installation</strong> method must be such as to make the probability of a secondearth fault negligible)L N L NLoadDiagram A2Configuration with two poles in series (with neutral connected to earth)• Interruption for phase to neutral fault: 2 poles in series• Interruption for phase to earth fault: single pole (same capacity as two polesin series, but limited to 125V)1SDC008038F0001L N LLoad<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 197


4 Special applications4.2 Networks at particular frequenciesDiagram B1Configuration with three poles in series (without neutral connected to earth)• Interruption for phase to neutral fault: 3 poles in series• Interruption for phase to earth fault: not considered(The <strong>installation</strong> method must be such as to make the probability of a secondearth fault negligible)L N L NLoadDiagram B2Configuration with three poles in series (with neutral connected to earth <strong>and</strong>interrupted)• Interruption for phase to neutral fault: 3 poles in series• Interruption for phase to earth fault: 2 poles in series1SDC008039F0001L N LDiagram CLoadConfiguration with three poles in series (with neutral connected to earth butnot interrupted)• Interruption for phase to neutral fault: 3 poles in series• Interruption for phase to earth fault: 3 poles in seriesLNLLoad198 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.2 Networks at particular frequenciesDiagram E-FConfiguration with four poles in series (without neutral connected to earth)• Interruption for phase to neutral fault: 4 poles in series• Interruption for phase to earth fault: not considered(The <strong>installation</strong> method must be such as to make the probability of a secondearth fault negligible)ELNFLNLoadLoad1SDC008042F0001Diagram DConfiguration with four poles in series, on one polarity (with neutral connectedto earth <strong>and</strong> not interrupted)• Interruption for phase to neutral fault: 4 poles in series• Interruption for phase to earth fault: 4 poles in seriesLNLoadDiagram E1Interruption with four poles in series (with neutral connected to earth <strong>and</strong>interrupted)• Interruption for phase to neutral fault: 4 poles in series• Interruption for phase to earth fault: 3 poles in series1SDC008041F0001LNLNLoad1SDC008040F0001<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 199


4 Special applications4.2 Networks at particular frequencies4.3 1000 Vdc <strong>and</strong> 1000 Vac networksExample:Network data:Rated voltage 250 VRated frequency 16 2/3 HzLoad current 120 APhase to neutral short-circuit current 45 kANeutral connected to earthAssuming that the probability of a phase to earth fault is negligible, Table 3shows that connections A2, B2 or B3 may be used.Therefore it is possible to choose a Tmax T2S160 In125 circuit-breaker, whichwith the connection according to diagram A2 (two poles in series) has a breakingcapacity of 50 kA, while according to diagrams B2 or B3 (three poles in series)the breaking capacity is 55 kA (Table 1). To determine the magnetic trip, seefactor k min Table 2. The magnetic threshold will be:I 3= 1250·0.9 = 1125 Awhichever diagram is used.If it is possible to have an earth fault with non significant impedance, the diagramsto be considered (Table 3) are only B2 or B3. In particular, in diagramB2 it can be seen that only 2 poles are working in series, the breaking capacitywill be 50 kA (Table 1), while with diagram B3, with 3 poles working in series,the breaking capacity is 55 kA.The Tmax <strong>and</strong> Emax /E 1000 V <strong>and</strong> 1150 V circuit-breakers are particularlysuitable for use in <strong>installation</strong>s in mines, petrochemical plants <strong>and</strong> servicesconnected to electrical traction (tunnel lighting).5.3.1 1000 V dc networks1000 Vdc Moulded case circuit-breakersGeneral characteristicsThe range of Tmax moulded-case circuit-breakers for use in <strong>installation</strong>s withrated voltage up to 1000 Vdc comply with international st<strong>and</strong>ard IEC 60947-2.The range is fitted with adjustable thermo-magnetic releases <strong>and</strong> is suitable forall <strong>installation</strong> requirements <strong>and</strong> has a range of available settings from 32 A to800 A. The four-pole version circuit-breakers allow high performance levels tobe reached thanks to the series connection of the poles.The circuit breakers in the Tmax 1000 V range maintain the same dimensions<strong>and</strong> fixing points as st<strong>and</strong>ard circuit breakers.These circuit-breakers can also be fitted with the relevant range of st<strong>and</strong>ardaccessories, with the exception of residual current releases for Tmax.In particular it is possible to use conversion kits for removable <strong>and</strong> withdrawablemoving parts <strong>and</strong> various terminal kits.200 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.3 1000 Vdc <strong>and</strong> 1000 Vac networks1000 V dc Moulded-case circuit-breakers T4Rated uninterrupted current, Iu[A] 250PolesNr.Rated operational voltage, Ue [V –]Rated impulse withst<strong>and</strong> voltage, Uimp[kV]Rated insulation voltage, Ui[V]Test voltage at industrial frequency for 1 min. [V]Rated ultimate short-circuit breaking capacity, Icu(4 poles in series) [kA]Rated services short-circuit breaking capacity, Ics(4 poles in series) [kA]Rated short-time withst<strong>and</strong> current for 1 s, Icw [kA]Utilisation category (EN 60947-2)Isolation behaviourIEC 60947-2, EN 60947-2Thermomagnetic releasesTMDThermomagnetic releasesTMAVersionsTerminalsFixedMechanical life [No. operations / operations per hours]Basic dimensions, fixedL [mm]D [mm]H [mm]41000810003500V4020–AFFC Cu20000/240140103.5205T5400/63041000810003500V40205 (400A)B (400A)-A (630A)–up to 500 AFFC Cu20000/120184103.5205T6630/80041000810003500L407.6 (630A) - 10 (800A)B–FF - FC CuAl - R20000/120280103.5268TERMINAL CAPTIONF = FrontEF = Front extendedES = Front extended spreadFC Cu =Front for copper cablesFC CuAl = Front for CuAl cablesR = Rear orientatedHR = Rear in horizontal flat barVR = Rear in vertical flat barMC = MulticableConnection diagramsPossible connection diagrams with reference to the type of distribution systemin which they can be used follow.Networks insulated from earthThe following diagrams can be used (the polarity may be inverted).+-LoadA) 3+1 poles in series (1000 Vdc)1SDC008043F0001<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 201


4 Special applications+4.3 1000 Vdc <strong>and</strong> 1000 Vac networks-Load1SDC008044F0001B) 2+2 poles in series (1000 Vdc)It is assumed that the risk of a double earth fault in which the first fault is downstreamof the breaker on one polarity <strong>and</strong> the second is upstream of the sameswitching device on the opposite polarity is null.In this condition the fault current, which can reach high values, effects only someof the 4 poles necessary to ensure the breaking capacity.It is possible to prevent the possibility of a double earth fault by installing adevice which signals the loss of insulation <strong>and</strong> identifies the position of the firstearth fault, allowing it to be eliminated quickly.Networks with one polarity connected to earthAs the polarity connected to earth does not have to be interrupted (in theexample it is assumed that the polarity connected to earth is negative, althoughthe following is also valid with the polarity inverted), the diagram which showsthe connection of 4 poles in series on the polarity not connected to earth maybe used.+-Load1SDC008045F0001C) 4 poles in series (1000 Vdc)202 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.3 1000 Vdc <strong>and</strong> 1000 Vac networksNetworks with median point of the supply source connected to earthIn the presence of an earth fault of positive or negative polarity, the poles involvedin the fault work at U/2 (500 V); the following diagram must be used:+-Load1SDC008046F0001D) 2+2 poles in series (1000 Vdc)Correction factors for tripping thresholdsWith regard to overload protection, no correction factors need to be applied.However, for the magnetic threshold values in use with 1000 Vdc with thepreviously described applicable diagrams, refer to the corresponding valuesfor alternating current, multiplied by the correction factors given in the followingtable:Circuit-breakerk mT4V 1T5V 0.9T6L 0.9Circuit-breakers with thermomagnetic release for direct currentIn [A] 32 (1) 50 (1) 80 (2) 100 (2) 125 (2) 160 (2) 200 (2) 250 (2) 320 (2) 400 (2) 500 (2) 630 (2) 800 (2)T4V 250 – – – – –T5V 400 – – – – – – – – – – –T5V 630 – – – – – – – – – – – –T6L 630 – – – – – – – – – – – –T6L 800 – – – – – – – – – – – –I3 = (10xI n) [A] 320 500 – – – – – – – – – – –I3 = (5 -10xI n) [A] – – 400÷800 500÷1000 625÷1250 800÷1600 1000÷2000 1250÷2500 1600÷32002000÷4000 2500÷5000 3150÷6300 4000÷8000(1)Thermal threshold adjustable from 0.7 <strong>and</strong> 1 x In; fixed magnetic threshold(2)Thermal threshold adjustable from 0.7 <strong>and</strong> 1 x In; magnetic threshold adjustable between 5 <strong>and</strong> 10 x In.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 203


4 Special applications4.3 1000 Vdc <strong>and</strong> 1000 Vac networksExampleTo ensure the protection of a user supplied with a network having the followingcharacteristics:Rated voltageU r= 1000 VdcShort-circuit currentI k= 18 kALoad currentI b= 420 ANetwork with both polarities insulated from earth.From the table of available settings, the circuit-breaker to be used is:T5V 630 I n=500 four-pole I cu@1000 Vdc = 40 kAThermal trip threshold adjustable from (0.7-1) x I ntherefore from 350 A to 500 Ato be set at 0.84.Magnetic trip threshold adjustable from (5-10) x I nwhich with correction factork m= 0.9 gives the following adjustment range: 2250 A to 4500 A. The magneticthreshold will be adjusted according to any conductors to be protected.The connection of the poles must be as described in diagrams A or B.A device which signals any first earth fault must be present.With the same system data, if the network is carried out with a polarity connectedto earth, the circuit-breaker must be connected as described in diagram C.204 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.3 1000 Vdc <strong>and</strong> 1000 Vac networks1000 Vdc air switch disconnectorsThe air switch disconnectors derived from the Emax air breakers are identifiedby the st<strong>and</strong>ard range code together with the code “/E MS”.These comply with the international St<strong>and</strong>ard IEC 60947-3 <strong>and</strong> are especiallysuitable for use as bus-ties or principle isolators in direct current <strong>installation</strong>s,for example in electrical traction applications.The overall dimensions <strong>and</strong> the fixing points remain unaltered from those ofst<strong>and</strong>ard breakers, <strong>and</strong> they can be fitted with various terminal kits <strong>and</strong> all theaccessories for the Emax range; they are available in both withdrawable <strong>and</strong>fixed versions, <strong>and</strong> in three-pole version (up to 750 Vdc) <strong>and</strong> four-pole (up to1000 Vdc).The withdrawable breakers are assembled with special version fixed parts forapplications of 750/1000 Vdc.The range covers all <strong>installation</strong> requirements up to 1000 Vdc / 6300 A or upto 750 Vdc / 6300 A.A breaking capacity equal to the rated short-time withst<strong>and</strong> current is attributedto these breakers when they are associated with a suitable external relay.The following table shows the available versions <strong>and</strong> their relative electricalperformance:E1B/E MS E2N/E MS E3H/E MS E4H/E MS E6H/E MSRated current (at 40 ϒC) Iu [A] 800 1250 1250 3200 5000[A] 1250 1600 1600 4000 6300[A] 2000 2000[A] 2500[A] 3200Poles 3 4 3 4 3 4 3 4 3 4Rated service voltage Ue [V] 750 1000 750 1000 750 1000 750 1000 750 1000Rated insulation voltage Ui [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000Rated impulse withst<strong>and</strong> voltage Uimp [kV] 12 12 12 12 12 12 12 12 12 12Rated short-time withst<strong>and</strong> current Icw (1s) [kA] 20 20 (1) 25 25 (1) 40 40 (1) 65 65 65 65Rated making capacity Icm 750V DC [kA] 42 42 52.5 52.5 105 105 143 143 143 1431000V DC- 42 - 52.5 - 105 - 143 - 143Note: The breaking capacity Icu, by means of external protection relay, with 500 ms maximum timing, is equal to the value of Icw (1s).(1) The performances at 750 V are:for E1B/E MS Icw = 25 kA,for E2N/E MS Icw = 40 kA <strong>and</strong>for E3H/E MS Icw = 50 kA.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 205


4 Special applications4.3 1000 Vdc <strong>and</strong> 1000 Vac networksConnection diagramsConnection diagrams to be used according to the type of distribution systemfollow.The risk of a double earth fault on different poles is assumed to be zero, thatis, the fault current involves only one part of the breaker poles.Networks insulated from earthThe following diagrams may be used (the polarity may be inverted).+-Load1SDC008047F0001E) 3+1 poles in series (1000 Vdc)+Load-F) 2+2 poles in series (1000 Vdc)1SDC008048F0001206 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications+-4.3 1000 Vdc <strong>and</strong> 1000 Vac networksLoad1SDC008050F0001G) 2+1 poles in series (750 Vdc)Networks with one polarity connected to earthThe polarity connected to earth does not have to be interrupted (in the examplesit is assumed that the polarity connected to earth is negative):+-1SDC008049F0001H) 4 poles in series (1000 Vdc)Load+-Load1SDC008051F0001I) 3 poles in series (750 Vdc)Networks with median point of the supply source connected to earthOnly four-pole breakers may be used as in the configuration shown in diagram F).<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 207


4 Special applications5.3.2 1000 Vac networks4.3 1000 Vdc <strong>and</strong> 1000 Vac networksMoulded-case circuit-breakers up to 1150 VacGeneral characteristicsThe circuit-breakers in the Tmax range up to 1150 V comply with the internationalst<strong>and</strong>ard IEC 60947-2.These circuit breakers can be fitted with thermo-magnetic releases (for thesmaller sizes) <strong>and</strong> with electronic releases. All <strong>installation</strong> requirements can bemet with a range of available settings from 32 A to 800 A <strong>and</strong> with breakingcapacity up to 20 kA at 1150 Vac.Moulded-case circuit-breakers up to 1150 VacRated uninterrupted current, IuPolesRated service voltage, Ue (ac) 50-60HzRated impulse withst<strong>and</strong> voltage, UimpRated insulation voltage, UiTest voltage at industrial frequency for 1 min.Rated ultimate short-circuit breaking capacity, IcuRated service short-circuit breaking capacity, IcsRated short-circuit making capacity IcmUtilisation category (EN 60947-2)Isolation behavourReference St<strong>and</strong>ardThermomagnetic releasesElectronic releasesTerminals(ac) 50-60 Hz 1000 V(ac) 50-60 Hz 1150 V(ac) 50-60 Hz 1000 V(ac) 50-60 Hz 1150 V(ac) 50-60 Hz 1000 V(ac) 50-60 Hz 1150 V[A]Nr.[V][kV][V][V][kA][kA][kA][kA][kA][kA]TMDTMAPR221DS/LSPR221DS/IPR222DS/P-LSIPR222DS/P-LSIGPR222DS/PD-LSIPR222DS/PD-LSIGPR222MP208 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>VersionMechanical life [No. operations ][No. operations per hours]Basic dimension-fixed version (5)3 poles W [mm]4 poles W [mm]D [mm]H [mm]Weigth fixed 3/4 poles [kg]plug-in 3/4 poles [kg]withdrawable 3/4 poles [kg](1)Power supply only from above(2)Icw=5kA(3)Icw=7.6kA (630A) - 10kA (800A)(4)Tmax T5630 is only available in the fixed version(5)Circuit-breaker without high terminal covers


4 Special applications4.3 1000 Vdc <strong>and</strong> 1000 Vac networksThe circuit-breakers in the range up to 1150 V maintain the same dimension asst<strong>and</strong>ard circuit breakers.These circuit-breakers can also be fitted with the relevant range of st<strong>and</strong>ardaccessories, with the exception of residual current releases.The following tables show the electrical characteristics of the range:T42503, 41000 115081000 11503500LV12 201212 12624 4024AT5400/6303, 41000 115081000 11503500L V (1)12 201210 10624 4024B (400 A) (2) /A (630 A)T6630/8003, 41000810003500L (1)12624B (3)--IEC 60947-2IEC 60947-2- --IEC 60947-2--FC CuF, P, W F20000240105140103.52052.35/3.05 2.35/3.053.6/4.653.85/4.9-FC CuF, P, W (4) F20000120140184103.52053.25/4.15 3.25/4.155.15/6.655.4/6.9-F-FC CuAI-RF20000120210280103.52689.5/12TERMINAL CAPTIONF=FrontFC Cu= Front for copper cablesFC CuAl=Front for CuAl cablesR= Rear orientated<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 209


4 Special applications4.3 1000 Vdc <strong>and</strong> 1000 Vac networksThe following tables show the available releases.Circuit-breakers with electronic release for alternating currentsIn100 In250 In320 In400 In630 In800T4 250 – – – –T5 400 – – – –T5 630 – – – – –T6L 630 – – – – –T6L 800 – – – – –I 3(1÷10x In) [A] (1) 100÷1000 250÷2500 320÷3200 400÷4000 630÷6300 800÷8000I 3(1.5÷12 x In) [A] (2) 150÷1200 375÷3000 480÷3840 600÷4800 945÷7560 1200÷9600(1)PR221(2)PR222Circuit-breakers with thermomagnetic release for alternating currentsIn [A] 32 (1) 50 (1) 80 (2) 100 (2) 125 (2) 160 (2) 200 (2) 250 (2) 320 (2) 400 (2) 500 (2) 630 (2) 800 (2)T4V 250 – – – – –T5V 400 – – – – – – – – – – –T5V 630 – – – – – – – – – – – –T6L 630 – – – – – – – – – – – –T6L 800 – – – – – – – – – – – –I 3= (10xI n) [A] 320 500 – – – – – – – – – – –I 3= (5 -10xI n) [A] – – 400÷800 500÷1000 625÷1250 800÷1600 1000÷2000 1250÷2500 1600÷3200 2000÷4000 2500÷5000 31500÷6300 4000÷8000(1)Thermal threshold adjustable from 0.7 <strong>and</strong> 1 x In; fixed magnetic threshold(2)Thermal threshold adjustable from 0.7 <strong>and</strong> 1 x In; magnetic threshold adjustable between 5 <strong>and</strong> 10 x In.Air circuit-breakers <strong>and</strong> switch disconnectors up to1150 VacFor 1150 V alternating current applications, the following devices are available:• Circuit-breakers in compliance with St<strong>and</strong>ard IEC 60947-2The special version breakers up to 1150 Vac are identified by the st<strong>and</strong>ardrange code together with the suffix “/E”, <strong>and</strong> are derived from the correspondentEmax st<strong>and</strong>ard breakers <strong>and</strong> retain the same versions, accessories <strong>and</strong>overall dimensions.The Emax range of breakers is available in both withdrawable <strong>and</strong> fixed versionswith three <strong>and</strong> four poles, <strong>and</strong> can be fitted with accessories <strong>and</strong> equippedwith the full range of electronic releases <strong>and</strong> microprocessors (PR332/P-PR333/P-PR121-PR122-PR123).• Switch disconnectors in compliance with St<strong>and</strong>ard IEC 60947-3These breakers are identified by the code of the st<strong>and</strong>ard range, from whichthey are derived, together with the suffix “/E MS”. Three-pole <strong>and</strong> four-poleversions are available in both withdrawable <strong>and</strong> fixed versions with the samedimensions, accessory characteristics <strong>and</strong> <strong>installation</strong> as the st<strong>and</strong>ard switchdisconnectors.210 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4.3 1000 Vdc <strong>and</strong> 1000 Vac networks4 Special applicationsThe following tables show the electrical characteristics of the devices:Air circuit-breakers (up to 1150 Vac)XIB/E E2B/E E2N/E E3H/E E4H/E E6H/E630/800Rated uninterruptedcurrent (at 40 °C) Iu[A]1000/12501600 1600 2000 1250 1600 2000 1250 1600 2000 2500 3200 3200 4000 4000 5000 6300Rated service voltage Ue [V~] 1000 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150 1150Rated insulation voltage Ui [V~] 1000 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250Rated ultimate breaking capacityunder short-circuit Icu1000 V [kA] 20 20 20 30 30 30 50 50 50 50 50 65 65 65 65 651150 V [kA] 20 20 30 30 30 30 30 30 30 30 65 65 65 65 65Rated service breaking capacityunder short-circuit Ics1000 V [kA] 20 20 20 30 30 30 50 50 50 50 50 65 65 65 65 651150 V [kA] 20 20 30 30 30 30 30 30 30 30 65 65 65 65 65Rated short-time withst<strong>and</strong>current Icw (1s) [kA] 20 20 20 30 30 30 50 (*) 50 (*) 50 (*) 50 (*) 50 (*) 65 65 65 65 65Rated making capacity undershort-circuit (peak value) Icm1000 V [kA] 40 40 40 63 63 63 105 105 105 105 105 143 143 143 143 1431150 V [kA] 40 40 63 63 63 63 63 63 63 63 143 143 143 143 143(*)30 kA @ 1150 VAir switch disconnectors (up to 1150 Vac)XIB/E MS E2B/E MS E2N/E MS E3H/E MS E4H/E MS E6H/E MSRated current (at 40 °C) Iu [A] 1000 1600 1250 1250 3200 4000[A] 1250 2000 1600 1600 4000 5000[A] 1600 2000 2000 6300[A] 2500[A] 3200Poles 3/4 3/4 3/4 3/4 3/4 3/4Rated service voltage Ue [V] 1000 1150 1150 1150 1150 1150Rated insulation voltage Ui [V] 1000 1250 1250 1250 1250 1250Rated impulse withst<strong>and</strong> voltage Uimp [kV] 12 12 12 12 12 12Rated short-time withst<strong>and</strong> voltage Icw (1s) [kA] 20 20 30 30 (1) 63 65Rated making capacity under short-circuit (peak value) Icm [kA] 40 40 63 63 (2) 143 143Note: The breaking capacity Icu, by means of external protection relay, with 500 msmaximum timing, is equal to the value of Icw (1s).(1)The performance at 1000V is 50 kA(2)The performance at 1000V is 105 kA<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 211


4.4 Automatic Transfer Switches4 Special applicationsIn the electrical plants, where a high reliability is required from the power supplysource because the operation cycle cannot be interrupted <strong>and</strong> the risk of a lackof power supply is unacceptable, an emergency line supply is indispensableto avoid the loss of large quantities of data, damages to working processes,plant stops etc.For these reasons, transfer switch devices are used mainly for:• power supply of hotels <strong>and</strong> airports;• surgical rooms <strong>and</strong> primary services in hospitals;• power supply of UPS groups;• databanks, telecommunication systems, PC rooms;• power supply of industrial lines for continuous processes.ATS020 (in the versions 021 <strong>and</strong> 022) is the solution offered by <strong>ABB</strong>: it is anautomatic transfer switch system with micro-processor based technology whichallows switching of the supply from the normal line (N-Line) to the emergency line(E-Line) in case any of the following anomalies occurs on the main network:• overvoltages <strong>and</strong> voltage dips;• lack of one of the phases;• asymmetries in the phase cycle;• frequency values out of the setting range.Then, when the network st<strong>and</strong>ard parameters are recovered, the systemswitches again the power supply to the main network (N-Line).ATS020 is used in systems with two distinct supply lines connected to thesame busbar system <strong>and</strong> functioning independently (“isl<strong>and</strong> condition”): the firstone is used as normal supply line, the second is used for emergency powersupply from a generator system. With ATS022 is also possible to provide thesystem with a device to disconnect the non-priority loads when the network issupplied from the E-Line.The following scheme shows a plant having a safety auxiliary power supply:Normal network(N-Line)GEmergency Generator(E-Line)-QF1Non-vital loadsATS022SD-QF2Vital loads1SDC008038F0201212 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


4 Special applications4.4 Automatic transfer switchesATS020 device is interfaced by means of appropriate terminals:- with the protection circuit-breakers of the N-Line <strong>and</strong> of the E-Line, motorized<strong>and</strong> mechanically interlocked, to detect their status <strong>and</strong> send opening <strong>and</strong>closing comm<strong>and</strong>s according to the set time delays;- with the <strong>control</strong> card of the Gen set to <strong>control</strong> its status <strong>and</strong> send start <strong>and</strong>stop comm<strong>and</strong>s;- with any further signals coming from the plant in order to block the switchinglogic;- with the N-Line to detect any possible anomaly <strong>and</strong> with the E-Line to verifythe voltage presence;- with an additional device to disconnect non-priority loads;- with an auxiliary power supply at 24 Vdc ± 20% (or 48 Vdc ± 10%). This supplysource shall be present also in case of lack of voltage on both lines (N-Line<strong>and</strong> E-Line).<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 213


5.1 <strong>Electrical</strong> switchboards5 SwitchboardsAn electrical assembly is a combination of more protection <strong>and</strong> switchingdevices, grouped together in one or more adjacent cases (column).In an assembly the following parts can be distinguished: a case, called enclosureby the St<strong>and</strong>ards, (it has the function of support <strong>and</strong> mechanical protection ofthe housed components), <strong>and</strong> the electrical equipment, formed by the internalconnections <strong>and</strong> by the incoming <strong>and</strong> outgoing terminals for the connectionsto the plant). As all the components of an electrical system, also assembliesshall comply with the relevant product st<strong>and</strong>ard.As far as St<strong>and</strong>ards are concerned, an evolution has occurred with thereplacement of the former IEC 60439-1 with the Stds. IEC 61439-1 <strong>and</strong> IEC61439-2. The recent publication of the new St<strong>and</strong>ard IEC 61439 has imposedan evolution <strong>and</strong> a refinement of the concept of switchgear <strong>and</strong> <strong>control</strong>gearassembly, which has remained actually unchanged since 1990 when “FactoryAssembled Boards” concept was replaced by TTA (Type-Tested Assemblies)<strong>and</strong> PTTA (Partially-Type-Tested Assemblies).The new St<strong>and</strong>ard still considers an assembly as a st<strong>and</strong>ard component of theplant, such as a circuit-breaker or a plug-<strong>and</strong>-socket, although it is constitutedby the assembling of more apparatus, grouped together in one or more adjacentunits (columns).In an assembly the following parts can be distinguished: a case, called enclosureby the St<strong>and</strong>ards, (it has the function of support <strong>and</strong> mechanical protection ofthe housed components), <strong>and</strong> the electrical equipment, formed by the internalconnections <strong>and</strong> by the incoming <strong>and</strong> outgoing terminals for the connectionsto the plant). Such system shall be assembled in order to meet the safetyrequirements <strong>and</strong> satisfy as much as possible the functions for which it hasbeen designed.From this point of view, in Italy, the Law 46/90 <strong>and</strong> now the Ministerial Decree37/08 oblige manufacturers to undersign a declaration of conformity to therule for each action carried out on a plant excepted for ordinary maintenance.In the m<strong>and</strong>atory enclosures to this Declaration, in the list of the materialsinstalled or changed, the assembly which has undergone actions is frequentlymentioned.As already known, to comply with the Article 2 of the Italian Law 186 dated1st March 1968, the equipment <strong>and</strong> plants realized in compliance with CEI ENSt<strong>and</strong>ards are considered in accordance with the “rule of the art”. Therefore,as all the components of an electrical plant, also the assembly shall complywith the relevant product St<strong>and</strong>ard. On this subject Stds. IEC 61439-1 <strong>and</strong> 2have recently entered in force at international level, acknowledged within thecorresponding Italian St<strong>and</strong>ards CEI EN 61439-1 <strong>and</strong> 2.214 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


5 Switchboards5.1 <strong>Electrical</strong> switchboardsThese St<strong>and</strong>ards apply to the low voltage assemblies for which the rated voltagedoes not exceed 1000 V in case of a.c. or 1500 V in case of d.c.).IEC 61439-1 gives the general rules for LV assemblies, whilst the other partsto be issued concern the specific typologies of assemblies <strong>and</strong> are to be readtogether with the general rules. The envisaged parts are the following ones:- IEC 61439-2: “Power switchgear <strong>and</strong> <strong>control</strong>gear”;- IEC 61439-3: “Distribution boards” (to supersede IEC 60439-3);- IEC 61439-4: “Assemblies for construction sites” (to supersede IEC 60439-4);- IEC 61439-5: “Assemblies for power distribution” (to supersede IEC 60439-5);- IEC 61439-6: “Busbar trunking systems” (to supersede IEC 60439-2).Two other documents published by IEC about swithchgear <strong>and</strong> <strong>control</strong>gearassemblies are still available:- the Std. IEC 60890 which represents a method of temperature rise assessmentby calculation or by the application of design rules;- the Std. IEC/TR 1117 which represents a method for assessing the shortcircuitwithst<strong>and</strong> strength by calculation or by the application of designrules.The Std. IEC 61439-1As already said, the new package of St<strong>and</strong>ards, defined by IEC throughcode 61439, consists of the basic St<strong>and</strong>ard 61439-1 <strong>and</strong> by the specificSt<strong>and</strong>ards referred to the assembly typology. The first St<strong>and</strong>ard deals with thecharacteristics, the properties <strong>and</strong> the performances which are in common toall the assemblies then considered in the relevant specific St<strong>and</strong>ard.This is the present structure of the new IEC 61439:1) IEC 61439-1: “Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear assemblies -Part 1: “General rules”;2) IEC 61439-2: “Power switchgear <strong>and</strong> <strong>control</strong>gear”;3) IEC 61439-3: “Distribution boards”;4) IEC 61439-4: “Assemblies for construction sites”;5) IEC 61439-5: “Assemblies for power distribution”;6) IEC 61439-6: “Busbar trunking systems”.As regards the declaration of conformity, each specific assembly typology shallbe declared in compliance with the relevant product st<strong>and</strong>ard (that is the powerswitchgear <strong>and</strong> <strong>control</strong>gear shall be declared complying with IEC 61439-2; thedistribution boards in compliance with IEC 61439-3).<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 215


5 Switchboards5.1 <strong>Electrical</strong> switchboardsThe passage, from the previous Std. IEC 60439 to the present IEC 61439, shalloccur as follows: The “old” Std. 60439-1 shall be gradually superseded by thenew St<strong>and</strong>ards 61439-1 <strong>and</strong> 2, which are already available, but shall remain inforce up to 31st October 2014 for the Power Switchgear <strong>and</strong> Controlgear (alsocalled PSC-ASSEMBLIES). After that date, the new PSC assemblies shall haveto comply only with the new St<strong>and</strong>ards.The period of validity for the Std. 60439-1 <strong>and</strong> for the other ones 60439-X extendsup to 2014, for the construction of the other special assemblies (constructionsites, busbar trunking systems, distribution, etc.), since for the time being thesenew st<strong>and</strong>ards are only envisaged, scheduled but non available yet.The basic St<strong>and</strong>ard establishes the requirements for the construction, safety <strong>and</strong>maintenance of the electrical assemblies by identifying the rated characteristics,the service environmental conditions, the mechanical <strong>and</strong> electrical requirements<strong>and</strong> the prescriptions relevant to the performances.The former Std. dated 1990 divided the assemblies into two types, definingthem TTA (type-tested assemblies) <strong>and</strong> PTTA (partially type-tested assemblies),according to their total or partial compliance with the laboratory type tests.The new St<strong>and</strong>ard eliminates this dualism replacing it with the concept of“conforming” assembly, that is any assembly which complies with the designverifications prescribed by the St<strong>and</strong>ard itself.To this purpose, the St<strong>and</strong>ard introduces three different but equivalent types ofverification of requirements of conformity for an assembly; they are:1) verification by laboratory testing (formerly called routine tests <strong>and</strong> now verification by testing);2) verification by calculation (using old <strong>and</strong> new algorithms);3) verification by satisfying design rules (analysis <strong>and</strong> considerations whichare independent from the tests; verification by physical/analytical criteria ordesign deductions).The different characteristics (temperature-rise, insulation, corrosion etc.) canbe guaranteed by using any of these three methods; following one way or theother to guarantee the conformity of the assembly is unimportant.Since it is not always possible to choose possible one of the three methods,Table D.1 of the Annex D of the St<strong>and</strong>ard (see Table on the following page) listsfor each characteristic to be verified which one of the three types of verificationmay be used.216 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


5.1 <strong>Electrical</strong> switchboards5 SwitchboardsNo.Characteristics to be verifiedClauses orsubclausesVerification options availableVerificationby testingVerificationby calculationVerificationbysatisfyingdesign rules1 Strength of materials <strong>and</strong> parts of the assembly: 10.2Resistance to corrosion 10.2.2 YES NO NOProperties of insulating materials: 10.2.3Thermal stability 10.2.3.1 YES NO NOResistance of insulating material to normal heat 10.2.3.2 YES NO NOResistance of insulating materials to abnormal heat<strong>and</strong> fire due to internal electric effects 10.2.3.3 YES NO NOResistance to ultraviolet (UV) radiationLifting 10.2.4 YES NO NOMechanical impact 10.2.4 YES NO NOMarking 10.2.6 YES NO NO10.2.7 YES NO NO2 Degree of protection of the enclosures 10.3 YES NO YES3 Clearances <strong>and</strong> creepage distances 10.4 YES YES YES4 <strong>Protection</strong> against electric shock <strong>and</strong> integrity ofprotective circuits: 10.5Effective continuity between the exposed conductiveparts of the assembly <strong>and</strong> the protective circuit 10.5.2 YES NO NOEffectiveness of the assembly for external faults 10.5.3 YES YES YES5 Installation of switching devices <strong>and</strong> components 10.6 NO NO YES6 Internal electrical circuits <strong>and</strong> connections 10.7 NO NO YES7 Terminals for external conductors 10.8 NO NO YES8 Dielectric properties: 10.9Power-frequency withst<strong>and</strong> voltage 10.9.2 YES NO NOImpulse withst<strong>and</strong> voltage 10.9.3 YES NO YES9 Temperature-rise limits 10.10 YES YES YES10 Short-circuit withst<strong>and</strong> strength 10.11 YES YES YES11 Electromagnetic compatibility (EMC) 10.12 YES NO YES12 Mechanical operation 10.13 YES NO NO<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 217


5 Switchboards5.1 <strong>Electrical</strong> switchboardsAs it can be noticed, for some characteristics, such as the resistance to corrosionor to mechanical impact only the verification by testing is accepted; instead,for other characteristics such as temperature-rise <strong>and</strong> short-circuit, the threeverification modalities are all accepted: testing, calculation or design rules.Another important change in the new St<strong>and</strong>ard is the better specification ofthe manufacturer figure. In particular two “ways of being” are defined for themanufacturer: the “original” manufacturer <strong>and</strong> the “assembly” manufacturer.The first one is the subject who has carried out initially the original design ofthe series to which belongs the assembly to be completed <strong>and</strong> to this purposehas carried out the design verifications (formerly type tests), the derivationcalculations or the design rules, to cover all the available possibilities for theassembly verification.It is evident that the highest <strong>and</strong> most performing the layouts that the originalmanufacturer is able to “st<strong>and</strong>ardize” <strong>and</strong> to propose, the greater the possibilitiesfor him to have his assemblies constructed <strong>and</strong> consequently to makea good profit. The second one, identified as “assembly” manufacturer, is thesubject who really builds the assembly, that is who gets the different parts <strong>and</strong>components <strong>and</strong> mounts them as required, thus carrying out the completedassembly, mounted <strong>and</strong> wired, exploiting one of the design opportunity alreadymentioned, ready to use, offered by the “original” manufacturer.The St<strong>and</strong>ard still accepts that some phases of the fitting of assemblies arecarried out also out of the manufacturer’s laboratory or workshop (on site or onmachine board), but the Std. instructions must be complied with.From an operational point of view, the manufacturers <strong>and</strong> the panel builders,i.e. the end manufacturers, could use as usual the products sold in kits <strong>and</strong>included in the catalogues of the “original” manufacturers, for assembling accordingto the arrangement they need.To summarize, the “original” manufacturer shall:- design (calculate, design <strong>and</strong> carry out) the desired assembly line;- test some prototypes belonging to that assembly line;- pass these tests to demonstrate the compliance with the m<strong>and</strong>atory prescriptionsof the St<strong>and</strong>ard;- derive from the tests other configurations by calculation or other evaluationsor measurements;- add other configurations obtained without testing but thanks to suitable“design rules”;- collect all the above mentioned information <strong>and</strong> make them available for theend customer by means of catalogues, slide rules or software, so that hecan build the new assembly <strong>and</strong> use it <strong>and</strong> manage it as best as possible, bycarrying out the suitable <strong>control</strong>s <strong>and</strong> maintenance.218 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


5 Switchboards5.1 <strong>Electrical</strong> switchboardsThe list of the design verifications prescribed by the St<strong>and</strong>ard under the responsibilityof the “original” manufacturer who, in compliance with Table of page 217,shall decide how to perform them includes the following:Verification of the characteristics relevant to construction:- Strength of materials <strong>and</strong> parts of the assembly;- Degrees of protection IP of the assembly;- Clearances <strong>and</strong> creepage distances;- <strong>Protection</strong> against electric shock <strong>and</strong> integrity of protective circuits;- Incorporation of switching devices <strong>and</strong> of components;- Internal electrical circuits <strong>and</strong> connections;- Terminals for external conductors.Verifications of the characteristic relevant to the performance:- Dielectric properties (power-frequency withst<strong>and</strong> voltage at 50 Hz <strong>and</strong> impulsewithst<strong>and</strong> voltage);- Verification of temperature-rise limits;- Short-circuit withst<strong>and</strong> strength;- Electromagnetic compatibility (EMC);- Mechanical operation.Instead, the “assembly” manufacturer shall have the responsibility of:- the choice <strong>and</strong> the fitting of the components in full compliance with the giveninstructions;- the performance of the routine verification on each manufactured assembly;- the assembly certification.The list of the routine tests prescribed by the St<strong>and</strong>ard under the responsibilityof the “assembly” manufacturer includes the following:Characteristics pertaining to construction:- Degrees of protection IP of the enclosure;- Clearances <strong>and</strong> creepage distances;- <strong>Protection</strong> against electric shock <strong>and</strong> integrity of protective circuits;- Incorporation of switching devices <strong>and</strong> of components;- Internal electrical circuits <strong>and</strong> connections;- Terminals for external conductors;- Mechanical operation.Characteristics relevant to the performance:- Dielectric properties (power-frequency withst<strong>and</strong> voltage at 50 Hz <strong>and</strong> impulsewithst<strong>and</strong> voltage);- Wiring <strong>and</strong> operation.These verifications can be carried out in any sequence.The fact that the routine verifications are carried out by the “assembly” manufacturerdoes not exempt the panel builder from verifying them after the transport<strong>and</strong> the erection of the assembly.The main changes <strong>and</strong> news, introduced by the IEC 61439 in comparison with formerIEC 60439, can be summarized with the diagrams shown in the next Figure.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 219


5 Switchboards5.1 <strong>Electrical</strong> switchboardsSt<strong>and</strong>ard IEC 60439-1 St<strong>and</strong>ard IEC 61439-1-2Low-voltage switchgear<strong>and</strong> <strong>control</strong>gear assembliesLow-voltage switchgear<strong>and</strong> <strong>control</strong>gear assembliesManufacturer of the assemblyType-testedassemblies (AS)Tests <strong>and</strong> verificationsRoutine testsPartially type-testedassemblies (ANS)Assembly complyingwith the St<strong>and</strong>ard IEC 60439-1AssemblerOriginal manufacturerAssembly manufacturer Original manufacturerDesign verifications to be performedby the original manufacturerVerificationby testingVerificationbycalculationAssemblyRoutine verificationAssembly complying withthe St<strong>and</strong>ard IEC 61439-1-2Verificationby designrules220 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


5 Switchboards5.1 <strong>Electrical</strong> switchboardsElementCode lettersFirst characteristicnumeralDegrees of protectionThe degree of protection IP indicates a level of protection provided by theassembly against access to or contact with live parts, against ingress of solidforeign bodies <strong>and</strong> against the ingress of liquid. The IP code is the system usedfor the identification of the degree of protection, in compliance with the requirementsof St<strong>and</strong>ard IEC 60529. Unless otherwise specified by the manufacturer,the degree of protection applies to the complete switchboard, assembled <strong>and</strong>installed for normal use (with door closed).The manufacturer shall also state the degree of protection applicable to particularconfigurations which may arise in service, such as the degree of protection withthe door open or with devices removed or withdrawn.Elements of the IP Code <strong>and</strong> their meaningsNumerialsor lettersIPMeaning for theprotection of equipmentAgainst ingress of the solidforeign objectsMeaning for theprotection of personsAgainst access tohazardous parts withCl.5Ref.SecondcharacteristicnumeralAdditional letter(optional)0123456012345678(non-protected)≥ 50 mm diameter≥ 12.5 mm diameter≥ 2.5 mm diameter≥ 1.0 mm diameterdust-protecteddust-tightAgainst ingress of waterwith harmful effects(non-protected)vertically drippingdripping (15° tilted)sprayingsplashingjettingpowerful jettingtemporary immersioncontinuous immersion(non-protected)back of h<strong>and</strong>fingertoolwirewirewireAgainst access tohazardous parts withCl.6Cl.7Supplementaryletter (optional)ABCDSupplemetary informationspecific to:back of h<strong>and</strong>fingertoolwireCl.8HMSWHight voltage apparatusMotion during water testStationary during water testWeather conditions<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 221


5 Switchboards5.1 <strong>Electrical</strong> switchboardsForm of separation <strong>and</strong> classification of switchboardsForms of internal separationBy form of separation it is meant the type of subdivision provided within theswitchboard. Separation by means of barriers or partitions (metallic or insulating)may have the function to:- provide protection against direct contact (at least IPXXB) in the case of accessto a part of the switchboard which is not live, with respect to the rest of theswitchboard which remains live;- reduce the risk of starting or propagating an internal arc;- impede the passage of solid bodies between different parts of the switchboard(degree of protection of at least IP2X).A partition is a separation element between two parts, while a barrier protectsthe operator from direct contact <strong>and</strong> from arcing effects from any interruptiondevices in the normal access direction.The following table from St<strong>and</strong>ard IEC 61439-1-2 highlights typical forms ofseparation which can be obtained using barriers or partitions:No separationMain criteriaSeparation of busbars from the functional unitsSeparation of busbars from the functional units <strong>and</strong>separation of all functional units from one another.Separation of the terminals for external conductorsfrom the functional units, but not from each otherSeparation of busbars from the functional units <strong>and</strong>separation of all functional units from one another,including the terminals for external conductorswhich are an integral part of the functional unitSubcriteriaTerminals for external conductors notseparated from busbarsTerminals for external conductorsseparated from busbarsTerminals for external conductors notseparated from busbarsTerminals for external conductorsseparated from busbarsTerminals for external conductors in thesame compartment as the associatedfunctional unitTerminals for external conductors not inthe same compartment as the associatedfunctional unit, but in individual, separate,enclosed protected spaces orcompartmentsFormForm 1Form 2aForm 2bForm 3aForm 3bForm 4aForm 4b222 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


5 Switchboards5.1 <strong>Electrical</strong> switchboardsSimbols Form 1Form 2Form 3Form 4(no internal segregation)(segregation of the busbarsfrom the functional units)Form 2aTerminals not separated fromthe busbars(separation of the busbars fromthe functional units + separationof the functional units from eachother)Form 3aTerminals not separated fromthe busbars((separation of the busbars fromthe functional units + separationof the functional units from eachother + separation of theterminals from each other)Form 4aTerminals in the samecompartment as the associatedfunctional unitabdcForm 2bTerminals separated from thebusbarsForm 3bTerminals separated from thebusbarsForm 4bTerminals in the samecompartment as the associatedfunctional unitCaptiona Housingb Internal segregationc Functional units including the terminals for the associatedexternal conductorsd Busbars, including the distribution busbars1SDC008039F0201ClassificationDifferent classifications of electrical switchboard exist, depending on a rangeof factors.Based on construction type, St<strong>and</strong>ard IEC 61439-1 firstly distinguishes betweenopen <strong>and</strong> enclosed assemblies.A switchboard is enclosed when it comprises protective panels on all sides,providing a degree of protection against direct contact of at least IPXXB. Switchboardsused in normal environments must be enclosed.Open switchboards, with or without front covering, which have the live partsaccessible. These switchboards may only be used in electrical plants.With regard to external design, switchboards are divided into the followingcategories:- Cubicle-type assemblyUsed for large scale <strong>control</strong> <strong>and</strong> distribution equipment; multi-cubicle-typeassembly can be obtained by placing cubicles side by side.- Desk-type assemblyUsed for the <strong>control</strong> of machinery or complex systems in the mechanical, iron<strong>and</strong> steel, <strong>and</strong> chemical industries.- Box-type assemblyCharacterized by wall mounting, either mounted on a wall or flush-fitting; theseswitchboards are generally used for distribution at department or zone levelin industrial environments <strong>and</strong> in the tertiary sector.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 223


5 Switchboards5.1 <strong>Electrical</strong> switchboards- Multi-box-type assemblyEach box, generally protected <strong>and</strong> flanged, contains a functional unit whichmay be an automatic circuit-breaker, a starter, a socket complete with lockingswitch or circuit-breaker.With regard to the intended function, switchboards may be divided into thefollowing types:- Main distribution boardsMain distribution boards are generally installed immediately downstream of MV/LV transformers, or of generators; they are also termed power centres. Maindistribution boards comprise one or more incoming units, busbar connectors,<strong>and</strong> a relatively smaller number of output units.- Secondary distribution boardsSecondary distribution boards include a wide range of switchboards for thedistribution of power, <strong>and</strong> are equipped with a single input unit <strong>and</strong> numerousoutput units.- Motor operation boardsMotor <strong>control</strong> boards are designed for the <strong>control</strong> <strong>and</strong> centralised protection ofmotors: therefore they comprise the relative coordinated devices for operation<strong>and</strong> protection, <strong>and</strong> auxiliary <strong>control</strong> <strong>and</strong> signalling devices.- Control, measurement <strong>and</strong> protection boardsControl, measurement <strong>and</strong> protection boards generally consist of deskscontaining mainly equipment for the <strong>control</strong>, monitoring <strong>and</strong> measurementof industrial processes <strong>and</strong> systems.- Machine-side boardsMachine-side boards are functionally similar to the above; their role is to providean interface between the machine with the power supply <strong>and</strong> the operator.- Assemblies for construction sites (ASC)Assemblies for construction sites may be of different sizes, from a simple plug<strong>and</strong> socket assembly to true distribution boards with enclosures of metal orinsulating material. They are generally mobile or, in any case, transportable.Verification of the temperature-rise limits insidean assemblyIntroductionThe verification of the temperature-rise limits imposed by the St<strong>and</strong>ardIEC 61439-1 can be carried out according to one or more of the followingmethods:- verification test with current (in laboratory);- deduction from design rules;- algebraic calculation.224 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


5 Switchboards5.1 <strong>Electrical</strong> switchboardsParts of assembliesTemperature-rise KBuilt-in components a)(*) In accordance with the relevant product St<strong>and</strong>ard requirements for theindividual components or, in accordance with the manufacturer’s instructionsf), taking into consideration the temperature in the assemblyTerminals for external insulated conductors 70 b)Busbars <strong>and</strong> conductorsLimited by:- mechanical strength of conducting material g) ;- possible effects on adjacent equipment;- permissible temperature limit of the insulating materials in contact with the conductor;- the effect of the temperature of the conductor on the apparatus connected to it;- for plug-in contacts, nature <strong>and</strong> surface treatment of the contact material.Manual operating means:- of metal 15 c)- of insulating materials 25 c)Accessible external enclosures <strong>and</strong> covers:- metal surfaces 30 d)- insulating surfaces 40 d)Discrete arrangements of plug <strong>and</strong> socket-typeconnectionsAs a matter of fact, the St<strong>and</strong>ard IEC 61439-1 prescribes compliance withthe same temperature-rise limits of the previous version, limits which must notbe exceeded during the temperature-rise test. These temperature-rise limitsare applied taking into consideration an ambient temperature which must notexceed +40 °C <strong>and</strong> its average value referred to a 24 hour period shall notexceed +35 °C.The following Table shows for the different components of the assembly, thetemperature-rise limits given by the St<strong>and</strong>ard.Determined by the limits of those components of the related equipment ofwhich they form part e)a)The term “built-in components” means:- conventional switchgear <strong>and</strong> <strong>control</strong>gear;- electronic sub-assemblies (e.g. rectifier bridge, printed circuit);- parts of the equipment (e.g. regulator, stabilized power supply unit, operational amplifier).b)The temperature rise limit of 70 K is a value based on the conventional test of 10.10. An ASSEMBLY used or testedunder <strong>installation</strong> conditions may have connections, the type, nature <strong>and</strong> disposition of which will not be the same asthose adopted for the test, <strong>and</strong> a different temperature rise of terminals may result <strong>and</strong> may be required or accepted.Where terminals of the built-in component are also the terminals for external insulated conductors, the lower of the correspondingtemperature-rise limits shall be applied.c)Manual operating means within assemblies which are only accessible after the assembly has been opened, for exampledraw-out h<strong>and</strong>les, which are operated infrequently, are allowed to assume a 25 K increase on these temperature-riselimits.d)Unless otherwise specified in the case of covers <strong>and</strong> enclosures which are accessible but need not be touched duringnormal operation, an increase in the temperature-rise limits by 10 K is permissible. External surfaces <strong>and</strong> parts over 2m from the base of the ASSEMBLY are considered inaccessible.e)This allows a degree of flexibility in respect to equipment (e.g. electronic devices) which is subject to temperature-riselimits different from those normally associated with switchgear <strong>and</strong> <strong>control</strong>gear.f)For temperature-rise tests according to 10.10 the temperature-rise limits have to be specified by the Original Manufacturertaking into account any additional measuring points <strong>and</strong> limits imposed by the component manufacturer.g)Assuming all other criteria listed are met a maximum temperature rise of 105 K for bare copper busbars <strong>and</strong> conductorsshall not be exceeded.Nota: 105 K relates to the temperature above which annealing of copper is likely to occur. Other materials may have adifferent maximum temperature rise.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 225


5 Switchboards5.1 <strong>Electrical</strong> switchboardsThermal verification of the assemblyAs regards the temperature-rise limits, from the point of view of switchgearcertification, it is possible to follow one of the three new available procedures,<strong>and</strong> in particular:1) the verification test (formerly defined type-test), in which the temperaturerises reached <strong>and</strong> maintained under service conditions are measured at predefinedpoints inside the prototype assemblies actually tested with currentat laboratory. Then these values are compared with the admissible ones(shown in the previous page); if the measured values are lower than or equalto the admissible ones, the test is considered as passed with those currentvalues <strong>and</strong> under that determined conditions around (ambient temperature,humidity, etc.);2) the derivation (from a cabled assembly tested) of similar variants; this procedure, applicable only if available the data obtained by testing, is used toverify the compliance of non-tested variants however answering to precisecomparative rules with respect to the tested assembly arrangements.The derived assemblies are considered in compliance if, compared with thetested arrangements, they have:- the functional units of the same type (e.g.: same electrical diagrams, apparatusof the same size, same arrangements <strong>and</strong> fixing, same assembling structure,same cables <strong>and</strong> wiring) as the functional units used for the test;- the same type of construction as used for the test;- the same or increased overall dimensions as used for the test;- the same or increased cooling conditions as used for the test (forced or naturalconvection, same or larger ventilation openings);- the same or reduced internal separation as used for the test (if any);- the same or reduced power losses in the same section as used for thetest;- the same or reduced number of outgoing circuits for every section.226 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


5 Switchboards5.1 <strong>Electrical</strong> switchboards3) the verification of the temperature rise through calculation. In this case thelaboratory tests are not to be considered <strong>and</strong> mathematical algorithms ofthermodynamic type – which are already in use since years by panel builders- are exploited. These methods of pure calculation are two, distinct <strong>and</strong>independent between them <strong>and</strong> alternative to tests. They are:a) the so called “method of the powers” based on not-exceeding the upperlimit of thermal power loss capability in a determined enclosure.To establish the value of losses, in watt, the temperature rise in the emptyassembly is simulated by inserting some adjustable heating resistors, whichshall make the enclosure reach its thermal steady state.Once the thermal steady state has been reached <strong>and</strong> after verifying that thetemperature rise limits are included in the defined range, for each enclosure,the maximum value of the thermal power loss can be obtained.This method is affected by some limitations <strong>and</strong> in particular is applied toswitchgear assemblies:1) with a single compartment <strong>and</strong> with current up to 630 A;2) with homogeneous distribution of the internal losses;3) in which the mechanical parts <strong>and</strong> the equipment installed are arrangedso that air circulation is not but little hampered;4) in which the conductors transport currents exceeding 200 A <strong>and</strong> thestructural parts are so arranged that the losses due to eddy currents arenegligible;5) which house equipment used by the 80% of the specific conventionalthermal current in free air.b) the calculation algorithm of the Std. IEC 60890, applicable to multiplecompartment assembliesth rated current up to 1600 A (formerly up to3150). In this case procedures of algebraic calculation without experimentaldata are used.It is a calculation procedure which leads to the tracing, from bottom to top,of the thermal map of the assembly under steady state conditions, accordingto temperature values which grow linearly <strong>and</strong> reach their maximum valueexactly at the top of the enclosure.Thus, through the total power loss, it is possible to evaluate the temperaturerise at different levels, inside the assembly, from bottom to top.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 227


5 Switchboards5.1 <strong>Electrical</strong> switchboardsThe St<strong>and</strong>ards IEC 60890 <strong>and</strong> the IEC 61439-1 establishes that this calculationmethod is applicable only when the following conditions are met:- the rated current of the assembly circuits shall not exceed 80% of the rated current(in free air) of the protective devices <strong>and</strong> of the electrical components installed inthe circuit;- there is an approximately even distribution of power loss inside the enclosure<strong>and</strong> there are no obstacles preventing its dispersion towards the outside of theassembly;- the installed assembly is arranged so as that air circulation is little impeded;- the installed assembly is designed for direct or alternating currents up to <strong>and</strong>including 60 Hz, with the total of supply currents not exceeding 1600 A;- the conductors carrying currents exceeding 200 A <strong>and</strong> the structural parts are soarranged that eddy current losses are negligible;- for the enclosures with ventilation openings, the cross-section of the air outletopenings is at least 1.1 times the cross-section of the air inlet openings;- there are no more than three horizontal partitions for each section of the assembly;- should the enclosures with external ventilation openings be divided into compartments,the surface of the ventilation openings in every internal horizontal partitionshall be at least equal to 50% of the horizontal section of the compartment.To calculate the temperature rise of the air inside an enclosure, once the requirementsf the St<strong>and</strong>ard have been met, the following must be considered:- Dimensions of the enclosure- Type of <strong>installation</strong>:- enclosure open to air on all sides;- wall-mounted enclosure;- enclosure designed for mounting in extremities;- enclosure in an internal position in a multicompartment witchboard;- Any ventilation openings, <strong>and</strong> their dimensions- Number of horizontal internal separators- Power losses from the effective current flowing through any device <strong>and</strong> onductorinstalled within the switchboard or compartment.The St<strong>and</strong>ard allows the calculation of temperature rise of the air at mid-height<strong>and</strong> at the highest point of the switchboard.Once the thermal map of the inside of the assembly from bottom to top has beendrawn, the assembly is verified if the calculated air temperature at the mountingheight of any device does not exceed the permissible ambient air temperatureas declared by the device manufacturer.This means for switching devices or electrical components in the main circuitsthat the continuous load does not exceed its permissible load at the calculatedlocal air temperature <strong>and</strong> not more than 80 % of its rated current.The Annex B explains the calculation method described in the St<strong>and</strong>ard.<strong>ABB</strong> supplies the client with calculation software which allows the temperaturerise inside the switchboard to be calculated quickly.228 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


5.2 MNS switchboards5 SwitchboardsMNS systems are suitable for applications in all fields concerning the generation,distribution <strong>and</strong> use of electrical energy; e. g., they can be used as:- main <strong>and</strong> sub-distribution boards;- motor power supply of MCCs (Motor Control Centres);- automation switchboards.The MNS system is a framework construction with maintenance-free boltedconnections which can be equipped as required with st<strong>and</strong>ardized components<strong>and</strong> can be adapted to any application. The consistent application of the modularprinciple both in electrical <strong>and</strong> mechanical design permits optional selection ofthe structural design, interior arrangement <strong>and</strong> degree of protection accordingto the operating <strong>and</strong> environmental conditions.The design <strong>and</strong> material used for the MNS system largely prevent the occurrenceof electric arcs, or provide for arc extinguishing within a short time. The MNSSystem complies with the requirements laid down in VDE0660 Part 500 as wellas IEC 61641 <strong>and</strong> has furthermore been subjected to extensive accidental arctests by an independent institute.The MNS system offers the user many alternative solutions <strong>and</strong> notableadvantages in comparison with conventional-type <strong>installation</strong>s:- compact, space-saving design;- back-to-back arrangement;- optimized energy distribution in the cubicles;- easy project <strong>and</strong> detail engineering through st<strong>and</strong>ardized components;- comprehensive range of st<strong>and</strong>ardized modules;- various design levels depending on operating <strong>and</strong> environmentalconditions;- easy combination of the different equipment systems, such as fixed <strong>and</strong>withdrawable modules in a single cubicle;- possibility of arc-proof design (st<strong>and</strong>ard design with fixed module design);- possibility of earthquake-, vibration- <strong>and</strong> shock-proof design;- easy assembly without special tools;- easy conversion <strong>and</strong> retrofit;- largely maintenance-free;- high operational reliability;- high safety for human beings.The basic elements of the frame are C-sections with holes at 25 mm intervals incompliance with St<strong>and</strong>ard DIN 43660. All frame parts are secured maintenancefreewith tapping screws or ESLOK screws. Based on the basic grid size of25 mm, frames can be constructed for the various cubicle types without anyspecial tools. Single or multi-cubicle switchgear assemblies for front or front<strong>and</strong> rear operations are possible.Different designs are available, depending on the enclosure required:- single equipment compartment door;- double equipment compartment door;- equipment <strong>and</strong> cable compartment door;- module doors <strong>and</strong>/or withdrawable module covers <strong>and</strong> cable compartmentdoor.The bottom side of the cubicle can be provided with floor plates. With the aidof flanged plates, cable ducts can be provided to suit all requirements. Doors<strong>and</strong> cladding can be provided with one or more ventilation opening, roof platescan be provided with metallic grid (IP 30 – IP40) or with ventilation chimney(IP 40, 41, 42).<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 229


5 Switchboards5.2 MNS switchboardsDepending on the requirements, a frame structure can be subdivided into thefollowing compartments (functional areas):- equipment compartment;- busbar compartment;- cable compartment.The equipment compartment holds the equipment modules, the busbarcompartment contains the busbars <strong>and</strong> distribution bars, the cable compartmenthouses the incoming <strong>and</strong> outgoing cables (optionally from above <strong>and</strong> frombelow) with the wiring required for connecting the modules as well as thesupporting devices (cable mounting rails, cable connection parts, parallelconnections, wiring ducts, etc.). The functional compartments of a cubicleas well as the cubicles themselves can be separated by partitions. Horizontalpartitions with or without ventilation openings can also be inserted betweenthe compartments.All incoming/outgoing feeder <strong>and</strong> bus coupler cubicles include one switchingdevice. These devices can be fixed-mounted switch disconnectors, fixedmountedor withdrawable air or moulded-case circuit-breakers.This type of cubicles is subdivided into equipment <strong>and</strong> busbar compartments;their size (H x W) is 2200 mm x 400 mm / 1200 mm x 600 mm, <strong>and</strong> the depthdepends on the dimensions of the switchgear used.Cubicles with air circuit-breakers up to 2000 A can be built in the reduceddimensioned version (W = 400 mm).It is possible to interconnect cubicles to form optimal delivery units with amaximum width of 3000 mm.5.3 ArTu distribution switchboardsThe range of <strong>ABB</strong> SACE ArTu distribution switchboards provides a complete<strong>and</strong> integrated offer of switchboards <strong>and</strong> kit systems for constructing primary<strong>and</strong> secondary low voltage distribution switchboards.With a single range of accessories <strong>and</strong> starting from simple assembly kits, theArTu switchboards make it possible to assembly a wide range of configurationsmounting modular, moulded-case <strong>and</strong> air circuit-breakers, with any internalseparation up to Form 4.<strong>ABB</strong> SACE offers a series of st<strong>and</strong>ardized kits, consisting of pre-drilled plates <strong>and</strong>panels for the <strong>installation</strong> of the whole range of circuit-breakers type System pro Mcompact, Tmax T, SACE Tmax XT <strong>and</strong> Emax X1, E1, E2, E3, E4 without theneed of additional drilling operations or adaptations.Special consideration has been given to cabling requirements, providing specialseats to fix the plastic cabling duct horizontally <strong>and</strong> vertically.St<strong>and</strong>ardization of the components is extended to internal separation of theswitchboard: in ArTu switchboards, separation is easily carried out <strong>and</strong> it doesnot require either construction of “made-to-measure” switchboards or anyadditional sheet cutting, bending or drilling work.ArTu switchboards are characterized by the following features:- integrated range of modular metalwork structures up to 4000 A with commonaccessories;- possibility of fulfilling all application requirements in terms of <strong>installation</strong>(wall-mounting, floor-mounting, monoblock <strong>and</strong> cabinet kits) <strong>and</strong> degree ofprotection (IP31, IP41, IP43, IP65);- structure made of hot-galvanized sheet;230 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


5 Switchboards5.3 ArTu distribution switchboards- maximum integration with modular devices <strong>and</strong> <strong>ABB</strong> SACE moulded-case<strong>and</strong> air circuit-breakers;- minimum switchboard assembly times thanks to the simplicity of the kits, thest<strong>and</strong>ardization of the small assembly items, the self-supporting elements<strong>and</strong> the presence of clear reference points for assembly of the plates <strong>and</strong>panels;- separations in kits up to Form 4.The range of ArTu switchboards includes four versions, which can be equippedwith the same accessories.ArTu L seriesArTu L series consists of a range of modular switchboard kits, with a capacityof 24/36 modules per row <strong>and</strong> degree of protection IP31 (without door) or IP43(basic version with door). These switchboards can be wall- or floor-mounted:- wall-mounted ArTu L series, with heights of 600, 800, 1000 <strong>and</strong> 1200 mm, depth204 mm, width 690 mm. Both System pro M modular devices <strong>and</strong> mouldedcasecircuit-breakers SACE Tmax XT <strong>and</strong> Tmax T1-T2-T3 are housed insidethis switchboard series;- floor-mounted ArTu L series, with heights of 1400, 1600, 1800 <strong>and</strong> 2000mm, depth 240 mm, width 690/890 mm. System pro M modular devices,moulded- case circuit-breakers type SACE Tmax XT <strong>and</strong> Tmax T1-T2-T3-T4-T5-T6 (fixed version with front terminals) are housed inside this switchboardseries.ArTu M seriesArTu M series consists of a range of modular switchboard kits, with a capacityof 24/36 modules per row <strong>and</strong> degree of protection IP31 (without door) or IP65.These switchboards can be wall- or floor-mounted:- wall-mounted ArTu M series, with heights of 600, 800, 1000 <strong>and</strong> 1200 mm,depth 150/200 mm, width 600 mm. Both System pro M modular devices <strong>and</strong>moulded-case circuit-breakers SACE Tmax XT1-XT2-XT3 <strong>and</strong> Tmax T1-T2-T3are housed inside this switchboard series;- floor-mounted ArTu M series, with heights of 1400, 1600, 1800 <strong>and</strong> 2000mm, depth 250 mm, width 600/800 mm. System pro M modular devices,moulded- case circuit-breakers type SACE Tmax XT <strong>and</strong> Tmax T1-T2-T3-T4-T5-T6 (fixed version with front terminals) are housed inside this switchboardseries.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 231


5 Switchboards5.3 ArTu distribution switchboardsArTu K seriesArTu K series consists of a range of modular switchboard kits for floor-mounted<strong>installation</strong> with four different depths (150, 225, 300, 500, 700 <strong>and</strong> 800 mm)<strong>and</strong> with degree of protection IP31 (without front door), IP41 (with front door<strong>and</strong> ventilated side panels) or IP65 (with front door <strong>and</strong> blind side panels), inwhich it is possible to mount System pro M modular devices, the whole rangeof moulded-case circuit–breakers Tmax XT, Tmax T <strong>and</strong> Emax circuit-breakersX1, E1, E2, E3 <strong>and</strong> E4.ArTu switchboards have three functional widths:- 400 mm, for the <strong>installation</strong> of moulded-case circuit-breakers up to 630 A (T5);- 600 mm, which is the basic dimension for the <strong>installation</strong> of all theapparatus;- 800 mm, for the creation of the side cable container within the structure of thefloor-mounted switchboard or for the use of panels with the same width.The available internal space varies in height from 600 mm (wall-mounted L series)to 2000 mm (floor-mounted M series <strong>and</strong> K series), thus offering a possiblesolution for the most varied application requirements.ArTu PB Series (Panelboard <strong>and</strong> Pan Assembly)The ArTu line is now upgraded with the new ArTu PB Panelboard solution.The ArTu PB Panelboard is suitable for distribution applications with an incomerup to 800A <strong>and</strong> outgoing feeders up to 250A.The ArTu PB Panelboard is extremely sturdy thanks to its new designedframework <strong>and</strong> it is available both in the wall-mounted version as well as in thefloor-mounted one.ArTu PB Panelboard customisation is extremely flexible due to the smart designbased on configurations of 6, 12 <strong>and</strong> 18 outgoing ways <strong>and</strong> to the new <strong>ABB</strong>plug-in system that allows easy <strong>and</strong> fast connections for Tmax XT1-XT2-XT3<strong>and</strong> Tmax T1-T2-T3.Upon request, extension boxes are available on all sides of the structure, formetering purposes too.The vertical trunking system is running behind the MCCB’s layer allowing easyaccess to every accessory wiring (SR’s, UV’s, AUX contacts).The ArTu PB Panelboard, supplied as a st<strong>and</strong>ard with a blind door, is availablewith a glazed one as well.232 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsThe Std. IEC 61439-1 specifies that ASSEMBLIES (referred to hereafter asswitchboards) shall be constructed so as to be capable of withst<strong>and</strong>ing thethermal <strong>and</strong> dynamic stresses resulting from short-circuit currents up to therated values.Furthermore, switchboards shall be protected against short-circuit currentsbymeans of circuit-breakers, fuses or a combination of both, which may eitherbe incorporated in the switchboard or arranged upstream.When ordering a switchboard, the user shall specify the short-circuit conditionsat the point of <strong>installation</strong>.This chapter takes into consideration the following aspects:- the need or not to carry out the verification of the short-circuit withst<strong>and</strong> insidethe assembly;- the suitability of a switchgear for a plant according to the prospective short-circuitcurrent of the plant <strong>and</strong> of the short-circuit parameters of the switchgear;- the suitability of the busbar system according to the short-circuit current <strong>and</strong>to the protection devices;- the verification of the short-circuit withst<strong>and</strong> of the assembly by applying thedesign rules defined in the IEC 61439-1.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 233


Annex A: <strong>Protection</strong> against short-circuit effectsAnnex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsVerification of short-circuit withst<strong>and</strong> strengthThe verification of the short-circuit withst<strong>and</strong> strength is dealt with in the St<strong>and</strong>ardIEC 61439-1, where, in particular, the cases requiring this verification <strong>and</strong> thedifferent types of verification are specified.The verification of the short-circuit withst<strong>and</strong> strength is not required if thefollowing conditions are fulfilled:• For switchboards having a rated short-time current (Icw) or rated conditionalcurrent (Ik) not exceeding 10 kA.• For switchboards protected by current limiting devices having a cut-off currentnot exceeding 17 kA at the maximum allowable prospective short-circuitcurrent at the terminals of the incoming circuit of the switchboard.• For auxiliary circuits of switchboards intended to be connected to transformerswhose rated power does not exceed 10 kVA for a rated secondary voltage ofnot less than 110 V, or 1.6 kVA for a rated secondary voltage less than 110 V,<strong>and</strong> whose short-circuit impedance is not less than 4%.Therefore, from an engineering point of view, the need to verify the short-circuitwithst<strong>and</strong> strength may be viewed as follows:Icw of switchboard ʺ 10 kAorIk conditional current of switchboard ʺ 10 kAYESNOYESThe conditionIp ʺ 17 kAis satisfied for the cut-off current of the protectivecircuit-breaker at the maximum allowableprospective short-circuit currentNOVerification notrequiredVerificationrequiredAs regards the details of the test performance, reference shall be made directlyto the St<strong>and</strong>ard IEC 61439-1.234 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex A: <strong>Protection</strong> against short-circuit effectsAnnex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsShort-circuit current <strong>and</strong> suitability of the switchboardfor the plantThe verification of the short-circuit withst<strong>and</strong> strength is based on two valuesstated by the manufacturer in alternative to each other:- the rated short-time current Icw- the rated conditional short-circuit current IkBased on one of these two values, it is possible to determine whether theswitchboard is suitable to be installed in a particular point of the system.It shall be necessary to verify that the breaking capacities of theapparatus inside the switchboard are compatible with the short-circuitvalues of the system.Rated short- time withst<strong>and</strong> current I cwis the r.m.s. value of the current relatingto the short-circuit test for 1 s without openings of the protections, declaredby the assembly manufacturer, that can be carried by the assembly withoutdamage under specified conditions, defined in terms of a current <strong>and</strong> time.Different I cwvalues for different times (e.g. 0.2 s; 3 s) may be assigned to anassembly. The switchboard shall be able to withst<strong>and</strong> the thermal <strong>and</strong> electrodynamicalstresses without damages or deformations which could compromisethe operation of the system. From this test (if passed) it is possible to obtain thespecific let-through energy (I 2 t) which can be carried by the switchboard:I 2 t = Icw 2 tThe test shall be carried out at a power factor value specified below in theTable 4 of the Std. IEC 61439-1. A factor “n” corresponding at this cosϕ valueallows to determine the peak value of the short-circuit current withstood by theswitchboard through the following formula:Ip = Icw . nTable 4power factorr.m.s. value of short-circuit current cosϕ nI ≤ 5 kA 0.7 1.55


Annex A: <strong>Protection</strong> against short-circuit effectsAnnex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsThe rated short-time withst<strong>and</strong> current of theswitchboard Icw (r.m.s.value) is knownIk (prospective, of the plant) < Icw (of the switchboard)YESNOYESOn the supply side of the switchboard acircuit-breaker is installed, which for theprospective Ik has I 2 t < I 2 t (of theswitchboard) <strong>and</strong> a cut-off currentIp < Ip (switchboard)NOSwitchboardsuitableSwitchboardnot suitableThe conditional short-circuit current ofthe switchboard (r.m.s.value) is knownIk (prospective, of the plant) < Ik(conditional current of the switchboard)(with a specified protective device)YESSwitchboardsuitableNOSwitchboardnot suitableThe breaking capacities of the apparatus inside the switchboard shall be verified to becompatible with the short-circuit values of the plant.236 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsExampleAnnex A: <strong>Protection</strong> against short-circuit effectsPlant data:Rated voltage Ur=400 VRated frequency fr=50HzShort-circuit current Ik=35kAAssume that in an existing system there is a switchboard with Icw equal to35kA <strong>and</strong> that, at the <strong>installation</strong> point of the switchboard, the prospectiveshort-circuit current is equal to 35kA.Now assume that an increase in the power supply of a plant is decided <strong>and</strong>that the short-circuit value rises to 60 kA.Plant data after the increase:Rated voltage Ur=400 VRated frequency fr=50HzShort-circuit current Ik=60kASince the Icw of the switchboard is lower than the short-circuit current of thesystem, in order to verify that the actual switchboard is still compatible, it isnecessary to:- determine the I 2 t <strong>and</strong> Ip values let-through by the circuit-breaker on the supplyside of the switchboard- verify that the protective devices installed inside the switchboard have asufficient breaking capacity (separately or in back-up)Icw = 35kA from which:I 2 t switchboard= 35 2 x1 =1225 MA 2 sIp switchboard= 73.5 kA (according to Table 4)Assuming that on the supply side of the switchboard a circuit-breaker typeTmax T5H (Icu=70kA@415V) is installedI 2 t CB< 4MA 2 sIp CB< 40kAsinceI 2 t switchboard> I 2 t CBIp switchboard> Ip CBit results that the switchboard (structure <strong>and</strong> busbar system) is suitable.Assume that the circuit-breakers installed inside the switchboard are circuitbreakerstype XT1, XT2 <strong>and</strong> XT3 version N with Icu=36kA@415V. From theback-up tables (see Chapter 3.3), it results that the circuit-breakers inside theswitchboard are suitable for the plant, since their breaking capacity is increasedto 65 kA thanks to the circuit-breaker type T5H on the supply side.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 237


Annex A: <strong>Protection</strong> against short-circuit effectsAnnex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsSelection of the distribution system in relation to shortcircuitwithst<strong>and</strong> strengthThe dimensioning of the distribution system of the switchboard is obtained bytaking into consideration the rated current flowing through it <strong>and</strong> the prospectiveshort-circuit current of the plant.The manufacturer usually provides tables which allow the choice of the busbarcross-section as a function of the rated current <strong>and</strong> give the mounting distancesof the busbar supports to ensure the short-circuit withst<strong>and</strong> strength.To select a distribution system compatible with the short-circuit data of theplant, one of these procedures shall be followed:• If the protective device on the supply side of the distribution systemis knownFrom the Icw value of the distribution system it results:Ik syst= Icw.n where n is the factor deduced from the Table 4I 2 t syst= Icw 2 .t where t is equal to 1 sIn correspondence with the prospective short-circuit current value of the plantthe following values can be determined:the cut-off current of the circuit-breakerIp CBthe specific let-through energy of the circuit-breaker I 2 t CBIf Ip CB


Annex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsExampleAnnex A: <strong>Protection</strong> against short-circuit effectsPlant data:Rated voltage Ur=400 VRated frequency fr=50HzShort-circuit current Ik=65kABy considering the need of using a system of 400 A busbars with shaped form,in the <strong>ABB</strong> SACE catalogue “ArTu distribution switchboards” the followingchoice is possible:BA0400 In=400 A (IP65) Icw=35kA.By assuming to have on the supply side of the busbar system a moulded-casecircuit-breaker type<strong>ABB</strong> SACE Tmax T5400 In400from the Icw of the busbar system, it derives:Ip syst= Icw.n = 35 . 2.1 = 73.5 [kA]I 2 t syst= Icw 2 .t = 35 2 . 1 = 1225 [(kA) 2 s]From the curves- Ik 65kA corresponds at about Ip CB=35 kA- Ik 65kA corresponds at about I 2 t CB=4 [(kA) 2 s]= 4 [MA 2 sec]Thus, sinceIp CB< Ip syst<strong>and</strong>I 2 t CB< I 2 t systit results that the busbar system is compatible with the switchboard.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 239


Annex A: <strong>Protection</strong> against short-circuit effectsAnnex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsSelection of conductors on the supply side of the protectivedevicesThe St<strong>and</strong>ard IEC 61439-1 prescribes that in a switchboard, the active conductors(distribution busbars included) positioned between the main busbars<strong>and</strong> the supply side of the single functional units, as well as the constructionalcomponents of these units, can be dimensioned according to the reducedshort-circuit stresses which occur on the load side of the short-circuit protectivedevice of the unit.This may be possible if the conductors are installed in such a way throughoutthe switchboard that, under normal operating conditions, an internal short-circuitbetween phases <strong>and</strong>/or between phase <strong>and</strong> earth is only a remote possibility. Itis advisable that such conductors are of solid rigid manufacture.As an example, this St<strong>and</strong>ard gives conductor types <strong>and</strong> <strong>installation</strong> requirementswhich allow to consider a short-circuit between phases <strong>and</strong>/or between phase<strong>and</strong> earth only a remote possibility.Type of conductorBare conductors or single-core conductors withbasic insulation, for example cables accordingto IEC 60227-3.Single-core conductors with basic insulation<strong>and</strong> a maximum permissible conductor-operatingtemperature above 90°C, for examplecables according to IEC 60245-3, or heatresistantPVC insulated cables according to IEC60227-3.Conductors with basic insulation, for examplecables according to IEC 60227-3, havingadditional secondary insulation, for exampleindividually covered cables with shrink sleevingor individually run cables in plastic conduits.Conductors insulated with a very high mechanicalstrength material, for example ETFE insulation,or double-insulated conductors with anenhanced outer sheath rated for use up to 3 kV,for example cables according to IEC 60502.Single or multi-core sheathed cables, forexample cables according to IEC 60245-4 or60227-4.RequirementsMutual contact or contact with conductive parts shallbe avoided, for example by use of spacers.Mutual contact or contact with conductive parts ispermitted where there is no applied external pressure.Contact with sharp edges must be avoided. There mustbe no risk of mechanical damage.These conductors may only be loaded such that anoperating temperature of 70°C is not exceeded.No additional requirements if there is no risk of mechanicaldamage.Under these conditions or if anyway the integral short-circuit may be considereda remote possibility, the above described procedure shall be used to verify thesuitability of the distribution system to the short-circuit conditions, when theseare determined as a function of the characteristics of the circuit-breakers onthe load side of the busbars.240 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsExamplePlant data:Rated voltage Ur=400 VRated frequency fr=50HzXT2 160Short-circuit current Ik=45kAXT2 160In the switchboard shown in the figure,the vertical distribution busbars arederived from the main busbars.XT3 250These are 800 A busbars with shapedsection <strong>and</strong> with the following characteristics:XT3 250In (IP65) = 800 A,Icw max = 35 kASince it is a “rigid” system with spacers,according to the Std. IEC 61439-1XT3 250a short-circuit between busbars is aremote possibility.Anyway, a verification that the stresses reduced by the circuit-breakers on theload side of the system are compatible with the system is required.Assuming that in the cubicles there are the following circuit-breakers:Tmax XT3S250Tmax XT2S160it is necessary to verify that, in the case of a short-circuit on any outgoingconductor, the limitations created by the circuit-breaker are compatible withthe busbar system; to comply with this requirement, at the maximum allowableprospective short-circuit current, the circuit-breaker with higher cut-off current<strong>and</strong> let-through energy must have an adequate current limiting capability forthe busbar system.In this case the circuit-breaker is type <strong>ABB</strong> SACE T3S250 In250.The verification shall be carried out as in the previous paragraph:From the Icw of the busbar system, it derives:Ip syst= Icw.n = 35 . 2.1 = 73.5 [kA]I 2 t syst= Icw 2 .t = 35 2 . 1 = 1225 [(kA) 2 s]From the limitation <strong>and</strong> let-through energy curves- Ik = 45kA corresponds at about Ip CB=30 kA- Ik = 45kA corresponds at about I 2 t CB=3 [(kA) 2 s]Thus, sinceIp CB


Annex A: <strong>Protection</strong> against short-circuit effectsAnnex A: <strong>Protection</strong> against short-circuit effectsinside low-voltage switchboardsShort-circuit verification by design-rulesIn compliance with the new Std. IEC 61439-1, the compliance of the assemblyunder short-circuit conditions can be proved in addition to laboratory tests (Icw)also by applying appropriate design-rules, which are pointed out in the followingTable (Table 13 of the Std. IEC 61439-1).ItemNo. Requirements to be considered YES NO1 Is the short-circuit withst<strong>and</strong> rating of each circuit of the ASSEMBLY to be assessed,less than or equal to,that of the reference design?2 Is the cross sectional dimensions of the busbars <strong>and</strong> connections of each circuitof the ASSEMBLY to be assessed, greater than or equal to, those of the referencedesign?3 Is the spacing of the busbars <strong>and</strong> connections of each circuit of the ASSEMBLY tobe assessed, greater than or equal to, those of the reference design?4 Are the busbar supports of each circuit of the ASSEMBLY to be assessed of thesame type, shape <strong>and</strong> material <strong>and</strong> have, the same or smaller spacing, along thelength of the busbar as the reference design?5 Are the material <strong>and</strong> the material properties of the conductors of each circuit of theASSEMBLY to be assessed the same as those of the reference design?6 Are the short-circuit protective devices of each circuit of the ASSEMBLY to beassessed equivalent, that is of the same make <strong>and</strong> series a) with the same or betterlimitation characteristics (I 2 t, I pk) based on the device manufacturer’s data, <strong>and</strong> withthe same arrangement as the reference design?7 Is the length of unprotected live conductors, in accordance with 8.6.4, of eachnon-protected circuit of the ASSEMBLY to be assessed less than or equal to thoseof the reference design?8 If the ASSEMBLY to be assessed includes an enclosure, did the reference designinclude an enclosure when verified by test?9 Is the enclosure of the ASSEMBLY to be assessed of the same design, type <strong>and</strong>have at least the same dimensions to that of the reference design?10 Is the enclosure of the ASSEMBLY to be assessed of the same design, type <strong>and</strong>have at least the same dimensions to that of the reference design?‘YES’ to all requirements – no further verification required.‘NO’ to any one requirement – further verification is required, see 10.11.4 <strong>and</strong> 10.11.5 of the St<strong>and</strong>ard.a)Short-circuit protective devices of the same manufacture but of a different series may be considered equivalentwhere the device manufacturer declares the performance characteristics to be the same or better in all relevantrespects to the series used for verification, e.g. breaking capacity <strong>and</strong> limitationcharacteristics (I2t, Ipk), <strong>and</strong> critical distances.242 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex B: Temperature rise evaluationaccording to IEC 60890The calculation method suggested in the St<strong>and</strong>ard IEC 60890 makes it possibleto evaluate the temperature rise inside an assembly; the St<strong>and</strong>ards IEC 60890<strong>and</strong> the IEC 61439-1 establishes that this calculation method is applicable onlywhen the following conditions are met:the rated current of the assembly circuits shall not exceed 80% of the ratedcurrent (in free air) of the protective devices <strong>and</strong> of the electrical componentsinstalled in the circuit;• there is an approximately even distribution of power loss inside the enclosure<strong>and</strong> there are no obstacles preventing its dispersion towards the outside ofthe assembly;• the installed assembly is arranged so as that air circulation is little impeded;• the installed assembly is designed for direct or alternating currents up to <strong>and</strong>including 60 Hz, with the total of supply currents not exceeding 1600 A;• the conductors carrying currents exceeding 200 A <strong>and</strong> the structural partsare so arranged that eddy current losses are negligible;• for the enclosures with ventilation openings, the cross-section of the air outletopenings is at least 1.1 times the cross-section of the air inlet openings;• there are no more than three horizontal partitions for each section of theassembly;• should the enclosures with external ventilation openings be divided intocompartments, the surface of the ventilation openings in every internal horizontalpartition shall be at least equal to 50% of the horizontal section of thecompartment.The data necessary for the calculation are:- dimensions of the enclosure: height, width, depth;- the type of <strong>installation</strong> of the enclosure (see Table 8);- presence of ventilation openings;- number of internal horizontal partitions;- the power loss of the equipment installed in the enclosure (see Tables 13 <strong>and</strong>14);- the power loss of the conductors inside the enclosure, equal to the sum ofthe power loss of every conductor, according to Tables 1, 2 <strong>and</strong> 3.For equipment <strong>and</strong> conductors not fully loaded, it is possible to evaluate thepower loss as:2IP = P n (b) (1)I nwhere:P is the actual power loss;P nis the rated power loss (at I r);I bis the actual current;I nis the rated current.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 243


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Table 1: Operating current <strong>and</strong> power losses of insulated conductorsCrosssection(Cu)1)d d d dAir temperature inside the enclosure around the conductorsoperating currentpower losses 2)operating currentpower losses 2)operating currentpower losses 2)operating currentpower losses 2)operating currentpower losses 2)operating currentpower losses 2)mm 2 A W/m A W/m A W/m A W/m A W/m A W/m1.52.54610162535507095120150185240300Conductors for auxiliary circuits0.120.140.200.220.300.340.500.560.751.001217222838522.62.93.23.64.44.76.48.29.32.12.52.62.83.03.71.21.31.11.31.41.41.81.61.91.8811141825341.71.92.12.32.93.14.25.46.10.91.11.11.21.31.60.50.60.50.50.60.60.80.70.80.812202532486485104130161192226275295347400Diam.0.4--0.50.60.60.8-1.0-2.13.53.43.74.85.66.37.57.98.48.79.611.710.912.013.21) Any arrangement desired with the values specified referring to six cores in a multi-core bundle with asimultaneous load 100%2) single length812182331425567851051251471671912252600.91.31.81.92.02.42.63.13.43.63.74.14.34.65.05.6122025325065851151501752252502753504004602.13.53.43.75.25.86.37.910.59.911.911.711.715.415.917.58122025325065851151491752102392733223710.91.32.22.32.13.43.75.06.27.27.28.38.89.410.311.41SDC008040F0201244 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Table 2: Operating current <strong>and</strong> power losses of bare conductors, invertical arrangement without direct connections to apparatusWidthxThicknessCrosssection(Cu)50 Hz to 60 Hz ac dc <strong>and</strong> ac to 16 2/3 Hz 50 Hz to 60 Hz ac dc <strong>and</strong> ac to 16 2/3 Hzoperating currentpower losses 1)operating currentpower losses 1)operating currentpower losses 1)operating currentpower losses 1)operating currentpower losses 1)operating currentpower losses 1)operating currentpower losses 1)operating currentpower losses 1)mm x mm12 x 215 x 215 x 320 x 220 x 320 x 520 x 1025 x 530 x 530 x 1040 x 540 x 1050 x 550 x 1060 x 560 x 1080 x 580 x 10100 x 5100 x 10120 x 10mm 2 A* W/m23.529.544.539.559.599.11991241492991993992494992995993997994999991200144170215215271364568435504762641951775113391513101170164914361982231419.521.723.126.127.629.936.934.138.444.447.052.755.760.964.168.580.785.0100.1101.7115.5*) one conductor per phaseA**2422823753514636651097779894141011121716132220081530228819292806230132983804W/m27.529.935.234.840.249.869.255.460.677.972.588.982.9102.994.2116.2116.4138.7137.0164.2187.3A* W/m144170215215271364569435505770644968782116492613571200174214762128251419.521.723.126.127.629.936.734.138.244.847.052.655.461.464.769.580.885.198.7102.6115.9A**242282375354463668110778899143611281796135721411583248720353165240738444509**) two conductors per phaseW/m27.529.935.235.440.250.369.655.660.777.872.390.583.4103.894.6117.8116.1140.4121.2169.9189.9A* W/m105124157157198266414317368556468694566826667955858120310481445168810.411.612.313.914.716.019.618.120.527.725.028.129.732.334.136.442.945.353.354.061.5A**17720627425633848580056865210288111251964146511161668140720471678240627741) single lengthW/m14.716.018.818.521.426.536.829.532.341.438.547.344.154.850.162.061.973.872.984.499.6A* W/m105124157157198266415317369562469706570849675989875127110771552183310.411.612.312.314.716.019.518.120.423.924.928.029.432.734.436.942.945.352.554.661.6A**1772062742583384878075726561048586131098915621154181414841756175628033288W/m14.716.018.818.821.426.737.029.532.341.538.548.144.355.350.362.761.874.869.890.4101.01SDC008041F0201<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 245


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Table 3: Operating current <strong>and</strong> power losses of bare conductors usedas connections between apparatus <strong>and</strong> busbarsWidthxThicknessCrosssection(Cu)50 Hz to 60 Hz ac <strong>and</strong> dc50 Hz to 60 Hz ac <strong>and</strong> dcoperating currentpower losses 1)operating currentpower losses 1)operating currentpower losses 1)operating currentpower losses 1)mm x mm mm 2 A* W/m A** W/m A* W/m12 x 215 x 215 x 320 x 220 x 320 x 520 x 1025 x 530 x 530 x 1040 x 540 x 1050 x 550 x 1060 x 560 x 1080 x 580 x 10100 x 5100 x 10120 x 1023.529.544.539.559.599.1199124149299199399249499299599399799499999120082961241151522183482532884823486484138054929606481256805156018485.96.47.16.98.09.912.810.711.617.212.822.714.728.517.234.122.745.829.258.468.3130150202184249348648413492960648124580515609601848125624321560268029287.47.89.58.910.812.722.314.216.932.722.341.927.953.532.763.242.685.854.886.285.76988102931251742842042334022845323386604027805321032660128015244.25.44.84.55.46.38.67.07.611.58.615.39.819.211.522.515.330.919.639.346.5*) one conductor per phase **) two conductors per phase 1) single lengthA**10512416217219828453233840278053210326551280780152410321920128021802400W/m4.95.46.17.76.88.415.09.511.321.615.028.818,536.021.643.028.853.536.957.057.61SDC008042F0201246 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Where enclosures without vertical partitions or individual sections have an effectivecooling surface greater than about 11.5 m or a width grater than about1.5 m, they should be divided for the calculation into fictitious sections, whosedimensions approximate to the foregoing values.The following diagram shows the procedure to evaluate the temperature rise.1SDC008043F0201<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 247


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Table 4: Surface factor b according to the type of <strong>installation</strong>Type of <strong>installation</strong>Surface factor bExposed top surface 1.4Covered top surface, e.g. of built-in enclosures 0.7Exposed side faces, e.g. front, rear <strong>and</strong> side walls 0.9Covered side faces, e.g. rear side of wall-mounted enclosures 0.5Side faces of central enclosures 0.5Floor surfaceNot taken into accountFictitious side faces of sections which have been introduced only for calculation purposesare not taken into accountTable 5: Factor d for enclosures without ventilation openings <strong>and</strong>with an effective cooling surface A e> 1.25 m 2Number of horizontal partitions nFactor d0 11 1.052 1.153 1.3Table 6: Factor d for enclosures with ventilation openings <strong>and</strong> with aneffective cooling surface A e> 1.25 m 2Number of horizontal partitions nFactor d0 11 1.052 1.13 1.15Table 7: Enclosure constant k for enclosures without ventilationopenings, with an effective cooling surface A e> 1.25 m 2A e[m 2 ] k A e[m 2 ] k1.25 0.524 6.5 0.1351.5 0.45 7 0.132 0.35 7.5 0.1252.5 0.275 8 0.123 0.225 8.5 0.1153.5 0.2 9 0.114 0.185 9.5 0.1054.5 0.17 10 0.15 0.16 10.5 0.0955.5 0.15 11 0.096 0.14 11.5 0.085248 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Table 8: Temperature distribution factor c for enclosures withoutventilation openings, with an effective cooling surface A e> 1.25 m 2h 1.35f =Type of <strong>installation</strong>A b1 2 3 4 50.6 1.225 1.21 1.19 1.17 1.1131 1.24 1.225 1.21 1.185 1.141.5 1.265 1.245 1.23 1.21 1.172 1.285 1.27 1.25 1.23 1.192.5 1.31 1.29 1.275 1.25 1.213 1.325 1.31 1.295 1.27 1.233.5 1.35 1.33 1.315 1.29 1.2554 1.37 1.355 1.34 1.32 1.2754.5 1.395 1.375 1.36 1.34 1.2955 1.415 1.395 1.38 1.36 1.325.5 1.435 1.415 1.4 1.38 1.346 1.45 1.435 1.42 1.395 1.3556.5 1.47 1.45 1.435 1.41 1.377 1.48 1.47 1.45 1.43 1.397.5 1.495 1.48 1.465 1.44 1.48 1.51 1.49 1.475 1.455 1.4158.5 1.52 1.505 1.49 1.47 1.439 1.535 1.52 1.5 1.48 1.449.5 1.55 1.53 1.515 1.49 1.45510 1.56 1.54 1.52 1.5 1.4710.5 1.57 1.55 1.535 1.51 1.47511 1.575 1.565 1.549 1.52 1.48511.5 1.585 1.57 1.55 1.525 1.4912 1.59 1.58 1.56 1.535 1.512.5 1.6 1.585 1.57 1.54 1.51where h is the height of the enclosure, <strong>and</strong> A bis the area of the base.For “Type of <strong>installation</strong>”:Type of <strong>installation</strong> n°1 Separate enclosure, detached on all sides2 First or last enclosure, detached type3Separate enclosure for wall-mountingCentral enclosure, detached typeFirst or last enclosure, wall-mounting type4Central enclosure for wall-mounting <strong>and</strong> with covered top surface5 Central enclosure, wall-mounting type1SDC008069F0001<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 249


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Table 9: Enclosure constant k for enclosures with ventilation openings <strong>and</strong> an effectivecooling surface A e> 1.25 m 2Ventilationopening A e[m 2 ]in cm 2 1 1.5 2 2.5 3 4 5 6 7 8 10 12 1450 0.36 0.33 0.3 0.28 0.26 0.24 0.22 0.208 0.194 0.18 0.165 0.145 0.135100 0.293 0.27 0.25 0.233 0.22 0.203 0.187 0.175 0.165 0.153 0.14 0.128 0.119150 0.247 0.227 0.21 0.198 0.187 0.173 0.16 0.15 0.143 0.135 0.123 0.114 0.107200 0.213 0.196 0.184 0.174 0.164 0.152 0.143 0.135 0.127 0.12 0.11 0.103 0.097250 0.19 0.175 0.165 0.155 0.147 0.138 0.13 0.121 0.116 0.11 0.1 0.095 0.09300 0.17 0.157 0.148 0.14 0.133 0.125 0.118 0.115 0.106 0.1 0.093 0.088 0.084350 0.152 0.141 0.135 0.128 0.121 0.115 0.109 0.103 0.098 0.093 0.087 0.082 0.079400 0.138 0.129 0.121 0.117 0.11 0.106 0.1 0.096 0.091 0.088 0.081 0.078 0.075450 0.126 0.119 0.111 0.108 0.103 0.099 0.094 0.09 0.086 0.083 0.078 0.074 0.07500 0.116 0.11 0.104 0.1 0.096 0.092 0.088 0.085 0.082 0.078 0.073 0.07 0.067550 0.107 0.102 0.097 0.093 0.09 0.087 0.083 0.08 0.078 0.075 0.07 0.068 0.065600 0.1 0.095 0.09 0.088 0.085 0.082 0.079 0.076 0.073 0.07 0.067 0.065 0.063650 0.094 0.09 0.086 0.083 0.08 0.077 0.075 0.072 0.07 0.068 0.065 0.063 0.061700 0.089 0.085 0.08 0.078 0.076 0.074 0.072 0.07 0.068 0.066 0.064 0.062 0.06Table 10: Temperature distribution factor c for enclosures with ventilation openings <strong>and</strong>an effective cooling surface A e> 1.25 m 2f =VentilationopeningA bin cm 2 1.5 2 3 4 5 6 7 8 9 1050 1.3 1.35 1.43 1.5 1.57 1.63 1.68 1.74 1.78 1.83100 1.41 1.46 1.55 1.62 1.68 1.74 1.79 1.84 1.88 1.92150 1.5 1.55 1.63 1.69 1.75 1.8 1.85 1.9 1.94 1.97200 1.56 1.61 1.67 1.75 1.8 1.85 1.9 1.94 1.97 2.01250 1.61 1.65 1.73 1.78 1.84 1.88 1.93 1.97 2.01 2.04300 1.65 1.69 1.75 1.82 1.86 1.92 1.96 2 2.03 2.06350 1.68 1.72 1.78 1.85 1.9 1.94 1.97 2.02 2.05 2.08400 1.71 1.75 1.81 1.87 1.92 1.96 2 2.04 2.07 2.1450 1.74 1.77 1.83 1.88 1.94 1.97 2.02 2.05 2.08 2.12500 1.76 1.79 1.85 1.9 1.95 1.99 2.04 2.06 2.1 2.13550 1.77 1.82 1.88 1.93 1.97 2.01 2.05 2.08 2.11 2.14600 1.8 1.83 1.88 1.94 1.98 2.02 2.06 2.09 2.12 2.15650 1.81 1.85 1.9 1.95 1.99 2.04 2.07 2.1 2.14 2.17700 1.83 1.87 1.92 1.96 2 2.05 2.08 2.12 2.15 2.18h 1.35250 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Table 11: Enclosure constant k for enclosures without ventilationopenings <strong>and</strong> with an effective cooling surface A e≤ 1.25 m 2A e[m 2 ] k A e[m 2 ] k0.08 3.973 0.65 0.8480.09 3.643 0.7 0.8030.1 3.371 0.75 0.7640.15 2.5 0.8 0.7280.2 2.022 0.85 0.6960.25 1.716 0.9 0.6680.3 1.5 0.95 0.6410.35 1.339 1 0.6180.4 1.213 1.05 0.5960.45 1.113 1.1 0.5760.5 1.029 1.15 0.5570.55 0.960 1.2 0.5400.6 0.9 1.25 0.524Table 12: Temperature distribution factor c for enclosures withoutventilation openings <strong>and</strong> with an effective cooling surface A e≤ 1.25 m 2g c g c0 1 1.5 1.2310.1 1.02 1.6 1.2370.2 1.04 1.7 1.240.3 1.06 1.8 1.2440.4 1.078 1.9 1.2460.5 1.097 2 1.2490.6 1.118 2.1 1.2510.7 1.137 2.2 1.2530.8 1.156 2.3 1.2540.9 1.174 2.4 1.2551 1.188 2.5 1.2561.1 1.2 2.6 1.2571.2 1.21 2.7 1.2581.3 1.22 2.8 1.2591.4 1.226where g is the ratio of the height <strong>and</strong> the width of the enclosure.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 251


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Total (3/4 poles)power loss in WTable 13: MCCB power lossesReleases In[A]XT1 XT2 XT3 XT4 T11P T1 T2 T3 T4 T5 T6 T7 S,H,L T7 VF P F P/W F P F P/W F F F P F P F P/W F P/W F W F W F W1 4.5 5.11.6 2 2.38 6.3 7.52 2.38 2.76 7.5 8.72.5 2.47 2.85 7.8 93 2.76 3.233.2 8.7 10.24 2.47 2.85 7.8 95 8.7 10.56.3 3.33 3.90 10.5 12.38 2.57 3.04 8.1 9.610 2.95 3.42 9.3 10.812.5 1.05 1.24 3.3 3.9TMF 16 4.5 4.5 1.33 1.52 1.5 4.5 4.2 4.8TMD20 5.4 6 1.62 1.90 1.8 5.4 5.1 6 10.8 10.8TMA25 6 8.4 2 6 6.9 8.4MF32 6.3 9.6 2.57 3.04 4.44 4.44 2.1 6.3 8.1 9.6 11.1 11.1MA40 7.8 13.8 3.71 4.37 4.49 4.72 2.6 7.8 11.7 13.850 11.1 15 4.09 4.75 4.68 4.92 3.7 11.1 12.9 15 11.7 12.363 12.9 18 4.85 5.70 4.3 5.1 5.30 5.76 4.3 12.9 15.3 18 12.9 15.380 14.4 21.6 5.8 6.84 4.8 5.8 5.52 6 4.8 14.4 18.3 21.6 14.4 17.4 13.8 15100 21 30 8.08 9.50 5.6 6.8 6.24 6.96 7 21 25.5 30 16.8 20.4 15.6 17.4125 32.1 44.1 11.4 13.97 6.6 7.9 7.44 8.64 10.7 32.1 36 44.1 19.8 23.7 18.6 21.6160 45 60 16.15 19 7.9 9.5 8.88 10.80 15 45 51 60 23.7 28.5 22.2 27200 13.2 15.8 11.88 14.88 39.6 47.4 29.7 37.2250 17.8 21.4 16.44 21.12 53.4 64.2 41.1 52.8320 40.8 62.7400 58.5 93500 86.4 110.1630 91.8 90800 93 118.810 1.5 1.825 3 3.663 10.5 12100 24 27.6 5.1 6.9160 51 60 13.2 18PR21… 250 32.1 43.8PR22… 320 52.8 72 31.8 53.7PR33… 400 49.5 84 15 27 24 36630 123 160.8 90 115 36 66 60 90800 96 124.8 57.9 105.9 96 1441000 150 90 165 150 2251250 141 258 234.9 351.91600 231 423The values indicated in the table refer to balanced loads, with a current flow equal to the In, <strong>and</strong> arevalid for both circuit-breakers <strong>and</strong> switch-disconnectors, three-pole <strong>and</strong> four-pole versions.For the latter, the current of the neutral is nil by definition.252 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890Table 14: Emax power lossesTotal (3/4 poles) X1-BN X1-L E1B-N E2B-N-S E2L E3N-S-H-V E3L E4S-H-V E6H-Vpower loss in W F W F W F W F W F W F W F W F W F WIn=630 31 60 61 90In=800 51 104 99 145 65 95 29 53 22 36In=1000 79 162 155 227 96 147 45 83 38 58In=1250 124 293 242 354 150 230 70 130 105 165 60 90In=1600 209 415 253 378 115 215 170 265 85 150In=2000 180 330 130 225 215 330In=2500 205 350 335 515In=3200 330 570 235 425 170 290In=4000 360 660 265 445In=5000 415 700In=6300 650 1100ExampleHereunder an example of temperature rise evaluation for a switchboard withthe following characteristics:- enclosure without ventilation openings- no internal segregation- separate enclosure for wall-mounting- one main circuit-breaker- 5 circuit-breakers for load supply- busbars <strong>and</strong> cable systemsEnclosureCircuit diagramI1BAI2CIGIGI1 I2 I3 I4 I5DI3DEI4HI5FDimensions [mm]Height Width DepthNumber of horizontalpartitions = 020001440840Separate enclosurefor wall-mountingW<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 253


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890The power losses from each component of the above switchboard are evaluatedhereunder.IbFor the circuit-breakers, the power losses are calculated as P = Pnwith In <strong>and</strong> Pn given in the Tables 14 <strong>and</strong> 15. ( ) 2InThe table below shows the values relevant to each circuit-breaker of theswitchboard in question:In CB Ib Power lossesCircuit-breakers [A] [A] [W]IG E2 2000 EL 2000 1340 80.7I1 T5 630 EL 630 330 33.7I2 T5 630 EL 630 330 33.7I3 T5 630 EL 630 330 33.7I4 XT3 250 TMD 250 175 26.2I5 XT3 250 TMD 250 175 26.2Total power loss of circuit-breakers [W] 234For the busbars, the power losses are calculated as P = Pn ( Ibwith In <strong>and</strong> Pn given in the Table 2.InThe table below shows the power losses of busbars:) 2 . (3 . Length)Cross-section Length Ib Power lossesBusbars nx[mm]x[mm] [m] [A] [W]A 2x60x10 0.393 1340 47.2B 80x10 0.332 1340 56C 80x10 0.300 1010 28.7D 80x10 0.300 680 13E 80x10 0.300 350 3.5F 80x10 0.300 175 0.9Total power loss of busbars [W] 149For the bare conductors connecting the busbars to the circuit-breakers, theIbpower losses are calculated as P = Pn (, with In <strong>and</strong> Pn) 2 . (3 . Lenght)Ingiven in the Table 2. Here below the values for each section:Connection Cross-section Length Ib Power lossesbare conductors nx[mm]x[mm] [m] [A] [W]Ig 2x60x10 0.450 1340 54I1 30x10 0.150 330 3.8I2 30x10 0.150 330 3.8I3 30x10 0.150 330 3.8I4 20x10 0.150 175 1.6I5 20x10 0.150 175 1.6Total power loss of bare conductors [W] 68254 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890For the cables connecting the circuit-breakers to the supply <strong>and</strong> the loads, theIbpower losses are calculated as P = Pn ( ) 2 . (3 . Length) , with In <strong>and</strong> PnIngiven in the Table 4.Here below the power losses for each connection:Cables Cross-section Length Ib Power losses[n]xmm 2 [m] [A] [W]IG 4x240 1.0 1340 133.8I1 240 2.0 330 64.9I2 240 1.7 330 55.2I3 240 1.4 330 45.4I4 120 1.1 175 19I5 120 0.8 175 13.8Total power loss of cables [W] 332Thus, the total power loss inside the enclosure is: P = 784 [W]From the geometrical dimensions of the switchboard, the effective coolingsurface Ae is determined below:Dimensions[m]x[m] A 0[m 2 ] b factor A 0Top 0.840x1.44 1.21 1.4 1.69Front 2x1.44 1.64 0.9 2.59Rear 2x1.44 1.64 0.5 1.44Left-h<strong>and</strong> side 2x0.840 1.68 0.9 1.51Right-h<strong>and</strong> side 2x0.840 1.68 0.9 1.51Ae=Σ(A 0⋅b) 8.75Making reference to the procedure described in the diagram at page 247, it ispossible to evaluate the temperature rise inside the switchboard.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 255


Annex B: temperature rise evaluationAnnex B: Temperature rise evaluationaccording to IEC 60890From Table 7, k results 0.112 (value interpolated)Since x = 0.804, the temperature rise at half the height of the enclosure is:∆t 0.5= d ⋅ k ⋅ P x =1 ⋅ 0.112 ⋅ 784 0.804 = 23.8 kFor the evaluation of the temperature rise at the top of the enclosure, it isnecessary to determine the c factor by using the f factor:2 1.35f = h1.35=(A bis the base area of the switchboard)A b1.44 ⋅ 0.84 = 2.107From Table 8, column 3 (separate enclosure for wall-mounting), c results to beequal to1.255 (value interpolated).∆t 1= c ⋅ ∆t 0.5= 1.255 ⋅ 23.8 = 29.8 kConsidering 35°C ambient temperature, as prescribed by the St<strong>and</strong>ard, thefollowing temperatures shall be reached inside the enclosure:t 0.5= 35 + 23.8 ≈ 59°Ct 1= 35 + 29.8 ≈ 65°CAssuming that the temperature derating of the circuit-breakers inside theswitchboard can be compared to the derating at an ambient temperaturedifferent from 40°C, through the tables of Chapter 2.5, it is possible to verify ifthe selected circuit-breakers can carry the required currents:E2 2000 at 65°C In=1765 [A] > Ig = 1340 [A]T5 630 at 65°C In=505 [A] > I1 = I2 = I3 = 330 [A]XT3 250 at 60° C In=216 [A] > I4 = I5 = 175 [A]256 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex C: Application examplesAdvanced protection functions with PR123/P<strong>and</strong> PR333/P releasesDual SettingThanks to the new PR123 <strong>and</strong> PR333 releases, it is possible to program twodifferent sets of parameters <strong>and</strong>, through an external comm<strong>and</strong>, to switchfrom one set to the other.This function is useful when there is an emergency source (generator) inthe system, only supplying voltage in the case of a power loss on the networkside.Example:In the system described below, in the case of a loss of the normal supplyon the network side, by means of <strong>ABB</strong> SACE ATS010 automatic transferswitch, it is possible to switch the supply from the network to the emergencypower unit <strong>and</strong> to disconnect the non-primary loads by opening the QS1switch-disconnector.Under normal service conditions of the <strong>installation</strong>, the circuit-breakers C areset in order to be selective with both circuit-breaker A, on the supply side, aswell as with circuit-breakers D on the load side.By switching from the network to the emergency power unit, circuit-breaker Bbecomes the reference circuit-breaker on the supply side of circuit-breakers C.This circuit-breaker, being the protection of a generator, must be set to triptimes shorter than A <strong>and</strong> therefore the setting values of the circuit-breakers onthe load side might not guarantee the selectivity with B.By means of the “dual setting” function of the PR123 <strong>and</strong> PR 333 releases, itis possible to switch circuit-breakers C from a parameter set which guaranteesselectivity with A, to another set which make them selective with B.However, these new settings could make the combination between circuitbreakersC <strong>and</strong> the circuit-breakers on the load side non-selective.UTM1Un2=400VGGS1Un=400VABEnon-priority loadsQS1C C CQS2D D D1SDC008049F0201<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 257


Annex C: Application examplesAnnex C: Application examplesAdvanced protection functions with PR123/P<strong>and</strong> PR333/P releasesThe figure at the sideshows the time-currentcurves of the <strong>installation</strong>under normal serviceconditions.The values set allowno intersection of thecurves.Time currentcurves10 3 s10 2 s10s1sDACThe figure at the sideshows the situation inwhich, after switching,the power is suppliedby the power unitthrough circuit-breakerB. If the settings ofcircuit-breakers C arenot modified, there willbe no selectivity with themain circuit-breaker B.This last figure showshow it is possibleto switch to a set ofparameters whichguarantees selectivityof circuit-breakers Cwith B by means of the“dual setting” function.Time currentcurvesTime currentcurves10 -1 s10 -2 s10 -3 s10 3 s10 2 s10s1s10 -1 s10 -2 s10 -3 s10 3 s10 2 s10s1s1kA 10kA 10 2 kA 10 3 kABCD1kA 10kA 10 2 kA 10 3 kABD1SDC008080F00011SDC008081F000110 -1 s10 -2 s10 -3 s258 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>C1kA 10kA 10 2 kA 10 3 kA1SDC008082F0001


Annex C: Application examplesAnnex C: Application examplesAdvanced protection functions with PR123/P<strong>and</strong> PR333/P releasesDouble GThe Emax type circuit-breakers, equipped with the PR123 <strong>and</strong> PR333 electronicreleases, allow two independent curves for protection G:-one for the internal protection (function G without external toroid);-one for the external protection (function G with external toroid)A typical application of function double G consists in simultaneous protectionboth against earth fault of the secondary of the transformer <strong>and</strong> of its connectioncables to the circuit-breaker terminals (restricted earth fault protection), aswell as against earth faults on the load side of the circuit-breaker (outside therestricted earth fault protection).Example:Figure 1 shows a fault on the load side of an Emax circuit-breaker: the faultcurrent flows through one phase only <strong>and</strong>, if the vectorial sum of the currentsdetected by the four current transformers (CTs) results to be higher than theset threshold, the electronic release activates function G (<strong>and</strong> the circuitbreakertrips).Figure 1Trasformersecondary windingL 1Emaxinternal CTsL 2L 3NPE1SDC008050F0201<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 259


Annex C: Application examplesAnnex C: Application examplesAdvanced protection functions with PR123/P<strong>and</strong> PR333/P releasesWith the same configuration, a fault on the supply side of the circuit-breaker(Figure 2) does not cause intervention of function G since the fault current doesnot affect either the CT of the phase or that of the neutral.Figure 2Trasformersecondary windingL 1Emaxinternal CTsL 2L 3NPE1SDC008051F0201The use of function “double G” allows <strong>installation</strong> of an external toroid, asshown in Figure 3, so that earth faults on the supply side of Emax CB can bedetectedas well. In this case, the alarm contact of the second G is exploited in order to tripthe circuit-breaker installed on the primary <strong>and</strong> to ensure fault disconnection.Figure 3Trasformersecondary windingEmaxinternal CTsL 1L 2ExternaltoroidL 3NPE1SDC008052F0201260 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex C: Application examplesAnnex C: Application examplesAdvanced protection functions with PR123/P<strong>and</strong> PR333/P releasesIf, with the same configuration as Figure 3, the fault occurs on the load side ofthe Emax circuit-breaker, the fault current would affect both the toroid as well asthe current transformers on the phases. To define which circuit-breaker is to trip(MV or LV circuit-breaker), suitable coordination of the trip times is required: inparticular, it is necessary to set the times so that LV circuit-breaker openingdue to internal function G is faster than realization of the alarm signal comingfrom the external toroid. Therefore, thanks to the time-current discriminationbetween the two G protection functions, before the MV circuit-breaker on theprimary of the transformer receives the trip comm<strong>and</strong>, the circuit-breaker onthe LV side is able to eliminate the earth fault.Obviously, if the fault occurred on the supply side of the LV circuit-breaker, onlythe circuit-breaker on the MV side would trip.The table shows the main characteristics of the range of toroids (available onlyin the closed version).Characteristics of the toroid rangesRated currentOuter dimensions of the tooidHW DInternal diameter of the toroid100 A, 250 A, 400 A, 800 AW = 165 mmD = 160 mmH = 112 mmØ = 112 mm1SDC008053F0201<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 261


Annex C: Application examplesAnnex C: Application examplesAdvanced protection functions with PR123/P<strong>and</strong> PR333/P releasesDouble SThanks to the new PR123 <strong>and</strong> PR333 releases, which allows two thresholds ofprotection function S to be set independently <strong>and</strong> be activated simultaneously,selectivity can also be achieved under highly critical conditions.Here is an example of how, by using the new release, it is possible to obtain abetter selectivity level compared with the use of a release without “double S”.This is the wiring diagram of the system under examination; in particular,attention must be focussed on:- the presence, on the supply side, of a MV circuit-breaker, which, for selectivityreasons, imposes low setting values for the Emax circuit-breaker on the LVside- the presence of a LV/LV transformer which, due to the inrush currents, imposeshigh setting values for the circuit-breakers on its primary sideUUref = 20000 VMV CBUn1 = 20000 VUn2 = 400 VSn = 800 kVAMV/LV TransformerWC1E2 1250Ik = 22.6 kAT5 630 PR222Un1 = 400 VUn2 = 230 VSn = 315 kVAMV/LV Transformer1SDC008054F0201262 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Annex C: Application examplesAnnex C: Application examplesAdvanced protection functions with PR123/P<strong>and</strong> PR333/P releasesSolution with a release without “double S”Time currentcurves@ 400V10 4 s10 3 sT5 630 E2 1250PR521 Ik10 2 s10s1sLV/LV Trans. 315kVA10 -1 s10 -2 s10 -1 kA 1kA10kA1SDC008083F0001MV CB (PR521)50 (I>): 50A t=0.5s51 (I>>): 500A t=0sE2N 1250 PR122LSIG R1250T5V 630 PR222DS/PLSIG R630L Setting 0.8 0.74Curve 108s 12sS t=constant Setting 3.5 4.2Curve 0.5s 0.25sI Setting OFF 7In the case of a short-circuit, the Emax E2 circuit-breaker <strong>and</strong> the MV circuitbreakerwill open simultaneously with this solution. Attention must be paidto the fact that, owing to the value Ik, function I of the E2 circuit-breaker hasto be disabled (I3=OFF) so that selectivity with the T5 on the load side isguaranteed.<strong>ABB</strong> | <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices 263


Annex C: Application examplesAnnex C: Application examplesAdvanced protection functions with PR123/P<strong>and</strong> PR333/P releasesSolution with the PR123 release with “double S”Time currentcurves@ 400V10 4 s10 3 s10 2 sT5 630 E2 1250PR521 Ik10s1sLV/LV Trans. 315kVA10 -1 s10 -2 s10 -1 kA 1kA10kA1SDC008084F0001MV CB (PR521)50 (I>): 50A t=0.5s51 (I>>): 500A t=0sE2N 1250 PR123 T5V 630 PR222DS/PLSIG R1250LSIG R630L Setting 0.8 0.74Curve 108s 12sS t=constant Setting 3.5 4.2Curve 0.5s 0.25sS2 t=constant Setting 5 -Curve 0.05s -I Setting OFF 7As evident, by means of the “double S” function, selectivity can be achievedboth with the T5 circuit-breaker on the load side as well as with the MV circuitbreakeron the supply side.A further advantage obtained by using the “double S” function is the reductionin the time of permanence of high current values under short-circuit conditions,which results in lower thermal <strong>and</strong> dynamic stresses on the busbars <strong>and</strong> on theother <strong>installation</strong> components.264 <strong>Protection</strong> <strong>and</strong> <strong>control</strong> devices | <strong>ABB</strong>


Part 2<strong>Electrical</strong> devicesIndex1 <strong>Protection</strong> of feeders1.1 Introduction......................................................2681.2 Installation <strong>and</strong> dimensioning of cables.............2711.2.1 Current carrying capacity <strong>and</strong> methodsof <strong>installation</strong>............................................271Installation not buried in the ground.........280Installation in ground................................2941.2.2 Voltage drop............................................3081.2.3 Joule-effect losses...................................3181.3 <strong>Protection</strong> against overload...............................3191.4 <strong>Protection</strong> against short-circuit..........................3221.5 Neutral <strong>and</strong> protective conductors....................3311.6 Busbar trunking systems..................................3392 <strong>Protection</strong> of electrical equipment2.1 <strong>Protection</strong> <strong>and</strong> switching of lighting circuits.......3532.2 <strong>Protection</strong> <strong>and</strong> switching of generators.............3622.3 <strong>Protection</strong> <strong>and</strong> switching of motors...................3672.4 <strong>Protection</strong> <strong>and</strong> switching of transformers..........4053 Power factor correction3.1 General aspects................................................4223.2 Power factor correction method........................4283.3 Circuit-breakers for the protection <strong>and</strong>switching of capacitor banks.............................4354 <strong>Protection</strong> of human beings4.1 General aspects: effects of currenton human beings..............................................4404.2 Distribution systems..........................................4424.3 <strong>Protection</strong> against both direct <strong>and</strong>indirect contact.................................................4454.4 TT system.........................................................4484.5 TN system........................................................4524.6 IT system..........................................................4544.7 Residual current devices...................................4564.8 Maximum protected length for theprotection of human beings..............................4595 Photovoltaic plants5.1 Operating principle............................................4645.2 Main components of a photovoltaic plants........4655.2.1 Photovoltaic generator.............................4655.2.2 Inverter....................................................4675.3 Typologies of photovoltaic plants......................4685.3.1 St<strong>and</strong>-alone plants..................................4685.3.2 Grid-connected plants.............................4685.4 Earthing <strong>and</strong> protection againstindirect contact.................................................4695.4.1 Plants with transformer............................4695.4.2 Plants without transformer.......................4735.5 <strong>Protection</strong> against overcurrents <strong>and</strong>overvoltages.....................................................4755.5.1 <strong>Protection</strong> against overcurrentson DC side..............................................4755.5.2 <strong>Protection</strong> against overcurrentson AC side...............................................4805.5.3 Choice of the switching <strong>and</strong>disconnecting devices.............................4815.5.4 <strong>Protection</strong> against overvoltages...............4816 Calculation of short-circuit current6.1 General aspects................................................4856.2 Fault typologies.................................................4856.3 Determination of the short-circuitcurrent: “short-circuit power method”...............4876.3.1 Calculation of the short-circuit current......4876.3.2 Calculation of the short-circuitpower at the fault point............................4906.3.3 Calculation of the short-circuitcurrent.....................................................4916.3.4 Examples.................................................4936.4 Determination of the short-circuit currentIk downstream of a cable as a functionof the upstream one..........................................4976.5 Algebra of sequences.......................................4996.5.1 General aspects......................................4996.5.2 Positive, negative <strong>and</strong> zerosequence systems...................................5006.5.3 Calculation of short-circuit currentswith the algebra of sequences.................5016.5.4 Positive, negative <strong>and</strong> zero sequenceshort-circuit impedances of electricalequipment...............................................5046.5.5 Formulas for the calculation of the faultcurrents as a function of the electricalparameters of the plant ...........................5076.6 Calculation of the peak value of theshort-circuit current ..........................................5106.7 Considerations about UPS contribution tothe short-circuit.................................................511Annex A: Calculation of load current I b................514Annex B: Harmonics .............................................518Annex C: Calculation of the coefficient kfor the cables ..........................................................526Annex D: Main physical quantities <strong>and</strong>electrotechnical formulas .....................................530


1 <strong>Protection</strong> of feeders1.1 IntroductionThe following definitions regarding electrical <strong>installation</strong>s are derived from theSt<strong>and</strong>ard IEC 60050.Characteristics of <strong>installation</strong>s<strong>Electrical</strong> <strong>installation</strong> (of a building) An assembly of associated electricalequipment to fulfil a specific purpose <strong>and</strong> having coordinated characteristics.Origin of an electrical <strong>installation</strong> The point at which electrical energy isdelivered to an <strong>installation</strong>.Neutral conductor (symbol N) A conductor connected to the neutral point ofa system <strong>and</strong> capable of contributing to the transmission of electrical energy.Protective conductor PE A conductor required by some measures forprotection against electric shock for electrically connecting any of the followingparts:- exposed conductive parts;- extraneous conductive parts;- main earthing terminal;- earth electrode;- earthed point of the source or artificial neutral.PEN conductor An earthed conductor combining the functions of bothprotective conductor <strong>and</strong> neutral conductorAmbient temperature The temperature of the air or other medium where theequipment is to be used.VoltagesNominal voltage (of an <strong>installation</strong>) Voltage by which an <strong>installation</strong> or part ofan <strong>installation</strong> is designated.Note: the actual voltage may differ from the nominal voltage by a quantity withinpermitted tolerances.CurrentsDesign current (of a circuit) The current intended to be carried by a circuit innormal service.Current-carrying capacity (of a conductor) The maximum current which canbe carried continuously by a conductor under specified conditions without itssteady-state temperature exceeding a specified value.Overcurrent Any current exceeding the rated value. For conductors, the ratedvalue is the current-carrying capacity.Overload current (of a circuit) An overcurrent occurring in a circuit in theabsence of an electrical fault.Short-circuit current An overcurrent resulting from a fault of negligibleimpedance between live conductors having a difference in potential undernormal operating conditions.268 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.1 IntroductionConventional operating current (of a protective device) A specified valueof the current which cause the protective device to operate within a specifiedtime, designated conventional time.Overcurrent detection A function establishing that the value of current in acircuit exceeds a predetermined value for a specified length of time.Leakage current <strong>Electrical</strong> current in an unwanted conductive path otherthan a short circuit.Fault current The current flowing at a given point of a network resulting froma fault at another point of this network.Wiring systemsWiring system An assembly made up of a cable or cables or busbars <strong>and</strong> theparts which secure <strong>and</strong>, if necessary, enclose the cable(s) or busbars.<strong>Electrical</strong> circuits<strong>Electrical</strong> circuit (of an <strong>installation</strong>) An assembly of electrical equipment of the<strong>installation</strong> supplied from the same origin <strong>and</strong> protected against overcurrentsby the same protective device(s).Distribution circuit (of buildings) A circuit supplying a distribution board.Final circuit (of building) A circuit connected directly to current usingequipment or to socket-outlets.Other equipment<strong>Electrical</strong> equipment Any item used for such purposes as generation,conversion, transmission, distribution or utilization of electrical energy, such asmachines, transformers, apparatus, measuring instruments, protective devices,equipment for wiring systems, appliances.Current-using equipment Equipment intended to convert electrical energyinto another form of energy, for example light, heat, <strong>and</strong> motive power.Switchgear <strong>and</strong> <strong>control</strong>gear Equipment provided to be connected to anelectrical circuit for the purpose of carrying out one or more of the followingfunctions: protection, <strong>control</strong>, isolation, switching.Portable equipment Equipment which is moved while in operation or which caneasily be moved from one place to another while connected to the supply.H<strong>and</strong>-held equipment Portable equipment intended to be held in the h<strong>and</strong>during normal use, in which the motor, if any, forms an integral part of theequipment.Stationary equipment Either fixed equipment or equipment not provided witha carrying h<strong>and</strong>le <strong>and</strong> having such a mass that it cannot easily be moved.Fixed equipment Equipment fastened to a support or otherwise secured ina specific location.<strong>ABB</strong> | <strong>Electrical</strong> devices 269


1 <strong>Protection</strong> of feeders1.1 IntroductionInstallation dimensioningThe flow chart below suggests the procedure to follow for the correct dimensioningof a plant.Load analysis:- definition of the power absorbed by the loads <strong>and</strong> relevant position;- definition of the position of the power distribution centers (switchboards);- definition of the paths <strong>and</strong> calculation of the length of the connection elements;-definition of the total power absorbed, taking into account the utilization factors<strong>and</strong> dem<strong>and</strong> factors.Dimensioning of conductors:- evaluation of the current (Ib) in the single connection elements;- definition of the conductor type (conductors <strong>and</strong> insulation materials,configuration,...);- definition of the cross section <strong>and</strong> of the current carrying capacity;- calculation of the voltage drop at the load current under specific referenceconditions (motor starting,…).Verification of the voltage drop limits at the final loadsnegativeoutcomeShort-circuit current calculation maximum values at the busbars (beginning ofline) <strong>and</strong> minimum values at the end of lineSelection of protective circuit-breakers with:- breaking capacity higher than the maximum prospective short-circuit current;- rated current I n not lower than the load curren I b;- characteristics compatible with the type of protected load (motors, capacitors...).Verification of the protection of conductors:- verification of the protection against overload: the rated current or the set currentof the circuit-breaker shall be higher than the load current, but lower than thecurrent carrying capacity of the conductor:I b ≤ I n ≤ I z- verification of the protection against short-circuit: the specific let-through energyby the circuit breaker under short-circuit conditions shall be lower than the specificlet-through energy which can be withstood by the cable:I 2 t ≤ k 2 S 2- verification of the protection against indirect contacts (depending on thedistribution system).negativeoutcomenegativeoutcomeVerification of the coordination with other equipments (discrimination <strong>and</strong>back-up, verification of the coordination with switch disconnectors...)Definition of the components (auxiliary circuits, terminals…) <strong>and</strong> switchboarddesign1SDC010001F0901270 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesConductors<strong>and</strong> cablesWithoutfixingsFor a correct dimensioning of a cable, it is necessary to:• choose the type of cable <strong>and</strong> <strong>installation</strong> according to the environment;• choose the cross section according to the load current;• verify the voltage drop.1.2.1 Current carrying capacity <strong>and</strong> methods of <strong>installation</strong>Selection of the cableThe international reference St<strong>and</strong>ard ruling the <strong>installation</strong> <strong>and</strong> calculation ofthe current carrying capacity of cables in residential <strong>and</strong> industrial buildings isIEC 60364-5-52 “<strong>Electrical</strong> <strong>installation</strong>s of buildings – Part 5-52 Selection <strong>and</strong>Erection of <strong>Electrical</strong> Equipment- Wiring systems”.The following parameters are used to select the cable type:• conductive material (copper or aluminium): the choice depends on cost,dimension <strong>and</strong> weight requirements, resistance to corrosive environments(chemical reagents or oxidizing elements). In general, the carrying capacityof a copper conductor is about 30% greater than the carrying capacity of analuminium conductor of the same cross section. An aluminium conductor ofthe same cross section has an electrical resistance about 60% higher <strong>and</strong> aweight half to one third lower than a copper conductor.• insulation material (none, PVC, XLPE-EPR): the insulation material affects themaximum temperature under normal <strong>and</strong> short-circuit conditions <strong>and</strong> thereforethe exploitation of the conductor cross section [see Chapter 1.4 “<strong>Protection</strong>against short-circuit”].• the type of conductor (bare conductor, single-core cable without sheath,single-core cable with sheath, multi-core cable) is selected according to mechanicalresistance, degree of insulation <strong>and</strong> difficulty of <strong>installation</strong> (bends,joints along the route, barriers...) required by the method of <strong>installation</strong>.Table 1 shows the types of conductors permitted by the different methodsof <strong>installation</strong>.ClippeddirectConduitsystemsMethod of <strong>installation</strong>Cable trunkingsystems(including skirtingtrunking, flush floortrunking)CableductingsystemsCable ladder,cable tray, cablebracketsOninsulatorsBare conductors - - - - - - + -Insulated conductors b - - + + a + - + -Shealtedcables(includingarmoured<strong>and</strong> mineralinsulatedMulti-core+ + + + + + 0 +Single-core 0 + + + + + 0 ++ Permitted.– Not permitted.0 Not applicable, or not normally used in practice.aInsulated conductors are admitted if the cable trunking systems provide at least the degree of protection IP4X orIPXXD <strong>and</strong> if the cover can only be removed by means of a tool or a deliberate action.bInsulated conductors which are used as protective conductors or protective bonding conductors may use anyappropriate method of <strong>installation</strong> <strong>and</strong> need not be laid in conduits, trunking or ducting systems.Supportwire<strong>ABB</strong> | <strong>Electrical</strong> devices 271


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesFor industrial <strong>installation</strong>s, multi-core cables are rarely used with cross sectiongreater than 95 mm 2 .Methods of <strong>installation</strong>To define the current carrying capacity of the conductor <strong>and</strong> therefore to identifythe correct cross section for the load current, the st<strong>and</strong>ardized method of<strong>installation</strong> that better suits the actual <strong>installation</strong> situation must be identifiedamong those described in the mentioned reference St<strong>and</strong>ard.From Tables 2 <strong>and</strong> 3 it is possible to identify the <strong>installation</strong> identificationnumber, the method of <strong>installation</strong> (A1, A2, B1, B2, C, D1, D2, E, F, G) <strong>and</strong>the tables to define the theoretical current carrying capacity of the conductor<strong>and</strong> any correction factors required to allow for particular environmental <strong>and</strong><strong>installation</strong> situations.Table 2: Method of <strong>installation</strong>BuildingvoidsSituationsWithoutfixingsClippeddirectConduitsystemsMethod of <strong>installation</strong>Cable trunkingsystems(including skirtingtrunking, flush floortrunking)CableductingsystemsCable ladder,cable tray, cablebracketsOninsulatorsAccessible 40 33 41, 42 6, 7, 8, 9, 12 43, 4430, 31, 32,33, 34- 0Not accessible 40 0 41, 42 0 43 0 0 0Cable channel 56 56 54, 55 0 30, 31, 32, 34 - -Buried in ground 72, 73 0 70, 71 - 70, 71 0 - --Embedded in structure 57, 58 3 1, 2, 59, 60 50, 51, 52, 53 46, 45 0 - -Surface mounted - 20, 21, 22, 4, 5 6, 7, 8, 9, 12 6, 7, 8, 9 30, 31, 32, 34 36 -23, 33Overhead/free in air - 33 0 10, 11 10, 11 30, 31, 32, 34 36 35Window frames 16 0 16 0 0 0 - -Architrave 15 0 15 0 0 0 - -Immersed 1 + + + - + 0 - --0+Not permitted.Not applicable or not normally used in practice.Follow manufacturer’s instructions.Supportwire272 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 3: Examples of methods of <strong>installation</strong>ItemNo.Methods of <strong>installation</strong>DescriptionReference method of<strong>installation</strong> to be used toobtain current-carryingcapacity1 RoomInsulated conductors or single-corecables in conduit in a thermallyinsulated wall a, cA12 Room Multi-core cables in conduit in athermally insulated wall a, cA23 RoomMulti-core cable direct in a thermallyinsulated wall a, cA14Insulated conductors or single-corecables in conduit on a wooden ormasonry wall or spaced less than0,3 × conduit diameter from it c B15Multi-core cable in conduit on awooden or masonry wall or spacedless than 0,3 × conduit diameterfrom it cB2676 7Insulated conductors or single-corecables in cable trunking (includesmulti-compartment trunking) on awooden or masonry wall– run horizontally b– run vertically b, c B18Multi-core cable in cable trunking(includes multi-compartment trunking)on a wooden or masonry wallUnder consideration d98 9– run horizontally b– run vertically b, cMethod B2 may be usedNOTE 1 The illustrations are not intended to depict actual product or <strong>installation</strong> practices but are indicative ofthe method described.<strong>ABB</strong> | <strong>Electrical</strong> devices 273


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesItemNoMethods of <strong>installation</strong>DescriptionReference method of<strong>installation</strong> to be used toobtain current-carryingcapacity10Insulated conductors or single-core cablein suspended cable trunking bB11110 11Multi-core cable in suspended cabletrunking bB212Insulated conductors or single-core cablerun in mouldings c,eA115Insulated conductors in conduit or singlecoreor multi-core cable in architrave c, fA116Insulated conductors in conduit or singlecoreor multi-core cable in windowframes c, fA1Single-core or multi-core cables:20– fixed on, or spaced less than 0,3 ×cable diameter from a wooden ormasonry wall cC21Single-core or multi-core cables:– fixed directly under a wooden ormasonry ceilingC, with item 3 ofTable 522Single-core or multi-core cables:– spaced from a ceilingUnder considerationMethod E may be used23Fixed <strong>installation</strong> of suspended currentusingequipmentC, with item 3 ofTable 5274 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesItemNo.Methods of <strong>installation</strong>DescriptionReference method of<strong>installation</strong> to be used toobtain current-carryingcapacity30>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesItemNo.Methods of <strong>installation</strong>DescriptionReference method of<strong>installation</strong> to be used toobtain current-carryingcapacity40DeD eVbuilding void c, h, i 5 D e V < 20 D eSingle-core or multi-core cable in a1,5 D e V < 5 D eB2B141DeD eVbuilding void c, i, j, k V 20 D eInsulated conductor in conduit in a1,5 D e V < 20 D eB2B142Single-core or multi-core cable in conduitin a building void c, kUnder considerationThe following may be used:1,5 D e V < 20 D eB2V 20 D eB143DeVD ein a building void c, i, j, k V 20 D eInsulated conductors in cable ducting1,5 D e V < 20 D eB2B144DeVD eSingle-core or multi-core cable in cableducting in a building void c, kUnder considerationThe following may be used:1,5 D e V < 20 D eB2V 20 D eB145VInsulated conductors in cable ducting inmasonry having a thermal resistivity notgreater than 2 K· m/W c, h, i 1,5 D e5 D eV < 5 D eB2V < 50 D eB146D eVSingle-core or multi-core cable in cableducting in masonry having a thermalresistivity not greater than 2 K· m/W cUnder considerationThe following may be used1,5 D e V < 20 D eB2V 20 D eB147De D eVSingle-core or multi-core cable:– in a ceiling void– in a raised floor h, i 1,5 D e5 D eV < 5 D eB2V < 50 D eB1276 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesItemNo.Methods of <strong>installation</strong>DescriptionReference method of<strong>installation</strong> to be used toobtain current-carryingcapacity50Insulated conductors or single-corecable in flush cable trunking in the floorB151Multi-core cable in flush cable trunkingin the floorB252TVISDN ICTTVISDN ICTInsulated conductors or single-corecables in flush cable trunking cB15352 53Multi-core cable in flush trunking cB254De D eVcable channel run horizontally orvertically c, i, l, n V 20 D eInsulated conductors or single-corecables in conduit in an unventilated1,5 D e V < 20 D eB2B155Insulated conductors in conduit inan open or ventilated cable channelin the floor m, nB156Sheathed single-core or multi-corecable in an open or ventilated cablechannel run horizontally or vertically nB157Single-core or multi-core cable direct inmasonry having a thermal resistivity notgreater than 2 K· m/WWithout added mechanicalprotection o, pC<strong>ABB</strong> | <strong>Electrical</strong> devices 277


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesItemNo.Methods of <strong>installation</strong>DescriptionReference method of<strong>installation</strong> to be used toobtain current-carryingcapacity58Single-core or multi-core cable direct inmasonry having a thermal resistivity notgreater than 2 K· m/WCWith added mechanical protection o, p59Insulated conductors or single-corecables in conduit in masonry pB160 Multi-core cables in conduit in masonry p B270Multi-core cable in conduit or in cableducting in the groundD171Single-core cable in conduit or in cableducting in the groundD172Sheathed single-core or multi-core cablesdirect in the ground– without added mechanical protection q D2278 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesItemNo.Methods of <strong>installation</strong>DescriptionReference method of<strong>installation</strong> to be used toobtain current-carryingcapacity73 Sheathed single-core or multi-core cablesD2direct in the ground– with added mechanical protection qa The inner skin of the wall has a thermal conductance of not less than 10 W/m 2·K.b Values given for <strong>installation</strong> methods B1 <strong>and</strong> B2 are for a single circuit. Where there is more thanone circuit in the trunking the group reduction factor given in Table 5 is applicable, irrespective of thepresence of an internal barrier or partition.c Care shall be taken where the cable runs vertically <strong>and</strong> ventilation is restricted. The ambient temperature atthe top of the vertical section can be increased considerably. The matter is under consideration.d Values for reference method B2 may be used.e The thermal resistivity of the enclosure is assumed to be poor because of the material of construction <strong>and</strong>possible air spaces. Where the construction is thermally equivalent to methods of <strong>installation</strong> 6 or 7, referencemethod B1 may be used.f The thermal resistivity of the enclosure is assumed to be poor because of the material of construction <strong>and</strong>possible air spaces. Where the construction is thermally equivalent to methods of <strong>installation</strong> 6, 7, 8, or 9,reference methods B1 or B2 may be used.g The factors in Table 5 may also be used.hD e is the external diameter of a multi-core cable:- 2,2 × the cable diameter when three single core cables are bound in trefoil, or- 3 × the cable diameter when three single core cables are laid in flat formation.ijlV is the smaller dimension or diameter of a masonry duct or void, or the vertical depth of a rectangular duct,floor or ceiling void or channel. The depth of the channel is more important than the width.D e is the external diameter of conduit or vertical depth of cable ducting.D e is the external diameter of the conduit.m For multi-core cable installed in method 55, use current-carrying capacity for reference method B2.n It is recommended that these methods of <strong>installation</strong> are used only in areas where access is restricted toauthorized persons so that the reduction in current-carrying capacity <strong>and</strong> the fire hazard due to theaccumulation of debris can be prevented.o For cables having conductors not greater than 16 mm 2 , the current-carrying capacity may be higher.p Thermal resistivity of masonry is not greater than 2 K·m/W, the term “masonry” is taken to include brickwork,concrete, plaster <strong>and</strong> the like (other than thermally insulating materials).q The inclusion of directly buried cables in this item is satisfactory when the soil thermal resistivity is of the orderof 2,5 K · m/W. For lower soil resistivities, the current-carrying capacity for directly buried cables is appreciablyhigher than for cables in ducts.<strong>ABB</strong> | <strong>Electrical</strong> devices 279


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesInstallation not buried in the ground: choice of thecross section according to cable carrying capacity <strong>and</strong>type of <strong>installation</strong>The cable carrying capacity of a cable that is not buried in the ground is obtainedby using this formula:where:• I 0is the current carrying capacity of the single conductor at 30 °C referenceambient temperature;• k 1is the correction factor if the ambient temperature is other than 30 °C;• k 2is the correction factor for cables installed bunched or in layers or for cablesinstalled in a layer on several supports.Correction factor k 1The current carrying capacity of the cables that are not buried in the groundrefers to 30 °C ambient temperature. If the ambient temperature of the placeof <strong>installation</strong> is different from this reference temperature, the correction factork 1on Table 4 shall be used, according to the insulation material.Table 4: Correction factor for ambient air temperature other than 30 °CInsulationAmbienttemperature (a)°C1015202535404550556065707580859095PVC1.221.171.121.060.940.870.790.710.610.50–––––––XLPE <strong>and</strong> EPR1.151.121.081.040.960.910.870.820.760.710.650.580.500.41–––PVC covered orbare <strong>and</strong> exposedto touch 70 °C1.261.201.141.070.930.850.870.670.570.45–––––––(a)For higher ambient temperatures, consult manufacturer.Mineral (a)Bare not exposedto touch 105 °C1.141.111.071.040.960.920.880.840.800.750.700.650.600.540.470.400.32280 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesCorrection factor k 2The cable current carrying capacity is influenced by the presence of othercables installed nearby. The heat dissipation of a single cable is different fromthat of the same cable when installed next to the other ones. The factor k 2istabled according to the <strong>installation</strong> of cables laid close together in layers orbunches.Definition of layer or bunchlayer: several circuits constituted by cables installed one next to another, spacedor not, arranged horizontally or vertically. The cables on a layer are installed ona wall, tray, ceiling, floor or on a cable ladder;> 2 De 2a)De 1 De 2b)c)< 30 cmCables in layers: a) spaced; b) not spaced; c) double layer1SDC010002F0001bunch: several circuits constituted by cables that are not spaced <strong>and</strong> are notinstalled in a layer; several layers superimposed on a single support (e.g. tray)are considered to be a bunch.<strong>ABB</strong> | <strong>Electrical</strong> devices 281


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesa)b)c)Bunched cables: a) in trunking; b) in conduit; c) on perforated tray1SDC010003F0001The value of correction factor k 2is 1 when:• the cables are spaced:- two single-core cables belonging to different circuits are spaced when thedistance between them is more than twice the external diameter of thecable with the larger cross section;- two multi-core cables are spaced when the distance between them is atleast the same as the external diameter of the larger cable;• the adjacent cables are loaded less than 30 % of their current carrying capacity.The correction factors for bunched cables or cables in layers are calculated byassuming that the bunches consist of similar cables that are equally loaded. Agroup of cables is considered to consist of similar cables when the calculation ofthe current carrying capacity is based on the same maximum allowed operatingtemperature <strong>and</strong> when the cross sections of the conductors is in the range ofthree adjacent st<strong>and</strong>ard cross sections (e.g. from 10 to 25 mm 2 ).The calculation of the reduction factors for bunched cables with different crosssections depends on the number of cables <strong>and</strong> on their cross sections. Thesefactors have not been tabled, but must be calculated for each bunch or layer.282 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesThe reduction factor for a group containing different cross sections of insulatedconductors or cables in conduits, cable trunking or cable ducting is:where:• k 2is the group reduction factor;• n is the number of multi-core cables of the number of circuit in the groupThe reduction factor obtained by this equation reduces the danger of overloadingof cables with a smaller cross section, but may lead to under utilization ofcables with a larger cross section. Such under utilization can be avoided if large<strong>and</strong> small cables are not mixed in the same group.The following tables show the reduction factor (k 2).Table 5: Reduction factor for grouped cablesnItem12345Arrangement(cables touching)Bunched in air, on asurface, embedded orenclosedSingle layer on wall,floor or unperforatedtraySingle layer fixeddirectly under awooden ceilingSingle layer on aperforated horizontal orvertical traySingle layer on laddersupport or cleats etc.12Number of circuits or multi-core cables3 4 5 6 7 8 9 121.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.45 0.41 0.381.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.700.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.611.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.721.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.781620No furtherreductionfactor for morethannine circuits ormulticore cablesTo be used withcurrent-carryingcapacities,referenceMethods A to FMethod CMethods E <strong>and</strong> FNOTE 1 These factors are applicable to uniform groups of cables, equally loaded.NOTE 2 Where horizontal clearances between adjacent cables exceeds twice their overall diameter, no reductionfactor need be applied.NOTE 3 The same factors are applied to:– groups of two or three single-core cables;– multi-core cables.NOTE 4 If a system consists of both two- <strong>and</strong> three-core cables, the total number of cables is taken as the number ofcircuits, <strong>and</strong> the corresponding factor is applied to the tables for two loaded conductors for the two-corecables, <strong>and</strong> to the tables for three loaded conductors for the three-core cables.NOTE 5 If a group consists of n single-core cables it may either be considered as n/2 circuits of two loadedconductors or n/3 circuits of three loaded conductors.NOTE 6 For some <strong>installation</strong>s <strong>and</strong> for other methods not provided for in the above table, it may be appropriate to usefactors calculated for specific case, see for example tables 6-7.<strong>ABB</strong> | <strong>Electrical</strong> devices 283


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 6: Reduction factor for single-core cables with method of<strong>installation</strong> FPerforatedtrays(note 3)Method of <strong>installation</strong> in Table 33120 mmTouching300 mmNumber oftrays123Number of three-phasecircuits (note 4)1 2 30.980.960.950.910.870.850.870.810.78Use as amultiplier torating forThree cables inhorizontalformationTouchingVerticalperforatedcable trayssystems(note 4)31225 mm120.960.950.860.84––Three cables inverticalformationCable laddersystemcleats, etc.(note 3)Perforatedcable trayssystem(note 3)Verticalperforatedcable trayssystem(note 4)CableLadder systemcleats, etc.(note 3)3233343131323334Touching20 mm≥2D e e20 mmSpaced225 mm2D e e20 mmDeD eD e≥2D eDeD e300 mm300 mm300 mm123123121231.000.980.971.000.970.961.001.001.000.970.960.970.930.900.980.930.920.910.901.000.950.940.960.890.860.960.890.860.890.861.000.930.90Three cables inhorizontalformationThree cables intrefoil formationNOTE 1 Values given are averages for the cable types <strong>and</strong> range of conductor sizes considered in Table 8 to 9 (<strong>installation</strong> methodsE, F <strong>and</strong> G). The spread of values is generally less than 5 %.NOTE 2 Factors are given for single layers of cables (or trefoil groups) as shown in the table <strong>and</strong> do not apply when cables areinstalled in more than one layer touching each other. Values for such <strong>installation</strong>s may be significantly lower <strong>and</strong> shouldbe determined by an appropriate method.NOTE 3 Values are given for vertical spacing between cable trays of 300 mm <strong>and</strong> at least 20 mm between cable trays <strong>and</strong> wall.For closer spacing the factors should be reduced.NOTE 4 Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted back to back. For closerspacing the factors should be reduced.NOTE 5 For circuits having more than one cable in parallel per phase, each three phase set of conductors should be consideredas a circuit for the purpose of this table.NOTE 6 If a circuit consists of m parallel conductors per phase, then for determining the reduction factor this circuitshould beconsidered as m circuits.1SDC010004F0201284 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 7: Reduction factor for multi-core cables with method of<strong>installation</strong> EMethod of <strong>installation</strong> in Table 3TouchingNumberof traysorladdersNumber of cables per tray or ladder1 2 3 4 6 911,000,880,820,790,760,7321,000,870,800,770,730,68Perforatedcable traysystems3120 mm 300 mm361,001,000,860,840,790,770,760,730,710,680,660,64(note 3)SpacedDDee 11,001,000,980,950,91–21,000,990,960,920,87–20 mm31,000,980,950,910,85–TouchingVerticalperforatedcable traysystems(note 4)31225 mm225mmSpaced121,001,000,880,880,820,810,780,760,730,710,720,70225 mm225mm12Dee1,001,000,910,910,890,880,880,870,870,85––TouchingUnperforatedcable traysystems3120 mm 300 mm12360,970,970,970,970,840,830,820,810,780,760,750,730,750,720,710,690,710,680,660,630,680,630,610,58TouchingCable laddersystems,cleats, etc.(note 3)32333420 mm300 mm 300 mm12361,001,001,001,000,870,860,850,840,820,800,790,770,800,780,760,730,790,760,730,680,780,730,700,64<strong>ABB</strong> | <strong>Electrical</strong> devices 285


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesMethod of <strong>installation</strong> in Table 3SpacedNumberof traysorladdersDDee 12320 mmNumber of cables per tray or ladder1 2 3 4 6 91,00 1,00 1,00 1,00 1,00 –1,00 0,99 0,98 0,97 0,96 –1,00 0,98 0,97 0,96 0,93 –NOTE 1 Values given are averages for the cable types <strong>and</strong> range of conductor sizes considered in Tables 8to 9 (<strong>installation</strong> methods E, F <strong>and</strong> G). The spread of values is generally less than 5 %.NOTE 2 Factors apply to single layer groups of cables as shown above <strong>and</strong> do not apply when cables are installed inmore than one layer touching each other. Values for such <strong>installation</strong>s may be significantly lower <strong>and</strong> has to bedetermined by an appropriate method.NOTE 3 Values are given for vertical spacing between cable trays of 300 mm <strong>and</strong> at least 20 mm between cabletrays <strong>and</strong> wall. For closer spacing the factors should be reduced.NOTE 4 Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted back toback. For closer spacing the factors should be reduced.286 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTo summarize:The following procedure shall be used to determine the cross section of thecable:1. from Table 3 identify the method of <strong>installation</strong>;2. from Table 4 determine the correction factor k 1according to insulation material<strong>and</strong> ambient temperature;3. use Table 5 for cables installed in layer or bunch, Table 6 for single-corecables in a layer on several supports, Table 7 for multi-core cables in a layeron several supports or the formula shown in the case of groups of cableswith different sections to determine the correction factor k 2appropriate forthe numbers of circuits or multi-core cables;4. calculate the value of current I’ bby dividing the load current I b(or the ratedcurrent of the protective device) by the product of the correction factorscalculated:5. from Table 8 or from Table 9, depending on the method of <strong>installation</strong>, oninsulation <strong>and</strong> conductive material <strong>and</strong> on the number of live conductors,determine the cross section of the cable with capacity I 0≥ I’ b;6. the actual cable current carrying capacity is calculated by I Z= I 0k 1k 2.<strong>ABB</strong> | <strong>Electrical</strong> devices 287


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 8: Current carrying capacity of cables with PVC or EPR/XLPEinsulation (method A-B-C)InstallationmethodA1A2ConductorInsulationXLPEEPRCuPVCXLPEEPRAlPVCXLPEEPRCuPVCXLPEEPRAlPVCCuXLPEEPRLoadedS[mm 2 conductors]2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 31.5 19 17 14.5 13.5 18.5 16.5 14 13.0 23 202.5 26 23 19.5 18 20 19 14.5 15 14 25 22 18.5 17.5 19.5 18 14.5 13.5 31 284 35 31 26 24 27 25 20 18.5 33 30 25 23 26 24 19.5 20 17.5 42 376 45 40 34 31 35 32 26 24 42 38 32 29 33 31 25 23 54 4810 61 54 46 42 48 44 36 32 57 51 43 39 45 41 33 31 75 6616 81 73 61 56 64 58 48 43 76 68 57 52 60 55 44 41 100 8825 106 95 80 73 84 76 63 57 99 89 75 68 78 71 58 53 133 11735 131 117 99 89 103 94 77 70 121 109 92 83 96 87 71 65 164 14450 158 141 119 108 125 113 93 84 145 130 110 99 115 104 86 78 198 17570 200 179 151 136 158 142 118 107 183 164 139 125 145 131 108 98 253 22295 241 216 182 164 191 171 142 129 220 197 167 150 175 157 130 118 306 269120 278 249 210 188 220 197 164 149 253 227 192 172 201 180 150 135 354 312150 318 285 240 216 253 226 189 170 290 259 219 196 230 206 172 155 393 342185 362 324 273 245 288 256 215 194 329 295 248 223 262 233 195 176 449 384240 424 380 321 286 338 300 252 227 386 346 291 261 307 273 229 207 528 450300 486 435 367 328 387 344 289 261 442 396 334 298 352 313 263 237 603 514400500630288 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesB1B2CPVCXLPEEPRAlPVCXLPEEPRCuPVCXLPEEPRAlPVCCuXLPEEPR PVC XLPE/EPR PVCAl2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 317.5 15.5 22 19.5 16.5 15 24 22 19.5 17.524 21 25 22 18.5 16.5 30 26 23 20 23 21 17.5 15.5 33 30 27 24 26 24 21 18.532 28 33 29 25 22.0 40 35 30 27 31 28 24 21 45 40 36 32 35 32 28 25.041 36 43 38 32 28 51 44 38 34 40 35 30 27.0 58 52 46 41 45 41 36 3257 50 59 52 44 39 69 60 52 46 54 48 41 36 80 71 63 57 62 57 49 4476 68 79 71 60 53 91 80 69 62 72 64 54 48 107 96 85 76 84 76 66 59101 89 105 93 79 70 119 105 90 80 94 84 71 62 138 119 112 96 101 90 83 73125 110 130 116 97 86 146 128 111 99 115 103 86 77 171 147 138 119 126 112 103 90151 134 157 140 118 104 175 154 133 118 138 124 104 92 209 179 168 144 154 136 125 110192 171 200 179 150 133 221 194 168 149 175 156 131 116 269 229 213 184 198 174 160 140232 207 242 217 181 161 265 233 201 179 210 188 157 139 328 278 258 223 241 211 195 170269 239 281 251 210 186 305 268 232 206 242 216 181 160 382 322 299 259 280 245 226 197300 262 307 267 234 204 334 300 258 225 261 240 201 176 441 371 344 299 324 283 261 227341 296 351 300 266 230 384 340 294 255 300 272 230 199 506 424 392 341 371 323 298 259400 346 412 351 312 269 459 398 344 297 358 318 269 232 599 500 461 403 439 382 352 305458 394 471 402 358 306 532 455 394 339 415 364 308 265 693 576 530 464 508 440 406 3511SDC010006F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 289


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 8: Current carrying capacity of cables with PVC or EPR/XLPEinsulation (method E-F-G)InstallationmethodEForInsulationCuXLPEEPR PVCXLPEEPRAl Cu AlPVCXLPEEPRPVCXLPEEPRPVCCuXLPEEPR PVCXLPEEPRAl Cu AlPVCXLPEEPRPVCXLPEEPRPVCS[mm 2 ]Loadedconductors2 32 31.5 26 22 23 18.52.5 36 30 28 23 32 252 24 19.5 54 49 40 38 31 42 34 32 266 63 51 49 39 54 43 42 3310 86 70 67 54 75 60 58 4616 115 94 91 73 100 80 77 6125 149 119 108 89 127 101 97 78 161 131 121 98 135110 103 84535 185 148 135 111 158 126 120 96 200 162 150 122 169 137 129 10550 225 180 164 135 192 153 146 117 242 196 184 149 207 167 159 12870 289 232 211 173 246 196 187 150 310 251 237 192 268 216 206 16695 352 282 257 210 298 238 227 183 377 304 289 235 328 264 253 203120 410 328 300 244 346 276 263 212 437 352 337 273 383 308 296 237150 473 379 346 282 399 319 304 245 504 406 389 316 444 356 343 274185 542 434 397 322 456 364 347 280 575 463 447 363 510 409 395 315240 641 514 470 380 538 430 409 330 679 546 530 430 607 485 471 375300 741 593 543 439 621 497 471 381 783 629 613 497 703 561 547 434400 940 754 740 600 823 656 663 526500 1083 868 856 694 946 749 770 610630 1254 1005 996 808 1088 855 899 711290 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesGorD eD eCuXLPEEPR PVCAlXLPEEPRPVCXLPEEPRCuPVCCXLPEEPRAlPVC33H 3V 3H 3V 3H 3V 3H 3V141 114 107 87 182 161 146 130 138 122 112 99176 143 135 109 226 201 181 162 172 153 139 124216 174 165 133 275 246 219 197 210 188 169 152279 225 215 173 353 318 281 254 271 244 217 196342 275 264 212 430 389 341 311 332 300 265 241400 321 308 247 500 454 396 362 387 351 308 282464 372 358 287 577 527 456 419 448 408 356 327533 427 413 330 661 605 521 480 515 470 407 376634 507 492 392 781 719 615 569 611 561 482 447736 587 571 455 902 833 709 659 708 652 557 519868 689 694 552 1085 1008 852 795 856 792 671 629998 789 806 640 1253 1169 982 920 991 921 775 7301151 905 942 746 1454 1362 1138 1070 1154 1077 900 8521SDC010100F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 291


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 9: Current carrying capacity of cables with mineral insulationInstallationmethodCSheathPVC covered orbare exposed to touchBare cable notexposed to touchPVC covered orbare exposed to touchLoadedconductorsoror500 V750 VS[mm 2 ]1.52.541.52.546101625355070951201501852402 3 3 2 3 3 2 323 19 21 28 24 27 25 2131 26 29 38 33 36 33 2840 35 38 51 44 47 44 3725 21 23 31 26 30 26 2234 28 31 42 35 41 36 3045 37 41 55 47 53 47 4057 48 52 70 59 67 60 5177 65 70 96 81 91 82 69102 86 92 127 107 119 109 92133 112 120 166 140 154 142 120163 137 147 203 171 187 174 147202 169 181 251 212 230 215 182247 207 221 307 260 280 264 223296 249 264 369 312 334 317 267340 286 303 424 359 383 364 308388 327 346 485 410 435 416 352440 371 392 550 465 492 472 399514 434 457 643 544 572 552 466Note 1 For single-core cables the sheaths of the cables of the circuit are connected together at both ends.Note 2 For bare cables exposed to touch, values should be multiplied by 0.9.Note 3 D e is the external diameter of the cable.Note 4 For metallic sheath temperature 105 ϒC no correction for grouping need to be applied.292 <strong>Electrical</strong> devices | <strong>ABB</strong>


1.2 Installation <strong>and</strong> dimensioning of cables1 <strong>Protection</strong> of feedersE or FGBare cable notexposed e to touchPVC covered orbare exposed to touchBare cable notexposed to touchor or or orD eD eD eD e3 223 3131 4141 5426 3334 4545 6057 7677 104102 137132 179161 220198 272241 333289 400331 460377 526426 596496 6973 3 3 3 3 326 29 26 29 33.0 37.035 39 34 39 43 4946 51 45 51 56 6428 32 28 32 35 4038 43 37 43 47 5450 56 49 56 61 7064 71 62 71 78 8987 96 84 95 105 120115 127 110 125 137 157150 164 142 162 178 204184 200 173 197 216 248228 247 213 242 266 304279 300 259 294 323 370335 359 309 351 385 441385 411 353 402 441 505441 469 400 454 498 565500 530 446 507 557 629584 617 497 565 624 7041SDC010007F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 293


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesInstallation in ground: choice of the cross sectionaccording to cable carrying capacity <strong>and</strong> type of<strong>installation</strong>The current carrying capacity of a cable buried in the ground is calculated byusing this formula:where:• I 0is the current carrying capacity of the single conductor for <strong>installation</strong> in theground at 20°C reference temperature;• k 1is the correction factor if the temperature of the ground is other than20°C;• k 2is the correction factor for adjacent cables;• k 3is the correction factor if the soil thermal resistivity is different from thereference value, 2.5 Km/W.Correction factor k 1The current carrying capacity of buried cables refers to a ground temperature of20 °C. If the ground temperature is different, use the correction factor k 1shownin Table 10 according to the insulation material.Table 10: Correction factors for ambient ground temperatures otherthan 20 °CGroundtemperature°C1015253035404550556065707580PVC1.101.050.950.890.840.770.710.630.550.45––––InsulationXLPE <strong>and</strong> EPR1.071.040.960.930.890.850.800.760.710.650.600.530.460.38294 <strong>Electrical</strong> devices | <strong>ABB</strong>


1.2 Installation <strong>and</strong> dimensioning of cables1 <strong>Protection</strong> of feedersCorrection factor k 2The cable current carrying capacity is influenced by the presence of other cablesinstalled nearby. The heat dissipation of a single cable is different from that ofthe same cable installed next to the other ones.The correction factor k 2is obtained by the formula:Tables 11, 12, <strong>and</strong> 13 show the factor k 2’ values for single-core <strong>and</strong> multicorecables that are laid directly in the ground or which are installed in buriedducts, according to their distance from other cables or the distance betweenthe ducts.Table 11: Reduction factors for cables laid directly in the ground(<strong>installation</strong> method D2)Numberof circuitsNil(cables touching)One cablediameterCable to cable clearance0,125 m 0,25 m 0,5 m2 0,75 0,80 0,85 0,90 0,903 0,65 0,70 0,75 0,80 0,854 0,60 0,60 0,70 0,75 0,805 0,55 0,55 0,65 0,70 0,806 0,50 0,55 0,60 0,70 0,807 0,45 0,51 0,59 0,67 0,768 0,43 0,48 0,57 0,65 0,759 0,41 0,46 0,55 0,63 0,7412 0,36 0,42 0,51 0,59 0,7116 0,32 0,38 0,47 0,56 0,3820 0,29 0,35 0,44 0,53 0,66Multi-core cablesaaaaSingle-core cablesaaNOTE 1 Values given apply to an <strong>installation</strong> depth of 0,7 m <strong>and</strong> a soil thermal resistivity of 2,5 K·m/W.They are average values for the range of cable sizes <strong>and</strong> types quoted for Tables 8-15-16. The processof averaging, together with rounding off, can result in some cases in errors up to ±10 %. (Where moreprecise values are required they may be calculated by methods given in IEC 60287-2-1.)NOTE 2 In case of a thermal resistivity lower than 2,5 K· m/W the corrections factors can, in general, beincreased <strong>and</strong> can be calculated by the methods given in IEC 60287-2-1.NOTE 3 If a circuit consists of m parallel conductors per phase, then for determining the reductionfactor, this circuit should be considered as m circuits.<strong>ABB</strong> | <strong>Electrical</strong> devices 295


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesN umberof cablesTable 12: Reduction factors for multi-core cables laid in single wayducts in the ground (<strong>installation</strong> method D1)Nil(ducts touching)Multi-core cables in single-way ductsDuct to duct clearance0,25 m 0,5 m 1,0 m2 0,85 0,90 0,95 0,953 0,75 0,85 0,90 0,954 0,70 0,80 0,85 0,905 0,65 0,80 0,85 0,906 0,60 0,80 0,80 0,907 0,57 0,76 0,80 0,888 0,54 0,74 0,78 0,889 0,52 0,73 0,77 0,8710 0,49 0,72 0,76 0,8611 0,47 0,70 0,75 0,8612 0,45 0,69 0,74 0,8513 0,44 0,68 0,73 0,8514 0,42 0,68 0,72 0,8415 0,41 0,67 0,72 0,8416 0,39 0,66 0,71 0,8317 0,38 0,65 0,70 0,8318 0,37 0,65 0,70 0,8319 0,35 0,64 0,69 0,8220 0,34 0,63 0,68 0,82Multi-core cablesaNOTE 1 Values given apply to an <strong>installation</strong> depth of 0,7 m <strong>and</strong> a soil thermal resistivity of 2,5 K·m/W.They are average values for the range of cable sizes <strong>and</strong> types quoted for Tables 8-15-16. The processof averaging, together with rounding off, can result in some cases in errors up to ±10 %. (Where moreprecise values are required they may be calculated by methods given in IEC 60287-2-1.)NOTE 2 In case of a thermal resistivity lower than 2,5 K· m/W the corrections factors can, in general, beincreased <strong>and</strong> can be calculated by the methods given in IEC 60287-2-1.NOTE 3 If a circuit consists of m parallel conductors per phase, then for determining the reductionfactor, this circuit should be considered as m circuits.296 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesNumber of singlecorecircuits of twoor three cablesTable 13: Reduction factors for single-core cables laid in single wayducts in the ground (<strong>installation</strong> method D1)Single-core cables in non- magnetic single-way ductsNil(ducts touching)Duct to duct clearance0,25 m 0,5 m 1,0 m2 0,80 0,90 0,90 0,953 0,70 0,80 0,85 0,904 0,65 0,75 0,80 0,905 0,60 0,70 0,80 0,906 0,60 0,70 0,80 0,907 0,53 0,66 0,76 0,878 0,50 0,63 0,74 0,879 0,47 0,61 0,73 0,8610 0,45 0,59 0,72 0,8511 0,43 0,57 0,70 0,8512 0,41 0,56 0,69 0,8413 0,39 0,54 0,68 0,8414 0,37 0,53 0,68 0,8315 0,35 0,52 0,67 0,8316 0,34 0,51 0,66 0,8317 0,33 0,50 0,65 0,8218 0,31 0,49 0,65 0,8219 0,30 0,48 0,64 0,8220 0,29 0,47 0,63 0,81Single-core cablesaaaaNOTE 1 Values given apply to an <strong>installation</strong> depth of 0,7 m <strong>and</strong> a soil thermal resistivity of 2,5 K·m/W.They are average values for the range of cable sizes <strong>and</strong> types quoted for Tables 8-15-16. The processof averaging, together with rounding off, can result in some cases in errors up to ±10 %. (Where moreprecise values are required they may be calculated by methods given in IEC 60287-2-1.)NOTE 2 In case of a thermal resistivity lower than 2,5 K· m/W the corrections factors can, in general, beincreased <strong>and</strong> can be calculated by the methods given in IEC 60287-2-1.NOTE 3 If a circuit consists of m parallel conductors per phase, then for determining the reductionfactor, this circuit should be considered as m circuits.<strong>ABB</strong> | <strong>Electrical</strong> devices 297


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesFor correction factor k 2’’:• for cables laid directly in the ground or if there are not other conductors withinthe same duct, the value of k 2’’ is 1;• if several conductors of similar sizes are present in the same duct (for themeaning of “group of similar conductors”, see the paragraphs above), k 2’’ isobtained from the first row of Table 5;• if the conductors are not of similar size, the correction factor is calculated byusing this formula:where:n is the number of circuits in the duct.Correction factor k 3Soil thermal resistivity influences the heat dissipation of the cable. Soil with lowthermal resistivity facilitates heat dissipation, whereas soil with high thermalresistivity limits heat dissipation. IEC 60364-5-52 states as reference value forthe soil thermal resistivity 2.5 Km/W.Table 14: Correction factors for soil thermal resistivities other than2.5 Km/WThermal resistivity, K ·m/W 0,5 0,7 1 1,5 2 2,5 3Correction factor for cables in buried ducts 1,28 1,20 1,18 1,1 1,05 1 0,96Correction factor for direct buried cables 1,88 1,62 1,5 1,28 1,12 1 0,90NOTE 1 The correction factors given have been averaged over the range of conductor sizes <strong>and</strong> types of<strong>installation</strong> included in Tables 8-15-16. The overall accuracy of correction factors is within ±5 %.NOTE 2 The correction factors are applicable to cables drawn into buried ducts; for cables laid direct in theground the correction factors for thermal resistivities less than 2,5 K· m/W will be higher. Where more precisevalues are required they may be calculated by methods given in the IEC 60287 series.NOTE 3 The correction factors are applicable to ducts buried at depths of up to 0,8 m.NOTE 4 It is assumed that the soil properties are uniform. No allowance had been made for the possibility ofmoisture migration which can lead to a region of high thermal resistivity around the cable. If partial drying out ofthe soil is foreseen, the permissible current rating should be derived by the methods specified in the IEC 60287series.298 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTo summarize:Use this procedure to determine the cross section of the cable:1. from Table 10, determine the correction factor k 1according to the insulationmaterial <strong>and</strong> the ground temperature;2. use Table 11, Table 12, Table 13 or the formula for groups of non-similar cablesto determine the correction factor k 2according to the distance betweencables or ducts;3. from Table 14 determine factor k 3corresponding to the soil thermal resistivity;4. calculate the value of the current I’ bby dividing the load current I b(or therated current of the protective device) by the product of the correction factorscalculated:5. from Tables 15-16, determine the cross section of the cable with I 0≥ I’ b, accordingto the method of <strong>installation</strong>, the insulation <strong>and</strong> conductive material<strong>and</strong> the number of live conductors;6. the actual cable current carrying capacity is calculated by.Table 15: Current carrying capacity of cables buried in the ground(<strong>installation</strong> method D1)InstallationmethodD1ConductorInsulationXLPEEPRCuPVCXLPEEPRAlPVCS[mm 2 ]1.52.54610162535507095120150185240300Loadedconductors2 3 2 3 2 3 2 325334853719111613916420323927130634339549621283644587596115135167197223251281324365222937466078991191401732042312612923363791824303850648298116143169192217243280316263342557190108128158186211238267307346222835465975901061301541741972202532862229364761779310913515918020422826229618.5243039506477911121321501691902182471SDC010008F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 299


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 16: Current carrying capacity of cables buried in the ground(<strong>installation</strong> method D2)InstallationmethodD2ConductorInsulationXLPEEPRCuPVCXLPEEPRAlPVCS[mm 2 ]1.52.54610162535507095120150185240300Loadedconductors2 3 2 3 2 3 2 32735465877100129155183225270306343387448502233039496574107129153188226257287324375419222838486483110132156192230261293331382427192433415470921101301621932202462783203597698117139170204233261296343386648298117144172197220250290326638298117145173200224255298336536983991221481691892142502821SDC010012F0201300 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cables1SDC010009F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 301


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesNote on current carrying capacity tables <strong>and</strong> loaded conductorsTables 8, 9, 15 <strong>and</strong> 16 provide the current carrying capacity of loaded conductors(current carrying conductors) under normal service conditions.In single-phase circuits, the number of loaded conductors is two.In balanced or slightly unbalanced three-phase circuits the number of loadedconductors is three, since the current in the neutral conductor is negligible.In three-phase systems with high unbalance, where the neutral conductorin a multi-core cable carries current as a result of an unbalance in the phasecurrents the temperature rise due to the neutral current is offset by the reductionin the heat generated by one or more of the phase conductors. In this case theconductor size shall be chosen on the basis of the highest phase current. In allcases the neutral conductor shall have an adequate cross section.Effect of harmonic currents on balanced three-phasesystems: reduction factors for harmonic currents in fourcore<strong>and</strong> five-core cables with four cores carrying currentWhere the neutral conductor carries current without a corresponding reductionin load of the phase conductors, the current flowing in the neutral conductorshall be taken into account in ascertaining the current-carrying capacity of thecircuit.This neutral current is due to the phase currents having a harmonic contentwhich does not cancel in the neutral. The most significant harmonic whichdoes not cancel in the neutral is usually the third harmonic. The magnitude ofthe neutral current due to the third harmonic may exceed the magnitude of thepower frequency phase current. In such a case the neutral current will have asignificant effect on the current-carrying capacity of the cables in the circuit.ABNC1SDC010007F0001302 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesEquipment likely to cause significant harmonic currents are, for example, fluorescentlighting banks <strong>and</strong> dc power supplies such as those found in computers(for further information on harmonic disturbances see the IEC 61000).The reduction factors given in Table 16 only apply in the balanced three-phasecircuits (the current in the fourth conductor is due to harmonics only) to cableswhere the neutral conductor is within a four-core or five-core cable <strong>and</strong> is ofthe same material <strong>and</strong> cross-sectional area as the phase conductors. Thesereduction factors have been calculated based on third harmonic currents. Ifsignificant, i.e. more than 10 %, higher harmonics (e.g. 9th, 12th, etc.) areexpected or there is an unbalance between phases of more than 50 %, thenlower reduction factors may be applicable: these factors can be calculated onlyby taking into account the real shape of the current in the loaded phases.Where the neutral current is expected to be higher than the phase current thenthe cable size should be selected on the basis of the neutral current.Where the cable size selection is based on a neutral current which is not significantlyhigher than the phase current, it is necessary to reduce the tabulatedcurrent carrying capacity for three loaded conductors.If the neutral current is more than 135 % of the phase current <strong>and</strong> the cable sizeis selected on the basis of the neutral current, then the three phase conductorswill not be fully loaded. The reduction in heat generated by the phase conductorsoffsets the heat generated by the neutral conductor to the extent that it isnot necessary to apply any reduction factor to the current carrying capacity forthree loaded conductors.Third harmonic contentof phase current%Table 17: Reduction factors for harmonic currents in four-core <strong>and</strong>five-core cablesSize selection isbased on phasecurrentCurrent to take inaccount for thecable selectionI b’Reduction factorSize selection isbased on neutralcurrentCurrent to take inaccount for thecable selectionI b’0 ÷ 151--15 ÷ 330.86--33 ÷ 45--0.86> 45--1Where I Nis the current flowing in the neutral calculated as follows:I bis the load current;k totis the total correction factor;k IIIis the third harmonic content of phase current;<strong>ABB</strong> | <strong>Electrical</strong> devices 303


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesExample of cable dimensioning in a balanced threephasecircuit without harmonicsDimensioning of a cable with the following characteristics:• conductor material: : copper• insulation material: : PVC• type of cable: : multi-core• <strong>installation</strong>: : cables bunched on horizontalperforated tray• load current: : 100 AInstallation conditions:• ambient temperature: : 40 °C• adjacent circuits with a) three-phase circuit consisting of 4single-core cables, 4x50 mm 2 ;b) three-phase circuit consisting ofone multi-core cable, 1x(3x50) mm 2 ;c) three-phase circuit consisting of 9single-core (3 per phase) cables,9x95 mm 2 ;d) single-phase circuit consisting of 2single-core cables, 2x70 mm 2 .abcd1SDC010008F0001304 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesProcedure:Type of <strong>installation</strong>In Table 3, it is possible to find the reference number of the <strong>installation</strong> <strong>and</strong>the method of <strong>installation</strong> to be used for the calculations. In this example, thereference number is 31, which corresponds to method E (multi-core cable ontray).Correction factor of temperature k 1From Table 4, for a temperature of 40 °C <strong>and</strong> PVC insulation material,k 1= 0.87.Correction factor for adjacent cables k 2For the multi-core cables grouped on the perforated tray see Table 5.As a first step, the number of circuits or multi-core cables present shall bedetermined; given that:• each circuit a), b) <strong>and</strong> d) constitute a separate circuit;• circuit c) consists of three circuits, since it is composed by three cables inparallel per phase;• the cable to be dimensioned is a multi-core cable <strong>and</strong> therefore constitutesa single circuit;the total number of circuits is 7.Referring to the row for the arrangement (cables bunched) <strong>and</strong> to the columnfor the number of circuits (7)After k 1<strong>and</strong> k 2have been determined, I’ bis calculated by:From Table 8, for a multi-core copper cable with PVC insulation, method of<strong>installation</strong> E, with three loaded conductors, a cross section with current carryingcapacity of I 0≥ I’ b= 212.85 A, is obtained. A 95 mm 2 cross section cable cancarry, under St<strong>and</strong>ard reference conditions, 238 A.The current carrying capacity, according to the actual conditions of <strong>installation</strong>,is I z= 238 . 0.87. 0.54 = 111.81 A<strong>ABB</strong> | <strong>Electrical</strong> devices 305


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesExample of dimensioning a cable in a balanced threephasecircuit with a significant third-harmonic contentDimensioning of a cable with the following characteristics:• conductor material: : copper• insulation material: : PVC• type of cable: : multi-core• <strong>installation</strong>: : layer on horizontal perforated tray• load current: : 115 AInstallation conditions:• ambient temperature: : 30 °C• no adjacent circuits.Procedure:Type of <strong>installation</strong>On Table 3, it is possible to find the reference number of the <strong>installation</strong> <strong>and</strong>the method of <strong>installation</strong> to be used for the calculations. In this example, thereference number is 31, which corresponds to method E (multi-core cable ontray).Temperature correction factor k 1From Table 4, for a temperature of 30 °C <strong>and</strong> PVC insulation materialCorrection factor for adjacent cables k 2As there are no adjacent cables, soAfter k 1<strong>and</strong> k 2have been determined, I’ bis calculated by:306 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesIf no harmonics are present, from Table 8, for a multi-core copper cable withPVC insulation, method of <strong>installation</strong> E, with three loaded conductors, a crosssection with current carrying capacity of I 0≥ I’ b= 115 A, is obtained. A 35 mm 2cross section cable can carry, under St<strong>and</strong>ard reference conditions, 126 A.The current carrying capacity, according to the actual conditions of <strong>installation</strong>,is still 126 A, since the value of factors k 1<strong>and</strong> k 2is 1.The third harmonic content is assumed to be 28%.Table 16 shows that for a third harmonic content of 28% the cable must bedimensioned for the current that flows through the phase conductors, but areduction factor of 0.86 must be applied. The current I’ bbecomes:From Table 8, a 50 mm 2 cable with carrying capacity of 153 A shall be selected.If the third harmonic content is 40 %, Table 17 shows that the cable shall bedimensioned according to the current of the neutral conductor <strong>and</strong> a reductionfactor of 0.86 must be applied.The current in the neutral conductor is:<strong>and</strong> the value of current I’ bis:From Table 8, a 70 mm 2 cable with 196 A current carrying capacity shall beselected.If the third harmonic content is 60 %, Table 16 shows that the cable shall bedimensioned according to the current of the neutral conductor, but a reductionfactor of 1 must be applied.The current in the neutral conductor is:<strong>and</strong> current I’ bis:From Table 8, a 95 mm 2 cable with current carrying capacity of 238 A mustbe selected.<strong>ABB</strong> | <strong>Electrical</strong> devices 307


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cables1.2.2 Voltage dropIn an electrical <strong>installation</strong> it is important to evaluate voltage drops from thepoint of supply to the load.The performance of a device may be impaired if supplied with a voltage differentfrom its rated voltage. For example:• motors: the torque is proportional to the square of the supply voltage; therefore,if the voltage drops, the starting torque shall also decrease, making itmore difficult to start up motors; the maximum torque shall also decrease;• inc<strong>and</strong>escent lamps: the more the voltage drops the weaker the beam becomes<strong>and</strong> the light takes on a reddish tone;• discharge lamps: in general, they are not very sensitive to small variations involtage, but in certain cases, great variation may cause them to switch off;• electronic appliances: they are very sensitive to variations in voltage <strong>and</strong> thatis why they are fitted with stabilizers;• electromechanical devices: the reference St<strong>and</strong>ard states that devices suchas contactors <strong>and</strong> auxiliary releases have a minimum voltage below whichtheir performances cannot be guaranteed. For a contactor, for example, theholding of the contacts becomes unreliable below 85% of the rated voltage.To limit these problems the St<strong>and</strong>ards set the following limits:• IEC 60364-5-52 “<strong>Electrical</strong> <strong>installation</strong>s of buildings. Selection <strong>and</strong> erection ofelectrical equipment - Wiring systems” Annex G states that the voltage dropbetween the origin of an <strong>installation</strong> <strong>and</strong> any load point should not be greaterthan the values in Table 18 expressed with respect to the value of the nominalvoltage of the <strong>installation</strong>.Type of <strong>installation</strong>A – Low voltage <strong>installation</strong>s supplied directly from a public lowvoltage distribution systemB – Low voltage <strong>installation</strong> supplied from private LV supply aLighting%Other uses%3 5a As far as possible, it is recommended that voltage drop within the final circuits do not exceed those indicated in<strong>installation</strong> type A.Table 18: Voltage dropWhen the main wiring systems of the <strong>installation</strong>s are longer than 100 m, these voltage drops may be increasedby 0,005 % per metre of wiring system beyond 100 m, without this supplement being greater than 0,5 %.Voltage drop is determined from the dem<strong>and</strong> by the current-using equipment, applying diversity factors whereapplicable, or from the values of the design current of the circuits.NOTE 1 A greater voltage drop may be accepted– for motor during starting periods,– for other equipment with high inrush current,provided that in both cases it is ensured that the voltage variations remains within the limits specified inthe relevant equipment st<strong>and</strong>ard.68NOTE 2The following temporary conditions are excluded:– voltage transients;– voltage variation due to abnormal operation.308 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cables• IEC 60204-1”Safety of machinery – <strong>Electrical</strong> equipment of machines – Generalrequirements” Clause 13.5 recommends that: “the voltage drop from the pointof supply to the load shall not exceed 5% of the rated voltage under normaloperating conditions”.• IEC 60364-7-714 “<strong>Electrical</strong> <strong>installation</strong>s of buildings - Requirements forspecial <strong>installation</strong>s or locations - External lighting <strong>installation</strong>s” Clause 714.512requires that “the voltage drop in normal service shall be compatible with theconditions arising from the starting current of the lamps”.Voltage drop calculationFor an electrical conductor with impedance Z, the voltage drop is calculatedby the following formula:where• k is a coefficient equal to:- 2 for single-phase <strong>and</strong> two-phase systems;- for three-phase systems;• I b[A] is the load current; if no information are available, the cable carryingcapacity I zshall be considered;• L [km] is the length of the conductor;• n is the number of conductors in parallel per phase;• r [Ω/km] is the resistance of the single cable per kilometre;• x [Ω/km] is the reactance of the single cable per kilometre;• cosϕ is the power factor of the load:Normally, the percentage value in relation to the rated value U ris calculatedby:Resistance <strong>and</strong> reactance values per unit of length are set out on the followingtable by cross-sectional area <strong>and</strong> cable formation, for 50 Hz; in case of 60 Hz,the reactance value shall be multiplied by 1.2.<strong>ABB</strong> | <strong>Electrical</strong> devices 309


1.2 Installation <strong>and</strong> dimensioning of cables1 <strong>Protection</strong> of feedersTable 1: Resistance <strong>and</strong> reactance per unit of length of copper cablessingle-core cabletwo-core/three-core cableS r[Ω/km] x[Ω/km] r[Ω/km] x[Ω/km][mm 2 ] @ 80 [°C] @ 80 [°C]1.5 14.8 0.168 15.1 0.1182.5 8.91 0.156 9.08 0.1094 5.57 0.143 5.68 0.1016 3.71 0.135 3.78 0.095510 2.24 0.119 2.27 0.086116 1.41 0.112 1.43 0.081725 0.889 0.106 0.907 0.081335 0.641 0.101 0.654 0.078350 0.473 0.101 0.483 0.077970 0.328 0.0965 0.334 0.075195 0.236 0.0975 0.241 0.0762120 0.188 0.0939 0.191 0.074150 0.153 0.0928 0.157 0.0745185 0.123 0.0908 0.125 0.0742240 0.0943 0.0902 0.0966 0.0752300 0.0761 0.0895 0.078 0.075Table 2: Resistance <strong>and</strong> reactance per unit of length of aluminiumcablessingle-core cabletwo-core/three-core cableS r[Ω/km] x[Ω/km] r[Ω/km] x[Ω/km][mm 2 ] @ 80 [°C] @ 80 [°C]1.5 24.384 0.168 24.878 0.1182.5 14.680 0.156 14.960 0.1094 9.177 0.143 9.358 0.1016 6.112 0.135 6.228 0.095510 3.691 0.119 3.740 0.086116 2.323 0.112 2.356 0.081725 1.465 0.106 1.494 0.081335 1.056 0.101 1.077 0.078350 0.779 0.101 0.796 0.077970 0.540 0.0965 0.550 0.075195 0.389 0.0975 0.397 0.0762120 0,310 0.0939 0.315 0.074150 0.252 0.0928 0.259 0.0745185 0.203 0.0908 0.206 0.0742240 0.155 0.0902 0.159 0.0752300 0.125 0.0895 0.129 0.075310 <strong>Electrical</strong> devices | <strong>ABB</strong>


1.2 Installation <strong>and</strong> dimensioning of cables1 <strong>Protection</strong> of feedersThe following tables show the ∆U x[V/(A.km)] values by cross section <strong>and</strong> formationof the cable according to the most common cosϕ values.Table 3: Specific voltage drop at cosϕ = 1 for copper cablescosϕ = 1single-core cable two-core cable three-core cableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 29.60 25.63 30.20 26.152.5 17.82 15.43 18.16 15.734 11.14 9.65 11.36 9.846 7.42 6.43 7.56 6.5510 4.48 3.88 4.54 3.9316 2.82 2.44 2.86 2.4825 1.78 1.54 1.81 1.5735 1.28 1.11 1.31 1.1350 0.95 0.82 0.97 0.8470 0.66 0.57 0.67 0.5895 0.47 0.41 0.48 0.42120 0.38 0.33 0.38 0.33150 0.31 0.27 0.31 0.27185 0.25 0.21 0.25 0.22240 0.19 0.16 0.19 0.17300 0.15 0.13 0.16 0.14Table 4: Specific voltage drop at cosϕ = 0.9 for copper cablescosϕ = 9single-core cable two-core cable three-core cableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 26.79 23.20 27.28 23.632.5 16.17 14.01 16.44 14.244 10.15 8.79 10.31 8.936 6.80 5.89 6.89 5.9610 4.14 3.58 4.16 3.6016 2.64 2.28 2.65 2.2925 1.69 1.47 1.70 1.4835 1.24 1.08 1.25 1.0850 0.94 0.81 0.94 0.8170 0.67 0.58 0.67 0.5895 0.51 0.44 0.50 0.43120 0.42 0.36 0.41 0.35150 0.36 0.31 0.35 0.30185 0.30 0.26 0.29 0.25240 0.25 0.22 0.24 0.21300 0.22 0.19 0.21 0.18<strong>ABB</strong> | <strong>Electrical</strong> devices 311


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 5: Specific voltage drop at cosϕ = 0.85 for copper cablescosϕ = 0.85single-core cabletwo-core cable three-core cableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 25.34 21.94 25.79 22.342.5 15.31 13.26 15.55 13.474 9.62 8.33 9.76 8.456 6.45 5.59 6.53 5.6510 3.93 3.41 3.95 3.4216 2.51 2.18 2.52 2.1825 1.62 1.41 1.63 1.4135 1.20 1.04 1.19 1.0350 0.91 0.79 0.90 0.7870 0.66 0.57 0.65 0.5695 0.50 0.44 0.49 0.42120 0.42 0.36 0.40 0.35150 0.36 0.31 0.35 0.30185 0.30 0.26 0.29 0.25240 0.26 0.22 0.24 0.21300 0.22 0.19 0.21 0.18Table 6: Specific voltage drop at cosϕ = 0.8 for copper cablescosϕ = 0.8single-core cable two-core cable three-core cableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 23.88 20.68 24.30 21.052.5 14.44 12.51 14.66 12.694 9.08 7.87 9.21 7.986 6.10 5.28 6.16 5.3410 3.73 3.23 3.74 3.2316 2.39 2.07 2.39 2.0725 1.55 1.34 1.55 1.3435 1.15 0.99 1.14 0.9950 0.88 0.76 0.87 0.7570 0.64 0.55 0.62 0.5495 0.49 0.43 0.48 0.41120 0.41 0.36 0.39 0.34150 0.36 0.31 0.34 0.29185 0.31 0.26 0.29 0.25240 0.26 0.22 0.24 0.21300 0.23 0.20 0.21 0.19312 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 7: Specific voltage drop at cosϕ=0.75 for copper cablescosϕ = 0.75single-core cable two-core cable three-core cableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 22.42 19.42 22.81 19.752.5 13.57 11.75 13.76 11.924 8.54 7.40 8.65 7.496 5.74 4.97 5.80 5.0210 3.52 3.05 3.52 3.0516 2.26 1.96 2.25 1.9525 1.47 1.28 1.47 1.2735 1.10 0.95 1.08 0.9450 0.84 0.73 0.83 0.7270 0.62 0.54 0.60 0.5295 0.48 0.42 0.46 0.40120 0.41 0.35 0.38 0.33150 0.35 0.31 0.33 0.29185 0.30 0.26 0.29 0.25240 0.26 0.23 0.24 0.21300 0.23 0.20 0.22 0.19Table 8: Specific voltage drop at cosϕ = 1 for aluminium cablescosϕ = 1single-core cable two-core cable three-corecableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 48.77 42.23 49.76 43.092.5 29.36 25.43 29.92 25.914 18.35 15.89 18.72 16.216 12.22 10.59 12.46 10.7910 7.38 6.39 7.48 6.4816 4.65 4.02 4.71 4.0825 2.93 2.54 2.99 2.5935 2.11 1.83 2.15 1.8750 1.56 1.35 1.59 1.3870 1.08 0.94 1.10 0.9595 0.78 0.67 0.79 0.69120 0.62 0.54 0.63 0.55150 0.50 0.44 0.52 0.45185 0.41 0.35 0.41 0.36240 0.31 0.27 0.32 0.28300 0.25 0.22 0.26 0.22<strong>ABB</strong> | <strong>Electrical</strong> devices 313


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 9: Specific voltage drop at cosϕ = 0.9 for aluminium cablescosϕ = 0.9single-core cable two-core cable three-core cableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 44.04 38.14 44.88 38.872.5 26.56 23.00 27.02 23.404 16.64 14.41 16.93 14.666 11.12 9.63 11.29 9.7810 6.75 5.84 6.81 5.8916 4.28 3.71 4.31 3.7325 2.73 2.36 2.76 2.3935 1.99 1.72 2.01 1.7450 1.49 1.29 1.50 1.3070 1.06 0.92 1.06 0.9195 0.78 0.68 0.78 0.68120 0.64 0.55 0.63 0.55150 0.53 0.46 0.53 0.46185 0.44 0.38 0.44 0.38240 0.36 0.31 0.35 0.30300 0.30 0.26 0.30 0.26Table 10: Specific voltage drop at cosϕ = 0.85 for aluminium cablescosϕ = 0.85single-core cable two-core cable three-core cableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 41.63 36.05 42.42 36.732.5 25.12 21.75 25.55 22.124 15.75 13.64 16.02 13.876 10.53 9.12 10.69 9.2610 6.40 5.54 6.45 5.5816 4.07 3.52 4.09 3.5425 2.60 2.25 2.63 2.2735 1.90 1.65 1.91 1.6650 1.43 1.24 1.43 1.2470 1.02 0.88 1.01 0.8895 0.76 0.66 0.76 0.65120 0.63 0.54 0.61 0.53150 0.53 0.46 0.52 0.45185 0.44 0.38 0,43 0.37240 0.36 0.31 0.35 0.30300 0.31 0.27 0.30 0.26314 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesTable 11: Specific voltage drop at cosϕ = 0.8 for aluminium cablescosϕ = 0.8single-core cable two-core cable three-core cableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 39.22 33.96 39.95 34.592.5 23.67 20.50 24.07 20.844 14.85 12.86 15.09 13.076 9.94 8.61 10.08 8.7310 6.05 5.24 6.09 5.2716 3.85 3.34 3.87 3.3525 2.47 2.14 2.49 2.1635 1.81 1.57 1.82 1.5750 1.37 1.18 1.37 1.1870 0.98 0.85 0.97 0.8495 0.74 0.64 0.73 0.63120 0.61 0.53 0.59 0.51150 0.51 0.45 0.50 0.44185 0.43 0.38 0.42 0.36240 0.36 0.31 0.34 0.30300 0.31 0.27 0.30 0.26Table 12: Specific voltage drop at cosϕ = 0.75 for aluminium cablescosϕ = 0.75single-core cable two-core cable three-core cableS[mm 2 ] single-phase three-phase single-phase three-phase1.5 36.80 31.87 37.47 32.452.5 22.23 19.25 22.58 19.564 13.95 12.08 14.17 12.276 9.35 8.09 9.47 8.2010 5.69 4.93 5.72 4.9616 3.63 3.15 3.64 3.1525 2.34 2.02 2.35 2.0335 1.72 1.49 1.72 1.4950 1.30 1.13 1.30 1.1270 0.94 0.81 0.92 0.8095 0.71 0.62 0.70 0.60120 0.59 0.51 0.57 0.49150 0.50 0.43 0.49 0.42185 0.42 0.37 0.41 0.35240 0.35 0.31 0.34 0.29300 0.31 0.27 0.29 0.25<strong>ABB</strong> | <strong>Electrical</strong> devices 315


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesExample 1To calculate a voltage drop on a three-phase cable with the followingspecifications:• rated voltage: 400 V;• cable length: 25 m;• cable formation: single-core copper cable, 3x50 mm 2 ;• load current I b: 100 A;• power factor cosϕ: 0.9.From Table 4, for a 50 mm 2 single-core cable it is possible to read that a ∆U xvoltage drop corresponds to 0.81 V/(A⋅km). By multiplying this value by thelength in km <strong>and</strong> by the current in A, it results:which corresponds to this percentage value:Example 2To calculate a voltage drop on a three-phase cable with the followingspecifications:• rated voltage: 690 V;• cable length: 50 m;• cable formation: multi-core copper cable, 2x(3x10) mm 2 ;• load current I b: 50 A;• power factor cosϕ: 0.85.From Table 5, for a multi-core 10 mm 2 cable it is possible to read that ∆U xvoltage drop corresponds to 3.42 V/(A⋅km). By multiplying this value by thelength in km <strong>and</strong> by the current in A, <strong>and</strong> by dividing it by the number of cablesin parallel, it results:which corresponds to this percentage value:316 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesMethod for defining the cross section of the conductor according tovoltage drop in the case of long cablesIn the case of long cables, or if particular design specifications impose lowlimits for maximum voltage drops, the verification using as reference the crosssection calculated on the basis of thermal considerations (calculation accordingto chapter 1.2.1 “Current carrying capacity <strong>and</strong> methods of <strong>installation</strong>”) mayhave a negative result.To define the correct cross section, the maximum ∆U xmaxvalue calculated byusing the formula:is compared with the corresponding values on Tables 4÷12 by choosing thesmallest cross section with a ∆U xvalue lower than ∆U xmax.Example:Supply of a three-phase load with P u= 35 kW (U r=400 V, f r= 50 Hz, cosϕ=0.9)with a 140 m cable installed on a perforated tray, consisting of a multi-corecopper cable with EPR insulation.Maximum permitted voltage drop 2%.Load current I bis:The Table 8 of Chapter 1.2.1 shows S = 10 mm 2 .From Table 4, for the multi-core 10 mm 2 cable it is possible to read that thevoltage drop per A <strong>and</strong> per km is 3.60 V/(A⋅km). By multiplying this value bythe length in km <strong>and</strong> by the current in A, it results:which corresponds to this percentage value:This value is too high.Formula (3) shows:<strong>ABB</strong> | <strong>Electrical</strong> devices 317


1 <strong>Protection</strong> of feeders1.2 Installation <strong>and</strong> dimensioning of cablesFrom Table 4 a cross section of 50 mm 2 can be chosen.For this cross section ∆U x= 0.81< 1.02 V/(A⋅km).By using this value it results:This corresponds to a percentage value of:1.2.3 Joule-effect lossesJoule-effect losses are due to the electrical resistance of the cable.The lost energy is dissipated in heat <strong>and</strong> contributes to the heating of theconductor <strong>and</strong> of the environment.A first estimate of three-phase losses is:whereas single-phase losses are:where:• I bis the load current [A];• r is the phase resistance per unit of length of the cable at 80 °C [Ω/km] (seeTable 1);• L is the cable length [m].Table 1: Resistance values [Ω/km] of single-core <strong>and</strong> multi-corecables in copper <strong>and</strong> aluminium at 80 °CSingle-core cableTwo-core/three-core cableS[mm 2 ] Cu AI Cu AI1.5 14.8 24.384 15.1 24.8782.5 8.91 14.680 9.08 14.9604 5.57 9.177 5.68 9.3586 3.71 6.112 3.78 6.22810 2.24 3.691 2.27 3.74016 1.41 2.323 1.43 2.35625 0.889 1.465 0.907 1.49435 0.641 1.056 0.654 1.07750 0.473 0.779 0.483 0.79670 0.328 0.540 0.334 0.55095 0.236 0.389 0.241 0.397120 0.188 0.310 0.191 0.315150 0.153 0.252 0.157 0.259185 0.123 0.203 0.125 0.206240 0.0943 0.155 0.0966 0.159300 0.0761 0.125 0.078 0.129318 <strong>Electrical</strong> devices | <strong>ABB</strong>


1.3 <strong>Protection</strong> against overload1 <strong>Protection</strong> of feedersThe St<strong>and</strong>ard IEC 60364-4-43 “<strong>Electrical</strong> <strong>installation</strong> of buildings - <strong>Protection</strong>against overcurrent” specifies coordination between conductors <strong>and</strong> overloadprotective devices (normally placed at the beginning of the conductor to beprotected) so that it shall satisfy the two following conditions:Where:• I bis the current for which the circuit is dimensioned;• I zis the continuous current carrying capacity of the cable;• I nis the rated current of the protective device; for adjustable protective releases,the rated current I nis the set current;• I 2is the current ensuring effective operation in the conventional time of theprotective device.IbInIzI21.45Iz1SDC010009F0001According to condition (1) to correctly choose the protective device, it isnecessary to check that the circuit-breaker has a rated (or set) current that is:• higher than the load current, to prevent unwanted tripping;• lower than the current carrying capacity of the cable, to prevent cable overload.The St<strong>and</strong>ard allows an overload current that may be up to 45% greater thanthe current carrying capacity of the cable but only for a limited period.The verification of condition (2) is not necessary in the case of circuit-breakersbecause the protective device is automatically tripped if:• I 2= 1.3⋅I nfor circuit-breakers complying with IEC 60947-2 (circuit-breakersfor industrial use);• I 2= 1.45⋅I nfor circuit-breakers complying with IEC 60898 (circuit-breakers forhousehold <strong>and</strong> similar <strong>installation</strong>s).Therefore, for circuit-breakers, if I n≤ I z, the formula I 2≤ 1.45⋅I zwill also beverified.When the protective device is a fuse, it is also essential to check formula (2)because IEC 60269-2-1 on “Low-voltage fuses” states that a 1.6⋅I ncurrentmust automatically melt the fuse. In this case, formula (2) becomes1.6⋅I n≤ 1.45⋅I zor I n≤ 0.9⋅I z.<strong>ABB</strong> | <strong>Electrical</strong> devices 319


1 <strong>Protection</strong> of feeders1.3 <strong>Protection</strong> against overloadTo summarize: to carry out by a fuse protection against overload, the followingmust be achieved:≤≤<strong>and</strong> this means that the cable is not fully exploited.I bI nI z1SDC010010F0001Circuit-breaker: choice of rated currentI bI n0.9 I z1SDC010011F0001Fuse: choice of rated currentWhere the use of a single conductor per phase is not feasible, <strong>and</strong> the currentsin the parallel conductors are unequal, the design current <strong>and</strong> requirements foroverload protection for each conductor shall be considered individually.ExamplesExample 1Load specificationsP r= 120 kW; U r= 400 V; cosϕ = 0.9; three-phase load so I b= 192.6 ACable specificationsI z= 239 AProtective device specificationsXT3N 250 TMD I n200; set current I1 = 1 x I n= 200 A320 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.3 <strong>Protection</strong> against overloadExample 2Load specificationsP r= 70 kW; cosϕ = 0.9; U r= 400 V; three-phase load so I b= 112 ACable specificationsI z= 134 AProtective device specificationsXT2N 160 Ekip LSI I n160; set current I1 = 0.8 x I n= 128 AExample 3Load specificationsP r= 100 kW; cosϕ = 0.9; U r= 400 V ; three-phase load so I b= 160 ACable specificationsI z= 190 AProtective device specificationsXT3N 250 TMD I n200; set current I1 = 0.9 x I n= 180 AExample 4Load specificationsP r= 50 kW; cosϕ = 0.9; U r= 230 V ; single-phase load so I b= 241 ACable specificationsI z= 262 AProtective device specificationsXT4N 250 Ekip LSIG I n250; set current I1 = 0.98 x I n= 245 A<strong>ABB</strong> | <strong>Electrical</strong> devices 321


1.4 <strong>Protection</strong> against short-circuit1 <strong>Protection</strong> of feedersA cable is protected against short-circuit if the specific let-through energy ofthe protective device (I 2 t) is lower or equal to the withstood energy of the cable(k 2 S 2 ):where• I 2 t is the specific let-through energy of the protective device whichcan be read on the curves supplied by the manufacturer (see Part 1,Chapter 2.4 “Specific let-through energy curves”) or from a directcalculation in the case of devices that are not limiting <strong>and</strong> delaying;• S is the cable cross section [mm 2 ]; in the case of conductors in parallel it isthe cross section of the single conductor;• k is a factor that depends on the cable insulating <strong>and</strong> conducting material.The values of the most common <strong>installation</strong>s are shown in Table 1; for a moredetailed calculation, see Annex C.Table 1: Values of k for phase conductorConductor insulationInitial temperature °CPVC≤300 mm 270PVC EPR>300 mm 2 XLPE7090Rubber60 °C60PVC70MineralBare105Final temperature °C160140250200160250Material of conductor:Copper115103143141115135/115 aAluminiumtin-soldered jointsin copper conductors7611568-94-93-----aThis value shall be used for bare cables exposed to touch.NOTE 1 Other values of k are under consideration for.- small conductors (particularly for cross section less than 10 mm 2 );- duration of short-circuit exceeding 5 s;- other types of joints in conductors;- bare conductors.NOTE 2 The nominal current of the short-circuit protective device may be greater than the current carryingcapacity of the cable.NOTE 3 The above factors are based on IEC 60724.1SDC010010F0201322 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.4 <strong>Protection</strong> against short-circuitTable 2 shows the maximum withstood energy for cables according to the crosssection, the conductor material <strong>and</strong> the type of insulation, which are calculatedby using the parameters of Table 1.Table 2: Maximum withstood energy for cables k 2 S 2 [(kA) 2 s]CablePVCEPR/XLPERubberCross section [mm 2 ]k 1.5 2.5 4 6 10 16 25 35Cu 115 2.98·10 -2 8.27·10 -2 2.12·10 -1 4.76·10 -1 1.32 3.39 8.27 1.62·10 1Al 76 1.30·10 -2 3.61·10 -2 9.24·10 -2 2.08·10 -1 5.78·10 -1 1.48 3.61 7.08Cu 143 4.60·10 -2 1.28·10 -1 3.27·10 -1 7.36·10 -1 2.04 5.23 1.28·10 1 2.51·10 1Al 94 1.99·10 -2 5.52·10 -2 1.41·10 -1 3.18·10 -1 8.84·10 -1 2.26 5.52 1.08·10 1Cu 141 4.47·10 -2 1.24·10 -1 3.18·10 -1 7.16·10 -1 1.99 5.09 1.24·10 1 2.44·10 1Al 93 1.95·10 -2 5.41·10 -2 1.38·10 -1 3.11·10 -1 8.65·10 -1 2.21 5.41 1.06·10 1CablePVCEPR/XLPEG2Cross section [mm 2 ]k 50 70 95 120 150 185 240 300Cu 115 3.31·10 1 6.48·10 1 1.19·10 2 1.90·10 2 2.98·10 2 4.53·10 2 7.62·10 2 1.19·10 3Al 76 1.44·10 1 2.83·10 1 5.21·10 1 8.32·10 1 1.30·10 2 1.98·10 2 3.33·10 2 5.20·10 2Cu 143 5.11·10 1 1.00·10 1 1.85·10 1 2.94·10 2 4.60·10 2 7.00·10 2 1.18·10 3 1.84·10 3Al 94 2.21·10 1 4.33·10 1 7.97·10 1 1.27·10 2 1.99·10 2 3.02·10 2 5.09·10 2 7.95·10 2Cu 141 4.97·10 1 9.74·10 1 1.79·10 1 2.86·10 2 4.47·10 2 6.80·10 2 1.15·10 3 1.79·10 3Al 93 2.16·10 1 4.24·10 1 7.81·10 1 1.25·10 2 1.95·10 2 2.96·10 2 4.98·10 2 7.78·10 21SDC010002F0901The formula (1) must be verified along the whole length of the cable. Due to theshape of the specific let-through energy curve of a circuit breaker, it is generallysufficient to verify formula (1) only for the maximum <strong>and</strong> minimum short-circuitcurrent that may affect the cable. The maximum value is normally the valueof the three-phase short-circuit current at the beginning of the line, while theminimum value is the value of the phase to neutral short-circuit current (phaseto phase if the neutral conductor is not distributed) or phase to earth at theend of the cable.<strong>ABB</strong> | <strong>Electrical</strong> devices 323


1 <strong>Protection</strong> of feeders1.4 <strong>Protection</strong> against short-circuit[(KA) 2 s] 10 210110 -110 -2 110 -3 [KA]1SDC010011F000110 -110This verification can be simplified by comparing only the let-through energy valueof the circuit-breaker at the maximum short-circuit current with the withstoodenergy of the cable <strong>and</strong> by ensuring that the circuit breaker trips instantaneouslyat the minimum short-circuit current: the threshold of the short-circuit protection(taking into consideration also the tolerances) shall therefore be lower than theminimum short-circuit current at the end of the conductor.324 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.4 <strong>Protection</strong> against short-circuitTypeT5T5Circuit-breakerIcu(kA)N=36S=50H=70L=120V=200Ratedcurrent(A)Phase conductorPVC insulatedPhaseconductor(mm 2 )Max energy(I 2 t)320-630 16 3385600320-630 25 8265625Phase conductorEPR insulatedPhaseconductor(mm 2 )Max energy(I 2 t)16 5234944Circuit-breakerPhase conductorPVC insulatedPhase conductorEPR insulatedTypeT6Icu(kA)N=36S=50H=70L=100Ratedcurrent(A)Phaseconductor(mm 2 )Max energy(I 2 t)630* 35 16200625800**1000**50 33062500conduttoredi fase(mm 2 )Max energy(I 2 t)35 25050025* with circuit-breakers type T6N (Icu=36kA) it is possible to use a 25mm 2 cable, EPRinsulated** with circuit-breakers type T6N (Icu=36kA) it is possible to use a 35mm 2 cable, PVCinsulatedTypeT7Circuit-breakerIcu(kA)S=50H=70V=150Ratedcurrent(A)Phase conductorPVC insulatedPhaseconductor(mm 2 )Max energy(I 2 t)Phase conductorEPR insulatedPhaseconductor(mm 2 )Max energy(I 2 t)400-1250 50 33062500 50* 51122500T7 L=120 400-1600 70 64802500 50 51122500* with circuit-breakers type T7S (Icu=50kA) it is possible to use a 35mm 2 cable, EPRinsulated<strong>ABB</strong> | <strong>Electrical</strong> devices 325


1 <strong>Protection</strong> of feeders1.4 <strong>Protection</strong> against short-circuitCalculation of short-circuit current at end of the conductorMinimum short-circuit current can be calculated by the following approximateformulas:with non-distributed neutral conductor (2.1)with distributed neutral conductor (2.2)where:• I kminis the minimum value of the prospective short-circuit current [kA];• U ris the supply voltage [V];• U 0is the phase to earth supply voltage [V];• ρ is the resistivity at 20 °C of the material of the conductors in Ωmm 2 /m <strong>and</strong>is:- 0.018 for copper;- 0.027 for aluminium;• L is the length of the protected conductor [m];• S is the cross section of the conductor [mm 2 ];• k secis the correction factor which takes into account the reactance of thecables with cross section larger than 95 mm 2 :S[mm 2 ] 120 150 185 240 300k sec0.9 0.85 0.80 0.75 0.72• k paris the correcting coefficient for conductors in parallel:number of parallelconductors 2 3 4 5k par* 2 2.7 3 3.2*k par= 4 (n-1)/n where: n = number of conductors in parallel per phase• m is the ratio between the resistances of the neutral conductor <strong>and</strong> the phaseconductor (if they are made of the same material m is the ratio between thecross section of the phase conductor <strong>and</strong> the cross section of the neutralconductor).After calculating the minimum short-circuit current, verify thatwhere:• I 3is the current that trips the magnetic protection of the circuit-breaker;• 1.2 is the tolerance at the trip threshold.326 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.4 <strong>Protection</strong> against short-circuitExampleChoice of CB1System data:Rated voltage 415 VI k= 30 kACable data:Insulated copper conductor in PVCLength = 150 mS = 50 mm 2I z= 134 AULU r = 415 VCB1XT1N160 In160PVC CuI k = 30 kACable Section 50 mm 2Iz = 134.0 AL = 150 m<strong>Protection</strong> against short-circuit at the beginning of the conductorXT1N 160 In160 (breaking capacity 36 kA@415 V)I 2 t (@30 kA) = 7.5 10 -1 (kA) 2 sk 2 S 2 = 115 2 ⋅ 50 2 = 3.31 . 10 1 (kA) 2 sThe cable is therefore protected against short-circuit at the beginning of theconductor.<strong>Protection</strong> against short-circuit at end of the conductorThe minimum short-circuit current at end of the conductor (k sec=1 <strong>and</strong> k par=1) is:1SDC010011F0201The magnetic threshold of the circuit breaker XT1N 160 In160 is set at 1600 A.If tolerance is 20%, the circuit breaker shall definitely trip if the values exceed1920 A; the cable is therefore fully protected against short-circuit.Maximum protected lengthThe formula (3), when solved for the length, enables the maximum length protectedby the protective device to be obtained for a precise instantaneous tripthreshold. In Table 3, the maximum protected length can be identified for a givencross section of the cable <strong>and</strong> for the setting threshold of the instantaneousprotection of the circuit breaker against short-circuit:- three-phase system, 400 V rated voltage;- non-distributed neutral;- copper conductor with resistivity equal to 0.018 Ωmm 2 /m.The values on the table below take into account the 20% tolerance coefficientfor the magnetic trip value, the increase in cable resistivity due to heating causedby the short-circuit current <strong>and</strong> the reduction of voltage due to the fault.The correction factors shown after the table must be applied if the systemconditions are different from the reference conditions.<strong>ABB</strong> | <strong>Electrical</strong> devices 327


1 <strong>Protection</strong> of feeders1.4 <strong>Protection</strong> against short-circuitTable 3: Maximum protected lengthsection [mm 2 ]I 3[A] 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 30020 370 61730 246 412 65840 185 309 494 74150 148 247 395 59360 123 206 329 49470 105 176 282 423 70580 92 154 246 370 61790 82 137 219 329 549100 74 123 197 296 494 790120 61 102 164 246 412 658140 52 88 141 211 353 564150 49 82 131 197 329 527160 46 77 123 185 309 494 772180 41 68 109 164 274 439 686200 37 61 98 148 247 395 617220 33 56 89 134 224 359 561 786250 29 49 79 118 198 316 494 691280 26 44 70 105 176 282 441 617300 24 41 65 98 165 263 412 576320 23 38 61 92 154 247 386 540 772350 21 35 56 84 141 226 353 494 705380 19 32 52 78 130 208 325 455 650400 18 30 49 74 123 198 309 432 617420 17 29 47 70 118 188 294 412 588450 16 27 43 65 110 176 274 384 549 768480 15 25 41 61 103 165 257 360 514 720500 14 24 39 59 99 158 247 346 494 691520 14 23 38 57 95 152 237 332 475 665550 13 22 35 53. 90 144 224 314 449 629580 12 21 34 51 85 136 213 298 426 596 809600 12 20 32 49 82 132 206 288 412 576 782620 11 19 31 47 80 127 199 279 398 558 757650 11 19 30 45 76 122 190 266 380 532 722680 10 18 29 43 73 116 182 254 363 508 690700 10 17 28 42 71 113 176 247 353 494 670 847750 16 26 39 66 105 165 230 329 461 626 790 840800 15 24 37 62 99 154 216 309 432 586 667 787850 14 23 34 58 93 145 203 290 407 552 627 741900 13 21 32 55 88 137 192 274 384 521 593 700950 13 20 31 52 83 130 182 260 364 494 561 6631000 12 19 29 49 79 123 173 247 346 469 533 630 7311250 15 23 40 63 99 138 198 277 375 427 504 585 7111500 13 19 33 53 82 115 165 230 313 356 420 487 5931600 12 18 31 49 77 108 154 216 293 333 394 457 556 6672000 14 25 40 62 86 123 173 235 267 315 365 444 5332500 11 20 32 49 69 99 138 188 213 252 292 356 4273000 16 26 41 58 82 115 156 178 210 244 296 3563200 15 25 39 54 77 108 147 167 197 228 278 3334000 12 20 31 43 62 86 117 133 157 183 222 2675000 10 16 25 35 49 69 94 107 126 146 178 2136300 13 20 27 39 55 74 85 100 116 141 1698000 10 15 22 31 43 59 67 79 91 111 1339600 13 18 26 36 49 56 66 76 93 11110000 12 17 25 35 47 53 63 73 89 10712000 10 14 21 29 39 44 52 61 74 8915000 12 16 23 31 36 42 49 59 7120000 12 17 23 27 31 37 44 5324000 10 14 20 22 26 30 37 4430000 12 16 20 25 30 40 49328 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.4 <strong>Protection</strong> against short-circuitCorrection factor for voltage other than 400 V: k vMultiply the length value obtained from the table by the correction factor k v:U r[V]k v(three-phase value)230 (*) 0.58400 1440 1.1500 1.25690 1.73(*)230 V single-phase is the equivalent of a three-phase 400 V system with distributedneutral <strong>and</strong> with the cross section of the phase conductor the same as the cross sectionarea of the neutral conductor, so that k vis 0.58.Correction factor for distributed neutral: k dMultiply the length value obtained from the table by the correction factor k d:where• S is the phase cross section [mm 2 ];• S Nis the neutral cross section [mm 2 ].In particular:Correction factor for aluminium conductors: k rIf the cable is in aluminium, multiply the length value obtained from the tableabove by the correction factor k r= 0.67.<strong>ABB</strong> | <strong>Electrical</strong> devices 329


1 <strong>Protection</strong> of feeders1.4 <strong>Protection</strong> against short-circuitTo summarize:On the table, for the cross section <strong>and</strong> magnetic trip threshold it is possibleto read a maximum protected value L 0. This length shall then be multiplied, ifnecessary, by the correction factors in order to obtain a value that is compatiblewith the <strong>installation</strong> operating conditions:Example 1Neutral not distributedRated voltage = 400 VProtective device: XT2N 160 TMA In100Magnetic threshold: I 3= 1000 A (max setting)Phase cross section = Neutral cross section = 70 mm 2The table shows that at I 3= 1000 A, the 70 mm 2 cable is protected up to346 m.Example 2Neutral distributedRated voltage = 400 VProtective device: XT4N 250 TMA In200Magnetic threshold: I 3= 2000 A (max setting)Phase cross section = 300 mm 2Neutral cross section = 150 mm 2For I 3= 2000 A <strong>and</strong> S = 300 mm 2 , a protected length equivalent of L 0= 533m is obtained.By applying the correction factor k drequired when the neutral is distributed:L= L 0 . 0.39 = 533 . 0.39 = 207.9 mThis is the maximum protected length with neutral distributed.330 <strong>Electrical</strong> devices | <strong>ABB</strong>


1.5 Neutral <strong>and</strong> protective conductors1 <strong>Protection</strong> of feedersNeutral conductorThe neutral conductor is a conductor that is connected to the system neutralpoint (which generally but not necessarily coincides with the star centre of thesecondary windings of the transformer or the windings of the generator); it isable to contribute to the transmission of electric power, thereby making availablea voltage that is different from the phase to phase voltage. In certain cases <strong>and</strong>under specific conditions, the functions of neutral conductor <strong>and</strong> protectiveconductor can be combined in a single conductor (PEN).<strong>Protection</strong> <strong>and</strong> disconnection of the neutral conductorIf fault conditions arise, a voltage to earth may occur on the neutral conductor.This may be caused by a phase to neutral short-circuit <strong>and</strong> by the disconnectionof the neutral conductor due to accidental breaking or to tripping of single-poledevices (fuses or single-pole circuit breakers).If the neutral conductor only is disconnected in a four-conductor circuit, thesupply voltage to the single-phase loads may be altered so that they are suppliedby a voltage different from the U 0phase to neutral voltage (as shown in Fig. 1).Therefore, all the necessary measures to prevent this type of fault shall be taken,e.g. by not protecting the neutral conductor with single-pole devices.PPPNU1R1R2U 1=3 . U . 0R1RR+1 21SDC010013F0001Figure 1: Disconnection of the neutral conductorMoreover, in TN-C systems, voltage to earth arising on the neutral conductorconstitutes a hazard for people; in fact, since this conductor is also a protectiveconductor, this voltage reaches the connected exposed conductive parts. ForTN-C systems, the St<strong>and</strong>ards specify minimum cross sections (see next clause)for the neutral conductor in order to prevent accidental breaking <strong>and</strong> theyforbid the use of any device (single-pole or multi-pole) that could disconnectthe PEN.The need for protection on the neutral conductor <strong>and</strong> the possibility ofdisconnecting the circuit depend on the distribution system:<strong>ABB</strong> | <strong>Electrical</strong> devices 331


1 <strong>Protection</strong> of feeders1.5 Neutral <strong>and</strong> protective conductorsTT or TN systems:• if the cross section of the neutral conductor is the same or larger than thecross section of the phase conductor, there is neither the need to detectovercurrents on the neutral conductor nor to use a breaking device (neutralconductor is not protected or disconnected); this requirement applies only ifthere are no harmonics that may, at any instant, cause r.m.s. current valueson the neutral conductor higher than the maximum current detected on thephase conductors;• if the cross section of the neutral conductor is less than the cross section ofthe phase conductor, overcurrents on the neutral conductor must be detectedso as to have the phase conductors, but not necessarily the neutral conductor,disconnected (neutral conductor protected but not disconnected): in this casethe overcurrents on the neutral conductor do not need to be detected if thefollowing conditions are simultaneously fulfilled:1. the neutral conductor is protected against short-circuit by theprotective device of the phase conductors;2. the maximum current that can flow through the neutralconductor during normal service is lower than the neutralcurrent carrying capacity.In TN-S systems, the neutral need not be disconnected if the supply conditionsare such that the neutral conductor can be considered to be reliable at earthpotential.As already mentioned, in TN-C systems, the neutral conductor is also aprotective conductor <strong>and</strong> cannot therefore be disconnected. Furthermore, ifthe neutral conductor is disconnected, the exposed conductive parts of thesingle-phase equipment could take the system rated voltage to earth.In certain specific cases, the neutral conductor has to be disconnected toprevent currents circulating between parallel supply sources (see Figures 2<strong>and</strong> 3).Figure 2: Three-phase alternative power supply with a 4-pole switchPower supply 1Power supply 2NOTE - This methodprevents electromagneticfields due to stray currentsin the main supply systemof an <strong>installation</strong>. The sumof the currents within onecable must be zero. Thisensures that the neutralcurrent will flow only in theneutral conductor of therespective switched oncircuit. The 3rd harmonic(150 Hz) current of the lineconductors will be addedwith the same phase angleto the neutral conductorcurrent.L1L2L3PENPEL1L2L3Current using equipmentSupplierUser1SDC010012F0201332 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.5 Neutral <strong>and</strong> protective conductorsFigure 3: Three-phase alternative power supply with non-suitable3-pole switchL1L2L3PENPEL1L2L3NOTE – A three-phasealternative power supplywith a non-suitable3-pole switch, due tounintentional circularstray currents generatingelectromagnetic fields.1SDC010014F0001IT system:The St<strong>and</strong>ard advises against distributing the neutral conductor in IT systems.If the neutral conductor is distributed, the overcurrents must be detected on theneutral conductor of each circuit in order to disconnect all the live conductorson the corresponding circuit, including the neutral one (neutral conductorprotected <strong>and</strong> disconnected).Overcurrents do not need to be detected on the neutral conductor in any ofthe following cases:• the neutral conductor is protected against short-circuit by a protective devicefitted upstream;• the circuit is protected by a residual current device with rated residual currentlower than 0.15 times the current carrying capacity of the correspondingneutral conductor. This device must disconnect all the live conductors, theneutral conductor included.For all distribution systems, whenever necessary, connection <strong>and</strong> disconnectionof the neutral conductor, shall ensure that:• the neutral conductor is not disconnected before the phase conductor;• the neutral conductor is connected at the same moment or before the phaseconductor.<strong>ABB</strong> | <strong>Electrical</strong> devices 333


1 <strong>Protection</strong> of feeders1.5 Neutral <strong>and</strong> protective conductorsSTARTnoUpstream protectionfor the neutral?yesnoTT/TN System?yesS N≥ S?noyesnoIs the circuit protectedby a RCD withI∆n≤ 0.15 x Neutralcarrying capacity ?Is the neutral protected bythe short-circuit protectionof the phase conductor?noyesyesNeutral max current


1 <strong>Protection</strong> of feeders1.5 Neutral <strong>and</strong> protective conductorsDetermination of the minimum cross section of the neutral conductorThe neutral conductor, if any, shall have the same cross section as the lineconductor:• in single-phase, two-wire circuits whatever the section;• in polyphase <strong>and</strong> single-phase three-wire circuits, when the size of theline conductors is less than or equal to 16 mm 2 in copper, or 25 mm 2 inaluminium. 1The cross section of the neutral conductor can be less than the cross section ofthe phase conductor when the cross section of the phase conductor is greaterthan 16 mm 2 with a copper cable, or 25 mm 2 with an aluminium cable, if boththe following conditions are met:• the cross section of the neutral conductor is at least 16 mm 2 for copperconductors <strong>and</strong> 25 mm 2 for aluminium conductors;• there is no high harmonic distortion of the load current. If there is high harmonicdistortion (the harmonic content is greater than 10%), as for example inequipment with discharge lamps, the cross section of the neutral conductorcannot be less than the cross section of the phase conductors.Table 1: Minimum cross sections of the neutral conductorPhase cross section Min. neutral cross sectionS [mm 2 ] S N[mm 2 ]Single-phase/two-phase circuitsCu/Al Any S *Three-phase circuits S ≤ 16 S *Cu S > 16 16Three-phase circuits S ≤ 25 S *Al S > 25 25*for TN-C systems, the St<strong>and</strong>ards specify a minimum cross section of 10 mm 2 forcopper <strong>and</strong> 16 mm 2 for aluminium conductors1The cross section of phase conductors shall be dimensioned in compliance with theinstructions of the Chapter 1.2.1 “Current carrying capacity <strong>and</strong> methods of <strong>installation</strong>”<strong>ABB</strong> | <strong>Electrical</strong> devices 335


1 <strong>Protection</strong> of feeders1.5 Neutral <strong>and</strong> protective conductorsProtective conductorDetermination of the minimum cross sectionsThe minimum cross section of the protective conductor can be determined byusing the following table:Table 2: Cross section of the protective conductorCross section ofMinimum cross section of the correspondingline conductor Sprotective conductor2[mm ]2[mm ]If the protective conductor is of thesame material as the line conductorIf the protective conductor is not of the samematerial as the line conductorS ʺ 16Sk 1k2. S16 < S ʺ 35 16 *k 1 .16k2S > 35S * k S 1 .2k 2 2Wherek 1 is the value of k for the line conductor, selected from Table 1 Chapter 1.4 according to the materials ofthe conductor <strong>and</strong> insulation;k 2 is the value of k for the protective conductor.* For a PEN conductor, the reduction of the cross section is permitted only in accordance with the rules for sizing of the neutral conductor.1SDC010014F0201For a more accurate calculation <strong>and</strong> if the protective conductor is subjectedto adiabatic heating from an initial known temperature to a final specified temperature(applicable for fault extinction time no longer than 5s), the minimumcross section of the protective conductor S PEcan be obtained by using thefollowing formula:where:• S PEis the cross section of the protective conductor [mm 2 ];• I is the r.m.s. current flowing through the protective conductor in the event ofa fault with low impedance [A];• t is the trip time of the protective device [s];336 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.5 Neutral <strong>and</strong> protective conductors• k is a constant which depends on the material of the protective conductor, onthe type of insulation <strong>and</strong> on initial <strong>and</strong> final temperature. The most commonvalues can be taken from Tables 3 <strong>and</strong> 4.Table 3: Values of k for insulated protective conductors not incorporatedin cables <strong>and</strong> not bunched with other cablesConductor insulation70 °C PVC90 °C PVC90 °C thermosetting60 °C rubber85 °C rubberSilicon rubberTemperatureMaterial of conductor°C b Copper Aluminium SteelInitial Final Values for k30 160/140 a 143/133 a 95/88 a30 143/133 a 143/133 a 95/88 a30250176116302001591053022016811030350201133aThe lower value applies to PVC insulated conductors of cross section greater than 300 mm 2 .bTemperature limits for various types of insulation are given in IEC 60724.52/49 a52/49 a645860731SDC010015F0201Table 4: Values of k for protective conductors as a core incorporatedin a cable or bunched with other cables or insulated conductorsConductor insulation70 °C PVC90 °C PVC90 °C thermosetting60 °C rubber85 °C rubberSilicon rubberTemperatureMaterial of conductor°C b Copper Aluminium SteelInitial Final Values for k70 160/140 a 115/103 a 76/68 a90 160/140 a 100/86 a 66/57 a90250143946020014193852201348918035013287aThe lower value applies to PVC insulated conductors of cross section greater than 300 mm 2 .bTemperature limits for various types of insulation are given in IEC 60724.42/37 a36/31 a525148471SDC010015F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 337


1 <strong>Protection</strong> of feeders1.5 Neutral <strong>and</strong> protective conductorsFurther values of k can be taken from the Tables in Annex D, which providesthe formula for accurate calculation of the value of k.If Table 2 or formula (1) do not provide a st<strong>and</strong>ardized cross section, a largerst<strong>and</strong>ardized cross section shall be chosen.Regardless of whether Table 2 or formula (1) are used, the cross section of theprotective conductor, which is not part of the supply cable, shall be at least:- 2.5 mm 2 Cu/16 mm 2 Al, if a mechanical protection is provided;- 4 mm 2 Cu/16 mm 2 Al, if no mechanical protection is provided.For current using equipment intended for permanent connection <strong>and</strong> with aprotective conductor current exceeding 10 mA, reinforced protective conductorsshall be designed as follows:• either the protective conductor shall have a cross-sectional area of at least10 mm 2 Cu or 16 mm 2 Al, through its total run;• or a second protective conductor of at least the same cross-sectional areaas required for protection against indirect contact shall be laid up to a pointwhere the protective conductor has a cross-sectional area not less than10 mm 2 Cu or 16 mm 2 Al. This requires that the appliance has a separateterminal for a second protective conductor.When overcurrent protective devices are used for protection against electricshock, the protective conductor shall be incorporated in the same wiring systemas the live conductors or be located in their immediate proximity.338 <strong>Electrical</strong> devices | <strong>ABB</strong>


1.6 Busbar trunking systems (BTSs)1 <strong>Protection</strong> of feedersIn electrical <strong>installation</strong>s for industrial environments, busbar trunking systems(BTSs) optimize the power distribution despite the inevitable modifications thatare carried out (additions, displacements, replacement of loads) <strong>and</strong> to facilitatemaintenance work <strong>and</strong> safety verifications.They are mainly used for:- supplying sources of light, safety <strong>and</strong> low power distribution;- lighting lines (medium power);- power supply <strong>and</strong> distribution (medium <strong>and</strong> large power);- supplying moving equipment (bridge cranes).Busbar trunking systems are subject to the following St<strong>and</strong>ards:- IEC 61439 – 1 “Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear assemblies – Part 1:General rules”- IEC 60439 – 2 “Low-voltage switchgear <strong>and</strong> <strong>control</strong>gear assemblies – Part 2:Particular requirements for busbar trunking systems (busways)”.BTSs consist of:- conductors/busbars;- coupling: electrical <strong>and</strong> mechanical connecting elements for different elements;- straight elements: base elements of the line for carrying energy from the sourceto the loads;- routing elements: flexible joints for the creation of curves or overcoming obstacles,horizontal <strong>and</strong> vertical angles, tee joints <strong>and</strong> cross elements to createany type of route;- pull boxes: elements that enable lamps or operating machines to be supplieddirectly with integrated protection (fuses or circuit breakers);- suspensions/accessories: hanging <strong>and</strong> fixing elements for BTS <strong>and</strong> for anysupport required for special loads (lighting components, etc).Dimensioning of a BTSTo dimension a BTS, the load current must be determined using the followingdata:Power supply• General type of load supply:- single-phase- three-phase.• Type of BTS supply:- from one end;- from both ends;- central power supply.• Rated voltage• Short-circuit current at the supply point• Ambient temperature.Loads• Number, distribution, power <strong>and</strong> cosϕ <strong>and</strong> type of loads supplied by the sameBTS<strong>ABB</strong> | <strong>Electrical</strong> devices 339


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsBTS geometry• Type of <strong>installation</strong>:- flat;- edge-on;- vertical.• Length.NOTE: BTSs shall be placed at a distance from the walls <strong>and</strong> the ceilings in such a wayas to enable visual inspection of connections during assembly <strong>and</strong> to facilitate insertionof the branch units.If possible, it is preferable to install the BTS edge-on so as to improve mechanical resistance<strong>and</strong> reduce any possible deposit of powder <strong>and</strong> polluting substances that might affect thelevel of internal insulation.Load current calculation for three-phase systemLoad current I bfor a three-phase system is calculated by the following formula:where:• P tis the sum of the active power of all the installed loads [W];• b is the supply factor, which is:- 1 if the BTS is supplied from one side only;- 1/2 if the BTS is supplied from the centre or from both endssimultaneously;• U ris the operating voltage [V];• cosϕ mis the average power factor of the loads.Choice of BTS current carrying capacityA BTS shall be chosen so that its current carrying capacity I zcomplies withthe following formula:where:• I Z0is the current that the BTS can carry for an indefinite time at the referencetemperature (40 °C);• I bis the load current;• k tis the correction factor for ambient temperature values other than the referenceambient temperature shown on Table 1.Table 1: Correction factor k tfor ambient temperature other than 40 °CAmbientTemperature [°C] 15 20 25 30 35 40 45 50k t1.2 1.17 1.12 1.08 1.05 1 0.95 0.85340 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsNote: the following tables show typical parameters of the BTS present on themarketTable 2: Current carrying capacity I Z0of copper BTSNumber of I Z0r ph* x phU rSize Generic type conductors [A] [mΩ/m] [mΩ/m] [V]25 25A 4 cond. Cu 4 25 6.964 1.144 40025 25A 4 cond. Cu 4 25 6.876 1.400 40025 25A 4+4 cond. Cu 4+4 25 6.876 1.400 40040 40A 4 cond. Cu 4 40 3.556 0.792 40040 40A 4 cond. Cu 4 40 3.516 1.580 40040 40A 4+4 cond. Cu 4+4 40 3.516 1.580 40040 40A 4 cond. Cu 4 40 2.173 0.290 40063 63A 4 cond. Cu 4 63 1.648 0.637 400100 100A 4 cond. Cu 4 100 0.790 0.366 400160 160A 4 cond. Cu 4 160 0.574 0.247 400160 160A 4 cond. Cu 4 160 0.335 0.314 500160 160A 5 cond. Cu 5 160 0.335 0.314 500250 250A 4 cond. Cu 4 250 0.285 0.205 1000250 250A 5 cond. Cu 5 250 0.285 0.205 1000250 250A 4 cond. Cu 4 250 0.194 0.205 500250 250A 5 cond. Cu 5 250 0.194 0.205 500315 315A 4 cond. Cu 4 315 0.216 0.188 1000315 315A 5 cond. Cu 5 315 0.216 0.188 1000350 350A 4 cond. Cu 4 350 0.142 0.188 500350 350A 5 cond. Cu 5 350 0.142 0.188 500400 400A 4 cond. Cu 4 400 0.115 0.129 1000400 400A 5 cond. Cu 5 400 0.115 0.129 1000500 500A 4 cond. Cu 4 500 0.092 0.129 500500 500A 5 cond. Cu 5 500 0.092 0.129 500630 630A 4 cond. Cu 4 630 0.073 0.122 1000630 630A 5 cond. Cu 5 630 0.073 0.122 1000700 700A 4 cond. Cu 4 700 0.077 0.122 500700 700A 5 cond. Cu 5 700 0.077 0.122 500700 700A 5 cond. Cu 5 700 0.077 0.122 500700 700A 4 cond. Cu 4 700 0.077 0.122 500<strong>ABB</strong> | <strong>Electrical</strong> devices 341


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsTable 2Number of I Z0r ph* x phU rSize Generic type conductors [A] [mΩ/m] [mΩ/m] [V]800 800A 4 cond. Cu 4 800 0.047 0.122 1000800 800A 5 cond. Cu 5 800 0.047 0.122 1000800 800A 4 cond. Cu 4 800 0.038 0.027 1000800 800A 4 cond. Cu 4 800 0.072 0.122 500800 800A 5 cond. Cu 5 800 0.072 0.122 5001000 1000A 4 cond. Cu 4 1000 0.038 0.120 10001000 1000A 5 cond. Cu 5 1000 0.038 0.120 10001000 1000A 4 cond. Cu 4 1000 0.037 0.026 10001000 1000A 4 cond. Cu 4 1000 0.038 0.097 10001000 1000A 4 cond. Cu 4 1000 0.068 0.120 5001000 1000A 5 cond. Cu 5 1000 0.068 0.120 5001200 1200A 4 cond. Cu 4 1200 0.035 0.021 10001250 1250A 4 cond. Cu 4 1250 0.034 0.023 10001250 1250A 4 cond. Cu 4 1250 0.035 0.076 10001500 1500A 4 cond. Cu 4 1500 0.030 0.022 10001600 1600A 4 cond. Cu 4 1600 0.025 0.018 10001600 1600A 4 cond. Cu 4 1600 0.034 0.074 10002000 2000A 4 cond. Cu 4 2000 0.020 0.015 10002000 2000A 4 cond. Cu 4 2000 0.025 0.074 10002400 2400A 4 cond. Cu 4 2400 0.019 0.012 10002500 2500A 4 cond. Cu 4 2500 0.016 0.011 10002500 2500A 4 cond. Cu 4 2500 0.019 0.040 10003000 3000A 4 cond. Cu 4 3000 0.014 0.011 10003000 3000A 4 cond. Cu 4 3000 0.017 0.031 10003200 3200A 4 cond. Cu 4 3200 0.013 0.009 10003200 3200A 4 cond. Cu 4 3200 0.015 0.031 10004000 4000A 4 cond. Cu 4 4000 0.011 0.007 10004000 4000A 4 cond. Cu 4 4000 0.011 0.026 10005000 5000A 4 cond. Cu 4 5000 0.008 0.005 10005000 5000A 4 cond. Cu 4 5000 0.008 0.023 1000*phase resistance at I z0342 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsTable 3: Current carrying capacity I Z0of aluminium BTSNumber of I Z0r ph* x phU rSize Generic type conductors [A] [mΩ/m] [mΩ/m] [V]160 160A 4 cond. Al 4 160 0.591 0.260 1000160 160A 5 cond. Al 5 160 0.591 0.260 1000160 160A 4 cond. Al 4 160 0.431 0.260 500160 160A 5 cond. Al 5 160 0.431 0.260 500250 250A 4 cond. Al 4 250 0.394 0.202 1000250 250A 5 cond. Al 5 250 0.394 0.202 1000250 250A 4 cond. Al 4 250 0.226 0.202 500250 250A 5 cond. Al 5 250 0.226 0.202 500315 315A 4 cond. Al 4 315 0.236 0.186 1000315 315A 5 cond. Al 5 315 0.236 0.186 1000315 315A 4 cond. Al 4 315 0.181 0.186 500315 315A 5 cond. Al 5 315 0.181 0.186 500400 400A 4 cond. Al 4 400 0.144 0.130 1000400 400A 5 cond. Al 5 400 0.144 0.130 1000400 400A 4 cond. Al 4 400 0.125 0.130 500400 400A 5 cond. Al 5 400 0.125 0.130 500500 500A 4 cond. Al 4 500 0.102 0.127 500500 500A 5 cond. Al 5 500 0.102 0.127 500630 630A 4 cond. Al 4 630 0.072 0.097 1000630 630A 5 cond. Al 5 630 0.072 0.097 1000630 630A 4 cond. Al 4 630 0.072 0.029 1000630 630A 4 cond. Al 4 630 0.073 0.097 500630 630A 5 cond. Al 5 630 0.073 0.097 500800 800A 4 cond. Al 4 800 0.062 0.096 1000800 800A 5 cond. Al 5 800 0.062 0.096 1000800 800A 4 cond. Al 4 800 0.067 0.027 1000800 800A 4 cond. Al 4 800 0.071 0.096 500800 800A 5 cond. Al 5 800 0.071 0.096 5001000 1000A 4 cond. Al 4 1000 0.062 0.023 10001000 1000A 4 cond. Al 4 1000 0.068 0.087 10001200 1200A 4 cond. Al 4 1200 0.054 0.023 10001250 1250A 4 cond. Al 4 1250 0.044 0.021 10001250 1250A 4 cond. Al 4 1250 0.044 0.066 10001500 1500A 4 cond. Al 4 1500 0.041 0.023 10001600 1600A 4 cond. Al 4 1600 0.035 0.017 10001600 1600A 4 cond. Al 4 1600 0.041 0.066 10002000 2000A 4 cond. Al 4 2000 0.029 0.016 10002000 2000A 4 cond. Al 4 2000 0.034 0.053 10002250 2250A 4 cond. Al 4 2250 0.032 0.049 10002400 2400A 4 cond. Al 4 2400 0.028 0.012 10002500 2500A 4 cond. Al 4 2500 0.022 0.011 10002500 2500A 4 cond. Al 4 2500 0.022 0.034 10003000 3000A 4 cond. Al 4 3000 0.020 0.011 10003200 3200A 4 cond. Al 4 3200 0.017 0.009 10003200 3200A 4 cond. Al 4 3200 0.020 0.034 10004000 4000A 4 cond. Al 4 4000 0.014 0.008 10004000 4000A 4 cond. Al 4 4000 0.017 0.024 10004500 4500A 4 cond. Al 4 4500 0.014 0.024 1000*phase resistance at I z0<strong>ABB</strong> | <strong>Electrical</strong> devices 343


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsBTS protection<strong>Protection</strong> against overloadBTSs are protected against overload by using the same criterion as that usedfor the cables. The following formula shall be verified:where:• I bis the current for which the circuit is designed;• I nis the rated current of the protective device; for adjustable protective devices,the rated current I nis the set current;• I zis the continuous current carrying capacity of the BTS.NOTE - The protectionagainst short-circuit doesnot need to be checkedif MCBs up to 63 A areused whenever correctlydimensioned for overloadprotection. In suchcases, in fact, protectionagainst both thermal <strong>and</strong>electrodynamic effectsis certainly adequatebecause of the energy <strong>and</strong>peak limitations offered bythese protective devices.<strong>Protection</strong> against short-circuitThe BTS must be protected against thermal overload <strong>and</strong> electrodynamic effectsdue to the short-circuit current.<strong>Protection</strong> against thermal overloadThe following formula shall be fulfilled:where:• I 2 t CBis the specific let-through energy of the circuit-breaker at the maximumshort-circuit current value at the <strong>installation</strong> point. This can be extrapolatedfrom the curves shown in Part 1 Chapter 1.4;• I 2 t BTSis the withstood energy of the BTS <strong>and</strong> it is normally given by the manufacturer(see Tables 4 <strong>and</strong> 5).<strong>Protection</strong> against electrodynamic effectsThe following formula shall be fulfilled:where:• I kp CBis the peak limited by the circuit-breaker at the maximum short-circuitcurrent value at the <strong>installation</strong> point. This can be extrapolated from the limitationcurves;• I kp BTSis the maximum peak current value of the BTS (see Tables 4 <strong>and</strong> 5).344 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsSTARTIbTemperature 40 °C ?yesnokt=1kt fromTable 1BTS choice(Ib < kt*I Z0 =IZ)Voltage dropOK ?noyesCircuit-breakerchoiceIb < InCB < I Z ?noyesI 2 t CB < I 2 t BTS?yesIkp < I kp?CByesBTSnono1SDC010017F0201END<strong>ABB</strong> | <strong>Electrical</strong> devices 345


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsTable 4: Values of the withstood energy <strong>and</strong> peak current of copper BTSI 2 t phI 2 t NI 2 t PEI peakphI peakNSize Generic type [(kA) 2 s] [(kA) 2 s] [(kA) 2 s] [kA] [kA]25 25A 4 cond. Cu 0.48 0.48 0.48 10 1025 25A 4 cond. Cu 0.64 0.64 0.64 10 1025 25A 4+4 cond. Cu 0.64 0.64 0.64 10 1040 40A 4 cond. Cu 0.73 0.73 0.73 10 1040 40A 4 cond. Cu 1 1 1 10 1040 40A 4+4 cond. Cu 1 1 1 10 1040 40A 4 cond. Cu 7.29 7.29 7.29 10 1063 63A 4 cond. Cu 7.29 7.29 7.29 10 10100 100A 4 cond. Cu 20.25 20.25 20.25 10 10160 160A 4 cond. Cu 30.25 30.25 30.25 10 10160 160A 4 cond. Cu 100 60 60 17 10.2160 160A 5 cond. Cu 100 100 100 17 10.2160 160A 4 cond. Cu 100 100 100 17 10.2250 250A 4 cond. Cu 312.5 187.5 187.5 52.5 31.5250 250A 5 cond. Cu 312.5 312.5 312.5 52.5 31.5250 250A 4 cond. Cu 169 101.4 101.4 26 15.6250 250A 5 cond. Cu 169 169 169 26 15.6250 250A 4 cond. Cu 169 169 169 26 15.6315 315A 4 cond. Cu 312.5 187.5 187.5 52.5 31.5315 315A 5 cond. Cu 312.5 312.5 312.5 52.5 31.5350 350A 4 cond. Cu 169 101.4 101.4 26 15.6350 350A 5 cond. Cu 169 169 169 26 15.6350 350A 4 cond. Cu 169 169 169 26 15.6400 400A 4 cond. Cu 900 540 540 63 37.8400 400A 5 cond. Cu 900 900 900 63 37.8500 500A 4 cond. Cu 756.25 453.75 453.75 58 34.8500 500A 5 cond. Cu 756.25 756.25 756.25 58 34.8500 500A 4 cond. Cu 756.25 756.25 756.25 58 34.8630 630A 4 cond. Cu 1296 777.6 777.6 75.6 45.4630 630A 5 cond. Cu 1296 1296 1296 75.6 45.4700 700A 4 cond. Cu 756.25 453.75 453.75 58 34.8700 700A 5 cond. Cu 756.25 756.25 756.25 58 34.8700 700A 4 cond. Cu 756.25 756.25 756.25 58 34.8346 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsI 2 t phI 2 t NI 2 t PEI peakphI peakNSize Generic type [(kA) 2 s] [(kA) 2 s] [(kA) 2 s] [kA] [kA]800 800A 4 cond. Cu 1296 777.6 777.6 75.6 45.4800 800A 5 cond. Cu 1296 1296 1296 75.6 45.4800 800A 4 cond. Cu 3969 3969 2381.4 139 83.4800 800A 4 cond. Cu 756.25 453.75 453.75 58 34.8800 800A 5 cond. Cu 756.25 756.25 756.25 58 34.8800 800A 4 cond. Cu 756.25 756.25 756.25 58 34.81000 1000A 4 cond. Cu 1296 777.6 777.6 75.6 45.41000 1000A 5 cond. Cu 1296 1296 1296 75.6 45.41000 1000A 4 cond. Cu 3969 3969 2381.4 139 83.41000 1000A 4 cond. Cu 1600 1600 960 84 50.41000 1000A 4 cond. Cu 1024 614.4 614.4 60 361000 1000A 5 cond. Cu 1024 1024 1024 60 361000 1000A 4 cond. Cu 1024 1024 1024 60 361200 1200A 4 cond. Cu 7744 7744 4646.4 194 116.41250 1250A 4 cond. Cu 7744 7744 4646.4 194 116.41250 1250A 4 cond. Cu 2500 2500 1500 105 631500 1500A 4 cond. Cu 7744 7744 4646.4 194 116.41600 1600A 4 cond. Cu 7744 7744 4646.4 194 116.41600 1600A 4 cond. Cu 2500 2500 1500 105 632000 2000A 4 cond. Cu 7744 7744 4646.4 194 116.42000 2000A 4 cond. Cu 3600 3600 2160 132 79.22400 2400A 4 cond. Cu 7744 7744 4646.4 194 116.42500 2500A 4 cond. Cu 7744 7744 4646.4 194 116.42500 2500A 4 cond. Cu 4900 4900 2940 154 92.43000 3000A 4 cond. Cu 30976 30976 18585.6 387 232.23000 3000A 4 cond. Cu 8100 8100 4860 198 118.83200 3200A 4 cond. Cu 30976 30976 18585.6 387 232.23200 3200A 4 cond. Cu 8100 8100 4860 198 118.84000 4000A 4 cond. Cu 30976 30976 18585.6 387 232.24000 4000A 4 cond. Cu 8100 8100 4860 198 118.85000 5000A 4 cond. Cu 30976 30976 18585.6 387 232.25000 5000A 4 cond. Cu 10000 10000 6000 220 132<strong>ABB</strong> | <strong>Electrical</strong> devices 347


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsTable 5: Values of the withstood energy <strong>and</strong> peak current ofaluminium BTSI 2 t phI 2 t NI 2 t PEI peakphI peakNSize Generic type [(kA) 2 s] [(kA) 2 s] [(kA) 2 s] [kA] [kA]160 160A 4 cond. Al 112.5 67.5 67.5 30 18160 160A 5 cond. Al 112.5 112.5 112.5 30 18160 160A 4 cond. Al 100 60 60 17 10.2160 160A 5 cond. Al 100 100 100 17 10.2160 160A 4 cond. Al 100 100 100 17 10.2250 250A 4 cond. Al 312.5 187.5 187.5 52.5 31.5250 250A 5 cond. Al 312.5 312.5 312.5 52.5 31.5250 250A 4 cond. Al 169 101.4 101.4 26 15.6250 250A 5 cond. Al 169 169 169 26 15.6250 250A 4 cond. Al 169 169 169 26 15.6315 315A 4 cond. Al 625 375 375 52.5 31.5315 315A 5 cond. Al 625 625 625 52.5 31.5315 315A 4 cond. Al 169 101.4 101.4 26 15.6315 315A 5 cond. Al 169 169 169 26 15.6315 315A 4 cond. Al 169 169 169 26 15.6400 400A 4 cond. Al 900 540 540 63 37.8400 400A 5 cond. Al 900 900 900 63 37.8400 400A 4 cond. Al 625 375 375 52.5 31.5400 400A 5 cond. Al 625 625 625 52.5 31.5400 400A 4 cond. Al 625 625 625 52.5 31.5500 500A 4 cond. Al 625 375 375 52.5 31.5500 500A 5 cond. Al 625 625 625 52.5 31.5500 500A 4 cond. Al 625 625 625 52.5 31.5630 630A 4 cond. Al 1296 777.6 777.6 75.6 45.4630 630A 5 cond. Al 1296 1296 1296 75.6 45.4630 630A 4 cond. Al 1444 1444 866.4 80 48630 630A 4 cond. Al 1024 614.4 614.4 67.5 40.5630 630A 5 cond. Al 1024 1024 1024 67.5 40.5348 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsI 2 t phI 2 t NI 2 t PEI peakphI peakNSize Generic type [(kA) 2 s] [(kA) 2 s] [(kA) 2 s] [kA] [kA]630 630A 4 cond. Al 1024 1024 1024 67.5 40.5800 800A 4 cond. Al 1296 777.6 777.6 75.6 45.4800 800A 5 cond. Al 1296 1296 1296 75.6 45.4800 800A 4 cond. Al 1764 1764 1058.4 88 52.8800 800A 4 cond. Al 1024 614.4 614.4 67.5 40.5800 800A 5 cond. Al 1024 1024 1024 67.5 40.5800 800A 4 cond. Al 1024 1024 1024 67.5 40.51000 1000A 4 cond. Al 6400 6400 3840 176 105.61000 1000A 4 cond. Al 1600 1600 960 84 50.41200 1200A 4 cond. Al 6400 6400 3840 176 105.61250 1250A 4 cond. Al 6400 6400 3840 176 105.61250 1250A 4 cond. Al 2500 2500 1500 105 631500 1500A 4 cond. Al 6400 6400 3840 176 105.61600 1600A 4 cond. Al 6400 6400 3840 176 105.61600 1600A 4 cond. Al 2500 2500 1500 105 632000 2000A 4 cond. Al 6400 6400 3840 176 105.62000 2000A 4 cond. Al 3600 3600 2160 132 79.22250 2250A 4 cond. Al 4900 4900 2940 154 92.42400 2400A 4 cond. Al 25600 25600 15360 352 211.22500 2500A 4 cond. Al 25600 25600 15360 352 211.22500 2500A 4 cond. Al 8100 8100 4860 198 118.83000 3000A 4 cond. Al 25600 25600 15360 352 211.23200 3200A 4 cond. Al 25600 25600 15360 352 211.23200 3200A 4 cond. Al 8100 8100 4860 198 118.84000 4000A 4 cond. Al 25600 25600 15360 352 211.24000 4000A 4 cond. Al 8100 8100 4860 198 118.84500 4500A 4 cond. Al 10000 10000 6000 220 132<strong>ABB</strong> | <strong>Electrical</strong> devices 349


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systems<strong>Protection</strong> of the outgoing feedersIf the outgoing feeder, which generally consists of cable duct, is not alreadyprotected against short-circuit <strong>and</strong> overload by the device located upstreamof the cable, the following measures shall be taken:- protection against short-circuit:there is no need to protect the feeder against the short-circuit if simultaneously:a. the length does not exceed 3 metres;b. the risk of short-circuit is minimized;c. there is no inflammable material nearby.In explosive environments <strong>and</strong> environments with greater risk of fire, protectionagainst short-circuit is always required;- protection against overload:the current carrying capacity of the feeder is generally lower than that of theBTS. It is therefore necessary to protect also the feeder against overload.The protection device against overload can be placed inside the pull box oron the incoming panel.In the latter case, protection against overload can also be provided by thecircuit-breakers protecting the single outgoing feeder from the panel only if thesum of their rated currents is lower or equal to the current carrying capacity I zof the outgoing feeder.In locations with greater risk of fire, the overload protection device shall beinstalled at the outgoing point, i.e. inside the pull box.Voltage dropIf a BTS is particularly long, the value of the voltage drop must be verified.For three-phase systems with a power factor (cosϕ m) not lower than 0.8, thevoltage drop can be calculated by using the following simplified formula:For single-phase BTS the formula is:where:• a is the current distribution factor, which depends on the circuit supply <strong>and</strong>the arrangement of the electric loads along the BTS, as shown in Table 6:350 <strong>Electrical</strong> devices | <strong>ABB</strong>


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsTable 6: Current distribution factorType of Arrangement Current distributionsupply of loads factorFrom one end only Load concentrated at the end 1Evenly distributed load 0.5From both ends Evenly distributed load 0.25Central Load concentrated at the ends 0.25Evenly distributed load 0.125• I bis the load current [A];• L is the BTS length [m];• r tis the phase resistance per unit of length of BTS, measured under thermalsteady-state conditions [mΩ/m];• x is the phase reactance per unit of length of BTS [mΩ/m];• cosϕ mis average power factor of the loads.Percentage voltage drop is obtained from:where U ris rated voltage.To reduce the voltage drop in very long BTS the power can be supplied at anintermediate position rather than at the end (see Table 6).Calculation of voltage drop for unevenly distributed loadsIf the loads cannot be considered to be evenly distributed, the voltage drop canbe calculated more accurately by using the formulas below.L3L2L1Ll1Ll2Ll31SDC010015F0001For the distribution of the three-phase loads shown in the figure, the voltagedrop can be calculated by the following formula if the BTS has a constant crosssection (as usual):<strong>ABB</strong> | <strong>Electrical</strong> devices 351


1 <strong>Protection</strong> of feeders1.6 Busbar trunking systemsGenerally speaking, this formula becomes:where:• r tis the phase resistance per unit of length of BTS, measured under thermalsteady-state conditions [mΩ/m];• x is the phase reactance per unit of length of BTS [mΩ/m];• cosϕ mis average power factor of the i-th load;• I iis i-th load current [A];• L iis the distance of the i-th load from the beginning of the BTS [m].Joule-effect lossesJoule-effect losses are due to the electrical resistance of the BTS.The losses are dissipated in heat <strong>and</strong> contribute to the heating of the trunking<strong>and</strong> of the environment. Calculation of power losses is useful for correctlydimensioning the air-conditioning system for the building.Three-phase losses are:while single-phase losses are:where:• I bis the current used [A];• r tis the phase resistance per unit of length of BTS measured under thermalsteady-state conditions [mΩ/m];• L is the length of BTS [m].For accurate calculations, losses must be assessed section by section on thebasis of the currents flowing through them; e.g. in the case of distribution ofloads shown in the previous figure:Length Current Losses1° section L 1I 1+I 2+I 3P 1=3r tL 1(I 1+I 2+I 3) 22° section L 2-L 1I 2+I 3P 2=3r t(L 2-L 1)(I 2+I 3) 23° section L 3-L 2I 3P 3=3r t(L 3-L 2)(I 3) 2Total losses in BTS P tot=P 1+P 2+P 3352 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.1 <strong>Protection</strong> <strong>and</strong> switching of lightingcircuitsIntroduction2 <strong>Protection</strong> of electrical equipmentUpon supply of a lighting <strong>installation</strong>, for a brief period an initial current exceedingthe rated current (corresponding to the power of the lamps) circulates on thenetwork. This possible peak has a value of approximately 15÷20 times the ratedcurrent, <strong>and</strong> is present for a few milliseconds according to the type of lighting;there may also be an inrush current with a value of approximately 1.5÷3 timesthe rated current, lasting up to some minutes. The correct dimensioning of theswitching <strong>and</strong> protection devices must take these problems into account.Peak current diagramI [A]Inrush current diagramI [A]Peak15√20 InIn4-5 milliseconds Time [milliseconds]Inrush1.5√3 In3- 5 min.Time [minutes]1SDC010003F0901The most commonly used lamps are of the following types:- inc<strong>and</strong>escent;- halogen;- fluorescent;- high intensity discharge: mercury vapour, metal halide <strong>and</strong> sodium vapour.Inc<strong>and</strong>escent lampsInc<strong>and</strong>escent lamps are made up of a glass bulb containing a vacuum or inertgas <strong>and</strong> a tungsten filament. The current flows through this filament, heatingit until light is emitted.The electrical behaviour of these lamps involves a high peak current, equal toapproximately 15 times the rated current; after a few milliseconds the currentreturns to the rated value. The peak is caused by the lamp filament which,initially cold, presents a very low electrical resistance. Subsequently, due to thevery fast heating of the element, the resistance value increases considerably,causing the decrease in the current absorbed.<strong>ABB</strong> | <strong>Electrical</strong> devices 353


2 <strong>Protection</strong> of electrical equipmentHalogen lamps2.1 <strong>Protection</strong> <strong>and</strong> switching of lighting circuitsHalogen lamps are a special type of inc<strong>and</strong>escent lamp in which the gas containedwithin the bulb prevents the vaporized material of the tungsten filament fromdepositing on the surface of the bulb <strong>and</strong> forces re-deposition on the filament.This phenomenon slows the deterioration of the filament, improves the qualityof the light emitted <strong>and</strong> increases the life of the lamp.The electrical behaviour of these lamps is the same as that of inc<strong>and</strong>escentlamps.Fluorescent lampsFluorescent lamps are a so-called discharge light source. The light is producedby a discharge within a transparent enclosure (glass, quartz, etc. depending onthe type of lamp) which contains mercury vapour at low pressure.Once the discharge has started, the gas within the enclosure emits energy inthe ultraviolet range which strikes the fluorescent material; in turn, this materialtransforms the ultraviolet radiation into radiation which has a wavelengthwithin the visible spectrum. The colour of the light emitted depends upon thefluorescent material used.The discharge is created by an appropriate peak in voltage, generated by astarter. Once the lamp has been switched on, the gas offers an ever lowerresistance, <strong>and</strong> it is necessary to stabilize the intensity of the current, usinga <strong>control</strong>ler (reactor); this lowers the power factor to approximately 0.4÷0.6;normally a capacitor is added to increase the power factor to a value of morethan 0.9There are two types of <strong>control</strong>lers, magnetic (conventional) <strong>and</strong> electronic,which absorb from 10% to 20% of the rated power of the lamp. Electronic<strong>control</strong>lers offer specific advantages such as a saving in the energy absorbed,a lower dissipation of heat, <strong>and</strong> ensure a stable, flicker-free light. Some typesof fluorescent lamps with electronic reactors do not need a starter.Compact fluorescent lamps are made up of a folded tube <strong>and</strong> a plastic basewhich contains, in some cases, a conventional or electronic <strong>control</strong>ler.The value of the inrush current depends upon the presence of a power factorcorrection capacitor:- non PFC lamps have inrush currents equal to approximately twice the ratedcurrent <strong>and</strong> a turn-on time of about ten seconds;- in PFC lamps, the presence of the capacitor allows the reduction of the turnontime to a few seconds, but requires a high peak current, determined bythe charge of the capacitor, which can reach 20 times the rated current.If the lamp is fitted with an electronic <strong>control</strong>ler, the initial transient current maylead to peak currents equal to, at maximum, 10 times the rated current.354 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.1 <strong>Protection</strong> <strong>and</strong> switching of lighting circuits2 <strong>Protection</strong> of electrical equipmentHigh intensity discharge lamps: mercury vapour, metalhalide <strong>and</strong> sodium vapourThe functioning of high intensity discharge lamps is the same as that offluorescent lamps with the difference that the discharge occurs in the presenceof a gas at high pressure. In this case, the arc is able to vaporize the metallicelements contained in the gas, releasing energy in the form of radiation whichis both ultraviolet <strong>and</strong> within the visible spectrum. The special type of bulbglass blocks the ultraviolet radiation <strong>and</strong> allows only the visible radiation to passthrough. There are three main types of high intensity discharge lamps: mercuryvapour, metal halide <strong>and</strong> sodium vapour. The colour characteristics <strong>and</strong> theefficiency of the lamp depend upon the different metallic elements present inthe gas, which are struck by the arc.High intensity discharge lamps require a suitably sized <strong>control</strong>ler <strong>and</strong> a heatingperiod which can last some minutes before the emission of the rated lightoutput. A momentary loss of power makes the restarting of the system <strong>and</strong>the heating necessary.Non PFC lamps have inrush currents of up to twice the rated current forapproximately 5 minutes.PFC lamps have a peak current equal to 20 times the rated current, <strong>and</strong> aninrush current of up to twice the rated current for approximately 5 minutes.Lamp type Peak current Inrush current Turn-on timeInc<strong>and</strong>escent lamps 15In - -Halogen lamps 15In - -Fluorescent Non PFC - 2In 10 slamp PFC 20In 1÷6 sHigh intensity Non PFC − 2In 2÷8 mindischarge lamps PFC 20In 2In 2÷8 min<strong>Protection</strong> <strong>and</strong> switching devicesIEC 60947-4-1 identifies two specific utilization categories for lamp <strong>control</strong>contactors:• AC-5a switching of electric discharge lamps <strong>control</strong>s;• AC-5b switching of inc<strong>and</strong>escent lamps.The documentation supplied by the manufacturer includes tables for contactorselection, according to the number of lamps to be <strong>control</strong>led, <strong>and</strong> to their type.<strong>ABB</strong> | <strong>Electrical</strong> devices 355


2.1 <strong>Protection</strong> <strong>and</strong> switching of lighting circuits2 <strong>Protection</strong> of electrical equipmentFor the selection of a protection device the following verifications shall becarried out:- the trip characteristic curve shall be above the turning-on characteristic curveof the lighting device to avoid unwanted trips; an approximate example isshown in Figure1;- coordination shall exist with the contactor under short-circuit conditions(lighting <strong>installation</strong>s are not generally characterized by overloads).With reference to the above verification criteria, the following tables show the maximumnumber of lamps per phase which can be <strong>control</strong>led by the combinationof <strong>ABB</strong> circuit-breakers <strong>and</strong> contactors for some types of lamps, according totheir power <strong>and</strong> absorbed current I b(* ) , for three phase <strong>installation</strong>s with a ratedvoltage of 400 V <strong>and</strong> a maximum short-circuit current of 15 kA.(* ) For calculation see Annex B Calculation of load current I bTable 1: Inc<strong>and</strong>escent <strong>and</strong> halogen lampsUr= 400 V Ik= 15 kAInc<strong>and</strong>escent/halogen lampsCircuit-breaker typeS200P D20 S200P D20 S200P D25Setting Ekip LS/IContactor type----A26----A26----A26Rated Power [W]601002003005001000Rated current Ib [A]0.270.450.911.372.284.55573417116365381912747042201384S200P D32----A26103623020126S200P D50----A30142854228168356 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.1 <strong>Protection</strong> <strong>and</strong> switching of lighting circuits2 <strong>Protection</strong> of electrical equipmentFigure 1: Approximate diagram for the coordination of lamps withprotection <strong>and</strong> switching devices[t]Contactor IcwTurning-on characteristics[A]1SDC010004F0901Circuit-breaker characteristicsXT2N160 In63XT2N160 In63XT2N160 In100XT2N160 In100XT2N160 In100XT2N160 In160L= 0.68-12s S=8-0.1L= 0.96-12s S=10-0.1L= 0.68-12s S=8-0.1L= 0.76-12s S=8-0.1L= 0.96-12s S=10-0.1L= 0.72-12s S=7-0.1A40A50N° lamps per phaseA63A75A95A1101552202462723553909313214716321024046301896543261373482914805332161057042211208048241SDC010032F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 357


2.1 <strong>Protection</strong> <strong>and</strong> switching of lighting circuits2 <strong>Protection</strong> of electrical equipmentTable 2: Fluorescent lampsUr= 400 VIk= 15 kAFluorescent lamps non PFCCircuit-breaker typeSetting Ekip LS/IS200P D16S200P D20S200P D20S200P D32S200P D40Contactor typeRated Power [W] Rated current Ib [A]A26A26A26A26A30204065801001100.380.450.70.81.151.24033211813124437242114145042272316157362403524231008454473331Ur= 400 VIk= 15 kAFluorescent lamps PFCRated Power [W]Circuit-breaker typeSetting Ekip LS/IContactor typeRated current Ib [A]S200P D25---A26S200P D25---A26S200P D32---A26204065801001100.180.260.420.520.650.78358352823219465403226241057545362927358 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.1 <strong>Protection</strong> <strong>and</strong> switching of lighting circuits2 <strong>Protection</strong> of electrical equipmentS200P D50S200P D63XT2N160 In100XT2N160 In100XT2N160 In100XT2N160 In160A40N° lamps per phaseA50L= 0.68-12s S=10-0.1A63L= 0.76-12s S=10-0.1A75L= 0.96-12s S=10-0.1A95L= 0.68-12s S=10-0.1A11011093605236351571338575525017314594825755192162104916360250210135118827927823415013292881SDC010033F0201S200P D40S200P D63XT2N160 In63XT2N160 In63XT2N160 In100XT2N160 In100XT2N160 In100------L= 0.68-12s S=8-0.1L= 1-12s S=10-0.1L= 0.68-12s S=10-0.1L= 0.76-12s S=10-0.1L= 0.96-12s S=10-0.1A26A30A40A50N° lamps per phaseA63A75A951552152333353604005301071501602302552803656692100142158173225537480115126140180435964921011121454055598594104135<strong>ABB</strong> | <strong>Electrical</strong> devices 359


2.1 <strong>Protection</strong> <strong>and</strong> switching of lighting circuits2 <strong>Protection</strong> of electrical equipmentTable 3: High intensity discharge lampsUr= 400 VIk= 15 kAFluorescent lamps non PFCCircuit-breaker typeSetting Ekip LS/IS200P D16S200P D20S200P D20S200P D32S200P D40Contactor typeRated Power [W] Rated current Ib [A]1501.825034004.46006.2100010.3A266431-A2674321A2685321A26117432A30159643Ur= 400 VIk= 15 kAFluorescent lamps PFCRated Power [W]Circuit-breaker typeSetting Ekip LS/IContactor typeRated current Ib [A]S200P D16---A26S200P D20---A26S200P D20---A26S200P D32---A26S200P D40---A30150250400600100011.52.53.36.213854-14954-151065-231597428181184360 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.1 <strong>Protection</strong> <strong>and</strong> switching of lighting circuits2 <strong>Protection</strong> of electrical equipmentS200P D40S200P D50S200P D63XT2N160 In100L=0.8-12s S=6.5-0.1sXT2N160 In100L=1-12s S=8-0.1sXT2N160 In160L=0.8-12s S=6.5-0.1sA40N° lamps per phaseA50A63A75A95A110171075323149742616108529171285382315116412517127S200P D40XT2N160 In100XT2N160 In100XT2N160 In100XT2N160 In160XT2N160 In160---L= 0.8-12s S=6.5-0.1sL= 0.88-12s S=6.5-0.1sL= 1-12s S=6.5-0.1sL= 0.84-12s S=4.5-0.1s L=0.88-12s S=4.5-0.1sA40A50N° lamps per phaseA63A75A95A110305058638188201295332015838231794225191054322413593627141SDC010034F0201Example:Switching <strong>and</strong> protection of a lighting system, supplied by a three phasenetwork at 400 V 15 kA, made up of 55 inc<strong>and</strong>escent lamps, of 200 W each,per phase.In Table 1, on the row corresponding to 200 W, select the cell showing thenumber of <strong>control</strong>lable lamps immediately above the number of lamps perphase present in the <strong>installation</strong>. In the specific case, corresponding to the cellfor 65 lamps per phase the following equipment are suggested:- SACE Tmax XT2N160 In63 circuit-breaker with Ekip LS/I type electronicrelease, with protection L set at 0.96, t1 at 12s <strong>and</strong> protection S set at 10,t2 at 0.1s;- A50 contactor.<strong>ABB</strong> | <strong>Electrical</strong> devices 361


2.2 <strong>Protection</strong> <strong>and</strong> switching of generators2 <strong>Protection</strong> of electrical equipmentThe need to guarantee an ever greater continuity of service has led to an increasein the use of emergency supply generators, either as an alternative to, or inparallel with the public utility supply network.Typical configurations include:• “Isl<strong>and</strong> supply” (independent functioning) of the priority loads in the case of alack of energy supply through the public network;• supply to the user <strong>installation</strong> in parallel with the public supply network.Unlike the public supply network, which has a constant contribution, in caseof a short-circuit, the current supplied by the generator is a function of theparameters of the machine itself, <strong>and</strong> decreases with time; it is possible toidentify the following successive phases:1. a subtransient phase: with a brief duration (10÷50 ms), characterized bythe subtransient reactance X” d(5÷20% of the rated impedance value),<strong>and</strong> by the subtransient time constant T” d(5÷30 ms);2. a transitory phase: may last up to some seconds (0.5÷2.5 s), <strong>and</strong> ischaracterized by the transitory reactance X’ d(15÷40% of the ratedimpedance value), <strong>and</strong> by the transitory time constant T’ d(0.03÷2.5 s);3. a synchronous phase: may persist until the tripping of external protection,<strong>and</strong> is characterized by the synchronous reactance X d(80÷300% of therated impedance value).t [s] 101Synchronousphase1Transientphase10-110-210-3110Subtransientphase1SDC010018F0201102x I rg362 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.2 <strong>Protection</strong> <strong>and</strong> switching of generators2 <strong>Protection</strong> of electrical equipmentAs a first approximation, it can be estimated that the maximum value of theshort-circuit current of a generator, with rated power S rg, at the rated voltageof the <strong>installation</strong> U r, is equal to:whereI rgis the rated current of the generator:The circuit-breaker for the protection of the generator shall be selected accordingto the following criteria:• the set current higher than the rated current of the generator: I 1≥ I rg;• breaking capacity I cuor I cshigher than the maximum value of short-circuitcurrent at the <strong>installation</strong> point:- in the case of a single generator: I cu(I cs) ≥ I kg;- in the case of n identical generators in parallel: I cu(I cs) ≥ I kg·(n-1);- in the case of operation in parallel with the network: I cu(I cs) ≥ I kNet,as the short-circuit contribution from the network is normallygreater than the contribution from the generator;• for circuit-breakers with thermomagnetic releases: low magnetic trip threshold:I 3=2.5/3·I n;• for circuit-breakers with electronic releases:-trip threshold of the delayed short-circuit protection function (S),set between 1.5 <strong>and</strong> 4 times the rated current of the generator, insuch a way as to “intercept” the decrement curve of the generator:I 2= (1.5÷4)·I rg; if the function S is not present, function I can be setat the indicated values I 3= (1.5÷4)·I rg;-trip threshold of the instantaneous short-circuit protection function(I 3) set at a value greater than the rated short-circuit current of thegenerator, so as to achieve discrimination with the devices installeddownstream, <strong>and</strong> to allow fast tripping in the event of a short-circuitupstream of the device (working in parallel with other generators orwith the network):<strong>ABB</strong> | <strong>Electrical</strong> devices 363


2.2 <strong>Protection</strong> <strong>and</strong> switching of generators2 <strong>Protection</strong> of electrical equipmentThe following tables give <strong>ABB</strong> SACE suggestions for the protection <strong>and</strong> switchingof generators; the tables refer to 400 V (Table 1), 440 V (Table 2), 500 V (Table3) <strong>and</strong> 690 V (Table 4). Molded-case circuit-breakers can be equipped withboth thermomagnetic (TMG) as well as electronic releases.Table 1 400 V Table 2 440 VS rg [kVA] MCB MCCB ACB4 S200 B6679S200 B10S200 B1311 S200 B161417S200 B251921 S200 B322228XT1 160S200 B50 XT2 160313538 S200 B63424448 S280 B805569 S280 B1008087100111138159XT3 250XT4 250173180190208T4 320218242T5 4002773083113463814154364845546927278651107T5 630T6 800T7 1000T7 1250T7 1600X1 630X1 800X1 1000**X1 1250**X1 1600**1730 E3 25002180221422502500280031503500E3 3200E4 4000E6 5000E6 6300** also Emax CB type E1 can be used for this applicationS rg [kVA] MCB MCCB ACB4 S200 B66 S200 B87 S200 B109 S200 B1311 S200 B1614 S200 B2017 S200 B251921 S200 B322228 S200 B4031S200 B50353842 S200 B634448S280 B805569 S280 B1008087100111138159173180190208218242XT1 160XT2 160XT3 250XT4 250T4 320277 T5 400308311346T5 630381415436484T6 800554692727T7 1000865T7 12501107T7 160017302180221422502500280031503500X1 630X1 800**X1 1000**X1 1250**X1 1600**E3 2500E3 3200E4 3600E4 4000E6 50001SDC010016F0001364 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.2 <strong>Protection</strong> <strong>and</strong> switching of generators2 <strong>Protection</strong> of electrical equipmentTable 3 500 V Table 4 690 VS rg [kVA] MCB MCCB ACB46791114171921222831353842444855698087100111138159173180190208218242277308311346381415436484554692727865110717302180221422502500280031503500XT1 160XT2 160XT3 250XT4 250T4 320T5 400T5 630T6 800T7 1000T7 1600X1 630X1 800**X1 1000**X1 1600**E2 2000E3 3200E4 4000E6 5000S rg [kVA]46791114171921222831353842444855698087100111138159173180190208218242277308311346381415436484554692727865110717302180221422502500280031503500MCB MCCB ACBXT1 160XT2 160XT3 250XT4 250T4 320T5 400T5 630T6 800T7 1000T7 1600X1 630X1 800**X1 1000**X1 1600**E2 2000E3 2500E3 32001SDC010017F0001** also Emax CB type E1 can be used for this application<strong>ABB</strong> | <strong>Electrical</strong> devices 365


2.2 <strong>Protection</strong> <strong>and</strong> switching of generators2 <strong>Protection</strong> of electrical equipmentExample:<strong>Protection</strong> of a generator with S rg= 100 kVA, in a system with a rated voltageof 440 V.The generator parameters are:U r= 440 VS rg= 100 kVAf = 50 HzI rg= 131.2 AX ’’ = 6.5 % (subtransient reactance)dX ’ = 17.6 % (transient reactance)dX d= 230 % (synchronous reactance)T ’’ = 5.5 ms (subtransient time constant)d= 39.3 ms (transient time constant)T ’ dFrom table 2, an SACE Tmax XT2N160 circuit-breaker is selected, with I n= 160A, with electronic trp unit Ekip G LS/I. For correct protection of the generator,the following settings are selected:function L: 0.84 – 3s, corresponding to 134.4 A, value greater than I rgfunction I: 1.5410 sTime-Current Curves10 3 sXT2 16010 2 s10 1 s1s10 -1 s100 kVA generatordecrement curve10 -2 s10 -1 kA 1kA 10 1 kA1SDC010019F0201366 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.3 <strong>Protection</strong> <strong>and</strong> switching of motors2 <strong>Protection</strong> of electrical equipmentElectromechanical starterThe starter is designed to:- start motors;- ensure continuous functioning of motors;- disconnect motors from the supply line;- guarantee protection of motors against working overloads.The starter is typically made up of a switching device (contactor) <strong>and</strong> an overloadprotection device (thermal release).The two devices must be coordinated with equipment capable of providingprotection against short-circuit (typically a circuit-breaker with magnetic releaseonly), which is not necessarily part of the starter.The characteristics of the starter must comply with the international St<strong>and</strong>ardIEC 60947-4-1, which defines the above as follows:Contactor: a mechanical switching device having only one position ofrest, operated otherwise than by h<strong>and</strong>, capable of making, carrying <strong>and</strong>breaking currents under normal circuit conditions including operating overloadconditions.Thermal release: thermal overload relay or release which operates in the caseof overload <strong>and</strong> also in case of loss of phase.Circuit-breaker: defined by IEC 60947-2 as a mechanical switching device,capable of making, carrying <strong>and</strong> breaking currents under normal circuitconditions <strong>and</strong> also making, carrying for a specified time <strong>and</strong> breaking currentsunder specified abnormal circuit conditions.The main types of motor which can be operated <strong>and</strong> which determinethe characteristics of the starter are defined by the following utilizationcategories:Table 1: Utilization categories <strong>and</strong> typical applicationsCurrent type Utilization categories Typical applicationsSlip-ring motors: starting,AC-2switching offAlternating Current acSquirrel-cage motors: starting,AC-3 switching off during running (1)AC-4Squirrel-cage motors: starting,plugging, inching(1)AC-3 categories may be used for occasionally inching or plugging for limited time periodssuch as machine set-up; during such limited time periods the number of such operationsshould not exceed five per minutes or more than ten in a 10 minutes period.<strong>ABB</strong> | <strong>Electrical</strong> devices 367


2 <strong>Protection</strong> of electrical equipment2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsThe choice of the starting method <strong>and</strong> also, if necessary, of the type of motor tobe used depends on the typical resistant torque of the load <strong>and</strong> on the shortcircuitpower of the motor supplying network.With alternating current, the most commonly used motor types are asfollows:- asynchronous three-phase squirrel-cage motors (AC-3): the most widespreadtype due to the fact that they are of simple construction, economical <strong>and</strong>sturdy; they develop high torque with short acceleration times, but requireelevated starting currents;- slip-ring motors (AC-2): characterized by less dem<strong>and</strong>ing starting conditions,<strong>and</strong> have quite a high starting torque, even with a supply network of lowpower.Starting methodsThe most common starting methods for asynchronous squirrel-cage motorsare detailed below:Direct startingWith direct starting, the DOL (Direct On Line) starter, with the closing of linecontactor KL, the line voltage is applied to the motor terminals in a singleoperation. Hence a squirrel-cage motor develops a high starting torque with arelatively reduced acceleration time. This method is generally used with small<strong>and</strong> medium power motors which reach full working speed in a short time.These advantages are, however, accompanied by a series of drawbacks,including, for example:- high current consumption <strong>and</strong> associated voltage drop which may causedamages to the other parts of the system connected to the network;- violent acceleration which has negative effects on mechanical transmissioncomponents (belts, chains <strong>and</strong> mechanical joints), reducing working life.MCCBKLTORMotor1SDC010018F0001368 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipment2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsOther types of starting for squirrel-cage motors are accomplished by reducingthe supply voltage of the motor: this leads to a reduction in the starting current<strong>and</strong> of the motor torque, <strong>and</strong> an increase in the acceleration time.Star-Delta starterThe most common reduced voltage starter is the Star-Delta starter (Y-∆), inwhich:- on starting, the stator windings are star-connected, thus achieving thereduction of peak inrush current;- once the normal speed of the motor is nearly reached, the switchover to deltais carried out.After the switchover, the current <strong>and</strong> the torque follow the progress of the curvesassociated with normal service connections (delta).As can be easily checked, starting the motor with star-connection gives avoltage reduction of √3, <strong>and</strong> the current absorbed from the line is reduced by1/3 compared with that absorbed with delta-connection.The start-up torque, proportional to the square of the voltage, is reduced by3 times, compared with the torque that the same motor would supply whendelta-connected.This method is generally applied to motors with power from 15 to 355 kW, butintended to start with a low initial resistant torque.MCCBKLK∆KYTORMotor1SDC010019F0001Starting sequenceBy pressing the start button, contactors KL <strong>and</strong> KY are closed. The timer startsto measure the start time with the motor connected in star. Once the set timehas elapsed, the first contact of the timer opens the KY contactor <strong>and</strong> thesecond contact, delayed by approximately 50 ms, closes the K∆ contactor.With this new configuration, contactors KL <strong>and</strong> K∆ closed, the motor becomesdelta-connected.<strong>ABB</strong> | <strong>Electrical</strong> devices 369


2 <strong>Protection</strong> of electrical equipment2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsThe thermal release TOR, inserted in the delta circuit, can detect any 3 rd harmoniccurrents, which may occur due to saturation of the magnetic pack <strong>and</strong> by addingto the fundamental current, overload the motor without involving the line.With reference to the connection diagram, the equipment used for a Star/Deltastarter must be able to carry the following currents:3KL line contactor <strong>and</strong> K∆ delta contactor3KY star contactoroverload protection release3where I ris the rated current of the motor.Starting with autotransformersStarting with autotransformers is the most functional of the methods usedfor reduced voltage starting, but is also the most expensive. The reduction ofthe supply voltage is achieved by using a fixed tap autotransformer or a moreexpensive multi tap autotransformer.Applications can be found with squirrel-cage motors which generally have apower from 50 kW to several hundred kilowatts, <strong>and</strong> higher power doublecagemotors.MCCBK2K3K1MotorTOR1SDC010020F0001The autotransformer reduces the network voltage by the factor K (K=1.25÷1.8),<strong>and</strong> as a consequence the start-up torque is reduced by K 2 times comparedwith the value of the full rated voltage.On starting, the motor is connected to the taps of the autotransformer <strong>and</strong> thecontactors K2 <strong>and</strong> K1 are closed.370 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipment2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsTherefore, the motor starts at a reduced voltage, <strong>and</strong> when it has reachedapproximately 80% of its normal speed, contactor K1 is opened <strong>and</strong> maincontactor K3 is closed. Subsequently, contactor K2 is opened, excluding theautotransformer so as to supply the full network voltage.Starting with inductive reactors or resistorsThis type of starting is used for simple or double-cage rotors. The reduction ofthe supply voltage is achieved by the insertion of inductive reactors or resistors,in series to the stator. On start-up, the current is limited to 2.5÷3.5 times therated value.On starting, the motor is supplied via contactor K2; once the normal speed isreached, the reactors are short-circuited by the closing of contactor K1, <strong>and</strong>are then excluded by the opening of contactor K2.It is possible to achieve exclusions by step of the resistors or reactors with timedelayedcomm<strong>and</strong>s, even for motors with power greater than 100 kW.The use of reactors notably reduces the power factor, while the use of resistorscauses the dissipation of a high power (Joule effect), even if limited to thestarting phase.For a reduction K (0.6÷0.8) of the motor voltage, the torque is reduced by K 2times (0.36÷0.64).K1K2InductanceMotorTOR1SDC010021F0001In compliance with the above mentioned St<strong>and</strong>ard, starters can also be classifiedaccording to tripping time (trip classes), <strong>and</strong> according to the type of coordinationachieved with the short-circuit protection device (Type 1 <strong>and</strong> Type 2).<strong>ABB</strong> | <strong>Electrical</strong> devices 371


372 <strong>Electrical</strong> devices | <strong>ABB</strong>2 <strong>Protection</strong> of electrical equipmentTrip classesTable 2: Trip classTrip Class2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsThe trip classes differentiate between the thermal releases according to theirtrip curve.The trip classes are defined in the following table 2:Tripping time in seconds (Tp)10A 2 < Tp ≤ 1010 4 < Tp ≤ 1020 6 < Tp ≤ 2030 9 < Tp ≤ 30where Tp is the cold trip time of the thermal release at 7.2 times the set currentvalue (for example: a release in class 10 at 7.2 times the set current value mustnot trip within 4 s, but must trip within 10 s).It is normal procedure to associate class 10 with a normal start-up type, <strong>and</strong>class 30 with a heavy duty start-up type.Coordination typeType 1It is acceptable that in the case of short-circuit the contactor <strong>and</strong> the thermalrelease may be damaged. The starter may still not be able to function <strong>and</strong> mustbe inspected; if necessary, the contactor <strong>and</strong>/or the thermal release must bereplaced, <strong>and</strong> the breaker release reset.Type 2In the case of short-circuit, the thermal release must not be damaged, while thewelding of the contactor contacts is allowed, as they can easily be separated(with a screwdriver, for example), without any significant deformation.In order to clearly determine a coordination type, <strong>and</strong> therefore the equipmentnecessary to achieve it, the following must be known:• power of the motor in kW <strong>and</strong> type;• rated system voltage;• rated motor current;• short-circuit current at <strong>installation</strong> point;• starting type: DOL or Y/∆ - normal or heavy duty – Type 1 or Type 2.The requested devices shall be coordinated with each other in accordance withthe prescriptions of the St<strong>and</strong>ard.For the most common voltages <strong>and</strong> short-circuit values (400 V - 440 V - 500 V -690 V 35 kA - 50 kA) <strong>and</strong> for the most frequently used starting types, such asdirect starting <strong>and</strong> Star/Delta starting, for asynchronous squirrel-cage motor(AC-3), <strong>ABB</strong> supplies solutions with:• magnetic circuit-breaker - contactor - thermal release;• thermomagnetic circuit-breaker - contactor;• circuit-breaker with Ekip M LIU-LRIU or PR222MP electronic release - contactor.


2 <strong>Protection</strong> of electrical equipmentThe following is an example of the type of tables available:Table 3: 400 V 35 kA DOL Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1,1 XT2N160 MF 2 28 A9 TA25DU1.4 1 1,40,55 1,5 XT2N160 MF 2 28 A9 TA25DU1.8 1,3 1,80,75 1,9 XT2N160 MF 2 28 A9 TA25DU2.4 1,7 2,41,1 2,7 XT2N160 MF 4 56 A9 TA25DU4 2,8 41,5 3,6 XT2N160 MF 4 56 A16 TA25DU5 3,5 52,2 4,9 XT2N160 MF 8.5 120 A26 TA25DU6.5 4,5 6,53 6,5 XT2N160 MF 8.5 120 A26 TA25DU8.5 6 8,54 8,5 XT2N160 MF 12.5 175 A30 TA25DU11 7,5 115,5 11,5 XT2N160 MF 12.5 175 A30 TA25DU14 10 147,5 15,5 XT2N160 MA 20 210 A30 TA25DU19 13 1911 22 XT2N160 MA 32 288 A30 TA42DU25 18 2515 29 XT2N160 MA 52 392 A50 TA75DU42 29 4218,5 35 XT2N160 MA 52 469 A50 TA75DU52 36 5222 41 XT2N160 MA 52 547 A50 TA75DU52 36 5230 55 XT2N160 MA 80 840 A63 TA75DU80 60 8037 66 XT2N160 MA 80 960 A75 TA75DU80 60 8045 80 XT2N160 MA 100 1200 A95 TA110DU110 80 11055 97 XT3N250 MA 160 1440 A110 TA110DU110 80 11075 132 XT3N250 MA 200 1800 A145 TA200DU175 130 17590 160 XT3N250 MA 200 2400 A185 TA200DU200 150 200110 195 T4N320 PR221-I In320 2720 A210 E320DU320 100 320132 230 T5N400 PR221-I In400 3200 A260 E320DU320 100 320160 280 T5N400 PR221-I In400 4000 A300 E320DU320 100 320200 350 T5N630 PR221-I In630 5040 AF400 E500DU500 150 500250 430 T6N630 PR221-I In630 6300 AF460 E500DU500 150 500290 520 T6N800 PR221-I In800 7200 AF580 E800DU800 250 800315 540 T6N800 PR221-I In800 8000 AF580 E800DU800 250 800355 610 T6N800 PR221-I In800 8000 AF750 E800DU800 250 800MA: magnetic only adjustable releaseMF: fixed magnetic only releaseminmax<strong>ABB</strong> | <strong>Electrical</strong> devices 373


2 <strong>Protection</strong> of electrical equipmentTable 4: 400 V 50 kA DOL Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1,1 XT2S160 MF 2 28 A9 TA25DU1.4 1 1,40,55 1,5 XT2S160 MF 2 28 A9 TA25DU1.8 1,3 1,80,75 1,9 XT2S160 MF 2 28 A9 TA25DU2.4 1,7 2,41,1 2,7 XT2S160 MF 4 56 A9 TA25DU4 2,8 41,5 3,6 XT2S160 MF 4 56 A16 TA25DU5 3,5 52,2 4,9 XT2S160 MF 8.5 120 A26 TA25DU6.5 4,5 6,53 6,5 XT2S160 MF 8.5 120 A26 TA25DU8.5 6 8,54 8,5 XT2S160 MF 12.5 175 A30 TA25DU11 7,5 115,5 11,5 XT2S160 MF 12.5 175 A30 TA25DU14 10 147,5 15,5 XT2S160 MA 20 210 A30 TA25DU19 13 1911 22 XT2S160 MA 32 288 A30 TA42DU25 18 2515 29 XT2S160 MA 52 392 A50 TA75DU42 29 4218,5 35 XT2S160 MA 52 469 A50 TA75DU52 36 5222 41 XT2S160 MA 52 547 A50 TA75DU52 36 5230 55 XT2S160 MA 80 840 A63 TA75DU80 60 8037 66 XT2S160 MA 80 960 A75 TA75DU80 60 8045 80 XT2S160 MA 100 1200 A95 TA110DU110 80 11055 97 XT3S250 MA 160 1440 A110 TA110DU110 80 11075 132 XT3S250 MA 200 1800 A145 TA200DU175 130 17590 160 XT3S250 MA 200 2400 A185 TA200DU200 150 200110 195 T4S320 PR221-I In320 2720 A210 E320DU320 100 320132 230 T5S400 PR221-I In400 3200 A260 E320DU320 100 320160 280 T5S400 PR221-I In400 4000 A300 E320DU320 100 320200 350 T5S630 PR221-I In630 5040 AF400 E500DU500 150 500250 430 T6S630 PR221-I In630 6300 AF460 E500DU500 150 500290 520 T6S800 PR221-I In800 7200 AF580 E800DU800 250 800315 540 T6S800 PR221-I In800 8000 AF580 E800DU800 250 800355 610 T6S800 PR221-I In800 8000 AF750 E800DU800 250 800MA: magnetic only adjustable releaseMF: fixed magnetic only releaseminmax374 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 5: 400 V 70 kA DOL Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1,1 XT2H160 MF 2 28 A9 TA25DU1.4 1 1,40,55 1,5 XT2H160 MF 2 28 A9 TA25DU1.8 1,3 1,80,75 1,9 XT2H160 MF 2 28 A9 TA25DU2.4 1,7 2,41,1 2,7 XT2H160 MF 4 56 A16 TA25DU4 2,8 41,5 3,6 XT2H160 MF 4 56 A26 TA25DU5 3,5 52,2 4,9 XT2H160 MF 8.5 120 A26 TA25DU6.5 4,5 6,53 6,5 XT2H160 MF 8.5 120 A26 TA25DU8.5 6 8,54 8,5 XT2H160 MF 12.5 175 A30 TA25DU11 7,5 115,5 11,5 XT2H160 MF 12.5 175 A50 TA25DU14 10 147,5 15,5 XT2H160 MA 20 210 A50 TA25DU19 13 1911 22 XT2H160 MA 32 288 A50 TA42DU25 18 2515 29 XT2H160 MA 52 392 A50 TA75DU42 29 4218,5 35 XT2H160 MA 52 469 A50 TA75DU52 36 5222 41 XT2H160 MA 52 547 A50 TA75DU52 36 5230 55 XT2H160 MA 80 840 A63 TA75DU80 60 8037 66 XT2H160 MA 80 960 A75 TA75DU80 60 8045 80 XT2H160 MA 100 1200 A95 TA110DU110 80 11055 97 XT4H250 Ekip-I In160 1360 A110 TA110DU110 80 11075 132 XT4H250 Ekip-I In250 1875 A145 E200DU200 60 20090 160 XT4H250 Ekip-I In250 2500 A185 E200DU200 60 200110 195 T4H320 PR221-I In320 2720 A210 E320DU320 100 320132 230 T5H400 PR221-I In400 3200 A260 E320DU320 100 320160 280 T5H400 PR221-I In400 4000 A300 E320DU320 100 320200 350 T5H630 PR221-I In630 5040 AF400 E500DU500 150 500250 430 T6H630 PR221-I In630 6300 AF460 E500DU500 150 500290 520 T6H800 PR221-I In800 7200 AF580 E800DU800 250 800315 540 T6H800 PR221-I In800 8000 AF580 E800DU800 250 800355 610 T6H800 PR221-I In800 8000 AF750 E800DU800 250 800MA: magnetic only adjustable releaseMF: fixed magnetic only releaseminmax<strong>ABB</strong> | <strong>Electrical</strong> devices 375


2 <strong>Protection</strong> of electrical equipmentTable 6: 400 V 80 kA DOL Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1,1 XT2L160 MF 2 28 A9 TA25DU1.4 1 1,40,55 1,5 XT2L160 MF 2 28 A9 TA25DU1.8 1,3 1,80,75 1,9 XT2L160 MF 2 28 A9 TA25DU2.4 1,7 2,41,1 2,7 XT2L160 MF 4 56 A16 TA25DU4 2,8 41,5 3,6 XT2L160 MF 4 56 A26 TA25DU5 3,5 52,2 4,9 XT2L160 MF 8.5 120 A26 TA25DU6.5 4,5 6,53 6,5 XT2L160 MF 8.5 120 A26 TA25DU8.5 6 8,54 8,5 XT2L160 MF 12.5 175 A30 TA25DU11 7,5 115,5 11,5 XT2L160 MF 12.5 175 A50 TA25DU14 10 147,5 15,5 XT2L160 MA 20 210 A50 TA25DU19 13 1911 22 XT2L160 MA 32 288 A50 TA42DU25 18 2515 29 XT2L160 MA 52 392 A50 TA75DU42 29 4218,5 35 XT2L160 MA 52 469 A50 TA75DU52 36 5222 41 XT2L160 MA 52 547 A50 TA75DU52 36 5230 55 XT2L160 MA 80 840 A63 TA75DU80 60 8037 66 XT2L160 MA 80 960 A75 TA75DU80 60 8045 80 XT2L160 MA 100 1200 A95 TA110DU110 80 11055 97 XT4L250 Ekip-I In160 1360 A110 TA110DU110 80 11075 132 XT4L250 Ekip-I In250 1875 A145 E200DU200 60 20090 160 XT4L250 Ekip-I In250 2500 A185 E200DU200 60 200110 195 T4L320 PR221-I In320 2720 A210 E320DU320 100 320132 230 T5L400 PR221-I In400 3200 A260 E320DU320 100 320160 280 T5L400 PR221-I In400 4000 A300 E320DU320 100 320200 350 T5L630 PR221-I In630 5040 AF400 E500DU500 150 500250 430 T6L630 PR221-I In630 6300 AF460 E500DU500 150 500290 520 T6L800 PR221-I In800 7200 AF580 E800DU800 250 800315 540 T6L800 PR221-I In800 8000 AF580 E800DU800 250 800355 610 T6L800 PR221-I In800 8000 AF750 E800DU800 250 800MA: magnetic only adjustable releaseMF: fixed magnetic only releaseminmax376 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 7: 400 V 35 kA DOL Normal Type 2(Tmax XT/T – Contactor – EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1,1 XT2N160 MF 2 28 A9 E16DU2.7 0,9 2,70,55 1,5 XT2N160 MF 2 28 A9 E16DU2.7 0,9 2,70,75 1,9 XT2N160 MF 2 28 A9 E16DU2.7 0,9 2,71,1 2,7 XT2N160 MF 4 56 A9 E16DU6.3 2 6,31,5 3,6 XT2N160 MF 4 56 A16 E16DU6.3 2 6,32,2 4,9 XT2N160 MF 8.5 120 A26 E16DU6.3 2 6,33 6,5 XT2N160 MF 8.5 120 A26 E16DU18.9 5,7 18,94 8,5 XT2N160 MF 12.5 175 A30 E16DU18.9 5,7 18,95,5 11,5 XT2N160 MF 12.5 175 A30 E16DU18.9 5,7 18,97,5 15,5 XT2N160 MA 20 210 A30 E16DU18.9 5,7 18,911 22 XT2N160 MA 32 288 A30 E45DU45 15 4515 29 XT2N160 MA 52 392 A50 E45DU45 15 4518,5 35 XT2N160 MA 52 469 A50 E80DU80 27 8022 41 XT2N160 MA 52 547 A50 E80DU80 27 8030 55 XT2N160 MA 80 840 A63 E80DU80 27 8037 66 XT2N160 MA 80 960 A75 E80DU80 27 8045 80 XT2N160 MA 100 1200 A95 E140DU140 50 14055 97 XT3N250 MA 160 1440 A110 E200DU200 60 20075 132 XT3N250 MA 200 1800 A145 E200DU200 60 20090 160 XT3N250 MA 200 2400 A185 E200DU200 60 200110 195 T4N320 PR221-I In320 2720 A210 E320DU320 100 320132 230 T5N400 PR221-I In400 3200 A260 E320DU320 100 320160 280 T5N400 PR221-I In400 4000 A300 E320DU320 100 320200 350 T5N630 PR221-I In630 5040 AF400 E500DU500 150 500250 430 T6N630 PR221-I In630 6300 AF460 E500DU500 150 500290 520 T6N800 PR221-I In800 7200 AF580 E800DU800 250 800315 540 T6N800 PR221-I In800 8000 AF580 E800DU800 250 800355 610 T6N800 PR221-I In800 8000 AF750 E800DU800 250 800minmax<strong>ABB</strong> | <strong>Electrical</strong> devices 377


2 <strong>Protection</strong> of electrical equipmentTable 8: 400 V 50 kA DOL Normal Type 2(Tmax XT/T – Contactor – EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1,1 XT2S160 MF 2 28 A9 E16DU2.7 0,9 2,70,55 1,5 XT2S160 MF 2 28 A9 E16DU2.7 0,9 2,70,75 1,9 XT2S160 MF 2 28 A9 E16DU2.7 0,9 2,71,1 2,7 XT2S160 MF 4 56 A9 E16DU6.3 2 6,31,5 3,6 XT2S160 MF 4 56 A16 E16DU6.3 2 6,32,2 4,9 XT2S160 MF 8.5 120 A26 E16DU6.3 2 6,33 6,5 XT2S160 MF 8.5 120 A26 E16DU18.9 5,7 18,94 8,5 XT2S160 MF 12.5 175 A30 E16DU18.9 5,7 18,95,5 11,5 XT2S160 MF 12.5 175 A30 E16DU18.9 5,7 18,97,5 15,5 XT2S160 MA 20 210 A30 E16DU18.9 5,7 18,911 22 XT2S160 MA 32 288 A30 E45DU45 15 4515 29 XT2S160 MA 52 392 A50 E45DU45 15 4518,5 35 XT2S160 MA 52 469 A50 E80DU80 27 8022 41 XT2S160 MA 52 547 A50 E80DU80 27 8030 55 XT2S160 MA 80 840 A63 E80DU80 27 8037 66 XT2S160 MA 80 960 A75 E80DU80 27 8045 80 XT2S160 MA 100 1200 A95 E140DU140 50 14055 97 XT3S250 MA 160 1440 A110 E200DU200 60 20075 132 XT3S250 MA 200 1800 A145 E200DU200 60 20090 160 XT3S250 MA 200 2400 A185 E200DU200 60 200110 195 T4S320 PR221-I In320 2720 A210 E320DU320 100 320132 230 T5S400 PR221-I In400 3200 A260 E320DU320 100 320160 280 T5S400 PR221-I In400 4000 A300 E320DU320 100 320200 350 T5S630 PR221-I In630 5040 AF400 E500DU500 150 500250 430 T6S630 PR221-I In630 6300 AF460 E500DU500 150 500290 520 T6S800 PR221-I In800 7200 AF580 E800DU800 250 800315 540 T6S800 PR221-I In800 8000 AF580 E800DU800 250 800355 610 T6S800 PR221-I In800 8000 AF750 E800DU800 250 800minmax378 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 9: 400 V 70 kA DOL Normal Type 2(Tmax XT/T – Contactor – EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1,1 XT2H160 MF 2 28 A9 E16DU2.7 0,9 2,70,55 1,5 XT2H160 MF 2 28 A9 E16DU2.7 0,9 2,70,75 1,9 XT2H160 MF 2 28 A9 E16DU2.7 0,9 2,71,1 2,7 XT2H160 MF 4 56 A16 E16DU6.3 2 6,31,5 3,6 XT2H160 MF 4 56 A26 E16DU6.3 2 6,32,2 4,9 XT2H160 MF 8.5 120 A26 E16DU6.3 2 6,33 6,5 XT2H160 MF 8.5 120 A26 E16DU18.9 5,7 18,94 8,5 XT2H160 MF 12.5 175 A30 E16DU18.9 5,7 18,95,5 11,5 XT2H160 MF 12.5 175 A50 E16DU18.9 5,7 18,97,5 15,5 XT2H160 MA 20 210 A50 E16DU18.9 5,7 18,911 22 XT2H160 MA 32 288 A50 E45DU45 15 4515 29 XT2H160 MA 52 392 A50 E45DU45 15 4518,5 35 XT2H160 MA 52 469 A50 E80DU80 27 8022 41 XT2H160 MA 52 547 A50 E80DU80 27 8030 55 XT2H160 MA 80 840 A63 E80DU80 27 8037 66 XT2H160 MA 80 960 A75 E80DU80 27 8045 80 XT2H160 MA 100 1200 A95 E140DU140 50 14055 97 XT4H250 Ekip-I In160 1360 A110 E200DU200 60 20075 132 XT4H250 Ekip-I In250 1875 A145 E200DU200 60 20090 160 XT4H250 Ekip-I In250 2500 A185 E200DU200 60 200110 195 T4H320 PR221-I In320 2720 A210 E320DU320 100 320132 230 T5H400 PR221-I In400 3200 A260 E320DU320 100 320160 280 T5H400 PR221-I In400 4000 A300 E320DU320 100 320200 350 T5H630 PR221-I In630 5040 AF400 E500DU500 150 500250 430 T6H630 PR221-I In630 6300 AF460 E500DU500 150 500290 520 T6H800 PR221-I In800 7200 AF580 E800DU800 250 800315 540 T6H800 PR221-I In800 8000 AF580 E800DU800 250 800355 610 T6H800 PR221-I In800 8000 AF750 E800DU800 250 800minmax<strong>ABB</strong> | <strong>Electrical</strong> devices 379


2 <strong>Protection</strong> of electrical equipmentTable 10: 400 V 80 kA DOL Normal Type 2(Tmax XT/T – Contactor – EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1,1 XT2L160 MF 2 28 A9 E16DU2.7 0,9 2,70,55 1,5 XT2L160 MF 2 28 A9 E16DU2.7 0,9 2,70,75 1,9 XT2L160 MF 2 28 A9 E16DU2.7 0,9 2,71,1 2,7 XT2L160 MF 4 56 A16 E16DU6.3 2 6,31,5 3,6 XT2L160 MF 4 56 A26 E16DU6.3 2 6,32,2 4,9 XT2L160 MF 8.5 120 A26 E16DU6.3 2 6,33 6,5 XT2L160 MF 8.5 120 A26 E16DU18.9 5,7 18,94 8,5 XT2L160 MF 12.5 175 A30 E16DU18.9 5,7 18,95,5 11,5 XT2L160 MF 12.5 175 A50 E16DU18.9 5,7 18,97,5 15,5 XT2L160 MA 20 210 A50 E16DU18.9 5,7 18,911 22 XT2L160 MA 32 288 A50 E45DU45 15 4515 29 XT2L160 MA 52 392 A50 E45DU45 15 4518,5 35 XT2L160 MA 52 469 A50 E80DU80 27 8022 41 XT2L160 MA 52 547 A50 E80DU80 27 8030 55 XT2L160 MA 80 840 A63 E80DU80 27 8037 66 XT2L160 MA 80 960 A75 E80DU80 27 8045 80 XT2L160 MA 100 1200 A95 E140DU140 50 14055 97 XT4L250 Ekip-I In160 1360 A110 E200DU200 60 20075 132 XT4L250 Ekip-I In250 1875 A145 E200DU200 60 20090 160 XT4L250 Ekip-I In250 2500 A185 E200DU200 60 200110 195 T4L320 PR221-I In320 2720 A210 E320DU320 100 320132 230 T5L400 PR221-I In400 3200 A260 E320DU320 100 320160 280 T5L400 PR221-I In400 4000 A300 E320DU320 100 320200 350 T5L630 PR221-I In630 5040 AF400 E500DU500 150 500250 430 T6L630 PR221-I In630 6300 AF460 E500DU500 150 500290 520 T6L800 PR221-I In800 7200 AF580 E800DU800 250 800315 540 T6L800 PR221-I In800 8000 AF580 E800DU800 250 800355 610 T6L800 PR221-I In800 8000 AF750 E800DU800 250 800minmax380 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 11: 440 V 50 kA DOL Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1 XT2S160 MF 1 14 A9 TA25DU1.4 1 1,40,55 1,3 XT2S160 MF 2 28 A9 TA25DU1.8 1,3 1,80,75 1,7 XT2S160 MF 2 28 A9 TA25DU2.4 1,7 2,41,1 2,4 XT2S160 MF 4 56 A9 TA25DU3.1 2,2 3,11,5 3,2 XT2S160 MF 4 56 A16 TA25DU4 2,8 42,2 4,3 XT2S160 MF 8.5 120 A26 TA25DU5 3,5 53 5,7 XT2S160 MF 8.5 120 A26 TA25DU6.5 4,5 6,54 7,4 XT2S160 MF 8.5 120 A30 TA25DU11 7,5 115,5 10,1 XT2S160 MF 12 175 A30 TA25DU14 10 147,5 13,6 XT2S160 MA 20 180 A30 TA25DU19 13 1911 19,3 XT2S160 MA 32 240 A30 TA42DU25 18 2515 25,4 XT2S160 MA 32 336 A50 TA75DU32 22 3218,5 30,7 XT2S160 MA 52 469 A50 TA75DU42 29 4222 35,9 XT2S160 MA 52 547 A50 TA75DU52 36 5230 48,2 XT2S160 MA 80 720 A63 TA75DU63 45 6337 58 XT2S160 MA 80 840 A75 TA75DU80 60 8045 70 XT2S160 MA 100 1050 A95 TA110DU90 65 9055 85 XT4S250 Ekip-I In160 1200 A110 TA110DU110 80 11075 116 XT4S250 Ekip-I In250 1750 A145 E200DU200 60 20090 140 XT4S250 Ekip-I In250 2000 A185 E200DU200 60 200110 171 XT4S250 Ekip-I In250 2500 A210 E320DU320 100 320132 202 T5H400 PR221-I In320 3200 A260 E320DU320 100 320160 245 T5H400 PR221-I In400 3600 A300 E320DU320 100 320200 307 T5H630 PR221-I In630 4410 AF 400 E500DU500 150 500250 377 T6H630 PR221-I In630 5355 AF 460 E500DU500 150 500290 448 T6H630 PR221-I In630 6300 AF 580 E500DU500* 150 500315 473 T6H800 PR221-I In800 7200 AF 580 E800DU800 250 800355 535 T6H800 PR221-I In800 8000 AF 580 E800DU800 250 800minmax(*) Connection kit not available. To use connection kit provide E800DU800MA: magnetic only adjustable releaseMF: fixed magnetic only release<strong>ABB</strong> | <strong>Electrical</strong> devices 381


2 <strong>Protection</strong> of electrical equipmentTable 12: 440 V 65 kA DOL Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1 XT2H160 MF 1 14 A9 TA25DU1.4 1 1,40,55 1,3 XT2H160 MF 2 28 A9 TA25DU1.8 1,3 1,80,75 1,7 XT2H160 MF 2 28 A9 TA25DU2.4 1,7 2,41,1 2,4 XT2H160 MF 4 56 A16 TA25DU3.1 2,2 3,11,5 3,2 XT2H160 MF 4 56 A16 TA25DU4 2,8 42,2 4,3 XT2H160 MF 8.5 120 A26 TA25DU5 3,5 53 5,7 XT2H160 MF 8.5 120 A30 TA25DU6.5 4,5 6,54 7,4 XT2H160 MF 8.5 120 A30 TA25DU11 7,5 115,5 10,1 XT2H160 MF 12.5 175 A30 TA25DU14 10 147,5 13,6 XT2H160 MA 20 180 A30 TA25DU19 13 1911 19,3 XT2H160 MA 32 240 A50 TA42DU25 18 2515 25,4 XT2H160 MA 32 336 A50 TA75DU32 22 3218,5 30,7 XT2H160 MA 52 469 A50 TA75DU42 29 4222 35,9 XT2H160 MA 52 547 A50 TA75DU52 36 5230 48,2 XT2H160 MA 80 720 A63 TA75DU63 45 6337 58 XT2H160 MA 80 840 A75 TA75DU80 60 8045 70 XT2H160 MA 100 1050 A95 TA110DU90 65 9055 85 XT4H250 Ekip-I In160 1200 A110 TA110DU110 80 11075 116 XT4H250 Ekip-I In250 1750 A145 E200DU200 60 20090 140 XT4H250 Ekip-I In250 2000 A185 E200DU200 60 200110 171 XT4H250 Ekip-I In250 2500 A210 E320DU320 100 320132 202 T5H400 PR221-I In320 3200 A260 E320DU320 100 320160 245 T5H400 PR221-I In400 3600 A300 E320DU320 100 320200 307 T5H630 PR221-I In630 4410 AF 400 E500DU500 150 500250 377 T6L630 PR221-I In630 5355 AF 460 E500DU500 150 500290 448 T6L630 PR221-I In630 6300 AF 580 E500DU500* 150 500315 473 T6L800 PR221-I In800 7200 AF 580 E800DU800 250 800355 535 T6L800 PR221-I In800 8000 AF 580 E800DU800 250 800minmax(*) Connection kit not available. To use connection kit provide E800DU800MA: magnetic only adjustable releaseMF: fixed magnetic only release382 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 13: 440 V 50 kA DOL Normal Type 2(Tmax XT/T – Contactor – EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1 XT2S160 MF 1 14 A9 E16DU2.7 0,9 2,70,55 1,3 XT2S160 MF 2 28 A9 E16DU2.7 0,9 2,70,75 1,7 XT2S160 MF 2 28 A9 E16DU2.7 0,9 2,71,1 2,4 XT2S160 MF 4 56 A9 E16DU2.7 0,9 2,71,5 3,2 XT2S160 MF 4 56 A16 E16DU6.3 2 6,32,2 4,3 XT2S160 MF 8.5 120 A26 E16DU6.3 2 6,33 5,7 XT2S160 MF 8.5 120 A26 E16DU6.3 2 6,34 7,4 XT2S160 MF 8.5 120 A30 E16DU18.9 5,7 18,95,5 10,1 XT2S160 MF 12 175 A30 E16DU18.9 5,7 18,97,5 13,6 XT2S160 MA 20 180 A30 E16DU18.9 5,7 18,911 19,3 XT2S160 MA 32 240 A30 E45DU45 15 4515 25,4 XT2S160 MA 32 336 A50 E45DU45 15 4518,5 30,7 XT2S160 MA 52 469 A50 E45DU45 15 4522 35,9 XT2S160 MA 52 547 A50 E45DU45 15 4530 48,2 XT2S160 MA 80 720 A63 E80DU80 27 8037 58 XT2S160 MA 80 840 A75 E80DU80 27 8045 70 XT2S160 MA 100 1050 A95 E140DU140 50 14055 85 XT4S250 Ekip-I In160 1200 A110 E200DU200 60 20075 116 XT4S250 Ekip-I In250 1750 A145 E200DU200 60 20090 140 XT4S250 Ekip-I In250 2000 A185 E200DU200 60 200110 171 XT4S250 Ekip-I In250 2500 A210 E320DU320 100 320132 202 T5H400 PR221-I In320 3200 A260 E320DU320 100 320160 245 T5H400 PR221-I In400 3600 A300 E320DU320 100 320200 307 T5H630 PR221-I In630 4410 AF 400 E500DU500 150 500250 377 T6H630 PR221-I In630 5355 AF 460 E500DU500 150 500290 448 T6H630 PR221-I In630 7560 AF 580 E800DU800 250 800315 473 T6H800 PR221-I In800 8000 AF 580 E800DU800 250 800355 535 T6H800 PR221-I In800 9600 AF 580 E800DU800 250 800minmax<strong>ABB</strong> | <strong>Electrical</strong> devices 383


2 <strong>Protection</strong> of electrical equipmentTable 14: 440 V 65 kA DOL Normal Type 2(Tmax XT/T – Contactor – EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 1 XT2H160 MF 1 14 A9 E16DU2.7 0,9 2,70,55 1,3 XT2H160 MF 2 28 A9 E16DU2.7 0,9 2,70,75 1,7 XT2H160 MF 2 28 A9 E16DU2.7 0,9 2,71,1 2,4 XT2H160 MF 4 56 A16 E16DU2.7 0,9 2,71,5 3,2 XT2H160 MF 4 56 A16 E16DU6.3 2 6,32,2 4,3 XT2H160 MF 8.5 120 A26 E16DU6.3 2 6,33 5,7 XT2H160 MF 8.5 120 A30 E16DU6.3 2 6,34 7,4 XT2H160 MF 8.5 120 A30 E16DU18.9 5,7 18,95,5 10,1 XT2H160 MF 12.5 175 A30 E16DU18.9 5,7 18,97,5 13,6 XT2H160 MA 20 180 A30 E16DU18.9 5,7 18,911 19,3 XT2H160 MA 32 240 A50 E45DU45 15 4515 25,4 XT2H160 MA 32 336 A50 E45DU45 15 4518,5 30,7 XT2H160 MA 52 469 A50 E45DU45 15 4522 35,9 XT2H160 MA 52 547 A50 E45DU45 15 4530 48,2 XT2H160 MA 80 720 A63 E80DU80 27 8037 58 XT2H160 MA 80 840 A75 E80DU80 27 8045 70 XT2H160 MA 100 1050 A95 E140DU140 50 14055 85 XT4H250 Ekip-I In160 1200 A110 E200DU200 60 20075 116 XT4H250 Ekip-I In250 1750 A145 E200DU200 60 20090 140 XT4H250 Ekip-I In250 2000 A185 E200DU200 60 200110 171 XT4H250 Ekip-I In250 2500 A210 E320DU320 100 320132 202 T5H400 PR221-I In320 3200 A260 E320DU320 100 320160 245 T5H400 PR221-I In400 3600 A300 E320DU320 100 320200 307 T5H630 PR221-I In630 4410 AF 400 E500DU500 150 500250 377 T6L630 PR221-I In630 5355 AF 460 E500DU500 150 500290 448 T6L630 PR221-I In630 6300 AF 580 E800DU800 250 800315 473 T6L800 PR221-I In800 7200 AF 580 E800DU800 250 800355 535 T6L800 PR221-I In800 8000 AF 580 E800DU800 250 800minmax384 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 15: 500 V 50 kA DOL Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 0,88 XT2H160 MF 1 14 A9 TA25DU1.0 0,63 10,55 1,2 XT2H160 MF 2 28 A9 TA25DU1.4 1 1,40,75 1,5 XT2H160 MF 2 28 A9 TA25DU1.8 1,3 1,81,1 2,2 XT2H160 MF 4 56 A9 TA25DU3.1 2,2 3,11,5 2,8 XT2H160 MF 4 56 A16 TA25DU4 2,8 42,2 3,9 XT2H160 MF 8.5 120 A26 TA25DU5 3,5 53 5,2 XT2H160 MF 8.5 120 A26 TA25DU6.5 4,5 6,54 6,8 XT2H160 MF 8.5 120 A30 TA25DU8.5 6 8,55,5 9,2 XT2H160 MF 12.5 175 A30 TA25DU11 7,5 117,5 12,4 XT2H160 MF 12.5 163 A30 TA25DU14 10 1411 17,6 XT2H160 MA 20 240 A30 TA25DU19 13 1915 23 XT2H160 MA 32 336 A50 TA75DU25 18 2518,5 28 XT2H160 MA 52 392 A50 TA75DU32 22 3222 33 XT2H160 MA 52 469 A50 TA75DU42 29 4230 44 XT2H160 MA 52 624 A63 TA75DU52 36 5237 53 XT2H160 MA 80 840 A75 TA75DU63 45 6345 64 XT2H160 MA 80 960 A95 TA80DU80 60 8055 78 XT2H160 MA 100 1200 A110 TA110DU90 65 9075 106 XT4H250 Ekip-I In160 1440 A145 E200DU200 60 20090 128 XT4H250 Ekip-I In250 1875 A145 E200DU200 60 200110 156 XT4H250 Ekip-I In250 2250 A185 E200DU200 60 200132 184 T4H320 PR221-I In320 2720 A210 E320DU320 100 320160 224 T5H400 PR221-I In400 3600 A260 E320DU320 100 320200 280 T5H400 PR221-I In400 4000 A300 E320DU320 100 320250 344 T5H630 PR221-I In630 4725 AF400 E500DU500 150 500290 394 T6H630 PR221-I In630 5040 AF460 E500DU500 150 500315 432 T6H630 PR221-I In630 6300 AF580 E500DU500* 150 500355 488 T6H630 PR221-I In630 6300 AF580 E800DU800 250 800(*) Connection kit not available. To use connection kit provide E800DU800minmax<strong>ABB</strong> | <strong>Electrical</strong> devices 385


2 <strong>Protection</strong> of electrical equipmentTable 16: 500 V 50 kA DOL Normal Type 2(Tmax XT/T – Contactor – EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeCurrent setting range[A]0,37 0,88 XT2H160 MF 1 14 A9 E16DU2.7 0,9 2,70,55 1,2 XT2H160 MF 2 28 A9 E16DU2.7 0,9 2,70,75 1,5 XT2H160 MF 2 28 A9 E16DU2.7 0,9 2,71,1 2,2 XT2H160 MF 4 56 A9 E16DU2.7 0,9 2,71,5 2,8 XT2H160 MF 4 56 A16 E16DU6.3 2 6,32,2 3,9 XT2H160 MF 8.5 120 A26 E16DU6.3 2 6,33 5,2 XT2H160 MF 8.5 120 A26 E16DU6.3 2 6,34 6,8 XT2H160 MF 8.5 120 A30 E16DU18.9 5,7 18,95,5 9,2 XT2H160 MF 12.5 175 A30 E16DU18.9 5,7 18,97,5 12,4 XT2H160 MF 12.5 163 A50 E16DU18.9 5,7 18,911 17,6 XT2H160 MA 20 240 A50 E45DU45 15 4515 23 XT2H160 MA 32 336 A50 E45DU45 15 4518,5 28 XT2H160 MA 52 392 A50 E45DU45 15 4522 33 XT2H160 MA 52 469 A50 E45DU45 15 4530 44 XT2H160 MA 52 624 A63 E80DU80 27 8037 53 XT2H160 MA 80 840 A75 E80DU80 27 8045 64 XT2H160 MA 80 960 A95 E140DU140 50 14055 78 XT2H160 MA 100 1200 A110 E200DU200 60 20075 106 XT4H250 Ekip-I In160 1440 A145 E200DU200 60 20090 128 XT4H250 Ekip-I In250 1875 A145 E200DU200 60 200110 156 XT4H250 Ekip-I In250 2250 A185 E320DU320 100 320132 184 T4H320 PR221-I In320 2720 A210 E320DU320 100 320160 224 T5H400 PR221-I In400 3600 A260 E320DU320 100 320200 280 T5H400 PR221-I In400 4000 A300 E500DU500 150 500250 344 T5H630 PR221-I In630 4725 AF400 E500DU500 150 500290 394 T6H630 PR221-I In630 5040 AF460 E800DU800 250 800315 432 T6H630 PR221-I In630 6300 AF580 E800DU800 250 800355 488 T6H630 PR221-I In630 6300 AF580 E800DU800 250 800minmax386 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 17: 690 V 25 kA DOL Normal Type 2(Tmax XT – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor KORC Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeNumberofturnsTypeCurrentsettingrange[A]0,37 0,64 XT2V160 MF 1 14 A9 TA25DU1 0,6 10,55 0,87 XT2V160 MF 1 14 A9 TA25DU1 0,6 10,75 1,1 XT2V160 MF 2 28 A9 TA25DU1.4 1 1,41,1 1,6 XT2V160 MF 2 28 A9 TA25DU1.8 1,3 1,81,5 2,1 XT2V160 MF 4 56 A9 TA25DU2.4 1,7 2,42,2 2,8 XT2V160 MF 4 56 A9 TA25DU3.1 * 2,2 3,13 3,8 XT2V160 MF 4 56 A9 TA25DU4 * 2,8 44 4,9 XT2V160 MF 8.5 120 A9 TA25DU5 * 3,5 55,5 6,7XT2V160 MF 8.5 120 A9 TA25DU6.5 6 5XT4V250 EKIP-I In 100 150 A95 4L185R/4 13** TA25DU2.4 6 57,5 8,9 XT4V250 EKIP-I In 100 150 A95 4L185R/4 10** TA25DU2.4 7,9 11,111 12,8 XT4V250 EKIP-I In 100 200 A95 4L185R/4 7** TA25DU2.4 11,2 15,915 17 XT4V250 EKIP-I In 100 250 A95 4L185R/4 7** TA25DU3.1 15,2 20,518,5 21 XT4V250 EKIP-I In 100 300 A95 4L185R/4 6 TA25DU3.1 17,7 23,922 24 XT4V250 EKIP-I In 100 350 A95 4L185R/4 6 TA25DU4 21,6 30,830 32 XT4V250 EKIP-I In 100 450 A145 4L185R/4 6 TA25DU5 27 38,537 39 XT4V250 EKIP-I In 100 550 A145 4L185R/4 4 TA25DU4 32,4 46,345 47 XT4V250 EKIP-I In 100 700 A145 4L185R/4 4 TA25DU5 40,5 57,855 57 XT4V250 EKIP-I In 100 800 A145 4L185R/4 3 TA25DU5 54 77,175 77 XT4V250 EKIP-I In 160 1120 A145 E200DU200 65 20090 93 XT4V250 EKIP-I In 160 1280 A145 E200DU200 65 200110 113 XT4V250 EKIP-I In 250 1625 A145 E200DU200 65 200132 134 XT4V250 EKIP-I In 250 2000 A185 E200DU200 65 200160 162 XT4V250 EKIP-I In 250 2250 A185 E200DU200 65 200(*) Type 1 coordination(**) Cable cross section equal to 4 mm2(***) No mounting kit to contactor is availableMA: magnetic only adjustable releaseMF: fixed magnetic only releaseminmax<strong>ABB</strong> | <strong>Electrical</strong> devices 387


2 <strong>Protection</strong> of electrical equipmentTable 18: 690 V 50 kA DOL Normal Type 2(Tmax T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor KORC Overload RelayRatedCurrent[A]TypeI 3[A]TypeTypeNumberofturnsTypeCurrentsettingrange[A]0,37 0,64 T2L160 MF1 13 A9 TA25DU1 0,6 10,55 0,87 T2L160 MF1 13 A9 TA25DU1 0,6 10,75 1,1 T2L160 MF 1.6 21 A9 TA25DU1.4 1 1,41,1 1,6 T2L160 MF 1.6 21 A9 TA25DU1.8 1,3 1,81,5 2,1 T2L160 MF 2.5 33 A9 TA25DU2.4; 1,7 2,42,2 2,8 T2L160 MF 3.2 42 A9 TA25DU3.1 * 2,2 3,13 3,8 T2L160 MF 4 52 A9 TA25DU4 * 2,8 44 4,9 T2L160 MF 5 65 A9 TA25DU5 * 3,5 55,5 6,7T2L160 MF 6.5 84 A9 TA25DU6.5 4,5 6,5T4L250 PR221-I In 100 150 A95 4L185R/4 13** TA25DU2.4 6 8,57,5 8,9 T4L250 PR221-I In 100 150 A95 4L185R/4 10** TA25DU2.4 7,9 11,111 12,8 T4L250 PR221-I In 100 200 A95 4L185R/4 7** TA25DU2.4 11,2 15,915 17 T4L250 PR221-I In 100 250 A95 4L185R/4 7** TA25DU3.1 15,2 20,518,5 21 T4L250 PR221-I In 100 300 A95 4L185R/4 6 TA25DU3.1 17,7 23,922 24 T4L250 PR221-I In 100 350 A95 4L185R/4 6 TA25DU4 21,6 30,830 32 T4L250 PR221-I In 100 450 A145 4L185R/4 6 TA25DU5 27 38,537 39 T4L250 PR221-I In 100 550 A145 4L185R/4 4 TA25DU4 32,4 46,345 47 T4L250 PR221-I In 100 700 A145 4L185R/4 4 TA25DU5 40,5 57,855 57 T4L250 PR221-I In 100 800 A145 4L185R/4 3 TA25DU5 54 77,175 77 T4L250 PR221-I In 160 1120 A145 E200DU200 65 20090 93 T4L250 PR221-I In 160 1280 A145 E200DU200 65 200110 113 T4L250 PR221-I In 250 1625 A145 E200DU200 65 200132 134 T4L250 PR221-I In 250 2000 A185 E200DU200 65 200160 162 T4L250 PR221-I In 250 2250 A185 E200DU200 65 200200 203 T5L400 PR221-I In 320 2720 A210 E320DU320 105 320250 250 T5L400 PR221-I In 400 3400 A300 E320DU320 105 320290 301 T5L630 PR221-I In 630 4410 AF400 E500DU500 150 500315 313 T5L630 PR221-I In 630 4410 AF400 E500DU500 150 500355 354 T5L630 PR221-I In 630 5355 AF580 E500DU500*** 150 500minmax(*) Type 1 coordination(**) Cable cross section equal to 4 mm2(***) No mounting kit to contactor is availableMA: magnetic only adjustable releaseMF: fixed magnetic only release388 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 19: 400 V 35 kA DOL Heavy duty Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeType*Turnson CTCurrentsetting range [A]0,37 1,1 XT2N160 MF 2 28 A9 TA25DU1.4 ^ 1 1,40,55 1,5 XT2N160 MF 2 28 A9 TA25DU1.8 ^ 1,3 1,80,75 1,9 XT2N160 MF 2 28 A9 TA25DU2.4 ^ 1,7 2,41,1 2,7 XT2N160 MF 4 56 A9 TA25DU4 ^ 2,8 41,5 3,6 XT2N160 MF 4 56 A16 TA25DU5 ^ 3,5 52,2 4,9 XT2N160 MF 8.5 120 A26 TA25DU6.5 ^ 4,5 6,53 6,5 XT2N160 MF 8.5 120 A26 TA25DU8.5 ^ 6 8,54 8,5 XT2N160 MF 12.5 175 A30 TA25DU11 ^ 7,5 115,5 11,5 XT2N160 MF 12.5 175 A30 TA450SU60 4 10 157,5 15,5 XT2N160 MA 20 210 A30 TA450SU60 3 13 2011 22 XT2N160 MA 32 288 A30 TA450SU60 2 20 3015 29 XT2N160 MA 52 392 A50 TA450SU80 2 23 4018,5 35 XT2N160 MA 52 469 A50 TA450SU80 2 23 4022 41 XT2N160 MA 52 547 A50 TA450SU60 40 6030 55 XT2N160 MA 80 840 A63 TA450SU80 55 8037 66 XT2N160 MA 80 960 A95 TA450SU80 55 8045 80 XT2N160 MA 100 1200 A110 TA450SU105 70 10555 97 XT3N250 MA 160 1440 A145 TA450SU140 95 14075 132 XT3N250 MA 200 1800 A185 TA450SU185 130 18590 160 XT3N250 MA 200 2400 A210 TA450SU185 130 185110 195 T4N320 PR221-I In320 2720 A260 E320DU320^ 100 320132 230 T5N400 PR221-I In400 3200 A300 E320DU320^ 100 320160 280 T5N400 PR221-I In400 4000 AF400 E500DU500^ 150 500200 350 T5N630 PR221-I In630 5040 AF460 E500DU500^ 150 500250 430 T6N630 PR221-I In630 6300 AF580 E500DU500**^ 150 500290 520 T6N800 PR221-I In800 7200 AF750 E800DU800 250 800315 540 T6N800 PR221-I In800 8000 AF750 E800DU800^ 250 800355 610 T6N800 PR221-I In800 8000 AF750 E800DU800^ 250 800Comments:(^) Provide by-pass contactor during motor start-up(*) Set EOL tripping characteristic to class 30 usable also for 415V(**) Connection kit not available. To use connection kit provide E800DU800MA: magnetic only adjustable releaseMF: fixed magnetic only releaseminmax<strong>ABB</strong> | <strong>Electrical</strong> devices 389


2 <strong>Protection</strong> of electrical equipmentTable 20: 400 V 50 kA DOL Heavy duty Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeType*Turnson CTCurrentsetting range [A]0,37 1,1 XT2S160 MF 2 28 A9 TA25DU1.4 ^ 1 1,40,55 1,5 XT2S160 MF 2 28 A9 TA25DU1.8 ^ 1,3 1,80,75 1,9 XT2S160 MF 2 28 A9 TA25DU2.4 ^ 1,7 2,41,1 2,7 XT2S160 MF 4 56 A9 TA25DU4 ^ 2,8 41,5 3,6 XT2S160 MF 4 56 A16 TA25DU5 ^ 3,5 52,2 4,9 XT2S160 MF 8.5 120 A26 TA25DU6.5 ^ 4,5 6,53 6,5 XT2S160 MF 8.5 120 A26 TA25DU8.5 ^ 6 8,54 8,5 XT2S160 MF 12.5 175 A30 TA25DU11 ^ 7,5 115,5 11,5 XT2S160 MF 12.5 175 A30 TA450SU60 4 10 157,5 15,5 XT2S160 MA 20 210 A30 TA450SU60 3 13 2011 22 XT2S160 MA 32 288 A30 TA450SU60 2 20 3015 29 XT2S160 MA 52 392 A50 TA450SU80 2 23 4018,5 35 XT2S160 MA 52 469 A50 TA450SU80 2 23 4022 41 XT2S160 MA 52 547 A50 TA450SU60 40 6030 55 XT2S160 MA 80 840 A63 TA450SU80 55 8037 66 XT2S160 MA 80 960 A95 TA450SU80 55 8045 80 XT2S160 MA 100 1200 A110 TA450SU105 70 10555 97 XT3S250 MA 160 1440 A145 TA450SU140 95 14075 132 XT3S250 MA 200 1800 A185 TA450SU185 130 18590 160 XT3S250 MA 200 2400 A210 TA450SU185 130 185110 195 T4S320 PR221-I In320 2720 A260 E320DU320 100 320132 230 T5S400 PR221-I In400 3200 A300 E320DU320 100 320160 280 T5S400 PR221-I In400 4000 AF400 E500DU500 150 500200 350 T5S630 PR221-I In630 5040 AF460 E500DU500 150 500250 430 T6S630 PR221-I In630 6300 AF580 E500DU500** 150 500290 520 T6S800 PR221-I In800 7200 AF750 E800DU800 250 800315 540 T6S800 PR221-I In800 8000 AF750 E800DU800 250 800355 610 T6S800 PR221-I In800 8000 AF750 E800DU800 250 800Comments:(^) Provide by-pass contactor during motor start-up(*) Set EOL tripping characteristic to class 30 usable also for 415V(**) Connection kit not available. To use connection kit provide E800DU800MA: magnetic only adjustable releaseMF: fixed magnetic only releaseminmax390 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 21: 440 V 50 kA DOL Heavy duty Type 2(Tmax XT/T – Contactor – TOR)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeType*Turnson CTCurrentsetting range [A]0,37 1 XT2S160 MF 1 14 A9 TA25DU1,4 ^ 1 1,40,55 1,3 XT2S160 MF 2 28 A9 TA25DU1,8 ^ 1,3 1,80,75 1,7 XT2S160 MF 2 28 A9 TA25DU2,4 ^ 1,7 2,41,1 2,2 XT2S160 MF 4 56 A9 TA25DU3,1 ^ 2,2 3,11,5 3,2 XT2S160 MF 4 56 A16 TA25DU4 ^ 2,8 42,2 4,3 XT2S160 MF 8.5 120 A26 TA25DU5 ^ 3,5 53 5,7 XT2S160 MF 8.5 120 A26 TA25DU6,5 ^ 4,5 54 7,4 XT2S160 MF 8.5 120 A30 TA25DU11 ^ 7,5 115,5 10,1 XT2S160 MF 12.5 175 A30 TA25DU14 ^ 10 147,5 13,6 XT2S160 MA 20 180 A30 TA450SU60 4 10 1511 19,3 XT2S160 MA 32 240 A30 TA450SU80 3 18 2715 25,4 XT2S160 MA 32 336 A50 TA450SU60 2 20 3018,5 30,7 XT2S160 MA 52 469 A50 TA450SU80 2 28 4022 35,9 XT2S160 MA 52 547 A50 TA450SU80 2 28 4030 48,2 XT2S160 MA 80 720 A63 TA450SU60 40 6037 58 XT2S160 MA 80 840 A95 TA450SU80 55 8045 70 XT2S160 MA 100 1050 A110 TA450SU105 70 10555 85 XT4S250 Ekip-I In160 1200 A145 E200DU200 60 20075 116 XT4S250 Ekip-I In250 1750 A185 E200DU200 60 20090 140 XT4S250 Ekip-I In250 2000 A210 E320DU320 100 320110 171 XT4S250 Ekip-I In250 2500 A260 E320DU320 100 320132 202 T5H400 PR221-I In320 3200 A300 E320DU320 100 320160 245 T5H400 PR221-I In400 3600 AF400 E500DU500 150 500200 307 T5H630 PR221-I In630 4410 AF460 E500DU500 150 500250 377 T6H630 PR221-I In630 5355 AF580 E500DU500*** 150 500290 448 T6H630 PR221-I In630 6300 AF750 E500DU500*** 150 500315 473 T6H800 PR221-I In800 7200 AF750 E800DU800 250 800355 535 T6H800 PR221-I In800 8000 AF750 E800DU800 250 800minmax(^) Provide by-pass contactor during motor start-up(x) Set EOL tripping characteristic to class 30(***) Connection kit not available. To use connection kit provide E800DU800 (x)<strong>ABB</strong> | <strong>Electrical</strong> devices 391


2 <strong>Protection</strong> of electrical equipmentTable 22: 440 V 65 kA DOL Heavy duty Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeType*Turnson CTCurrentsetting range [A]0,37 1 XT2H160 MF 1 14 A9 TA25DU1,4 ^ 1 1,40,55 1,3 XT2H160 MF 2 28 A9 TA25DU1,8 ^ 1,3 1,80,75 1,7 XT2H160 MF 2 28 A9 TA25DU2,4 ^ 1,7 2,41,1 2,4 XT2H160 MF 4 56 A9 TA25DU3,1 ^ 2,2 3,11,5 3,2 XT2H160 MF 4 56 A16 TA25DU4 ^ 2,8 42,2 4,3 XT2H160 MF 8.5 120 A26 TA25DU5 ^ 3,5 53 5,7 XT2H160 MF 8.5 120 A26 TA25DU6,5 ^ 4,5 6,54 7,4 XT2H160 MF 8.5 120 A30 TA25DU11 ^ 7,5 115,5 10,1 XT2H160 MF 12.5 175 A30 TA25DU14 ^ 10 147,5 13,6 XT2H160 MA 20 180 A30 TA450SU60 4 10 1511 19,3 XT2H160 MA 32 240 A30 TA450SU80 3 18 2715 25,4 XT2H160 MA 32 336 A50 TA450SU60 2 20 3018,5 30,7 XT2H160 MA 52 469 A50 TA450SU80 2 28 4022 35,9 XT2H160 MA 52 547 A50 TA450SU80 2 28 4030 48,2 XT2H160 MA 80 720 A63 TA450SU60 40 6037 58 XT2H160 MA 80 840 A95 TA450SU80 55 8045 70 XT2H160 MA 100 1050 A110 TA450SU105 70 10555 85 XT4H250 Ekip-I In160 1200 A145 E200DU200 60 20075 116 XT4H250 Ekip-I In250 1750 A185 E200DU200 60 20090 140 XT4H250 Ekip-I In250 2000 A210 E320DU320 100 320110 171 XT4H250 Ekip-I In250 2500 A260 E320DU320 100 320132 202 T5H400 PR221-I In320 3200 A300 E320DU320 100 320160 245 T5H400 PR221-I In400 3600 AF400 E500DU500 150 500200 307 T5H630 PR221-I In630 4410 AF460 E500DU500 150 500250 377 T6H630 PR221-I In630 5355 AF580 E500DU500*** 150 500290 448 T6H630 PR221-I In630 6300 AF750 E500DU500*** 150 500315 473 T6H800 PR221-I In800 7200 AF750 E800DU800 250 800355 535 T6H800 PR221-I In800 8000 AF750 E800DU800 250 800minmax(^) Provide by-pass contactor during motor start-up(x) Set EOL tripping characteristic to class 30(***) Connection kit not available. To use connection kit provide E800DU800 (x)392 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 23: 500 V 50 kA DOL Heavy duty Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeType*Turnson CTCurrentsetting range [A]0,37 0,88 XT2H160 MF 1 14 A9 TA25DU1.0 ^ 0,63 10,55 1,2 XT2H160 MF 2 28 A9 TA25DU1.4 ^ 1 1,40,75 1,5 XT2H160 MF 2 28 A9 TA25DU1.8 ^ 1,3 1,81,1 2,2 XT2H160 MF 4 56 A9 TA25DU3.1 ^ 2,2 3,11,5 2,8 XT2H160 MF 4 56 A16 TA25DU4 ^ 2,8 42,2 3,9 XT2H160 MF 4 56 A26 TA25DU5 ^ 3,5 53 5,2 XT2H160 MF 8.5 120 A26 TA25DU6.5 ^ 4,5 6,54 6,8 XT2H160 MF 8.5 120 A30 TA25DU8.5 ^ 6 8,55,5 9,2 XT2H160 MF 12.5 175 A30 TA25DU11 ^ 7,5 117,5 12,4 XT2H160 MF 12.5 175 A30 TA450SU60 4 10 1511 17,6 XT2H160 MA 20 240 A30 TA450SU60 3 13 2015 23 XT2H160 MA 32 336 A50 TA450SU60 2 20 3018,5 28 XT2H160 MA 52 392 A50 TA450SU80 2 27,5 4022 33 XT2H160 MA 52 469 A50 TA450SU80 2 27,5 4030 44 XT2H160 MA 52 624 A63 TA450SU60 40 8037 53 XT2H160 MA 80 840 A75 TA450SU60 40 8045 64 XT2H160 MA 80 960 A95 TA450SU80 55 8055 78 XT2H160 MA 100 1200 A145 TA450SU105 70 10575 106 XT4H250 Ekip-I In160 1440 A145 E200DU200 60 20090 128 XT4H250 Ekip-I In250 1875 A185 E200DU200 60 200110 156 XT4H250 Ekip-I In250 2125 A210 E320DU320 100 320132 184 T4H320 PR221-I In320 2720 A260 E320DU320 100 320160 224 T5H400 PR221-I In400 3200 A300 E320DU320 100 320200 280 T5H400 PR221-I In400 3600 AF400 E500DU500 150 500250 344 T5H630 PR221-I In630 4725 AF460 E500DU500 150 500290 394 T6L630 PR221-I In630 5040 AF580 E500DU500*** 150 500315 432 T6L630 PR221-I In630 6300 AF750 E500DU500*** 150 500355 488 T6L630 PR221-I In630 6300 AF750 E500DU500*** 150 500minmax(^) Provide by-pass contactor during motor start-up(x) Set EOL tripping characteristic to class 30(***) Connection kit not available. To use connection kit provide E800DU800 (x)<strong>ABB</strong> | <strong>Electrical</strong> devices 393


2 <strong>Protection</strong> of electrical equipmentTable 24: 690 V 25 kA DOL Heavy duty Type 2(Tmax T – Contactor – TOR)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeType*Turnson CTCurrentsetting range [A]0,37 0,64 XT2V160 MF1 14 A9 TA25DU0.63 ^ 0,4 0,630,55 0,87 XT2V160 MF1 14 A9 TA25DU1 ^ 0,63 10,75 1,1 XT2V160 MF 2 28 A9 TA25DU1.4 ^ 1 1,41,1 1,6 XT2V160 MF 2 28 A9 TA25D1.8 ^ 1,3 1,81,5 2,1 XT2V160 MF 4 56 A9 TA25DU2.4 ^ 1,7 2,42,2 2,8 XT2V160 MF 4 56 A9 TA25DU3.1 ^ 2,2 3,13 3,8 XT2V160 MF 4 56 A9 TA25DU4 ^ 2,8 44 4,9 XT2V160 MF 8.5 120 A9 TA25DU5 ^ 3,5 55,5 6,7XT2V160 MF 8.5 120 A9 TA25DU6.5 ^ 4,5 6,5XT4V250 EKIP-I In 100 150 A95 TA450SU60 7(+) 5,7 8,67,5 8,9 XT4V250 EKIP-I In 100 150 A95 TA450SU60 5(+) 8 1211 12,8 XT4V250 EKIP-I In 100 200 A95 TA450SU60 4(+) 10 1515 17 XT4V250 EKIP-I In 100 250 A95 TA450SU60 3(+) 10 2018,5 21 XT4V250 EKIP-I In 100 300 A95 TA450SU60 3 18 2722 24 XT4V250 EKIP-I In 100 350 A95 TA450SU60 2 20 3030 32 XT4V250 EKIP-I In 100 450 A145 TA450SU80 2 27,5 4037 39 XT4V250 EKIP-I In 100 550 A145 TA450SU60 40 6045 47 XT4V250 EKIP-I In 100 700 A145 TA450SU60 40 6055 57 XT4V250 EKIP-I In 100 800 A145 TA450SU80 55 8075 77 XT4V250 EKIP-I In 160 1120 A145 TA450SU105 70 10590 93 XT4V250 EKIP-I In 160 1280 A145 TA450SU105 70 105110 113 XT4V250 EKIP-I In 250 1625 A185 TA450SU140 95 140132 134 XT4V250 EKIP-I In 250 2000 A210 E320DU320 105 320160 162 XT4V250 EKIP-I In 250 2250 A210 E320DU320 105 320minmax(^) Provide by-pass contactor during motor start-up(x) Set EOL tripping characteristic to class 30(***) Connection kit not available. To use connection kit provide E800DU800 (x)(+) size wire 4mm394 <strong>Electrical</strong> devices | <strong>ABB</strong>


2 <strong>Protection</strong> of electrical equipmentTable 25: 690 V 50 kA DOL Heavy duty Type 2(Tmax T – Contactor – TOR)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsRatedPower[kW]Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]TypeType*Turnson CTCurrentsetting range [A]0,37 0,64 T2L160 MF1 13 A9 TA25DU0.63 ^ 0,4 0,630,55 0,87 T2L160 MF1 13 A9 TA25DU1 ^ 0,63 10,75 1,1 T2L160 MF 1.6 21 A9 TA25DU1.4 ^ 1 1,41,1 1,6 T2L160 MF 1.6 21 A9 TA25D1.8 ^ 1,3 1,81,5 2,1 T2L160 MF 2.5 33 A9 TA25DU2.4 ^ 1,7 2,42,2 2,8 T2L160 MF 3.2 42 A9 TA25DU3.1 ^ 2,2 3,13 3,8 T2L160 MF 4 52 A9 TA25DU4 ^ 2,8 44 4,9 T2L160 MF 5 65 A9 TA25DU5 ^ 3,5 55,5 6,7T2L160 MF 6.5 84 A9 TA25DU6.5 ^ 4,5 6,5T4L250 PR221-I In 100 150 A95 TA450SU60 7(+) 5,7 8,67,5 8,9 T4L250 PR221-I In 100 150 A95 TA450SU60 5(+) 8 1211 12,8 T4L250 PR221-I In 100 200 A95 TA450SU60 4(+) 10 1515 17 T4L250 PR221-I In 100 250 A95 TA450SU60 3(+) 13 2018,5 21 T4L250 PR221-I In 100 300 A95 TA450SU60 3 18 2722 24 T4L250 PR221-I In 100 350 A95 TA450SU60 2 20 3030 32 T4L250 PR221-I In 100 450 A145 TA450SU80 2 27,5 4037 39 T4L250 PR221-I In 100 550 A145 TA450SU60 40 6045 47 T4L250 PR221-I In 100 700 A145 TA450SU60 40 6055 57 T4L250 PR221-I In 100 800 A145 TA450SU80 55 8075 77 T4L250 PR221-I In 160 1120 A145 TA450SU105 70 10590 93 T4L250 PR221-I In 160 1280 A145 TA450SU105 70 105110 113 T4L250 PR221-I In 250 1625 A185 TA450SU140 95 140132 134 T4L250 PR221-I In 250 2000 A210 E320DU320 105 320160 162 T4L250 PR221-I In 250 2250 A210 E320DU320 105 320200 203 T5L400 PR221-I In 320 2720 A260 E320DU320 105 320250 250 T5L400 PR221-I In 400 3400 AF400 E500DU500 150 500290 301 T5L630 PR221-I In 630 4410 AF400 E500DU500 150 500315 313 T5L630 PR221-I In 630 4410 AF460 E500DU500 150 500355 354 T5L630 PR221-I In 630 5355 AF580 E500DU500*** 150 500minmax(^) Provide by-pass contactor during motor start-up(x) Set EOL tripping characteristic to class 30(***) Connection kit not available. To use connection kit provide E800DU800 (x)(+) size wire 4mm<strong>ABB</strong> | <strong>Electrical</strong> devices 395


RatedPower[kW]2 <strong>Protection</strong> of electrical equipmentTable 26: 400 V 35 kA Y/∆ Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsMotor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]LineTypeDeltaTypeStarTypeTypeCurrentsettingrange[A]18,5 35 XT2N160 MA52 469 A50 A50 A26 TA75DU25 18-2522 41 XT2N160 MA52 547 A50 A50 A26 TA75DU32 22-3230 55 XT2N160 MA80 720 A63 A63 A30 TA75DU42 29-4237 66 XT2N160 MA80 840 A75 A75 A30 TA75DU52 36-5245 80 XT2N160 MA100 1050 A75 A75 A30 TA75DU63 45 - 6355 97 XT2N160 MA100 1200 A75 A75 A40 TA75DU63 45 - 6375 132 XT3N250 MA160 1700 A95 A95 A75 TA110DU90 66 - 9090 160 XT3N250 MA200 2000 A110 A110 A95 TA110DU110 80 - 110110 195 XT4N250 MA200 2400 A145 A145 A95 TA200DU135 100 - 135132 230 T4N320 PR221-I In320 2880 A145 A145 A110 E200DU200 60 - 200160 280 T5N400 PR221-I In400 3600 A185 A185 A145 E200DU200 60 - 200200 350 T5N630 PR221-I In630 4410 A210 A210 A185 E320DU320 100 - 320250 430 T5N630 PR221-I In630 5670 A260 A260 A210 E320DU320 100 - 320290 520 T6N630 PR221-I In630 6300 AF400 AF400 A260 E500DU500 150 - 500315 540 T6N800 PR221-I In800 7200 AF400 AF400 A260 E500DU500 150 - 500355 610 T6N800 PR221-I In800 8000 AF400 AF400 A260 E500DU500 150 - 500RatedPower[kW]Table 27: 400 V 50 kA Y/∆ Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]LineTypeDeltaTypeStarTypeTypeCurrentsettingrange[A]18,5 35 XT2S160 MA52 469 A50 A50 A26 TA75DU25 18-2522 41 XT2S160 MA52 547 A50 A50 A26 TA75DU32 22-3230 55 XT2S160 MA80 720 A63 A63 A30 TA75DU42 29-4237 66 XT2S160 MA80 840 A75 A75 A30 TA75DU52 36-5245 80 XT2S160 MA100 1050 A75 A75 A30 TA75DU63 45 - 6355 97 XT2S160 MA100 1200 A75 A75 A40 TA75DU63 45 - 6375 132 XT3S250 MA160 1700 A95 A95 A75 TA110DU90 66 - 9090 160 XT3S250 MA200 2000 A110 A110 A95 TA110DU110 80 - 110110 195 XT3S250 MA200 2400 A145 A145 A95 TA200DU135 100 - 135132 230 T4S320 PR221-I In320 2880 A145 A145 A110 E200DU200 60 - 200160 280 T5S400 PR221-I In400 3600 A185 A185 A145 E200DU200 60 - 200200 350 T5S630 PR221-I In630 4410 A210 A210 A185 E320DU320 100 - 320250 430 T5S630 PR221-I In630 5670 A260 A260 A210 E320DU320 100 - 320290 520 T6S630 PR221-I In630 6300 AF400 AF400 A260 E500DU500 150 - 500315 540 T6S800 PR221-I In800 7200 AF400 AF400 A260 E500DU500 150 - 500355 610 T6S800 PR221-I In800 8000 AF400 AF400 A260 E500DU500 150 - 500396 <strong>Electrical</strong> devices | <strong>ABB</strong>


RatedPower[kW]2 <strong>Protection</strong> of electrical equipmentTable 28: 440 V 50 kA Y/∆ Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsMotor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]LineTypeDeltaTypeStarTypeTypeCurrentsettingrange[A]18,5 30,7 XT2S160 MA52 392 A50 A50 A16 TA75DU25 18-2522 35,9 XT2S160 MA52 469 A50 A50 A26 TA75DU25 18-2530 48,2 XT2S160 MA80 720 A63 A63 A26 TA75DU42 29-4237 58 XT2S160 MA80 840 A75 A75 A30 TA75DU42 29-4245 70 XT2S160 MA80 960 A75 A75 A30 TA75DU52 36-5255 85 XT2S160 MA100 1150 A75 A75 A40 TA75DU63 45-6375 116 XT4S250 Ekip-I In250 1625 A95 A95 A75 TA80DU80 60-8090 140 XT4S250 Ekip-I In250 1875 A95 A95 A75 TA110DU110 80-110110 171 XT4S250 Ekip-I In250 2250 A145 A145 A95 E200DU200 60-200132 202 T4H320 PR221-I In320 2720 A145 A145 A110 E200DU200 60-200160 245 T5H400 PR221-I In400 3200 A185 A185 A145 E200DU200 60-200200 307 T5H630 PR221-I In630 4095 A210 A210 A185 E320DU320 100-320250 377 T5H630 PR221-I In630 5040 A260 A260 A210 E320DU320 100-320290 448 T6H630 PR221-I In630 5670 AF400 AF400 A260 E500DU500 150 - 500315 473 T6H630 PR221-I In630 6300 AF400 AF400 A260 E500DU500 150 - 500355 535 T6H800 PR221-I In800 7200 AF400 AF400 A260 E500DU500 150 - 500RatedPower[kW]Table 29: 440 V 65 kA Y/∆ Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)Motor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]LineTypeDeltaTypeStarTypeTypeCurrentsettingrange[A]18,5 30,7 XT2H160 MA52 392 A50 A50 A16 TA75DU25 18-2522 35,9 XT2H160 MA52 469 A50 A50 A26 TA75DU25 18-2530 48,2 XT2H160 MA80 720 A63 A63 A26 TA75DU42 29-4237 58 XT2H160 MA80 840 A75 A75 A30 TA75DU42 29-4245 70 XT2H160 MA80 960 A75 A75 A30 TA75DU52 36-5255 85 XT2H160 MA100 1150 A75 A75 A40 TA75DU63 45-6375 116 XT4H250 Ekip-I In250 1625 A95 A95 A75 TA80DU80 60-8090 140 XT4H250 Ekip-I In250 1875 A95 A95 A75 TA110DU110 80-110110 171 XT4H250 Ekip-I In250 2250 A145 A145 A95 E200DU200 60-200132 202 T4H320 PR221-I In320 2720 A145 A145 A110 E200DU200 60-200160 245 T5H400 PR221-I In400 3200 A185 A185 A145 E200DU200 60-200200 307 T5H630 PR221-I In630 4095 A210 A210 A185 E320DU320 100-320250 377 T5H630 PR221-I In630 5040 A260 A260 A210 E320DU320 100-320290 448 T6H630 PR221-I In630 5670 AF400 AF400 A260 E500DU500 150 - 500315 473 T6H630 PR221-I In630 6300 AF400 AF400 A260 E500DU500 150 - 500355 535 T6H800 PR221-I In800 7200 AF400 AF400 A260 E500DU500 150 - 500<strong>ABB</strong> | <strong>Electrical</strong> devices 397


RatedPower[kW]2 <strong>Protection</strong> of electrical equipmentTable 30: 500 V 50 kA Y/∆ Normal Type 2(Tmax XT/T – Contactor – TOR/EOL)2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsMotor Moulded Case Circuit Breaker Contactor Overload RelayRatedCurrent[A]TypeI 3[A]LineTypeDeltaTypeStarTypeTypeCurrentsettingrange[A]22 33 XT2H160 MA52 430 A50 A50 A16 TA75DU25 18-2530 44 XT2H160 MA52 547 A63 A63 A26 TA75DU32 22-3237 53 XT2H160 MA80 720 A75 A75 A30 TA75DU42 29-4245 64 XT2H160 MA80 840 A75 A75 A30 TA75DU52 36-5255 78 XT2H160 MA100 1050 A75 A75 A30 TA75DU52 36-5275 106 XT4H250 Ekip-I In250 1375 A95 A95 A50 TA80DU80 60-8090 128 XT4H250 Ekip-I In250 1750 A95 A95 A75 TA110DU90 65-90110 156 XT4H250 Ekip-I In250 2000 A110 A110 A95 TA110DU110 80-110132 184 T4H320 PR221-I In320 2560 A145 A145 A95 E200DU200 60-200160 224 T4H320 PR221-I In320 2880 A145 A145 A110 E200DU200 60-200200 280 T5H400 PR221-I In400 3400 A210 A210 A145 E320DU320 100-320250 344 T5H630 PR221-I In630 4410 A210 A210 A185 E320DU320 100-320290 394 T5H630 PR221-I In630 5040 A260 A260 A210 E320DU320 100-320315 432 T6L630 PR221-I In630 5760 AF400 AF400 A210 E500DU500 150 - 500355 488 T6L630 PR221-I In630 6300 AF400 AF400 A260 E500DU500 150 - 500RatedPower[kW]MotorRatedCurrent[A]Table 31: 690 V 25 kA Y/∆ Normal Type 2(Tmax XT – Contactor – TOR/EOL)Moulded Case CircuitBreakerTypeI 3[A]LineTypeContactor KORC Overload RelayDeltaTypeStarTypeTypeN° ofturnsTypeCurrentsettingrange [A]5,5 6.7* XT4V250 Ekip-I In100 150 A95 A95 A26 185R/4** 13 TA25DU2.4** 6-8.57,5 8.9* XT4V250 Ekip-I In100 150 A95 A95 A26 185R/4** 10 TA25DU2.4** 7.9-11.111 12.8* XT4V250 Ekip-I In100 200 A95 A95 A26 185R/4** 7 TA25DU2.4** 11.2-15.915 17* XT4V250 Ekip-I In100 250 A95 A95 A26 185R/4** 7 TA25DU3.1** 15.2-20.518,5 21 XT4V250 Ekip-I In100 300 A95 A95 A30 185R/4** 6 TA25DU3.1** 17.7-23.922 24 XT4V250 Ekip-I In100 350 A95 A95 A30 185R/4** 6 TA25DU4** 21.6-30.830 32 XT4V250 Ekip-I In100 450 A145 A145 A30 185R/4** 6 TA25DU5** 27-38.537 39 XT4V250 Ekip-I In100 550 A145 A145 A30 TA75DU52** 36-5245 47 XT4V250 Ekip-I In100 650 A145 A145 A30 TA75DU52** 36 - 5255 57 XT4V250 Ekip-I In100 800 A145 A145 A40 TA75DU52** 36-5275 77 XT4V250 Ekip-I In160 1120 A145 A145 A50 TA75DU52 36 - 5290 93 XT4V250 Ekip-I In160 1280 A145 A145 A75 TA75DU63 45-63110 113 XT4V250 Ekip-I In160 1600 A145 A145 A75 TA75DU80 60-80132 134 XT4V250 Ekip-I In250 1875 A145 A145 A95 TA200DU110 80-110160 162 XT4V250 Ekip-I In250 2125 A145 A145 A110 TA200DU110 80-110Comments:*size wire 4mm**connect TOL at line-delta supply side398 <strong>Electrical</strong> devices | <strong>ABB</strong>


RatedPower[kW]MotorRatedCurrent[A]2 <strong>Protection</strong> of electrical equipmentTable 32: 690 V 50 kA Y/∆ Normal Type 2(Tmax T – Contactor – TOR/EOL)Moulded Case CircuitBreakerTypeI 3[A]LineType2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsContactor KORC Overload RelayDeltaTypeStarTypeTypeN° ofturnsTypeCurrentsettingrange [A]5,5 6.7* T4L250 PR221-I In100 150 A95 A95 A26 4L185R/4** 13 TA25DU2.4** 6-8.57,5 8.9* T4L250 PR221-I In100 150 A95 A95 A26 4L185R/4** 10 TA25DU2.4** 7.9-11.111 12.8* T4L250 PR221-I In100 200 A95 A95 A26 4L185R/4** 7 TA25DU2.4** 11.2-15.915 17* T4L250 PR221-I In100 250 A95 A95 A26 4L185R/4** 7 TA25DU3.1** 15.2-20.518,5 21 T4L250 PR221-I In100 300 A95 A95 A30 4L185R/4** 6 TA25DU3.1** 17.7-23.922 24 T4L250 PR221-I In100 350 A95 A95 A30 4L185R/4** 6 TA25DU4** 21.6-30.830 32 T4L250 PR221-I In100 450 A145 A145 A30 4L185R/4** 6 TA25DU5** 27-38.537 39 T4L250 PR221-I In100 550 A145 A145 A30 TA75DU52** 36-5245 47 T4L250 PR221-I In100 650 A145 A145 A30 TA75DU52** 36 - 5255 57 T4L250 PR221-I In100 800 A145 A145 A40 TA75DU52** 36-5275 77 T4L250 PR221-I In160 1120 A145 A145 A50 TA75DU52 36 - 5290 93 T4L250 PR221-I In160 1280 A145 A145 A75 TA75DU63 45-63110 113 T4L250 PR221-I In160 1600 A145 A145 A75 TA75DU80 60-80132 134 T4L250 PR221-I In250 1875 A145 A145 A95 TA200DU110 80-110160 162 T4L250 PR221-I In250 2125 A145 A145 A110 TA200DU110 80-110200 203 T4L320 PR221-I In320 2720 A185 A185 A110 TA200DU135 100-135250 250 T5L400 PR221-I In400 3200 AF400 AF400 A145 E500DU500 150-500290 301 T5L400 PR221-I In400 4000 AF400 AF400 A145 E500DU500 150-500315 313 T5L630 PR221-I In630 4410 AF400 AF400 A185 E500DU500 150-500355 354 T5L630 PR221-I In630 5040 AF400 AF400 A210 E500DU500 150-500400 420 T5L630 PR221-I In630 5670 AF460 AF460 A210 E500DU500 150-500450 470 T5L630 PR221-I In630 6300 AF460 AF460 A260 E500DU500 150-500Comments:*size wire 4mm**connect TOL at line-delta supply side<strong>ABB</strong> | <strong>Electrical</strong> devices 399


RatedPower[kW]2 <strong>Protection</strong> of electrical equipment2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsTable 33: 400 V 35 kA DOL Normal <strong>and</strong> Heavy duty Type 2(Tmax XT/T with Ekip M/PR222MP – Contactor)Motor Moulded Case Circuit Breaker ContactorRatedCurrent[A]Type***Inverse timetripping current*[A]Allowed settingcurrent[A]7,5 15,5 XT2N160 Ekip M-LIU In25 10-25 150 A63 2511 22 XT2N160 Ekip M-LIU In25 10-25 225 A63 2515 29 XT2N160 Ekip M-LIU In63 25-63 378 A75 5018,5 35 XT2N160 Ekip M-LIU In63 25-63 378 A75 5022 41 XT2N160 Ekip M-LIU In63 25-63 441 A75 5030 55 XT4N250 Ekip M-LIU In100 40-100 600 A95 9537 66 XT4N250 Ekip M-LIU In100 40-100 700 A95 9545 80 XT4N250 Ekip M-LIU In100 40-100 800 A95 9555 97 XT4N250 Ekip M-LIU In160 64-160 960 A145 14575 132 XT4N250 Ekip M-LIU In160 64-160 1280 A145 14590 160 T4N250 PR222 MP In200 80-200 1600 A185 185110 195 T5N400 PR222 MP In320 128-320 1920 A210 210132 230 T5N400 PR222 MP In320 128-320 2240 A260 260160 280 T5N400 PR222 MP In320 128-320 2560 AF400** 320200 350 T5N400 PR222 MP In400 160-400 3200 AF400 400250 430 T6N800 PR222 MP In630 252-630 5040 AF460 460290 520 T6N800 PR222 MP In630 252-630 5670 AF580 580315 540 T6N800 PR222 MP In630 252-630 5670 AF580 580355 610 T6N800 PR222 MP In630 252-630 5670 AF750 630Comments:* For Heavy start, select the class 30 on the EKIP M or MP release** In event of normal start, choose AF300*** EKIP M-LIU also available in M-LRIU versionI 3[A]Type400 <strong>Electrical</strong> devices | <strong>ABB</strong>


RatedPower[kW]2 <strong>Protection</strong> of electrical equipment2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsTable 34: 400 V 50 kA DOL Normal <strong>and</strong> Heavy duty Type 2(Tmax XT/T with Ekip M/PR222MP – Contactor)Motor Moulded Case Circuit Breaker ContactorRatedCurrent[A]Type***Inverse timetripping current*[A]Allowed settingcurrent[A]7,5 15,5 XT2S160 Ekip M-LIU In25 10-25 150 A63 2511 22 XT2S160 Ekip M-LIU In25 10-25 225 A63 2515 29 XT2S160 Ekip M-LIU In63 25-63 378 A75 5018,5 35 XT2S160 Ekip M-LIU In63 25-63 378 A75 5022 41 XT2S160 Ekip M-LIU In63 25-63 441 A75 5030 55 XT4S250 Ekip M-LIU In100 40-100 600 A95 9537 66 XT4S250 Ekip M-LIU In100 40-100 700 A95 9545 80 XT4S250 Ekip M-LIU In100 40-100 800 A95 9555 97 XT4S250 Ekip M-LIU In160 64-160 960 A145 14575 132 XT4S250 Ekip M-LIU In160 64-160 1280 A145 14590 160 T4S250 PR222 MP In200 80-200 1600 A185 185110 195 T5S400 PR222 MP In320 128-320 1920 A210 210132 230 T5S400 PR222 MP In320 128-320 2240 A260 260160 280 T5S400 PR222 MP In320 128-320 2560 AF400** 320200 350 T5S400 PR222 MP In400 160-400 3200 AF400 400250 430 T6S800 PR222 MP In630 252-630 5040 AF460 460290 520 T6S800 PR222 MP In630 252-630 5670 AF580 580315 540 T6S800 PR222 MP In630 252-630 5670 AF580 580355 610 T6S800 PR222 MP In630 252-630 5670 AF750 630Comments:* For Heavy start, select the class 30 on the EKIP M or MP release** In event of normal start, choose AF300*** EKIP M-LIU also available in M-LRIU versionI 3[A]Type<strong>ABB</strong> | <strong>Electrical</strong> devices 401


RatedPower[kW]2 <strong>Protection</strong> of electrical equipment2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsTable 35: 440 V 50 kA DOL Normal <strong>and</strong> Heavy duty Type 2(Tmax XT/T with Ekip M/PR222MP – Contactor)Motor Moulded Case Circuit Breaker ContactorRatedCurrent[A]Type***Inverse timetripping current*[A]I 3[A]TypeAllowed settingcurrent[A]7,5 13,6 XT2S160 Ekip M-LIU In25 10-25 150 A63 2511 19,3 XT2S160 Ekip M-LIU In25 10-25 225 A63 2515 25,4 XT2S160 Ekip M-LIU In63 25-63 378 A75 6318,5 30,7 XT2S160 Ekip M-LIU In63 25-63 378 A75 6322 35,9 XT2S160 Ekip M-LIU In63 25-63 378 A75 6330 48,2 XT4S250 Ekip M-LIU In100 40-100 600 A95 9337 58 XT4S250 Ekip M-LIU In100 40-100 600 A95 9345 70 XT4S250 Ekip M-LIU In100 40-100 700 A95 9355 85 XT4S250 Ekip M-LIU In160 64-160 960 A145 14575 116 XT4S250 Ekip M-LIU In160 64-160 1120 A145 14590 140 T4H250 PR222 MP In200 80-200 1400 A185 185110 171 T5H400 PR222 MP In320 128-320 1920 A210 210132 202 T5H400 PR222 MP In320 128-320 2240 A260 240160 245 T5H400 PR222 MP In320 128-320 2560 AF400** 320200 307 T5H400 PR222 MP In400 160-400 3200 AF400 400250 377 T6H800 PR222 MP In630 252-630 4410 AF460 460290 448 T6H800 PR222 MP In630 252-630 5040 AF460 460315 473 T6H800 PR222 MP In630 252-630 5040 AF580 580355 535 T6H800 PR222 MP In630 252-630 5670 AF580 580Comments:* For Heavy start, select the class 30 on the EKIP M or MP release** In event of normal start, choose AF300*** EKIP M-LIU also available in M-LRIU versionTable 36: 690 V 25 kA DOL Normal <strong>and</strong> Heavy duty Type 2(Tmax T with Ekip M – Contactor)RatedPower[kW]Motor Moulded Case Circuit Breaker ContactorRatedCurrent[A]TypeInverse timetripping current*[A]Allowed settingcurrent[A]11 12,8 XT2V160 EKIP M-LIU In25 10-25 150 A63 2515 17 XT2V160 EKIP M-LIU In25 10-25 175 A63 2518,5 21 XT2V160 EKIP M-LIU In25 10-25 225 A75 2522 24 XT2V160 EKIP M-LIU In63 25-63 250 A75 6330 32 XT2V160 EKIP M-LIU In63 25-63 378 A95 6337 39 XT2V250 EKIP M-LIU In63 25-63 378 A95 6345 47 XT2V250 EKIP M-LIU In63 25-63 504 A145 6355 57 XT4V250 EKIP M-LIU In63 25-63 567 A145 6375 77 XT4V250 EKIP M-LIU In100 40-100 800 A145 10090 93 XT4V250 EKIP M-LIU In160 64-160 960 A145 120110 113 XT4V250 EKIP M-LIU In160 64-160 1120 A145 120132 134 XT4V250 EKIP M-LIU In160 64-160 1440 A185 160Comments:* For Heavy start, select the class 30 on the MP releaseI 3[A]Type402 <strong>Electrical</strong> devices | <strong>ABB</strong>


RatedPower[kW]2 <strong>Protection</strong> of electrical equipment2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsTable 37: 500 V 50 kA DOL Normal <strong>and</strong> Heavy duty Type 2(Tmax XT/T with Ekip M/PR222MP – Contactor)Motor Moulded Case Circuit Breaker ContactorRatedCurrent[A]Type***Inverse timetripping current*[A]Table 38: 690 V 50 kA DOL Normal <strong>and</strong> Heavy duty Type 2(Tmax T with PR222MP – Contactor)Allowed settingcurrent[A]7,5 12,4 XT2H160 Ekip M-LIU In25 10-25 150 A63 2511 17,6 XT2H160 Ekip M-LIU In25 10-25 175 A63 2515 23 XT2H160 Ekip M-LIU In25 10-25 250 A75 2518,5 28 XT2H160 Ekip M-LIU In63 25-63 378 A75 6322 33 XT2H160 Ekip M-LIU In63 25-63 378 A75 6330 44 XT4H250 Ekip M-LIU In63 25-63 441 A95 6337 53 XT4H250 Ekip M-LIU In63 25-63 567 A95 6345 64 XT4H250 Ekip M-LIU In100 40-100 630 A145 10055 78 XT4H250 Ekip M-LIU In100 40-100 800 A145 10075 106 XT4H250 Ekip M-LIU In160 64-160 1120 A145 14590 128 XT4H250 Ekip M-LIU In160 64-160 1280 A145 145110 156 T4H250 PR222 MP In200 80-200 1600 A185 170132 184 T5H400 PR222 MP In320 128-320 1920 A210 210160 224 T5H400 PR222 MP In320 128-320 2240 A260 240200 280 T5H400 PR222 MP In400 160-400 2800 AF400** 400250 344 T5H400 PR222 MP In400 160-400 3200 AF400 400290 394 T6H800 PR222 MP In630 252-630 5040 AF460 460315 432 T6H800 PR222 MP In630 252-630 5040 AF460 460355 488 T6H800 PR222 MP In630 252-630 5670 AF580 580Comments:* For Heavy start, select the class 30 on the EKIP M or MP release** In event of normal start, choose AF300*** EKIP M-LIU also available in M-LRIU versionRatedPower[kW]I 3[A]TypeMotor Moulded Case Circuit Breaker ContactorRatedCurrent[A]TypeInverse timetripping current*[A]I 3[A]TypeAllowed settingcurrent[A]45 47 T4L250 PR222MP In 100 40-100 600 A145 10055 57 T4L250 PR222MP In 100 40-100 600 A145 10075 77 T4L250 PR222MP In 100 40-100 800 A145 10090 93 T4L250 PR222MP In 160 64-160 960 A145 120110 113 T4L250 PR222MP In 160 64-160 1120 A145 120132 134 T4L250 PR222MP In 160 64-160 1440 A185 160160 162 T4L250 PR222MP In 200 80-200 1600 A185 170200 203 T5L400 PR222MP In320 128-320 1920 A210 210250 250 T5L400 PR222MP In320 128-320 2240 AF300 280290 301 T5L400 PR222MP In400 160-400 2800 AF400 350315 313 T5L400 PR222MP In400 160-400 3200 AF400 350Comments:* For Heavy start, select the class 30 on the MP release<strong>ABB</strong> | <strong>Electrical</strong> devices 403


2 <strong>Protection</strong> of electrical equipment2.3 <strong>Protection</strong> <strong>and</strong> switching of motorsExample:For a DOL Normal starting Type 2, of a three phase asynchronous squirrel-cagemotor with the following data:rated voltage U r= 400 Vshort-circuit current I k= 50 kArated motor power P e= 22 kWfrom Table 4, on the relevant row, the following information can be found:• I r(rated current): 41 A;• short-circuit protection device: circuit-breaker XT2S160 MA52;• magnetic trip threshold: I 3= 547 A;• contactor: A50;• thermal release TA75 DU52, setting range 36÷52 AFor a Y/∆ Normal starting Type 2, of a three phase asynchronous squirrel-cagemotor with the following data:rated voltage U r= 400 Vshort-circuit current I k= 50 kArated motor power P e= 200 kWfrom Table 27, on the relevant row, the following information can be found:• I r(rated current): 350 A;• short-circuit protection device: circuit-breaker T5S630 PR221-I In630;• magnetic trip threshold: I 3= 4410 A;• line contactor: A210;• delta contactor: A210;• star contactor: A185;• thermal release E320DU320, setting range 100÷320 A (to be set at ).For a DOL heavy-duty starting Type 2 with Ekip protection of a three phaseasynchronous squirrel-cage motor with the following data:rated voltage U r= 400 Vshort-circuit current Ik = 50 kArated motor power Pe = 55 kWfrom Table 34, on the relevant row, the following information can be found:• Ir (rated current): 97 A;• short-circuit protection device: circuit breaker XT4S250 Ekip M LIU(or Ekip M LRIU)* In160;• magnetic trip threshold: I 3= 960 A;• contactor: A145.* for heavy-duty start set the electronic release tripping class to class 30404 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.4 <strong>Protection</strong> <strong>and</strong> switching oftransformers2 <strong>Protection</strong> of electrical equipmentGeneral aspectsTransformers are used to achieve a change in the supply voltage, for bothmedium <strong>and</strong> low voltage supplies.The choice of the protection devices must take into account transient insertionphenomena, during which the current may reach values higher than the ratedfull load current; the phenomenon decays in a few seconds.The curve which represents these transient phenomena in the time-currentdiagram, termed “inrush current I0”, depends on the size of the transformer<strong>and</strong> can be evaluated with the following formula (the short-circuit power of thenetwork is assumed to be equal to infinity)where:K ratio between the maximum peak inrush current value ( I 0) <strong>and</strong> the ratedcurrent of the transformer (I 1r): (K= I 0/ I 1r);τ time constant of the inrush current;I 1rrated current of the primary;t time.The table below shows the indicative values for t <strong>and</strong> K parameters referred torated power Sr for oil transformers.Sr [kVA] 50 100 160 250 400 630 1000 1600 2000K = I /I o 1r15 14 12 12 12 11 10 9 8τ [s] 0.10 0.15 0.20 0.22 0.25 0.30 0.35 0.40 0.45Further to the above consideration, the follwing diagram shows the inrushcurrent curve for a 20/0.4kV of 400kVA transformer. This transformer has aninrush current during the very first moments equal to about 8 times the ratedcurrent; this transient phenomenon stops after a few tenths of a second.[s]10 -1 11SDC010022F000110 -2 10 -3 10 -2 10 -1 1[kA]<strong>ABB</strong> | <strong>Electrical</strong> devices 405


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentThe transformer protection devices must also guarantee that the transformercannot operate above the point of maximum thermal overload under shortcircuitconditions; this point is defined on the time-current diagram by the valueof short-circuit current which can pass through the transformer <strong>and</strong> by a timeequal to 2 s, as stated by St<strong>and</strong>ard IEC 60076-5. The short-circuit current (I k)flowing for a fault with low impedance at the LV terminals of the transformer iscalculated by using the following formula:where:• U ris the rated voltage of the transformer [V];• Z Netis the short-circuit impedance of the network [Ω];• Z tis the short-circuit impedance of the transformer; from the rated power ofthe transformer (S r[VA]) <strong>and</strong> the percentage short-circuit voltage (u k%) it isequal to:Considering the upstream short-circuit power of the network to be infinite(Z Net=0), formula (1) becomes:The diagram below shows the inrush current curve for a 20/0.4 kV of 400 kVAtransformer (u k% = 4 %) <strong>and</strong> the point referred to the thermal ability to withst<strong>and</strong>the short-circuit current (Ik; 2 sec.).1s10 -1 s10 -2 s1kA10kA1SDC010023F0001406 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentIn summary: for the correct protection of the transformer <strong>and</strong> to avoid unwantedtrips, the trip curve of the protection device must be above the inrush currentcurve <strong>and</strong> below the thermal overload point under short circuit conditions.Choice of the circuit-breakers on the primary of a LV/LV transformerThese types of transformer are mainly used to supply <strong>control</strong> <strong>and</strong> switch auxiliarycircuits, since they are often supplied at lower voltages in comparison withthose for power distribution; another application example can be representedby the need of changing the neutral system according to the <strong>installation</strong>requirements.As regards choice <strong>and</strong> settings of the circuit-breaker on the supply side ofthe primary, it is necessary to take into consideration both the “inrush current”phenomenon as well as the transformer maximum short-time thermal loadcapability, as described in the previous pages.The following figure shows the possible positioning of the trip curve of a circuitbreakeron the primary of a 250kVA transformer at 690/400 with u k=4%.410 s10 3 s10 2 sT4N250 PR221 In=250 A10 1 s1s250 kVA Trafo10 -1 s10 -2 s10 -1 kA 1kA 10kA1SDC010024F0001The following pages include some tables reporting - with reference to therated voltage of the primary winding - the circuit-breaker suitable for the application.As regards the circuit-breaker version, it is necessary to use one apparatus withIcu value higher than the short-circuit current at the circuit-breaker <strong>installation</strong>point.It is necessary to set properly the suggested circuit-breaker in order to obtaintransformer protection as in the figure of the example of above, by paying particularattention to the indications reported in the previous pages.<strong>ABB</strong> | <strong>Electrical</strong> devices 407


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentV1n=400S r[kVA]TransformerTrafo I r[A]Circuit-breaker withthermomagnetic releaseType<strong>ABB</strong> SACECircuit-breakerIn[A]Circuit-breaker withelectronic release1 x 63 91 XT1B-C-N-S-H 125 XT2N-S-H-L-V 1601 x 100 144 XT3N-S 200 XT4N-S-H-L-V 2501 x 125 180 XT3N-S 250 XT4N-S-H-L-V 2501 x 160 231 XT4N-S-H-L-V 250 XT4N-S-H-L-V 2501 x 200 289 T5N-S-H-L-V 320 T5N-S-H-L-V 4001 x 250 361 T5N-S-H-L-V 400 T5N-S-H-L-V 4001 x 315 455 T5N-S-H-L-V 500 T5N-S-H-L -V 6301 x 400 577 T6N-S-H-L 630 T6N-S-H-L -V 6301 x 500 722 T6N-S-H-L 800 T6N-S-H-L 8001 x 630 909 - - T7S-H-L-V/ X1B-N 10001 x 800 1155 - - T7S-H-L-V/ X1B-N 12501 x 1000 1443 - - T7S-H-L / X1B-N 16001 x 1250 1804 - - E2B-N-S 20001 x 1600 2309 - - E3N-S-H-V 25001 x 2000 2887 - - E3N-S-H-V 3200TypeIn[A]V1n=440S r[kVA]TransformerTrafo I r[A]Circuit-breaker withthermomagnetic releaseType<strong>ABB</strong> SACECircuit-breakerIn[A]Circuit-breaker withelectronic release1 x 63 83 XT1B-C-N-S-H 125 XT2N-S-H-L-V 1601 x 100 131 XT3N-S 200 XT4N-S-H-L-V 2501 x 125 164 XT3N-S 200 XT4N-S-H-L-V 2501 x 160 210 XT4N-S-H-L-V 250 XT4N-S-H-L-V 2501 x 200 262 T5N-S-H-L-V 320 T5N-S-H-L -V 4001 x 250 328 T5N-S-H-L-V 400 T5N-S-H-L -V 4001 x 315 413 T5N-S-H-L-V 500 T5N-S-H-L -V 6301 x 400 526 T6N-S-H-L 630 T6N-S-H-L 6301 x 500 656 T6N-S-H-L 800 T6N-S-H-L 8001 x 630 827 - - T7S-H-L-V-X1B-N 10001 x 800 1050 - - T7S-H-L-V/ X1B-N 12501 x 1000 1312 - - T7S-H-L / X1B-N 16001 x 1250 1640 - - E2B-N-S 20001 x 1600 2099 - - E3N-S-H-V 25001 x 2000 2624 - - E3N-S-H-V 3200TypeIn[A]408 <strong>Electrical</strong> devices | <strong>ABB</strong>


Vn=690S r[kVA]TransformerTrafo I r[A]2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentCircuit-breaker withthermomagnetic releaseType<strong>ABB</strong> SACECircuit-breakerIn[A]Circuit-breaker withelectronic release1 x 63 53 XT1B-C-N-S-H 80 XT2N-S-H-L-V 801 x 100 84 XT1B-C-N-S-H 125 XT2N-S-H-L-V 1601 x 125 105 XT1B-C-N-S-H 125 XT2N-S-H-L-V 1601 x 160 134 XT1B-C-N-S-H 160 XT2N-S-H-L-V 1601 x 200 168 XT3N-S 200 XT4N-S-H-L-V 2501 x 250 209 XT4N-S-H-L-V 250 XT4N-S-H-L-V 2501 x 315 264 T5N-S-H-L-V 320 T5N-S-H-L-V 4001 x 400 335 T5N-S-H-L-V 400 T5N-S-H-L-V 4001 x 500 419 T5N-S-H-L-V 500 T5N-S-H-L-V 6301 x 630 528 T6N-S-H-L 630 T6N-S-H-L 8001 x 800 670 T6N-S-H-L 800 T6N-S-H-L 8001 x 1000 838 - - T7S-H-L-V/ X1B-N 10001 x 1250 1047 - - T7S-H-L-V/ X1B-N 12501 x 1600 1340 - - T7S-H-L / X1B-N 16001 x 2000 1676 - - E2B-N-S 2000TypeIn[A]Criteria for the selection of protection devicesFor the protection on the LV side of MV/LV transformers, the selection of acircuit-breaker shall take into account:• the rated current on LV side of the protected transformer (this value is thereference value for the rated current of the circuit-breaker <strong>and</strong> the setting ofthe protections);• the maximum short-circuit current at the point of <strong>installation</strong> (this value determinesthe minimum breaking capacity (I cu/I cs) of the protection device).MV/LV unit with single transformerThe rated current on the LV side of the transformer (I r) is determined by thefollowing formula:⋅where:• S r• U r20is the rated power of the transformer [kVA];is the rated LV no-load voltage of the transformer [V].<strong>ABB</strong> | <strong>Electrical</strong> devices 409


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentThe full voltage three-phase short-circuit current (I k), at the LV terminals of thetransformer, can be expressed as (assuming that the short-circuit power ofthe network is infinite):⋅where:u k% is the short-circuit voltage of the transformer, in %.The protection circuit-breaker must have: (*)I n≥ I r;I cu(I cs) ≥ I k.If the short-circuit power of the upstream network is not infinite <strong>and</strong> cable orbusbar connections are present, it is possible to obtain a more precise value forI kby using formula (1), where Z Netis the sum of the impedance of the network<strong>and</strong> of the impedance of the connection.MV/LV substation with more than one transformer in parallelFor the calculation of the rated current of the transformer, the above applies(formula 4).The breaking capacity of each protection circuit-breaker on the LV side shallbe higher than the short-circuit current equivalent to the short-circuit current ofeach equal transformer multiplied by the number of them minus one.As can be seen from the diagram below, in the case of a fault downstream of atransformer circuit-breaker (circuit-breaker A), the short-circuit current that flowsthrough the circuit-breaker is equal to the contribution of a single transformer.In the case of a fault upstream of the same circuit-breaker, the short-circuitcurrent that flows is equal to the contribution of the other two transformersin parallel.(*)To carry out correct protection against overload it is advisable to use thermometric equipmentor other protection devices able to monitor temperature inside transformers.410 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentFor a correct dimensioning, a circuit-breaker with a breaking capacity higherthan twice the short-circuit current of one of the transformers must be chosen(assuming that all the transformers are equal <strong>and</strong> the loads are passive).The circuit-breakers positioned on the outgoing feeders (circuit-breakers B) shallhave a breaking capacity higher than the sum of the short-circuit currents ofthe three transformers, according to the hypothesis that the upstream networkshort-circuit power is 750 MVA <strong>and</strong> the loads are passive.I k1 I k2 I k3AI k2 + I k3I k = I k1 + I k2 + I k3B1SDC010025F0001<strong>ABB</strong> | <strong>Electrical</strong> devices 411


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentSelection of the circuit-breakerThe following tables show some possible choices of <strong>ABB</strong> SACE circuit-breakers,according to the characteristics of the transformer to be protected.TransformerS r u k Trafo I r Busbar I bTrafofeeder I k[kVA] [%] [A] [A] [kA]1 x 632 x 631 x 1002 x 1001 x 1252 x 1251 x 1602 x 1601 x 2002 x 2001 x 2502 x 2501 x 3152 x 3151 x 4002 x 4001 x 5002 x 5001 x 6302 x 6303 x 6301 x 8002 x 8003 x 8001 x 10002 x 10003 x 10001 x 12502 x 12503 x 1250444444444455515815825125131431440240250250262862879179110041004125512551581158115812008200820082510251025103138313831381583162515023146284028035021004628125579115811004200812552510158131634744200840166025251050207531313862769413Table 1: <strong>Protection</strong> <strong>and</strong> switching of 230 V transformers3.93.96.36.27.87.810.09.912.512.415.615.419.619.424.824.530.930.438.737.974.439.338.575.548.947.793.060.758.8114.1Circuit-breaker “A” (LV side)Release<strong>ABB</strong> SACEBusbar I ksizeCircuit-breakerminimumIn [A] setting [kA] 32 A 63 A 125 A 160 A 250 A 400 AXT1B160* 160 1 3.9 S200 XT1B160XT1B160* 160 1 7.9 S200 XT1B160 XT3N250T4N320 320 0.79 6.3 S200 XT1B160T4N320 320 0.79 12.5 S200 XT1B160 XT3N250 T5N400T5N400 400 0.79 7.8 S200 XT1B160 XT3N250T5N400 400 0.79 15.6 S200 XT1B160 XT3N250 T5N400T5N630 630 0.64 10.0 S200 XT1B160 XT3N250T5N630 630 0.64 19.9 S200 XT1B160 XT3N250 T5N400T5N630 630 0.8 12.5 S200 XT1B160 XT3N250 T5N400T5N630 630 0.8 24.8XT1B160XT3N250 T5N400T5N630 630 1 15.6 S200 XT1B160 XT3N250 T5N400T5N630 630 1 30.9XT1C160 XT3N250 T5N400T6N800 800 1 19.6XT1B160 XT3N250 T5N400T6N800 800 1 38.7XT1C160 XT3N250 T5N400T7S1250/X1B1250** 1250 0.81 24.8XT1B160 XT3N250 T5N400T7S1250/X1B1250** 1250 0.81 48.9XT1N160 XT3N250 T5N400T7S1600/X1B1600** 1600 0.79 30.9XT1C160 XT3N250 T5N400T7S1600/X1B1600** 1600 0.79 60.7XT1N160 XT3S250 T5N400T7S1600/X1B1600** 1600 1 38.7XT1C160 XT3N250 T5N400T7S1600/X1B1600** 1600 1 75.9XT1S160 XT3S250 T5S400T7S1600/E2S1600 1600 1 111.6XT2L160 XT4L250 T5L400E3N2500 2500 0.81 39.3XT1C160 XT3N250 T5N400E3N2500 2500 0.81 77.0XT1S160 XT3S250 T5S400E3H2500 2500 0.81 113.2XT2L160 XT4L250 T5L400E3N3200 3200 0.79 48.9XT1N160 XT3N250 T5N400E3N3200 3200 0.79 95.3XT1H160 XT4H250 T5H400E3H3200 3200 0.79 139.5XT2L160 XT4L250 T5L400E3N3200 3200 1 60.7XT1N160 XT3S250 T5N400E3N3200 3200 1 117.7XT2L160 XT4L250 T5L400E4V3200 3200 1 171.2XT2V160 XT4V250 T5L400* also Tmax series CBs equipped with electronic releases can be used for this application** Emax type E1 can be used for this application412 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentCircuit-breaker “B” (Feeder circuit-breaker)Feeder circuit-breaker type <strong>and</strong> rated current630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 AT5N630T5N630T5N630T5N630T5N630T5N630T5N630T5N630T5N630T5N630T5S630T5L630T5N630T5S630T5L630T5N630T5H630T5L630T5N630T5L630T5L630T6N800/X1B800T6N800/X1B800T6N800/X1B800T6N800/X1N800T6N800/X1B800T6N800/X1N800T6N800/X1B800T6S800/E2S800T6L800/E3V800T6N800/X1B800T6L800/E2S800T6L800/E3V800T6N800/X1N800T6H800/E3H800T6L800T6N800/X1N800T6L800/E3V800T6L800T7S1000/X1B1000T7S1000/X1N1000T7S1000/X1N1000T7S1000/X1B1000T7S1000/E2S1000T7L1000/E3V1250T7S1000/X1B1000T7S1000/E2S1000T7L1000/E3V1250T7S1000/X1N1000T7H1000/E3H1000T7L1000T7S1000/X1N1000T7L1000/E3V1250T7L1000T7S1250/X1B1250T7S1250/X1N1250T7S1250/X1N1250T7S1250/X1B1250T7S1250/E2S1250T7L1250/E3V1250T7S1250/X1B1250T7S1250/E2S1250T7L1250/E3V1250T7S1250/X1N1250T7H1250/E3H1250T7L1250T7S1250/X1N1250T7L1250/E3V1250T7L1250T7S1600/X1N1600T7S1600/X1N1600T7S1600/E2S1600T7L1600/E3V1600T7S1600/X1B1600T7S1600/E2S1600T7L1600/E3V1600T7S1600/X1N1600T7H1600/E3H1600T7L1600T7S1600/X1N1600T7L1600/E3V1600T7L1600E2N2000E2S2000E3V2000E2S2000E3V2000E2N2000E3H2000E4V3200E2N2000E3V2000E3H2500E3V2500E3H2500E3V2500E3H2500E4V3200E3N2500E3V2500E3V3200E3H3200E4V3200E3H3200E4V3200E3V3200E4V4000E4H4000E4V4000E4V40001SDC010035F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 413


TransformerS r u k Trafo I r Busbar I bTrafofeeder I k[kVA] [%] [A] [A] [kA]1 x 632 x 631 x 1002 x 1001 x 1252 x 1251 x 1602 x 1601 x 2002 x 2001 x 2502 x 2501 x 3152 x 3151 x 4002 x 4001 x 5002 x 5001 x 6302 x 6303 x 6301 x 8002 x 8003 x 8001 x 10002 x 10003 x 10001 x 12502 x 12503 x 12501 x 16002 x 16003 x 16001 x 20002 x 20003 x 20001 x 25001 x 312544444444445556.256.256.256.25919114414418018023123128928936136145545557757772272290990990911551155115514431443144318041804180423092309230928872887288736084510911821442881803602314622895783617224559105771154722144490918182727115523103465144328864329180436085412230946186927288757748661360845102.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentTable 2: <strong>Protection</strong> <strong>and</strong> switching of 400 V transformers2.22.23.63.64.54.45.75.77.27.18.98.811.211.114.21417.717.522.321.842.822.622.143.428.127.453.534.933.865.635.734.66744.342.681.954.867.7Circuit-breaker “A” (LV side)<strong>ABB</strong> SACEReleaseBusbar I ksize minimumCircuit-breaker In [A] setting [kA] 32 A 63 A 125 A 160 A 250 A 400 AXT1B*100 0.92 2.2 S200XT1B*100 0.92 4.4 S200 XT1B160XT1B*160 0.91 3.6 S200 XT1B160XT1B*160 0.91 7.2 S200 XT1B160XT3N250* 200 0.73 4.5 S200 XT1B160XT3N250* 200 0.73 8.8 S200 XT1B160XT3N250* 250 0.93 5.7 S200 XT1B160XT3N250* 250 0.93 11.4 S200M XT1B160 XT3N250T4N320320 0.91 7.2 S200 XT1B160 XT3N250T4N320320 0.91 14.2 S200M XT1B160 XT3N250 T5N400T5N400400 0.91 8.9 S200 XT1B160 XT3N250T5N400400 0.91 17.6XT1B160XT3N250 T5N400T5N630630 0.73 11.2 S200M XT1B160 XT3N250 T5N400T5N630630 0.73 22.2XT1C160XT3N250 T5N400T5N630630 0.92 14.2 S200M XT1B160 XT3N250 T5N400T5N630630 0.92 28XT1N160XT3N250 T5N400T6N800800 0.91 17.7XT1B160XT3N250 T5N400T6N800800 0.91 35.9XT1N160XT3N250 T5N400T7S1000/X1B1000** 1000 0.91 22.3XT1C160XT3N250 T5N400T7S1000/X1B1000** 1000 0.91 43.6XT1S160XT3S250 T5S400T7S1000/X1N1000** 1000 0.91 64.2XT1H160XT4H250 T5H400T7S1250/X1B1250** 1250 0.93 22.6XT1C160XT3N250 T5N400T7S1250/X1B1250** 1250 0.93 44.3XT1S160XT3S250 T5S400T7S1250/X1N1250** 1250 0.93 65XT1H160XT4H250 T5H400T7S1600/X1B1600** 1600 0.91 28.1XT1N160XT3N250 T5N400T7S1600/X1B1600** 1600 0.91 54.8XT1H160XT4H250 T5H400T7H1600/E2N1600 1600 0.91 80.2XT2L160XT4L250 T5L400E2B2000 2000 0.91 34.9XT1N160XT3N250 T5N400E2B2000 2000 0.91 67.7XT1H160XT4H250 T5H400E2S2000 2000 0.91 98.4XT2L160XT4L250 T5L400E3N2500 2500 0.93 35.7XT1N160XT3N250 T5N400E3N2500 2500 0.93 69.2XT1H160XT4H250 T5H400E3S2500 2500 0.93 100.6XT2L160XT4L250 T5L400E3N3200 3200 0.91 44.3XT1S160XT3S250 T5S400E3N3200 3200 0.91 85.1XT2L160XT4L250 T5L400E3H3200 3200 0.91 122.8XT2V160XT4V250 T5V400E4S4000 4000 0.91 54.8XT1H160XT4H250 T5H400E6H5000 5000 0.91 67.7XT1H160XT4H250 T5H400* also Tmax series CBs equipped with electronic releases can be used for this application** Emax type E1 can be used for this application414 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentCircuit-breaker “B” (Feeder circuit-breaker)Feeder circuit-breaker type <strong>and</strong> rated current630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 AT5N630T5N630T5N630T5N630T5N630T5S630T5H630T5N630T5S630T5H630T5N630T5H400T5L630T5N630T5H630T5L630T5N630T5H630T5L630T5S630T5L630T5V630T5H630T5H630T6N800/X1B800T6N800/X1B800T6S800/X1N800T6H800/X1N800T6N800/X1B800T6S800/X1N800T6H800/X1N800T6N800/X1B800T6H800/X1N800T6L800/E2S800T6N800/X1B800T6H800/E2S800T6L800/E3H800T6N800/X1B800T6H800/E2S800T7L800/E3V800T6S800/X1N800T6L800/E3H800T7V800/E3V800T6H800/X1N800T6H800/E2S800T7S1000/X1N1000T7H1000/X1N1000T7S1000/X1B1000T7S100/X1N1000T7H1000/X1N1000T7S100/X1B1000T7H1000/X1N1000T7L1000/E2S1000T7S1000/X1B1000T7H1000/E2S1000T7L1000/E3H1000T7S1000/X1B1000T7H1000/E2S1000T7L1000/E3V1250T7S1000/X1N1000T7L1000/E3H1000T7V1000/E3V1000T7H1000/X1N1000T7H1000/E2S1000T7S1250/X1N1250T7H1250/X1N1250T7S1250/X1N1250T7H1250/X1N1250T7S1250/X1B1250T7H1250/X1N1250T7L1250/E2S1250T7S1250/X1B1250T7H1250/E2S1250T7L1250/E3H1250T7S1250/X1B1250T7H1250/E2S1250T7L1250/E3V1250T7S1250/X1N1250T7L1250/E3H1250T7V1250/E3V1250T7H1250/X1N1250T7H1250/E2S1250T7H1600/X1N1600T7S1600/X1N1600T7H1600/X1N1600T7H1600/X1N1600T7L1600/E2S1600T7S1600/X1B1600T7H1600/E2S1600T7L1600/E3H1600T7S1600/X1B1600T7H1600/E2S1600T7L1600/E3V1600T7S1600/X1N1600T7L1600/E3H1600E3V1600T7H1600/X1N1600T7H1600/E2S1600E2N2000 E3N2500E2N2000E2S2000E2S2000E3H2000E2S2000E3V2000E2N2000E3H2000E3V2000E2N2000E2S2000E3H2500 E3H3200E3S2500E3H2500E3S2500E3V2500E3H2500E3V2500E3N2500E3S2500E3S3200E3H3200E3S3200E3V3200E3H3200E3V3200E3N3200E3S3200E4H4000E4S4000E4V4000E4H4000E4V4000E4S40001SDC010036F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 415


TransformerS r u k Trafo I r Busbar I bTrafofeeder I k[kVA] [%] [A] [A] [kA]1 x 632 x 631 x 1002 x 1001 x 1252 x 1251 x 1602 x 1601 x 2002 x 2001 x 2502 x 2501 x 3152 x 3151 x 4002 x 4001 x 5002 x 5001 x 6302 x 6303 x 6301 x 8002 x 8003 x 8001 x 10002 x 10003 x 10001 x 12502 x 12503 x 12501 x 16002 x 16003 x 16001 x 20002 x 20003 x 20001 x 25001 x 312544444444445556.256.256.256.25838313113116416421021026226232832841341352552565665682782782710501050105013121312131216401640164020992099209926242624262432804100831651312621643282104202625253286564138275251050656131282716532480105020993149131226243936164032804921209941996298262452497873328041002.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentTable 3: <strong>Protection</strong> <strong>and</strong> switching of 440 V transformers2.12.13.33.34.14.15.25.26.56.58.18.110.210.112.912.816.115.920.219.838.920.620.139.525.624.948.631.730.859.632.531.460.940.338.774.449.861.5Circuit-breaker “A” (LV side)Release<strong>ABB</strong> SACEBusbar IsizekminimumCircuit-breaker In [A] setting [kA] 32 A 63 A 125 A 160 A 250 A 400 AXT1B160* 100 0.83 2.1 S200XT1B160* 100 0.83 4.1 S200 XT1B160XT1B160* 160 0.82 3.3 S200XT1B160* 160 0.82 6.5XT1B160XT3N250* 200 0.82 4.1 S200 XT1B160XT3N250* 200 0.82 8.1XT1B160XT3N250XT3N250* 250 0.84 5.2 S200 XT1B160XT3N250* 250 0.84 10.4XT1B160 XT3N250T4N320320 0.82 6.5XT1B160T4N320320 0.82 12.9XT1B160 XT3N250 T5N400T5N400400 0.82 8.1XT1B160 XT3N250T5N400400 0.82 16.1XT1C160 XT3N250 T5N400T5N630630 0.66 10.2XT1B160 XT3N250T5N630630 0.66 20.2XT1C160 XT3N250 T5N400T5N630630 0.83 12.9XT1B160 XT3N250 T5N400T5N630630 0.83 25.6XT1N160 XT3S250 T5N400T6N800800 0.82 16.1XT1C160 XT3N250 T5N400T6N800800 0.82 31.7XT1N160 XT3S250 T5S400T7S1000/X1B1000** 1000 0.83 20.2XT1C160 XT3N250 T5N400T7S1000/X1B1000** 1000 0.83 39.7XT1S160 XT3S250 T5S400T7S1000/X1B1000** 1000 0.83 58.3XT1H160 XT4H250 T5H400T7S1250/X1B1250** 1250 0.84 20.6XT1C160 XT3N250 T5N400T7S1250/X1B1250** 1250 0.84 40.3XT1S160 XT4S250 T5H400T7S1250/X1B1250** 1250 0.84 59.2XT1H160 XT4H250 T5H400T7S1600/X1B1600** 1600 0.82 25.6XT1N160 XT3S250 T5N400T7S1600/X1B1600** 1600 0.82 49.8XT1S160 XT4S250 T5H400T7H1600/X1N1600** 1600 0.82 72.9XT2L160XT4L250 T5L400E2B2000 2000 0.82 31.7XT1N160 XT3S250 T5S400E2B2000 2000 0.82 61.5XT1H160 XT4H250 T5H400E2N2000 2000 0.82 89.5XT2L160XT4L250 T5L400E3N2500 2500 0.84 32.5XT1N160 XT3S250 T5S400E3N2500 2500 0.84 62.9XT1H160 XT4H250 T5H400E3N2500 2500 0.84 91.4XT2L160XT4L250 T5L400E3N3200 3200 0.82 40.3XT1S160 XT4S250 T5H400E3N3200 3200 0.82 77.4XT2L160XT4L250 T5L400E3S3200 3200 0.82 111.7XT2V160 XT4V250 T5V400E4S4000 4000 0.82 49.8XT1S160 XT4S250 T5H400E6H5000 5000 0.82 61.5XT1H160 XT4H250 T5H400* also Tmax series CBs equipped with electronic releases can be used for this application** Emax type E1 can be used for this application416 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentCircuit-breaker “B” (Feeder circuit-breaker)Feeder circuit-breaker type <strong>and</strong> rated current630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 AT5N630T5N630T5S630T5N630T5S630T5H630T5N630T5H630T5H630T5N630T5H630T5L630T5S630T5H630T5L630T5S630T5H630T5L630T5H630T5L630T5V630T5H630T5H630T6S800/X1B800T6S800/X1B800T6L800/X1N800T6N800/X1B800T6S800/X1B800T6L800/X1N800T6N800/X1B800T6H800/E1N800T6L800/E2S800T6S800/X1B800T6L800/X1N800T7L800/E3H800T6S800/X1B800T6L800/X1N800T7L800/E3H800T6S800/X1B800T6L800/E2S800T7V800/E3V800T6H800/X1N800T6L800/X1N800T7S1000/X1B1000T7H1000/X1N1000T7S1000/X1B1000T7H1000/X1N1000T7S1000/X1N1000T7L1000/E2S1000T7S1000/X1B1000T7H1000/X1N1000T7L1000/E3H1000T7S1000/X1B1000T7H1000/X1N1000T7L1000/E3H1000T7S1000/X1B1000T7L1000/E2S1000T7V1000/E3V1000T7S1000/X1N1000T7H1000/X1N1000T7S1250/X1B1250T7H1250/X1N1250T7S1250/X1B1250T7H1250/X1N1250T7S1250/X1N1250T7L1250/E2S1250T7S1250/X1B1250T7H1250/XN1250T7L1250/E3H1250T7S1250/X1B1250T7H1250/X1N1250T7L1250/E3H1250T7S1250/X1B1250T7L1250/E2S1250T7V1250/E3V1250T7S1250/X1N1250T7H1250/X1N1250T7H1600/X1N1600T7S1600/X1B1600T7H1600/X1N1600T7S1600/X1N1600T7L1600/E2S1600T7H1600/X1N1600T7L1600/E3H1600T7S1600/X1B1600T7H1600/X1N1600T7L1600/E3H1600T7S1600/X1B1600T7L1600/E2S1600E3V1600T7S1600/X1N1600T7H1600/X1N1600E2N2000E2N2000 E3N2500 E3N3200 E4S4000E2N2000E3S2000E2N2000 E3N2500E3H2000 E3H2500E2N2000E3H2000E2B2000E3H2000E3V2000E2N2000E2N2000E3S2500E3N2500E3H2500E3H2500E3V2500E3N2500E3N2500E3S3200E3H3200 E4H4000E3N3200E3H3200E3H3200E3V3200E3N3200E4H4000E4H4000E4V40001SDC010037F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 417


TransformerS r u k Trafo I r Busbar I bTrafofeeder I k[kVA] [%] [A] [A] [kA]1 x 632 x 631 x 1002 x 1001 x 1252 x 1251 x 1602 x 1601 x 2002 x 2001 x 2502 x 2501 x 3152 x 3151 x 4002 x 4001 x 5002 x 5001 x 6302 x 6303 x 6301 x 8002 x 8003 x 8001 x 10002 x 10003 x 10001 x 12502 x 12503 x 12501 x 16002 x 16003 x 16001 x 20002 x 20003 x 20001 x 25001 x 312544444444445556.256.256.256.2553538484105105134134167167209209264264335335418418527527527669669669837837837104610461046133913391339167316731673209226155310584167105209134268167335209418264527335669418837527105415816691339200883716732510104620923138133926784016167333475020209226152.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentTable 4: <strong>Protection</strong> <strong>and</strong> switching of 690 V transformers1.31.32.12.12.62.63.33.34.24.15.25.16.56.58.38.210.310.112.912.624.813.112.825.216.315.931.020.219.638.020.720.138.925.724.747.531.839.2Circuit-breaker “A” (LV side)Release<strong>ABB</strong> SACEBusbar IsizekCircuit-breakerminimumIn [A] setting [kA] 32 A 63 A 125 A 160 A 250 A 400 AXT1B*63 0.84 1.3 XT1B160XT1B*63 0.84 2.6 XT1B160XT1B* 100 0.84 2.1 XT1B160XT1B* 100 0.84 4.2XT1N160XT1B* 125 0.84 2.6 XT1B160XT1B* 125 0.84 5.2XT1N160XT1C* 160 0.84 3.3 XT1C160XT1C* 160 0.84 6.6XT1S160XT3N250* 200 0.84 4.2XT1N160XT3N250* 200 0.84 8.3XT1H160XT4N250XT3S250* 250 0.84 5.2XT1N160XT3S250* 250 0.84 10.3XT2S160XT4S250T4N320 320 0.82 6.5XT1S160T4N320 320 0.82 12.9XT2H160XT4H250 T5N400T5N400 400 0.84 8.3XT1H160XT4N250T5N400 400 0.84 16.3XT2L160XT4L250 T5N400T5N630 630 0.66 10.3XT2S160XT4S250T5N630 630 0.66 20.2XT4V250XT4V250 T5S400T5N630 630 0.84 12.9XT2H160XT4H250 T5N400T5N630 630 0.84 25.3T4H250***T4H250*** T5H400T5S630 630 0.84 37.2T4H250***T4H250*** T5H400T6N800 800 0.84 13.1XT2H160XT4H250 T5N400T6N800 800 0.84 25.7T4H250***T4H250*** T5H400T6L800 800 0.84 37.7T4H250***T4H250*** T5H400T7S1000/X1B1000** 1000 0.84 16.3XT2L160XT4L250 T5N400T7S1000/X1B1000** 1000 0.84 31.8T4H250***T4H250*** T5H400T7H1000/X1B1000** 1000 0.84 46.5T4L250***T4L250*** T5L400T7S1250/X1B1250** 1250 0.84 20.2XT4V250XT4V250 T5S400T7S1250/X1B1250** 1250 0.84 39.2T4H250***T4H250*** T5H400T7H1250/X1B1250** 1250 0.84 57.1T4L250***T4L250*** T5L400T7S1600/X1B1600** 1600 0.84 20.7XT4V250XT4V250 T5S400T7S1600/X1B1600** 1600 0.84 40.1T4L250***T4L250*** T5L400T7H1600/X1B1600** 1600 0.84 58.3T4L250***T4L250*** T5L400E2B2000 2000 0.84 25.7T4H250***T4H250*** T5H400E2B2000 2000 0.84 49.3T4L250***T4L250*** T5L400E2N2000 2000 0.84 71.2T4V250***T4V250*** T5V400E3N2500 2500 0.84 31.8T4H250***T4H250*** T5H400E3N3200 3200 0.82 39.2T4H250***T4H250*** T5H400* also Tmax series CBs equipped with electronic releases can be used for this application** Emax type E1 can be used for this application*** For XT4V with Icu = 90kA at 690V, please ask <strong>ABB</strong> SACE418 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentCircuit-breaker “B” (Feeder circuit-breaker)Feeder circuit-breaker type <strong>and</strong> rated current630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 AT5S630T5H630T5H630T7H800/X1B800T7H1000/X1B1000T7H1250/X1B1250T5H630T5H630T5N630T5H630T5L630T5S630T5H630T5L630T5S630T5L630T5L630T5H630T5L630T5V630T5H630T5H630T6L800/X1B800T7H800/X1N800T7H800/X1B800T7L800/X1N800T6S800/X1B800T7H800/X1B800T7V800/E2S800T6S800/X1B800T7H800/X1B800T7V800/E2S800T6L800/X1N800T7L800/X1N800T7H800/X1B800T7H800/X1B800E3S1000T7H1000/X1N1000T7H1000/X1B1000T7L1000/X1N1000T7H1000/X1B1000T7V1000/E2S1000T7S1000/X1B1000T7H1000/X1B1000T7V1000/X1B1000T7S1000/E2S1000T7L1000/X1N1000T7H1000/X1B1000T7H1000/X1B1000T7H1250/X1N1250T7H1250/X1B1250T7L1250/X1N1250T7H1250/X1B1250T7V1250/ES21250T7H1250/X1B1250T7V1250/ES21250T7S1250/X1N1250T7L1250/X1N1250E3S1250T7H1250/X1B1250T7H1250/X1B1250T7H1600/X1N1600T7L1600/X1N1600T7H1600/X1N1600E2S1600T7H1600/X1B1600E2S1600T7L1600/X1N1600E3S1600T7H1600/X1B1600T7H1600/X1B1600E2N2000E2S2000E2B2000E2S2000E2N2000E3S2000E2B2000E3N2500 E3N3200E3N2500E3S2500E3S3200 E4S40001SDC010038F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 419


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentNOTEThe tables refer to the previously specified conditions; the information for theselection of circuit-breakers is supplied only with regard to the current in use <strong>and</strong>the prospective short-circuit current. For a correct selection, other factors suchas selectivity, back-up protection, the decision to use limiting circuit- breakersetc. must also be considered. Therefore, it is essential that the design engineerscarry out precise checks.It must also be noted that the short-circuit currents given are determined usingthe hypothesis of 750 MVA power upstream of the transformers, disregardingthe impedances of the busbars or the connections to the circuit-breakers.Example:Supposing the need to size breakers A1/A2/A3, on the LV side of the threetransformers of 630 kVA 20/0.4 kV with u k% equal to 4% <strong>and</strong> outgoing feedercircuit-breakers B1/B2/B3 of 63-400-800 A:A1 A2 A3B1 B2 B363 A 400 A 800 A1SDC010026F0001420 <strong>Electrical</strong> devices | <strong>ABB</strong>


2.4 <strong>Protection</strong> <strong>and</strong> switching of transformers2 <strong>Protection</strong> of electrical equipmentFrom Table 2, corresponding to the row relevant to 3x630 kVA transformers,it can be read that:Level A circuit-breakers (LV side of transformer)• trafo I r(909 A) is the current that flows through the transformer circuitbreakers;• busbar I b(2727 A) is the maximum current that the transformers cansupply;• trafo feeder I k(42.8 kA) is the value of the short-circuit current to consider for thechoice of the breaking capacity of each of the transformer circuit-breakers;• T7S1000 or X1N1000 is the size of the transformer circuit-breaker;• In (1000 A) is the rated current of the transformer circuit-breaker (electronicrelease chosen by the user);• the minimum value 0.91 indicate the minimum settings of the L function ofthe electronic releases for CBs T7S1000 <strong>and</strong> X1N1000.Level B circuit-breakers (outgoing feeder)• busbar I k(64.2 kA) is the short-circuit current due to the contribution of allthree transformers;• corresponding to 63 A, read circuit-breaker B1 Tmax XT1H160;• corresponding to 400 A, read circuit-breaker B2 Tmax T5H400;• corresponding to 800 A, read circuit-breaker B3 Tmax T6H800 orEmax X1N800.The choice made does not take into account discrimination/back-uprequirements. Refer to the relevant chapters for selections appropriate to thevarious cases.<strong>ABB</strong> | <strong>Electrical</strong> devices 421


3 Power factor correction3.1 General aspectsUIRPISIQQIn alternating current circuits, the current absorbed by the user can be representedby two components:- the active component I R, in phase with the supply voltage, is directly correlatedto the output (<strong>and</strong> therefore to the part of electrical energy transformedinto energy of a different type, usually electrical with different characteristics,mechanical, light <strong>and</strong>/or thermal);- the reactive component I Q, in quadrature to the voltage, is used to produce theflow necessary for the conversion of powers through the electric or magneticfield. Without this, there could be no flow of power, such as in the core of atransformer or in the air gap of a motor.In the most common case, in the presence of ohmic-inductive type loads, thetotal current (I) lags in comparison with the active component I R.In an electrical <strong>installation</strong>, it is necessary to generate <strong>and</strong> transmit, other than theactive power P, a certain reactive power Q, which is essential for the conversionof electrical energy, but not available to the user. The complex of the powergenerated <strong>and</strong> transmitted constitutes the apparent power S.Power factor (cosϕ) is defined as the ratio between the active component I R<strong>and</strong> the total value of the current l; ϕ is the phase shifting between the voltageU <strong>and</strong> the current l.It results:ISThe reactive dem<strong>and</strong> factor (tanϕ) is the relationship between the reactive power<strong>and</strong> the active power:422 <strong>Electrical</strong> devices | <strong>ABB</strong>


3 Power factor correction3.1 General aspectsTable 1 shows some typical power factors:Table 1: Typical power factorLoad cosϕ tanϕpower factor reactive dem<strong>and</strong> factorTransformers (no load condition) 0.1÷0.15 9.9÷6.6Motor (full load) 0.7÷0.85 1.0÷0.62Motor (no load) 0.15 6.6Metal working apparatuses:- Arc welding 0.35÷0.6 2.7÷1.3- Arc welding compensated 0.7÷0.8 1.0÷0.75- Resistance welding: 0.4÷0.6 2.3÷1.3- Arc melting furnace 0.75÷0.9 0.9÷0.5Fluorescent lamps- compensated 0.9 0.5- uncompensated 0.4÷0.6 2.3÷1.3Mercury vapour lamps 0.5 1.7Sodium vapour lamp 0.65÷0.75 1.2÷0.9AC DC converters 0.6÷0.95 1.3÷0.3DC drives 0.4÷0.75 2.3÷0.9AC drives 0.95÷0.97 0.33÷0.25Resistive load 1 0The power factor correction is the action increasing the power factor in a specificsection of the <strong>installation</strong> by locally supplying the necessary reactive power,so as to reduce the current value to the equivalent of the power required, <strong>and</strong>therefore the total power absorbed from the upstream side. Thus, the supplylines, the generator <strong>and</strong> the transformers can be sized for a lower apparentpower value required by the load.In detail, as shown by Figure 1 <strong>and</strong> Figure 2, increasing the power factor ofthe load:- decreases the relative voltage drop u rpper unit of active power transmitted;- increases the transmittable active power <strong>and</strong> decreases the losses, the otherdimensioning parameters remaining equal.<strong>ABB</strong> | <strong>Electrical</strong> devices 423


3 Power factor correction3.1 General aspectsFigure 1: Relative voltage dropVoltage drop per unit of active power transmitted10Cable cross sectionRelative voltage drop0.50Load power factor11SDC010039F0201Figure 2: Transmittable active power1000Active power increase with equal dimensioning factorsoriginal power factor0.4 0.5 0.60.7 0.8 0.9Active Power % increase1001010.70 0.80 0.90 1.00Improved power factor1SDC010040F0201424 <strong>Electrical</strong> devices | <strong>ABB</strong>


3 Power factor correction3.1 General aspectsThe distribution authority is responsible for the production <strong>and</strong> transmission ofthe reactive power required by the user <strong>installation</strong>s, <strong>and</strong> therefore has a seriesof further inconveniences which can be summarized as:- oversizing of the conductors <strong>and</strong> of the components of the transmissionlines;- higher Joule-effect losses <strong>and</strong> higher voltage drops in the components <strong>and</strong>lines.The same inconveniences are present in the distribution <strong>installation</strong> of the finaluser. The power factor is an excellent index of the size of the added costs <strong>and</strong>is therefore used by the distribution authority to define the purchase price ofthe energy for the final user.The ideal situation would be to have a cosϕ slightly higher than the set referenceso as to avoid payment of legal penalties, <strong>and</strong> at the same time not to risk having,with a cosϕ too close to the unit, a leading power factor when the power factorcorrected device is working with a low load.The distribution authority generally does not allow others to supply reactivepower to the network, also due to the possibility of unexpected overvoltages.In the case of a sinusoidal waveform, the reactive power necessary to pass fromone power factor cosϕ 1to a power factor cosϕ 2is given by the formula:where:P is the active power;Q 1,ϕ 1are the reactive power <strong>and</strong> the phase shifting before power factorcorrection;Q 2,ϕ 2are the reactive power <strong>and</strong> the phase shifting after power factorcorrection;is the reactive power for the power factor correction.Q cP Q 2S 2Q c P Q 1 S 1PQ 2Q 1QS c2S 1Power factor correction unit(reactive power generator)Motor1SDC010041F0201<strong>ABB</strong> | <strong>Electrical</strong> devices 425


3.1 General aspects3 Power factor correctionTable 2 shows the value of the relationshipfor different values of the power factor before <strong>and</strong> after the correction.Table 2: Factor K cK ccosϕ 2cosϕ 10.80 0.85 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 10.60 0.583 0.714 0.849 0.878 0.907 0.938 0.970 1.005 1.042 1.083 1.130 1.191 1.3330.61 0.549 0.679 0.815 0.843 0.873 0.904 0.936 0.970 1.007 1.048 1.096 1.157 1.2990.62 0.515 0.646 0.781 0.810 0.839 0.870 0.903 0.937 0.974 1.015 1.062 1.123 1.2650.63 0.483 0.613 0.748 0.777 0.807 0.837 0.870 0.904 0.941 0.982 1.030 1.090 1.2330.64 0.451 0.581 0.716 0.745 0.775 0.805 0.838 0.872 0.909 0.950 0.998 1.058 1.2010.65 0.419 0.549 0.685 0.714 0.743 0.774 0.806 0.840 0.877 0.919 0.966 1.027 1.1690.66 0.388 0.519 0.654 0.683 0.712 0.743 0.775 0.810 0.847 0.888 0.935 0.996 1.1380.67 0.358 0.488 0.624 0.652 0.682 0.713 0.745 0.779 0.816 0.857 0.905 0.966 1.1080.68 0.328 0.459 0.594 0.623 0.652 0.683 0.715 0.750 0.787 0.828 0.875 0.936 1.0780.69 0.299 0.429 0.565 0.593 0.623 0.654 0.686 0.720 0.757 0.798 0.846 0.907 1.0490.70 0.270 0.400 0.536 0.565 0.594 0.625 0.657 0.692 0.729 0.770 0.817 0.878 1.0200.71 0.242 0.372 0.508 0.536 0.566 0.597 0.629 0.663 0.700 0.741 0.789 0.849 0.9920.72 0.214 0.344 0.480 0.508 0.538 0.569 0.601 0.635 0.672 0.713 0.761 0.821 0.9640.73 0.186 0.316 0.452 0.481 0.510 0.541 0.573 0.608 0.645 0.686 0.733 0.794 0.9360.74 0.159 0.289 0.425 0.453 0.483 0.514 0.546 0.580 0.617 0.658 0.706 0.766 0.9090.75 0.132 0.262 0.398 0.426 0.456 0.487 0.519 0.553 0.590 0.631 0.679 0.739 0.8820.76 0.105 0.235 0.371 0.400 0.429 0.460 0.492 0.526 0.563 0.605 0.652 0.713 0.8550.77 0.079 0.209 0.344 0.373 0.403 0.433 0.466 0.500 0.537 0.578 0.626 0.686 0.8290.78 0.052 0.183 0.318 0.347 0.376 0.407 0.439 0.474 0.511 0.552 0.599 0.660 0.8020.79 0.026 0.156 0.292 0.320 0.350 0.381 0.413 0.447 0.484 0.525 0.573 0.634 0.7760.80 0.130 0.266 0.294 0.324 0.355 0.387 0.421 0.458 0.499 0.547 0.608 0.7500.81 0.104 0.240 0.268 0.298 0.329 0.361 0.395 0.432 0.473 0.521 0.581 0.7240.82 0.078 0.214 0.242 0.272 0.303 0.335 0.369 0.406 0.447 0.495 0.556 0.6980.83 0.052 0.188 0.216 0.246 0.277 0.309 0.343 0.380 0.421 0.469 0.530 0.6720.84 0.026 0.162 0.190 0.220 0.251 0.283 0.317 0.354 0.395 0.443 0.503 0.6460.85 0.135 0.164 0.194 0.225 0.257 0.291 0.328 0.369 0.417 0.477 0.6200.86 0.109 0.138 0.167 0.198 0.230 0.265 0.302 0.343 0.390 0.451 0.5930.87 0.082 0.111 0.141 0.172 0.204 0.238 0.275 0.316 0.364 0.424 0.5670.88 0.055 0.084 0.114 0.145 0.177 0.211 0.248 0.289 0.337 0.397 0.5400.89 0.028 0.057 0.086 0.117 0.149 0.184 0.221 0.262 0.309 0.370 0.5120.90 0.029 0.058 0.089 0.121 0.156 0.193 0.234 0.281 0.342 0.484426 <strong>Electrical</strong> devices | <strong>ABB</strong>


3 Power factor correction3.1 General aspectsExampleSupposing the need to change from 0.8 to 0.93 the power factor of a threephase<strong>installation</strong> (U r= 400 V) which absorbs an average power of 300 kW.From Table 2, at the intersection of the column corresponding to the finalpower factor (0.93), <strong>and</strong> the row corresponding to the starting power factor(0.8), the value of K c(0.355) can be read. The reactive power Q cwhich mustbe generated locally shall be:Q c= K c . P = 0.355 . 300 = 106.5 KvarDue to the effect of power factor correction, the current absorbed decreasesfrom 540 A to 460 A (a reduction of approximately 15%).Characteristics of power factor correction capacitor banksThe most economical means of increasing the power factor, especially for an<strong>installation</strong> which already exists, is installing capacitors.Capacitors have the following advantages:- low cost compared with synchronous compensators <strong>and</strong> electronic powerconverters;- ease of <strong>installation</strong> <strong>and</strong> maintenance;- reduced losses (less than 0.5 W/kvar in low voltage);- the possibility of covering a wide range of powers <strong>and</strong> different load profiles,simply supplying in parallel different combinations of components, each witha relatively small power.The disadvantages are sensitivity to overvoltages <strong>and</strong> to the presence of nonlinearloads.The St<strong>and</strong>ards applicable to power factor correction capacitors are asfollows:- IEC 60831-1 “Shunt power capacitors of the self-healing type for a.c.systems having a rated voltage up to <strong>and</strong> including 1000 V - Part 1: General- Performance, testing <strong>and</strong> rating - Safety requirements - Guide for <strong>installation</strong><strong>and</strong> operation”;- IEC 60931-1 “Shunt power capacitors of the non-self-healing type for a.c.systems having a rated voltage up to <strong>and</strong> including 1000 V - Part 1: General-Performance, testing <strong>and</strong> rating - Safety requirements - Guide for <strong>installation</strong><strong>and</strong> operation”.<strong>ABB</strong> | <strong>Electrical</strong> devices 427


3 Power factor correction3.1 General aspectsThe characteristics of a capacitor, given on its nameplate, are:• rated voltage U r, which the capacitor must withst<strong>and</strong> indefinitely;• rated frequency f r(usually equal to that of the network);• rated power Q c, generally expressed in kvar (reactive power of the capacitorbank).From this data it is possible to find the size characteristics of the capacitors byusing the following formulae (5):Single-phaseconnectionThree-phasestar-connectionThree-phasedelta-connectionCapacity of the capacitor bankQcQcQcC =2C =2C =2 ≠ fr⋅ Ur2 ≠ fr⋅ Ur2 ≠ f ⋅2 r U r⋅ 3Rated current of the componentsLine currentIrc= 2≠ fr⋅ C ⋅Ur Irc= 2 ≠ fr⋅ C⋅Ur/ 3Il= I rcIl= I rcI = ≠rcIl2 fr⋅ C ⋅Ur= rcI ⋅31SDC010005F0901U r= line voltage systemIn a three-phase system, to supply the same reactive power, the star connectionrequires a capacitor with a capacitance three times higher than thedelta-connected capacitor.In addition, the capacitor with the star connection results to be subjected toa voltage √3 lower <strong>and</strong> flows through by a current √3 higher than a capacitorinserted <strong>and</strong> delta connected.Capacitors are generally supplied with connected discharge resistance, calculatedso as to reduce the residual voltage at the terminals to 75 V in 3 minutes,as stated in the reference St<strong>and</strong>ard.3.2 Power factor correction methodSingle PFCSingle or individual power factor correction is carried out by connecting acapacitor of the correct value directly to the terminals of the device whichabsorbs reactive power.Installation is simple <strong>and</strong> economical: capacitors <strong>and</strong> load can use the sameoverload <strong>and</strong> short-circuit protection, <strong>and</strong> are connected <strong>and</strong> disconnectedsimultaneously.The adjustment of cosϕ is systematic <strong>and</strong> automatic with benefit not only tothe energy distribution authority, but also to the whole internal distributionsystem of the user.This type of power factor correction is advisable in the case of large users withconstant load <strong>and</strong> power factor <strong>and</strong> long connection times.Individual PFC is usually applied to motors <strong>and</strong> fluorescent lamps. The capacitorunits or small lighting capacitors are connected directly to loads.428 <strong>Electrical</strong> devices | <strong>ABB</strong>


3 Power factor correction3.2 Power factor connection methodIndividual PFC of motorsThe usual connection diagrams are shown in the following figure:StarterStarterStarterMcMcMDiagram 1 Diagram 2 Diagram 3c1SDC010028F0001In the case of direct connection (diagrams 1 <strong>and</strong> 2) there is a risk that afterdisconnection of the supply, the motor will continue to rotate (residual kineticenergy) <strong>and</strong> self-excite with the reactive energy supplied by the capacitor bank,acting as an asynchronous generator. In this case, the voltage is maintained onthe load side of the switching <strong>and</strong> <strong>control</strong> device, with the risk of dangerousovervoltages of up to twice the rated voltage value.However, in the case of diagram 3, to avoid the risk detailed above, the normalprocedure is to connect the PFC bank to the motor only when it is running, <strong>and</strong>to disconnect it before the disconnection of the motor supply.As a general rule, for a motor with power P r, it is advisable to use a PFC withreactive power Q cbelow 90% of the reactive power absorbed by the no-loadmotor Q 0, at rated voltage U r, to avoid a leading power factor.Considering that under no-load conditions, the current absorbed I 0[A] is solelyreactive, if the voltage is expressed in volts, it results:1000The current I 0is generally given in the documentation supplied by themanufacturer of the motor.<strong>ABB</strong> | <strong>Electrical</strong> devices 429


3 Power factor correction3.2 Power factor connection methodTable 3 shows the values of reactive power for power factor correction of some<strong>ABB</strong> motors, according to the power <strong>and</strong> the number of poles.Table 3: Reactive power for power factor motor correctionP rQ cBefore PFC After PFC[kW] [kvar] cosϕ rI r[A] cosϕ 2I 2[A]400V / 50 Hz / 2 poles / 3000 r/min7.5 2.5 0.89 13.9 0.98 12.711 2.5 0.88 20 0.95 18.615 5 0.9 26.5 0.98 24.218.5 5 0.91 32 0.98 29.722 5 0.89 38.5 0.96 35.830 10 0.88 53 0.97 47.937 10 0.89 64 0.97 58.845 12.5 0.88 79 0.96 72.255 15 0.89 95 0.97 87.375 15 0.88 131 0.94 122.290 15 0.9 152 0.95 143.9110 20 0.86 194 0.92 181.0132 30 0.88 228 0.95 210.9160 30 0.89 269 0.95 252.2200 30 0.9 334 0.95 317.5250 40 0.92 410 0.96 391.0315 50 0.92 510 0.96 486.3400V / 50 Hz / 4 poles / 1500 r/min7.5 2.5 0.86 14.2 0.96 12.711 5 0.81 21.5 0.96 18.215 5 0.84 28.5 0.95 25.318.5 7.5 0.84 35 0.96 30.522 10 0.83 41 0.97 35.130 15 0.83 56 0.98 47.537 15 0.84 68 0.97 59.145 20 0.83 83 0.97 71.155 20 0.86 98 0.97 86.975 20 0.86 135 0.95 122.890 20 0.87 158 0.94 145.9110 30 0.87 192 0.96 174.8132 40 0.87 232 0.96 209.6160 40 0.86 282 0.94 257.4200 50 0.86 351 0.94 320.2250 50 0.87 430 0.94 399.4315 60 0.87 545 0.93 507.9430 <strong>Electrical</strong> devices | <strong>ABB</strong>


3 Power factor correction3.2 Power factor connection methodP rQ cBefore PFC After PFC[kW] [kvar] cosϕ rI r[A] cosϕ 2I 2[A]400V / 50 Hz / 6 poles / 1000 r/min7.5 5 0.79 15.4 0.98 12.411 5 0.78 23 0.93 19.315 7.5 0.78 31 0.94 25.718.5 7.5 0.81 36 0.94 30.922 10 0.81 43 0.96 36.530 10 0.83 56 0.94 49.437 12.5 0.83 69 0.94 60.845 15 0.84 82 0.95 72.655 20 0.84 101 0.96 88.775 25 0.82 141 0.93 123.990 30 0.84 163 0.95 144.2110 35 0.83 202 0.94 178.8132 45 0.83 240 0.95 210.8160 50 0.85 280 0.95 249.6200 60 0.85 355 0.95 318.0250 70 0.84 450 0.94 404.2315 75 0.84 565 0.92 514.4400V / 50 Hz / 8 poles / 750 r/min7.5 5 0.7 18.1 0.91 13.911 7.5 0.76 23.5 0.97 18.415 7.5 0.82 29 0.97 24.518.5 7.5 0.79 37 0.93 31.522 10 0.77 45 0.92 37.530 12.5 0.79 59 0.93 50.037 15 0.78 74 0.92 62.845 20 0.78 90 0.93 75.455 20 0.81 104 0.93 90.275 30 0.82 140 0.95 120.690 30 0.82 167 0.93 146.6110 35 0.83 202 0.94 178.8132 50 0.8 250 0.93 214.6<strong>ABB</strong> | <strong>Electrical</strong> devices 431


3 Power factor correction3.2 Power factor connection methodExampleFor a three-phase asynchronous motor, 110 kW (400 V - 50 Hz - 4 poles), thePFC power suggested in the table is 30 kvar.Individual power factor correction of three-phase transformersA transformer is an electrical device of primary importance which, due to thesystem requirements, is often constantly in service.In particular, in <strong>installation</strong>s constituted by several transformer substations, it isadvisable to carry out power factor correction directly at the transformer.In general, the PFC power (Q c) for a transformer with rated power S r[kVA]should not exceed the reactive power required under minimum reference loadconditions.Reading the data from the transformer nameplate, the percentage value ofthe no-load current i 0%, the percentage value of the short-circuit voltage u k%,the iron losses P fe<strong>and</strong> the copper losses P cu[kW], the PFC power required isapproximately:where K Lis the load factor, defined as the relationship between the minimumreference load <strong>and</strong> the rated power of the transformer.ExampleSupposing the need for PFC of a 630 kVA oil-distribution transformer whichsupplies a load which is less than 60% of its rated power.From the data on the transformer nameplate:i 0% = 1.8%u k% = 4%P cu= 8.9 kWP fe= 1.2 kWThe PFC power of the capacitor bank connected to the transformer is:while, when using the simplified formula, the result is:432 <strong>Electrical</strong> devices | <strong>ABB</strong>


3 Power factor correction3.2 Power factor connection methodTable 4 shows the reactive power of the capacitor bank Q c[kvar] to be connectedon the secondary side of an <strong>ABB</strong> transformer, according to the differentminimum estimated load levels.Table 4: PFC reactive power for <strong>ABB</strong> transformersQ c[kvar]S ru k% i o% P feP cuload factor K L[kVA] [%] [%] [kW] [kW] 0 0.25 0.5 0.75 1Oil Distribution Transformer MV-LV50 4 2.9 0.25 1.35 1.4 1.5 1.8 2.3 2.9100 4 2.5 0.35 2.30 2.5 2.7 3.3 4.3 5.7160 4 2.3 0.48 3.20 3.6 4 5 6.8 9.2200 4 2.2 0.55 3.80 4.4 4.8 6.1 8.3 11250 4 2.1 0.61 4.50 5.2 5.8 7.4 10 14315 4 2 0.72 5.40 6.3 7 9.1 13 18400 4 1.9 0.85 6.50 7.6 8.5 11 16 22500 4 1.9 1.00 7.40 9.4 11 14 20 28630 4 1.8 1.20 8.90 11 13 17 25 35800 6 1.7 1.45 10.60 14 16 25 40 601000 6 1.6 1.75 13.00 16 20 31 49 741250 6 1.6 2.10 16.00 20 24 38 61 931600 6 1.5 2.80 18.00 24 30 47 77 1182000 6 1.2 3.20 21.50 24 31 53 90 1422500 6 1.1 3.70 24.00 27 37 64 111 1753150 7 1.1 4.00 33.00 34 48 89 157 2524000 7 1.4 4.80 38.00 56 73 125 212 333Cast Resin Distribution Transformer MV-LV100 6 2.3 0.50 1.70 2.2 2.6 3.7 5.5 8160 6 2 0.65 2.40 3.1 3.7 5.5 8.4 12200 6 1.9 0.85 2.90 3.7 4.4 6.6 10 15250 6 1.8 0.95 3.30 4.4 5.3 8.1 13 19315 6 1.7 1.05 4.20 5.3 6.4 9.9 16 24400 6 1.5 1.20 4.80 5.9 7.3 12 19 29500 6 1.4 1.45 5.80 6.8 8.7 14 23 36630 6 1.3 1.60 7.00 8 10 17 29 45800 6 1.1 1.94 8.20 8.6 12 20 35 561000 6 1 2.25 9.80 9.7 13 25 43 691250 6 0.9 3.30 13.00 11 15 29 52 851600 6 0.9 4.00 14.50 14 20 38 67 1092000 6 0.8 4.60 15.50 15 23 45 82 1342500 6 0.7 5.20 17.50 17 26 54 101 1663150 8 0.6 6.00 19.00 18 34 81 159 269ExampleFor a 630 kVA oil-distribution transformer with a load factor of 0.5, the necessaryPFC power is 17 kvar.<strong>ABB</strong> | <strong>Electrical</strong> devices 433


3 Power factor correction3.2 Power factor connection methodPFC in groupsGroup of loads to be power factorcorrected1SDC010029F0001This consists of local power factor correction of groups of loads with similarfunctioning characteristics by installing a dedicated capacitor bank.This method achieves a compromise between the economical solution <strong>and</strong>the correct operation of the <strong>installation</strong>, since only the line downstream of the<strong>installation</strong> point of the capacitor bank is not correctly exploited.Centralized PFCLVFeedersC1SDC010030F0001The daily load profile is of fundamental importance for the choice of the mostsuitable type of power factor correction.In <strong>installation</strong>s, in which not all loads function simultaneously <strong>and</strong>/or in whichsome loads are connected for only a few hours a day, the solution of usingsingle PFC becomes unsuitable as many of the capacitors installed could stayidle for long periods.In the case of <strong>installation</strong>s with many loads occasionally functioning, thushaving a high installed power <strong>and</strong> a quite low average power absorption bythe loads which function simultaneously, the use of a single PFC system atthe <strong>installation</strong> origin ensures a remarkable decrease in the total power of thecapacitors to be installed.434 <strong>Electrical</strong> devices | <strong>ABB</strong>


3 Power factor correction3.2 Power factor connection methodCentralized PFC normally uses automatic units with capacitor banks divided intoseveral steps, directly installed in the main distribution switchboards; the useof a permanently connected capacitor bank is only possible if the absorptionof reactive energy is fairly regular throughout the day.The main disadvantage of centralized PFC is that the distribution lines of the<strong>installation</strong>, downstream of the PFC device, must be dimensioned taking intoaccount the full reactive power required by the loads.3.3 Circuit-breakers for the protection <strong>and</strong>switching of capacitor banksThe circuit-breakers for the protection <strong>and</strong> switching of capacitor banks in LVshall:1. withst<strong>and</strong> the transient currents which occur when connecting <strong>and</strong>disconnecting the banks. In particular, the instantaneous magnetic <strong>and</strong>electronic releases shall not trip due to these peak currents;2. withst<strong>and</strong> the periodic or permanent overcurrents due to the voltageharmonics <strong>and</strong> to the tolerance (+15%) of the rated value of capacity;3. perform a high number of no-load <strong>and</strong> on-load operations, also with highfrequency;4. be coordinated with any external device (contactors).Furthermore, the making <strong>and</strong> breaking capacity of the circuit-breaker must beadequate to the short- circuit current values of the <strong>installation</strong>.St<strong>and</strong>ards IEC 60831-1 <strong>and</strong> 60931-1 state that:- the capacitors shall normally function with an effective current value up to 130%of their rated current I rc(due to the possible presence of voltage harmonics inthe network);- a tolerance of 10% on the capacitance for banks up to 100 kvar <strong>and</strong> of 5%for banks exceeding 100 kvar is admited.The maximum current which can be absorbed by the capacitor bank I cmaxis:Therefore:- the rated current of the circuit-breaker shall be greater than 1.5⋅I rc;- the overload protection setting shall be equal to 1.5⋅I rc.The connection of a capacitor bank, similar to a closing operation under shortcircuitconditions, associated with transient currents with high frequency (1÷15kHz), of short duration (1÷3 ms), with high peak (25÷200 I rc).Therefore:- the circuit-breaker shall have an adequate making capacity;- the setting of the instantaneous short-circuit protection must not cause unwantedtrips.<strong>ABB</strong> | <strong>Electrical</strong> devices 435


3.3 Circuit-breakers for the protection <strong>and</strong> switching of capacitor banks3 Power factor correctionThe second condition is generally respected:• for thermomagnetic releases, the magnetic protection shall be set at a valuenot less than 10⋅I cmax≥ 10 I cmax14.3 I rc14.3≥ 10 I cmax13.65 I rc13.65• for electronic releases, the instantaneous short-circuit protection shall bedeactivated (I 3= OFF).Hereunder, the selection tables for circuit-breakers: for the definition of theversion according to the required breaking capacity, refer to Part 1, Chapter 2.1“General characteristics”.The following symbols are used in the tables (they refer to maximum values):- Q c= power of the capacitor bank which can be connected [kvar] with referenceto the indicated voltage <strong>and</strong> 50 Hz frequency;- I cn= rated current of the connected capacitor bank [A];- I cmax= maximum rated current of the connected capacitor bank [A];It is necessary to install limiting inductances in order to reduce the inrushcurrent.Table 5: Coordination type 2 circuit breaker-contactor for the switching of capacitor banksat 400 V, 50 kAQc[kvar]Icn[A]436 <strong>Electrical</strong> devices | <strong>ABB</strong>Icmax[A] MCCbs Contactor10 14 21 XT2S 160 TMD In=25 A3015 22 31 XT2S 160 TMD In=40 A/AF5020 29 41 XT2S 160 TMD In=50 A/AF5030 43 62 XT2S 160 TMD In=80 A/AF6340 58 83 XT2S 160 TMD In=100 A/AF6350 72 103 XT2S 160 TMD In=125 A/AF9560 87 124 XT2S 160 TMD In=160 A/AF9570 101 144 XT2S 160 TMD In=160* A/AF11080 115 165 XT3S TMD TMD In=200 A/AF14590 130 186 XT3S TMD TMD In=200 A/AF145110 159 217 XT3S TMD TMD In=250 A/AF185130 188 256 T4S320 PR221LI In=320 A/AF210150 217 296 T4S320 PR221LI In=320 A/AF260180 260 355 T5S400 PR221LI In=400 AF400200 289 394 T5S400 PR221LI In=400 AF400250 361 493 T6S630 PR221LI In=630 AF580280 404 552 T6S630 PR221LI In=630 AF580300 433 591 T6S630 PR221LI In=630 AF750* For plug-in version reduce the power of the capacitor bank by 10%


3.3 Circuit-breakers for the protection <strong>and</strong> switching of capacitor banks3 Power factor correctionTable 6: Coordination type 2 circuit breaker-contactor for the switching of capacitor banksat 440 V, 50 kAQc[kvar]Icn[A]Icmax[A] MCCbs Contactor10 13 19 XT2S 160 TMD In=25 A/AF5015 20 28 XT2S 160 TMD In=32 A/AF5020 26 38 XT2S 160 TMD In=40 A/AF5030 39 56 XT2S 160 TMD In=63 A/AF6340 52 75 XT2S 160 TMD In=100 A/AF9550 66 94 XT2S 160 TMD In=125 A/AF9560 79 113 XT2S 160 TMD In=125 A/AF9570 92 131 XT2S 160 TMD In=160 A/AF11080 105 150 XT2S 160 TMD In=160* A/AF14590 118 169 XT4S Ekip LS/I In=250 A/AF145110 144 197 XT4S Ekip LS/I In=250 A/AF185130 171 233 XT4S Ekip LS/I In=250 A/AF210150 197 269 T4H320 PR221LI In=320 A/AF260180 236 322 T5H400 PR221LI In=400 A/AF300200 262 358 T5H400 PR221LI In=400 AF400250 328 448 T6H630 PR221LI In=630 AF460280 367 502 T6H630 PR221LI In=630 AF580300 394 537 T6H630 PR221LI In=630 AF580350 459 627 T6H800 PR221LI In=800 AF750400 525 716 T6H800 PR221LI In=800 AF750* For plug-in version reduce the power of the capacitor bank by 10%Table 7: Coordination type 2 circuit breaker-contactor for the switching of capacitor banksat 500 V, 50 kAQc[kvar]Icn[A]Icmax[A] MCCbs Contactor10 12 17 XT2H 160 TMD In=20 A/AF5015 17 25 XT2H 160 TMD In=32 A/AF5020 23 33 XT2H 160 TMD In=40 A/AF5030 35 50 XT2H 160 TMD In=63 A/AF6340 46 66 XT2H 160 TMD In=80 A/AF7550 58 83 XT2H 160 TMD In=100 A/AF9560 69 99 XT2H 160 TMD In=125 A/AF9570 81 116 XT2H 160 TMD In=125 A/AF9580 92 132 XT2H 160 TMD In=160 A/AF11090 104 149 XT2H 160 TMD In=160* A/AF145110 127 173 XT4H Ekip LS/I In=250 A/AF145130 150 205 XT4H Ekip LS/I In=250 A/AF185150 173 236 XT4H Ekip LS/I In=250 A/AF210180 208 284 T4H320 PR221LI In=320 A/AF260200 231 315 T5H400 PR221LI In=400 A/AF300250 289 394 T5H400 PR221LI In=400 AF400280 323 441 T6H630 PR221LI In=630 AF460300 346 473 T6H630 PR221LI In=630 AF460350 404 552 T6H630 PR221LI In=630 AF580400 462 630 T6H800 PR221LI In=800 AF750* For plug-in version reduce the power of the capacitor bank by 10%<strong>ABB</strong> | <strong>Electrical</strong> devices 437


Qc[kvar]Icn[A]3.3 Circuit-breakers for the protection <strong>and</strong> switching of capacitor banks3 Power factor correctionTable 8: Coordination type 2 circuit breaker-contactor for the switching of capacitor banksat 690 V, 10 kAIcmax[A] MCCbs Contactor10 8 12 XT2N 160 TMD In=16 A/AF5015 13 18 XT2N 160 TMD In=20 A/AF5020 17 24 XT2N 160 TMD In=25 A/AF5030 25 36 XT2N 160 TMD In=40 A/AF5040 33 48 XT2N 160 TMD In=50 A/AF6350 42 60 XT2N 160 TMD In=63 A/AF6360 50 72 XT2N 160 TMD In=80 A/AF7570 59 84 XT2N 160 TMD In=100 A/AF9580 67 96 XT2N 160 TMD In=100 A/AF9590 75 108 XT2N 160 TMD In=125 A/AF110110 92 126 XT2N 160 TMD In=160 A/AF145130 109 148 XT2N 160 TMD In=160* A/AF185150 126 171 XT4N Ekip LS/I In=250 A/AF210180 151 206 XT4N Ekip LS/I In=250 A/AF260200 167 228 XT4N Ekip LS/I In=250 A/AF260250 209 286 T4N320 PR221LI In=320 AF400280 234 320 T5N400 PR221LI In=400 AF400300 251 343 T5N400 PR221LI In=400 AF400350 293 400 T6N630 PR221LI In=630 AF460400 335 457 T6N630 PR221LI In=630 AF580* For plug-in version reduce the power of the capacitor bank by 10%438 <strong>Electrical</strong> devices | <strong>ABB</strong>


3.3 Circuit-breakers for the protection <strong>and</strong> switching of capacitor banks3 Power factor correctionIn the following table regarding the switching <strong>and</strong> protection of capacitors bymeans of air circuit-breakers, the following symbols are used:- N mech= number of mechanical operations;- f mech= frequency of mechanical operations [op/h];- N el= number of electrical operations with reference to a voltage of 440 V;- f el= frequency of electrical operations [op/h].Table 9: Selection table for SACE Emax air circuit-breakersI CBnI cnQ C[kvar] N mechf mechN elf elCircuit-breaker [A] [A] 400 V 440 V 500 V 690 V [op/h] [op/h]X1 B-N 630 421 291 320 364 502 12500 60 6000 30X1 B-N 800 533 369 406 461 637 12500 60 6000 30X1 B-N 1000 666 461 507 576 795 12500 60 4000 30X1 B-N 1250 834 578 636 722 997 12500 60 4000 30X1 B-N 1600 1067 739 813 924 1275 12500 60 3000 30E1 B-N 800 533 369 406 461 637 25000 60 10000 30E1 B-N 1000 666 461 507 576 795 25000 60 10000 30E1 B-N 1250 834 578 636 722 997 25000 60 10000 30E1 B-N 1600 1067 739 813 924 1275 25000 60 10000 30E2 B-N-S 800 533 369 406 461 637 25000 60 15000 30E2 B-N-S 1000 666 461 507 576 795 25000 60 15000 30E2 B-N-S 1250 834 578 636 722 997 25000 60 15000 30E2 B-N-S 1600 1067 739 813 924 1275 25000 60 12000 30E2 B-N-S 2000 1334 924 1017 1155 1594 25000 60 10000 30E3 N-S-H-V 800 533 369 406 461 637 20000 60 12000 20E3 N-S-H-V 1000 666 461 507 576 795 20000 60 12000 20E3 N-S-H-V 1250 834 578 636 722 997 20000 60 12000 20E3 N-S-H-V 1600 1067 739 813 924 1275 20000 60 10000 20E3 N-S-H-V 2000 1334 924 1017 1155 1594 20000 60 9000 20E3 N-S-H-V 2500 1667 1155 1270 1444 1992 20000 60 8000 20E3 N-S-H-V 3200 2134 1478 1626 1848 2550 20000 60 6000 20E4 S-H-V 3200 2134 1478 1626 1848 2550 15000 60 7000 10E6 H-V 3200 2134 1478 1626 1848 2550 12000 60 5000 10<strong>ABB</strong> | <strong>Electrical</strong> devices 439


4.1 General aspects: effects of current onhuman beings4 <strong>Protection</strong> of human beingsDanger to persons due to contact with live parts is caused by the flow of thecurrent through the human body. The effects are:- tetanization: the muscles affected by the current flow involuntary contract<strong>and</strong> letting go of gripped conductive parts is difficult. Note: very high currentsdo not usually induce muscular tetanization because, when the body touchessuch currents, the muscular contraction is so sustained that the involuntarymuscle movements generally throw the subject away from the conductivepart;- breathing arrest: if the current flows through the muscles <strong>control</strong>ling thelungs, the involuntary contraction of these muscles alters the normal respiratoryprocess <strong>and</strong> the subject may die due to suffocation or suffer the consequencesof traumas caused by asphyxia;- ventricular fibrillation: the most dangerous effect is due to the superpositionof the external currents with the physiological ones which, by generatingun<strong>control</strong>led contractions, induce alterations of the cardiac cycle. This anomalymay become an irreversible phenomenon since it persists even when thestimulus has ceased;- burns: they are due to the heating deriving, by Joule effect, from the currentpassing through the human body.The St<strong>and</strong>ard IEC 60479-1 “Effects of current on human being <strong>and</strong> livestock” isa guide about the effects of current passing through the human body to be usedfor the definition of electrical safety requirements. This St<strong>and</strong>ard shows, on atime-current diagram, four zones to which the physiological effects of alternatingcurrent (15 ÷100 Hz) passing through the human body have been related.440 <strong>Electrical</strong> devices | <strong>ABB</strong>


4 <strong>Protection</strong> of human beings4.1 General aspect: effects of current on human beingsms 10.000Duration of current flow t5.0002.0001.00050020010050Figure 1: Time-current zones of the effects of alternating current onthe human bodyAC-1a b c 1 c 2 c 3AC-2AC-3AC-4.1AC-4.2AC-4.3AC-41SDC010042F020120ZonedesignationAC-1AC-2AC-3AC-4AC-4.1AC-4.2AC-4.3100,1 0,2 0,5 1 2 5 10 20 50 100 200 500 1.000 2.000 5.000 10.000Body current I BmAZonelimitsUp to 0.5 mAline a0.5 mAup toline b*Line bup tocurve c 1Abovecurve c 1c 1- c 2c 2- c 3Beyondcurve c 3Physiological effectsUsually no reaction.Usually no harmful physiological effects.Usually no organic damage to be expected. Likelihood of cramplike muscularcontractions <strong>and</strong> difficulty in breathing for durations of current-flowlonger than 2 s. Reversible disturbances of formation <strong>and</strong> conductionof impulses in the heart, including atrial fibrillation <strong>and</strong> transient cardiacarrest without ventricular fibrillation increasing with current magnitude<strong>and</strong> time.Increasing with magnitude <strong>and</strong> time, dangerous pathophysiological effectssuch as cardiac arrest, breathing arrest <strong>and</strong> severe burns may occur inaddition to the effects of zone 3.Probability of ventricular fibrillation increasing up to about 5%.Probability of ventricular fibrillation up to about 50%.Probability of ventricular fibrillation above 50%.* For durations of current-flow below 10 ms, the limit for the body current for line bremains constant at a value of 200 mA.This St<strong>and</strong>ard gives also a related figure for direct current.By applying Ohm’s law it is possible to define the safety curve for the allowablevoltages, once the human body impedance has been calculated. The electricalimpedance of the human body depends on many factors. The above mentionedSt<strong>and</strong>ard gives different values of impedance as a function of the touch voltage<strong>and</strong> of the current path.<strong>ABB</strong> | <strong>Electrical</strong> devices 441


4.2 Distribution systems4 <strong>Protection</strong> of human beingsThe earth fault modalities <strong>and</strong> the consequences caused by contact with liveparts, are strictly related to the neutral conductor arrangement <strong>and</strong> to theconnections of the exposed conductive parts.For a correct choice of the protective device, it is necessary to know which isthe distribution system of the plant.IEC 60364-1 classifies the distribution systems with two letters.The first letter represents the relationship of the power system to earth:- T: direct connection of one point to earth, in alternating current systems,generally the neutral point;- I: all live parts isolated from earth, or one point, in alternating current systems,generally the neutral point, connected to earth through an impedance.The second letter represents the relationship of the exposed conductive partsof the <strong>installation</strong> to earth:- T: direct electrical connection of the exposed conductive parts to earth;- N: direct electrical connection of the exposed conductive parts to the earthedpoint of the power system.Subsequent letters, if any, represent the arrangement of neutral <strong>and</strong> protectiveconductors:- S: protective function is provided by a conductor separate from the neutralconductor;- C: neutral <strong>and</strong> protective functions combined as a single conductor (PENconductor).Three types of distribution system are considered:TT SystemTN SystemL 1L 2L 3PENL 1L 2L 3N(TN-C)(TN-S)PENPE1SDC010032F00011SDC010033F0001442 <strong>Electrical</strong> devices | <strong>ABB</strong>


4 <strong>Protection</strong> of human beings4.2 Distribution systemsIT SystemL 1L 2L 3NPE1SDC010034F0001In TT systems, the neutral conductor <strong>and</strong> the exposed conductive parts areconnected to earth electrodes electrically independent; the fault current flowstowards the power supply neutral point through earth (Figure 1):I kL 1L 2L 3NR BI kR A1SDC010035F0001In TT <strong>installation</strong>s, the neutral conductor is connected to the supply star center,it is usually distributed <strong>and</strong> has the function of making the phase voltage (e.g.230 V) available, useful for single-phase load supply. The exposed conductiveparts, on the contrary, singularly or collectively, are locally connected to earth.TT systems are generally used for civil <strong>installation</strong>s.TN systems are typically used when the power supply is distributed to loadshaving their own electrical substation. The neutral conductor is directly earthedin the substation; the exposed conductive parts are connected to the sameearthing point of the neutral conductor, <strong>and</strong> can be locally earthed.Three types of TN system are considered according to the arrangement ofneutral <strong>and</strong> protective conductors:1. TN-C neutral <strong>and</strong> protective functions are combined in a single conductor(PEN conductor);2. TN-S neutral <strong>and</strong> protective conductors are always separated;3. TN-C-S neutral <strong>and</strong> protective functions are combined in a single conductorin a part of the system (PEN) <strong>and</strong> are separated in another part (PE + N).<strong>ABB</strong> | <strong>Electrical</strong> devices 443


4 <strong>Protection</strong> of human beings4.2 Distribution systemsIn TN systems, the fault current flows towards the power supply neutral pointthrough a solid metallic connection, practically without involving the earthelectrode (Figure 2).Figure 2: Earth fault in TN systemsI kL 10(TN-C)I kPEN(TN-S)L 2L 3PEN1SDC010036F0001IT systems have no live parts directly connected to earth, but they can beearthed through a sufficiently high impedance. Exposed conductive parts shallbe earthed individually, in groups or collectively to an independent earthingelectrode.The earth fault current flows towards the power supply neutral point throughthe earthing electrode <strong>and</strong> the line conductor capacitance (Figure 3).Figure 3: Earth fault in IT systemsL 1L 2I kL 3R tI kC 3 C 2 C 11SDC010037F0001These distribution systems are used for particular plants, where the continuityof supply is a fundamental requirement, where the absence of the supply cancause hazards to people or considerable economical losses, or where a lowvalue of a first earth fault is required. In these cases, an insulation monitoringdevice shall be provided for optical or acoustic signalling of possible earth faults,or failure of the supplied equipment.444 <strong>Electrical</strong> devices | <strong>ABB</strong>


4.3 <strong>Protection</strong> against both direct <strong>and</strong>indirect contact4 <strong>Protection</strong> of human beingsContacts of a person with live parts can be divided in two categories:- direct contacts;- indirect contacts.A direct contact occurs when a part of the human body touches a part of theplant, usually live (bare conductors, terminals, etc.).A contact is indirect when a part of the human body touches an exposedconductive parts, usually not live, but with voltage presence due to a failure orwear of the insulating materials.The measures of protection against direct contact are:- insulation of live parts with an insulating material which can only be removedby destruction (e.g. cable insulation);- barriers or enclosures: live parts shall be inside enclosures or behind barriersproviding at least the degree of protection IPXXB or IP2X; for horizontalsurfaces the degree of protection shall be of at least IPXXD or IP4X (for themeaning of the degree of protection codes please refer to Part 1, Chapter 5.1“<strong>Electrical</strong> switchboards”);- obstacles: the interposition of an obstacle between the live parts <strong>and</strong> theoperator prevents unintentional contacts only, but not an intentional contactby the removal of the obstacle without particular tools;- placing out of reach: simultaneously accessible parts at different potentialsshall not be within arm’s reach.An additional protection against direct contact can be obtained by using residualcurrent devices with a rated operating residual current not exceeding 30 mA.It must be remembered that the use of a residual current device as a mean ofprotection against direct contacts does not obviate the need to apply one ofthe above specified measures of protection.The measures of protection against indirect contact are:- automatic disconnection of the supply: a protective device shall automaticallydisconnect the supply to the circuit so that the touch voltage on the exposedconductive part does not persist for a time sufficient to cause a risk of harmfulphysiological effect for human beings;- supplementary insulation or reinforced insulation, e.g. by the use of Class IIcomponents;<strong>ABB</strong> | <strong>Electrical</strong> devices 445


4 <strong>Protection</strong> of human beings4.3 <strong>Protection</strong> against both direct <strong>and</strong> indirect contact- non-conducting locations: locations with a particular resistance value ofinsulating floors <strong>and</strong> walls (≥ 50 kΩ for U r≤ 500 V; ≥ 100 kΩ for U r> 500 V)<strong>and</strong> without protective conductors inside;- electrical separation, e.g. by using an isolating transformer to supply thecircuit;- earth-free local equipotential bonding: locations where the exposed conductiveparts are connected together but not earthed.Finally, the following measures provide combined protection against both direct<strong>and</strong> indirect contact:- SELV (Safety Extra Low Voltage) system <strong>and</strong> PELV (Protective Extra LowVoltage) system;- FELV (Functional Extra Low Voltage) system.The protection against both direct <strong>and</strong> indirect contact is ensured if therequirements stated in 411 from IEC 60364-4-41 are fulfilled; particularly:- the rated voltage shall not exceeds 50 V ac r.m.s. <strong>and</strong> 120 V ripple-free dc;- the supply shall be a SELV or PELV source;- all the <strong>installation</strong> conditions provided for such types of electrical circuits shallbe fulfilled.A SELV circuit has the following characteristics:1) it is supplied by an independent source or by a safety source. Independentsources are batteries or diesel-driven generators. Safety sources are suppliesobtained through an isolating transformer;2) there are no earthed points. The earthing of both the exposed conductiveparts as well as of the live parts of a SELV circuit is forbidden;3) it shall be separated from other electrical systems. The separation of a SELVsystem from other circuits shall be guaranteed for all the components; forthis purpose, the conductors of the SELV circuit may be contained in multiconductorcables or may be provided with an additional insulating sheath.A PELV circuit has the same prescription of a SELV system, except for theprohibition of earthed points; in fact in PELV circuits, at least one point isalways earthed.446 <strong>Electrical</strong> devices | <strong>ABB</strong>


4 <strong>Protection</strong> of human beings4.3 <strong>Protection</strong> against both direct <strong>and</strong> indirect contactFELV circuits are used when for functional reasons the requirements for SELV orPELV circuits cannot be fulfilled; they require compliance with the following rules:a) protection against direct contact shall be provided by either:- barriers or enclosures with degree of protection in accordance with whatstated above (measures of protection against direct contact);- insulation corresponding to the minimum test voltage specified for theprimary circuit. If this test is not passed, the insulation of accessible nonconductiveparts of the equipment shall be reinforced during erection sothat it can withst<strong>and</strong> a test voltage of 1500 V ac r.m.s. for 1 min.;b) protection against indirect contact shall be provided by:- connection of the exposed conductive parts of the equipment of the FELVcircuit to the protective conductor of the primary circuit, provided thatthe latter is subject to one of the measures of protection against directcontact;- connection of a live conductor of the FELV circuit to the protective conductorof the primary circuit provided that an automatic disconnection ofthe supply is applied as measure of protection;c) plugs of FELV systems shall not be able to enter socket-outlets of othervoltage systems, <strong>and</strong> plugs of other voltage systems shall not be able toenter socket-outlets of FELV systems.Figure 1 shows the main features of SELV, PELV <strong>and</strong> FELV systems.Figure 1: SELV, PELV, FELV systemsL1L2L3NPEsafety isolating transformeror equivalent source,connection to earthis admissibleno safety source,connection to earthis admissiblePEPEsafety isolatingtransformeror equivalentsource,no earthingSELVPELVEFELVEvoltage limits forextra-low voltages:50 V ac120 V dcClass IIequipmentEPEPELV circuitFELV circuitearth connections by estraneous conductive parts,e.g. by metal pipe or structural steelworkprotective conductorearth electrode1SDC010043F0201Note 1: Overcurrent protective devices are not shown in this figure.<strong>ABB</strong> | <strong>Electrical</strong> devices 447


4 <strong>Protection</strong> of human beings4.4 TT SystemAn earth fault in a TT system involves the circuit represented in Figure 1:Figure 1: Earth fault in TT systemI kL 1L 2L 3NR BI kR A1SDC010035F0001The fault current flows through the secondary winding of the transformer, theline conductor, the fault resistance, the protective conductor, <strong>and</strong> the earthelectrode resistances (R A, of the user’s plant, <strong>and</strong> R B, of the neutral).According to IEC 60364-4 prescriptions, the protective devices must be coordinatedwith the earthing arrangement in order to rapidly disconnect the supplyif the touch voltage reaches harmful values for the human body.Before describing such prescriptions, it is useful to know the different circuittypes described in the above mentioned St<strong>and</strong>ard; in particular, in a plant, thecircuits can be divided into:• final circuit: it is a circuit which usually supplies equipment (for example anaspirator, a bridge crane, etc.)• distribution circuit: it is a circuit which supplies a distribution board to whichother final circuits are connected.In a TT system, to achieve a correct protection against indirect contact throughthe automatic disconnection of the circuit, it is necessary to respect one of thefollowing conditions (in compliance with IEC 60364-4):<strong>Protection</strong> by means of residual current devicesBy assuming 50V as limit voltage (st<strong>and</strong>ard environments), to achieve protectionagainst indirect contact by means of residual current devices it is necessary tosatisfy the following condition:50VR A· I ∆n≤ 50V then: R A≤where:I ∆nR Ais the total resistance (in ohm) of the earth electrode <strong>and</strong> of the protectiveconductor of the exposed-conductive-parts 1 ;I ∆nis the rated residual operating current of the residual current circuitbreaker.1The resistance of the earth electrode is in series with that of the protective conductor, which is negligible ifcompared with the resistance R A; as a consequence, in the formula it is possible to take into considerationonly the resistance of the earth electrode of the user’s plant.448 <strong>Electrical</strong> devices | <strong>ABB</strong>


4 <strong>Protection</strong> of human beings4.4 TT SystemAs regards the disconnection times, the St<strong>and</strong>ard distinguishes two possibilities;• final circuits with rated currents not exceeding 32A: in this case it is necessarythat the above mentioned condition with the times shown in Table 1 (valuesreferred to fault currents significantly higher than the rated residual current ofthe residual current circuit-breakers typically 5·I ∆n) is fulfilled;• distribution circuit or final circuit with rated currents exceeding 32A: in thiscase it is necessary that the above mentioned condition is fulfilled with a timenot exceeding 1 s (conventional time).Table 1: Maximum disconnection times for final circuits not exceeding32A50V


4.4 TT System4 <strong>Protection</strong> of human beingsAs shown in the example, thanks to a more sensitive residual current device,from a practical point of view it will be easier to realize an earthing system coordinatedwith the characteristics of the device itself.The Table 2 shows the maximum values of earth resistance which can beobtained with residual current devices <strong>and</strong> making reference to a commonenvironment (50V):Table 2: Earth resistance valuesI ∆n[A]R A[Ω]0.01 50000.03 16660.1 5000.3 1660.5 1003 1610 530 1.6450 <strong>Electrical</strong> devices | <strong>ABB</strong>


4 <strong>Protection</strong> of human beings4.4 TT System<strong>Protection</strong> by means of overcurrent protective devicesThe choice of the automatic device for the protection against phase-to-earthfaults <strong>and</strong> indirect contact shall be carried out by coordinating properly thedisconnection times with the impedance of the fault loop.As a consequence, it is necessary to fulfill the following condition:Z s· I a≤ U 0where:Z Sis the impedance (in ohms) of the fault loop comprising- the source;- the line conductor up to the point of the fault;- the protective conductor of the exposed-conductive-parts;- the earthing conductor;- the earth electrode of the <strong>installation</strong>;- the earth electrode of the source;I ais the disconnection current in the times shown in Table 1 for final circuitswith currents not exceeding 32A or within 1 second for distribution circuits<strong>and</strong> for final circuits with currents exceeding 32A;U 0is the nominal a.c. r.m.s. voltage to earth (V).The choice of the automatic device shall be made by coordinating properly thedisconnection times with the impedance of the fault loop.The relationship Z s· I a≤ U 0may be expressed as :I a≤U 0Z s= I kL-to earthwhere I kL-to earthis the phase-to-earth fault current. Therefore, it is possible to statethat the protection against indirect contact is verified when the tripping current I aof the protective device (within the times shown in Table 1 or within 1s) is lowerthan the phase-to-earth fault current I kL-to earthat the exposed-conductive-partto be protected.It is to underline that in TT distribution systems the use of a residual currentdevice allows to have an earthing arrangement with an earth resistance valuewhich can be easily obtained, whereas the use of automatic circuit-breakersis possible only in case of low earth resistance values R A(very difficult to beobtained in practice); besides, in such circumstances, it could be very difficult tocalculate the impedance of the fault loop (Zs), because the earthing resistanceof the neutral cannot be considered negligible (in fact it could reach values ofthe same quantity of the earth resistance).<strong>ABB</strong> | <strong>Electrical</strong> devices 451


4 <strong>Protection</strong> of human beings4.5 TN SystemAn earth fault in a TN system involves the circuit represented in Figure 2:Figure 2=: Earth fault in TN systemI kL 10(TN-C)I kPEN(TN-S)L 2L 3PEN1SDC010036F0001The fault loop does not affect the earthing system <strong>and</strong> is basically formed by theconnection in series of the phase conductor <strong>and</strong> of the protective conductor.To provide a protection with automatic disconnection of the circuit, accordingto IEC 60364-4 prescriptions, the following condition shall be fulfilled:Z s· I a≤ U 0where:Z sis the impedance of the fault loop comprising the source, the liveconductor up to the point of the fault <strong>and</strong> the protective conductorbetween the point of the fault <strong>and</strong> the source [Ω];U 0is the nominal ac r.m.s. voltage to earth [V];I ais the disconnection current in amperes of the protective device withinthe times defined in Table 3 as a function of the rated voltage U 0forfinal circuits with currents not exceeding 32A or within 5 seconds fordistribution circuits <strong>and</strong> for final circuits with current exceeding 32A(for a description of the circuit typologies reference shall be madeto the indications given for TT systems).Table 3: Maximum disconnecting times for TN system50V


4 <strong>Protection</strong> of human beings4.5 TN SystemThe choice of the automatic device for the protection against phase-PE faults<strong>and</strong> against indirect contact shall be carried out by coordinating properly thedisconnection times with the impedance of the fault loop.In TN systems a bolted fault phase-PE on the LV side usually generates a currentsimilar to that of a short-circuit <strong>and</strong> the earth fault current flowing through theline conductor (or conductors) <strong>and</strong> the protective conductor does not absolutelyaffect the earthing arrangement.The relationship Z s· I a≤ U 0may be expressed as:I a≤U 0Z s= I kLPEwhere I kLPEis the phase-PE fault current. Therefore, it is possible to state thatthe protection against indirect contact is verified when the tripping currentI aof the protective device (within the times shown in Table 3 or within 5s) islower than the phase-PE fault current I kLPEat the exposed-conductive-part tobe protected.In TN systems the following devices are used for protection against indirectcontact:• circuit-breakers with thermomagnetic releases;• circuit-breakers with electronic releases;• residual current devices (TN-S only).Finally, it is important to highlight the fact that the residual current devicescannot be used in TN-C system, since the neutral <strong>and</strong> protective functionsare provided by a unique conductor: this configuration prevents the residualcurrent device from working.<strong>ABB</strong> | <strong>Electrical</strong> devices 453


4 <strong>Protection</strong> of human beings4.6 IT SystemAs represented in Figure 3, the earth fault current in an IT system flows throughthe line conductor capacitance to the power supply neutral point. For thisreason, the first earth fault is characterized by such an extremely low currentvalue to prevent the overcurrent protections from disconnecting; the derivingtouch voltage is very low.Figure3: Earth fault in IT systemL 1L 2I kL 3R tI kC 3 C 2 C 11SDC010037F0001According to IEC 60364-4, the automatic disconnection of the circuit in case ofthe first earth fault is not necessary only if the following condition is fulfilled:R A· I d≤ 50 Va.c.R A· I d≤ 120 Vd.c.where:R Ais the sum of the resistance, in ohms, of the earth electrode <strong>and</strong> protectiveconductor for exposed-conductive- parts;I dis the fault current, in amperes, of the first fault 2 of negligible impedancebetween a line conductor <strong>and</strong> an exposed-conductive-part; such valuetakes account of the leakage currents <strong>and</strong> of the total earthing impedanceof the electrical <strong>installation</strong>.If this condition is fulfilled, after the fault, the touch voltage on the exposedconductive-partwill be than 50 V (in alternating current), which is tolerable bythe human body for an indefinite time.In IT system <strong>installation</strong>s, an insulation monitoring device shall be provided to indicatethe presence of an anomalous condition after the occurrence of a fault.An insulation monitoring device complying with Std. IEC 61557-8 is a deviceconstantly monitoring the insulation of an electrical <strong>installation</strong>.It is aimed at signaling any remarkable reduction of the insulation level of an<strong>installation</strong> in order to find the cause of this reduction before a second faultoccurs, thus preventing disconnection of the power supply.2This is referred to by the St<strong>and</strong>ard as first fault to earth; the occurrence of two simultaneous faults ontwo different phases is called double fault to earth.454 <strong>Electrical</strong> devices | <strong>ABB</strong>


4 <strong>Protection</strong> of human beings4.6 IT Systemindicate the occurrence of a first earth fault; in the event of a second fault, thesupply shall be disconnected according to the following modalities:a) where exposed conductive parts are earthed in groups or individually, theconditions for protection are the same as for TT systems:where the exposed-conductive-parts are earthed in groups or individually,the following condition shall be fulfilled:R A· I a≤ 50Vwhere:R Ais the sum of the resistance of the earth electrode <strong>and</strong> of the protectiveconductor for the exposed-conductive-parts;I ais the current causing automatic disconnection of the protective device ina time complying with that for TT systems;b) where exposed conductive parts are interconnected by a protective conductorcollectively earthed, the conditions of a TN system apply; in particular,the following conditions shall be fulfilled:if the neutral is not distributed:Zs ≤U2·I awhere:U 0is the nominal voltage between line conductor <strong>and</strong> neutral conductor;U is the nominal voltage between line conductors;Zs is the impedance of the fault loop comprising the line conductor <strong>and</strong> theprotective conductor of the circuit;Z’s is the impedance of the fault loop comprising the neutral conductor <strong>and</strong>the protective conductor of the circuit;I aif the neutral is distributed:Z’s ≤ U 02·I ais the current causing operation of the protective device within the timerequired for TN systems.The St<strong>and</strong>ard suggests not to distribute the neutral conductor in IT systems.One of the reasons is the real difficulty in fulfilling the condition prescribed forthe impedance of the double fault loop Z’s. As a matter of fact, in the presenceof a neutral conductor distributed, the impedance must be 58% smaller thanthe impedance Zs, which is verified in the event of a double fault between thephases; in this way, it becomes evident that there is a greater difficulty in theco-ordination with the automatic disconnection device which must trip to provideprotection against indirect contact.Moreover, above all for quite complex industrial <strong>installation</strong>s, the presence of theneutral distributed may involve the risk of an accidental connection of it at anypoint to earth, thus eliminating the advantages offered by IT systems.The residual current device threshold shall be carefully chosen in order to avoidunwanted tripping, due also to the particular path followed by the first faultcurrent through the line conductor capacitance to the power supply neutralpoint (instead of the faulted line, another sound line with higher capacitancecould be affected by a higher fault current value).<strong>ABB</strong> | <strong>Electrical</strong> devices 455


4.7 Residual current devices (RCDs)4 <strong>Protection</strong> of human beingsGeneralities on residual current circuit-breakersThe operating principle of the residual current release is basically the detectionof an earth fault current, by means of a toroid transformer which embraces allthe live conductors, included the neutral if distributed.Figure 1: Operating principle of the residual current deviceLNRT1SDC010041F0001In absence of an earth fault, the vectorial sum of the currents I ∆is equal to zero;in case of an earth fault if the I ∆value exceeds the rated residual operating currentI ∆n, the circuit at the secondary side of the toroid sends a comm<strong>and</strong> signal to adedicated opening coil causing the tripping of the circuit-breaker.A first classification of RCDs can be made according to the type of the faultcurrent they can detect:- AC type: the tripping is ensured for residual sinusoidal alternating currents,whether suddenly applied or slowly rising;- A type: tripping is ensured for residual sinusoidal alternating currents <strong>and</strong>residual pulsating direct currents, whether suddenly applied or slowly rising;- B type: tripping is ensured for residual direct currents, for residual sinusoidalalternating currents <strong>and</strong> residual pulsating direct currents, whether suddenlyapplied or slowly rising.Another classification referred to the operating time delay is:- undelayed type;- time delayed S-type.456 <strong>Electrical</strong> devices | <strong>ABB</strong>


4 <strong>Protection</strong> of human beingsRCDs can be coupled, or not, with other devices; it is possible to distinguishamong:- pure residual current circuit-breakers (RCCBs): they have only the residualcurrent release <strong>and</strong> can protect only against earth fault. They must be coupledwith thermomagnetic circuit-breakers or fuses, for the protection againstthermal <strong>and</strong> dynamical stresses;- residual current circuit-breakers with overcurrent protection (RCBOs): theyare the combination of a thermomagnetic circuit-breaker <strong>and</strong> a RCD; for thisreason, they provide the protection against both overcurrents as well as earthfault current;- residual current circuit-breakers with external toroid: they are used in industrialplants with high currents. They are composed by a release connected to anexternal toroid with a winding for the detection of the residual current; in caseof earth fault, a signal comm<strong>and</strong>s the opening mechanism of a circuit-breakeror a line contactor.Given I ∆nthe operating residual current, a very important parameter for residualcurrent devices is the residual non-operating current, which represents themaximum value of the residual current which does not cause the circuit-breakertrip; it is equal to 0.5 I ∆n. Therefore, it is possible to conclude that:- for I ∆< 0.5⋅I ∆nthe RCD shall not operate;- for 0.5⋅I ∆n< I ∆< I ∆nthe RCD could operate;- for I ∆> I ∆nthe RCD shall operate.For the choice of the rated operating residual current, it is necessary to consider,in addition to the coordination with the earthing system, also the whole of theleakage currents in the plant; their vectorial sums on each phase shall not begreater than 0.5⋅I ∆nin order to avoid unwanted tripping.Discrimination between RCDsThe St<strong>and</strong>ard IEC 60364-5-53 states that discrimination between residual currentprotective devices installed in series may be required for service reasons,particularly when safety is involved, to provide continuity of supply to the partsof the <strong>installation</strong> not involved by the fault, if any. This discrimination can beachieved by selecting <strong>and</strong> installing RCDs in order to provide the disconnectionfrom the supply by the RCD closest to the fault.There are two types of discrimination between RCDs:- horizontal discrimination: it provides the protection of each line by using adedicated residual current circuit-breaker; in this way, in case of earth fault,only the faulted line is disconnected, since the other RCDs do not detect anyfault current. However, it is necessary to provide protective measures againstindirect contacts in the part of the switchboard <strong>and</strong> of the plant upstream theRCD;- vertical discrimination: it is realized by using RCDs connected in series.Figure 2: Horizontal discrimination between RCDs4.7 Resiual current devices (RCDs)I∆I ∆ 0.3 At 0.5 sI∆I ∆ 0.3 At 0.5 s<strong>ABB</strong> | <strong>Electrical</strong> devices 457


4 <strong>Protection</strong> of human beingsFigure 3: Vertical discrimination between RCDs4.7 Resiual current devices (RCDs)According to IEC 60364-5-53, to ensure discrimination between two residualcurrent protective devices in series, these devices shall satisfy both the followingconditions:- the non-actuating time-current characteristic of the residual current protectivedevice located on the supply side (upstream) shall lie above the total operatingtime-current characteristic of the residual current protective device located onthe load side (downstream);- the rated residual operating current on the device located on the supply sideshall be higher than that of the residual current protective device located onthe load side.The non-actuating time-current characteristic is the curve reporting themaximum time value during which a residual current greater than the residualnon-operating current (equal to 0.5.I ∆n) involves the residual current circuitbreakerwithout causing the tripping.As a conclusion, discrimination between two RCDs connected in series canbe achieved:- for S type residual current circuit-breakers, located on the supply side, (complyingwith IEC 61008-1 <strong>and</strong> IEC 61009), time-delayed type, by choosinggeneral type circuit-breakers located downstream with I ∆nequal to one thirdof I ∆nof the upstream ones;- for electronic residual current releases by choosing the upstream device withtime <strong>and</strong> current thresholds directly greater than the downstream device,keeping carefully into consideration the tolerances.For the protection against indirect contacts in distribution circuits in TT system,the maximum disconnecting time at I ∆nshall not exceed 1 s (IEC 60364-4-41,par. 411.3.2.4)458 <strong>Electrical</strong> devices | <strong>ABB</strong>


4 <strong>Protection</strong> of human beings4.8 Maximum protected length for theprotection of human beingsAs described in the previous chapters, the St<strong>and</strong>ards give indications aboutthe maximum disconnecting time for the protective devices, in order to avoidpathophysiological effects for people touching live parts.For the protection against indirect contact, it shall be verified that the circuitbreakertrips within a time lower than the maximum time stated by the St<strong>and</strong>ard;this verification is carried out by comparing the minimum short-circuit currentof the exposed conductive part to be protected with the operating currentcorresponding to the time stated by the St<strong>and</strong>ard.The minimum short-circuit current occurs when there is a short-circuit betweenthe phase <strong>and</strong> the protective conductors at the farthest point on the protectedconductor.For the calculation of the minimum short-circuit current, an approximate methodcan be used, assuming that:- a 50 % increasing of the conductors resistance, with respect to the 20 °Cvalue, is accepted, due to the overheating caused by the short-circuitcurrent;- a 80 % reduction of the supply voltage is considered as effect of theshort-circuit current;- the conductor reactance is considered only for cross sections larger than95 mm 2 .The formula below is obtained by applying Ohm’s law between the protectivedevice <strong>and</strong> the fault point.Legend of the symbols <strong>and</strong> constants of the formula:- 0.8 is the coefficient representing the reduction of the voltage;- 1.5 is the coefficient representing the increasing in the resistance;- U ris the rated voltage between phases;- U 0is the rated voltage between phase <strong>and</strong> ground;- S is the phase conductor cross section;- S Nis the neutral conductor cross section;- S PEis the protection conductor cross section;- ρ is the conductor resistivity at 20 °C;- L is the length of the cable;- is the ratio between the total phase conductor cross section(single phase conductor cross section S multiplied by n, number ofconductors in parallel) <strong>and</strong> the protective conductor cross section S PEassuming they are made of the same conductor material;- is the ratio between the total neutral conductor crosssection (single neutral conductor cross section S Nmultiplied by n, numberof conductors in parallel) <strong>and</strong> the protective conductor cross section S PEassuming they are made of the same conductor material;- k 1is the correction factor which takes into account the reactance of cableswith cross section larger than 95 mm 2 , obtainable from the followingtable:Phase conductor cross section[mm 2 ] 120 150 185 240 300k 10.90 0.85 0.80 0.75 0.72<strong>ABB</strong> | <strong>Electrical</strong> devices 459


4.8 Maximum protected length for the protection of human beings4 <strong>Protection</strong> of human beings- k 2is the correction factor for conductors in parallel, obtainable by thefollowing formula:where n is the number of conductor in parallel per phase;- 1.2 is the magnetic threshold tolerance allowed by the St<strong>and</strong>ard.TN systemThe formula for the evaluation of the minimum short circuit current is:<strong>and</strong> consequently:DyL1L2L3NPEPEPEI k N L3 L2 L1R EN1SDC010043F0001IT systemThe formulas below are valid when a second fault turns the IT system into aTN system.It is necessary to separately examine <strong>installation</strong>s with neutral not distributed<strong>and</strong> neutral distributed.460 <strong>Electrical</strong> devices | <strong>ABB</strong>


4.8 Maximum protected length for the protection of human beings4 <strong>Protection</strong> of human beingsNeutral not distributedWhen a second fault occurs, the formula becomes:<strong>and</strong> consequently:DyL1L2L3PEZPEPEI k L3 L2 L1R ENPEI kL3L2 L11SDC010044F0001Neutral distributedCase A: three-phase circuits in IT system with neutral distributedThe formula is:<strong>and</strong> consequently:Case B: three-phase + neutral circuits in IT system with neutral distributedThe formula is:<strong>and</strong> consequently:<strong>ABB</strong> | <strong>Electrical</strong> devices 461


4.8 Maximum protected length for the protection of human beings4 <strong>Protection</strong> of human beingsDyL1L2L3NPEZPEPEI k L3 L2 L1RAENPEI kNL3L2 L1B1SDC010045F0001Note for the use of the tablesThe tables showing the maximum protected length (MPL) have been definedconsidering the following conditions:- one cable per phase;- rated voltage equal to 400 V (three-phase system);- copper cables;- neutral not distributed, for IT system only;- protective conductor cross section according to Table 1:Table 1: Protective conductor cross sectionPhase conductor cross section S Protective conductor cross section S PE[mm 2 ] [mm 2 ]S ≤ 16S16 < S ≤ 35 16S > 35 S/2Note: phase <strong>and</strong> protective conductors having the same isolation <strong>and</strong> conductive materialsWhenever the S function (delayed short-circuit) of electronic releases is usedfor the definition of the maximum protected length, it is necessary to verify thatthe tripping time is lower than the time value reported in Chapter 4.5 Table 1for TN systems <strong>and</strong> in Chapter 4.6 Table 1 for IT systems.For conditions different from the reference ones, the following correction factorsshall be applied.462 <strong>Electrical</strong> devices | <strong>ABB</strong>


4.8 Maximum protected length for the protection of human beings4 <strong>Protection</strong> of human beingsCorrection factorsCorrection factor for cable in parallel per phase: the value of the maximumprotected length read in Table 2 (TN system) or Table 3 (IT system) shall bemultiplied by the following factor:n 2 3 4 5 6 7 8k p2 2.7 3 3.2 3.3 3.4 3.5n is the number of conductors in parallel per phaseCorrection factor for three-phase voltage different from 400 V: the value ofthe maximum protected length read in Table 2 (TN system) or Table 3 (IT system)shall be multiplied by the following factor:voltage [V] 230 400 440 500 690k V0.58 1 1.1 1.25 1.73For 230 V single-phase systems, no correction factor is necessary.Correction factor for aluminium cables: the value of the maximum protectedlength read in Table 2 (TN system) or Table 3 (IT system) shall be multiplied bythe following factor:k Al0.64Correction factor for protective conductor cross section S PEdifferentfrom the cross sections stated in Table 1: the value of the maximum protectedlength shall be multiplied by the coefficient corresponding to the phaseconductor cross section <strong>and</strong> to the ratio between the protective conductor (PE)<strong>and</strong> the phase cross sections:S PE/S 0.5 0.55 0.6 0.66 0.75 0.87 1 1.25 1.5 2S≤16 mm 2 0.67 0.71 0.75 0.80 0.86 0.93 1.00 1.11 1.20 1.3325 mm 2 0.85 0.91 0.96 1.02 1.10 1.19 1.28 1.42 1.54 1.7135 mm 2 1.06 1.13 1.20 1.27 1.37 1.48 1.59 1.77 1.91 2.13>35 mm 2 1.00 1.06 1.13 1.2 1.29 1.39 1.5 1.67 1.8 2.00k PECorrection factor for neutral distributed in IT systems (for Table 3 only):the value of the maximum protected length shall be multiplied by 0.58.<strong>ABB</strong> | <strong>Electrical</strong> devices 463


5.1 Operating principle5 Photovoltaic plantsA photovoltaic (PV) plant transforms directly <strong>and</strong> instantaneously solar energyinto electrical energy without using any fuels. As a matter of fact, the photovoltaic(PV) technology exploits the photoelectric effect, through which somesemiconductors suitably “doped” generate electricity when exposed to solarradiation.The main advantages of photovoltaic (PV) plants can be summarized as follows:• distribuited generation where needed;• no emission of polluting materials;• saving of fossil fuels;• reliability of the plants since they do not have moving parts (useful lifeusually over 20 years);• reduced operating <strong>and</strong> maintenance costs;• system modularity (to increase the plant power it is sufficient to raise thenumber of panels) according to the real requirements of users.However, the initial cost for the development of a PV plant is quite high due to amarket which has not reached its full maturity from a technical <strong>and</strong> economicalpoint of view. Moreover the generation of power is erratic due to the variabilityof the solar energy source.The annual electrical power output of a PV plant depends on different factors.Among them:• solar radiation incident on the <strong>installation</strong> site;• inclination <strong>and</strong> orientation of the panels;• presence or not of shading;• technical performances of the plant components (mainly modules <strong>and</strong>inverters).The main applications of PV plants are:1. <strong>installation</strong>s (with storage systems) for users isolated from the grid;2. <strong>installation</strong>s for users connected to the LV grid;3. solar PV power plants, usually connected to the MV grid.Feed-in Tariff incentives are granted only for the applications of type 2 <strong>and</strong> 3,in plants with rated power not lower than 1 kW.A PV plant is essentially constituted by a generator (PV panels), by a supportingframe to mount the panels on the ground, on a building or on any buildingstructure, by a system for power <strong>control</strong> <strong>and</strong> conditioning, by a possible energystorage system, by electrical switchboards <strong>and</strong> switchgear assemblies housingthe switching <strong>and</strong> protection equipment <strong>and</strong> by the connection cables.464 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.2 Main components of a photovoltaicplants5.2.1 Photovoltaic generatorThe elementary component of a PV generator is the photovoltaic cell where theconversion of the solar radiation into electric current is carried out.The cell is constituted by a thin layer of semiconductor material, generallysilicon properly treated, with a thickness of about 0.3 mm <strong>and</strong> a surface from100 to 225 cm 2 .Silicon, which has four valence electrons (tetravalent), is “doped” by adding trivalentatoms (e.g. boron – P doping) on one “layer” <strong>and</strong> quantities of pentavalentatoms (e.g. phosphorus – N doping) on the other one. The p-type region has anexcess of holes, whereas the n-type region has an excess of electrons.In the contact area between the two layers differently doped (P-N junction), theelectrons tend to move from the electron rich half (N) to the electron poor half(P), thus generating an accumulation of negative charge in the P region. A dualphenomenon occurs for the electron holes, with an accumulation of positivecharge in the region N. Therefore an electric field is created across the junction<strong>and</strong> it opposes the further diffusion of electric charges.By applying a voltage from the outside, the junction allows the current to flowin one direction only (diode functioning).When the cell is exposed to light, due to the photovoltaic effect 1 , some electronholecouples arise both in the N region as well as in the P region.The internal electric field allows the excess electrons (derived from the absorptionof the photons from part of the material) to be separated from the holes <strong>and</strong>pushes them in opposite directions in relation one to another. As a consequence,once the electrons have passed the depletion region they cannot move backsince the field prevents them from flowing in the reverse direction.By connecting the junction with an external conductor, a closed circuit is obtained,in which the current flows from the layer N, having higher potential, tothe layer N, having lower potential, as long as the cell is illuminated.The silicon region which contributes to supply the current is the area surroundingthe P-N junction; the electric charges form in the far off areas, but there is notthe electric field which makes them move <strong>and</strong> therefore they recombine.As a consequence it is important that the PV cell has a great surface: the greaterthe surface, the higher the generated current.1The photovoltaic effect occurs when an electron in the valence b<strong>and</strong> of a material (generallya semiconductor) is promoted to the conduction b<strong>and</strong> due to the absorption ofone sufficiently energetic photon (quantum of electromagnetic radiation) incident on thematerial. In fact, in the semiconductor materials, as for insulating materials, the valenceelectrons cannot move freely, but comparing semiconductor with insulating materials theenergy gap between the valence b<strong>and</strong> <strong>and</strong> the conduction b<strong>and</strong> (typical of conductingmaterials) is small, so that the electrons can easily move to the conduction b<strong>and</strong> whenthey receive energy from the outside. Such energy can be supplied by the luminousradiation, hence the photovoltaic effect.<strong>ABB</strong> | <strong>Electrical</strong> devices 465


5 Photovoltaic plants5.2 Main components of a photovoltaic plantsFigure 1 represents the photovoltaic effect <strong>and</strong> the energy balance showingthe considerable percentage of incident solar energy which is not convertedinto electric energy.Photovoltaic effect1 Separation of the charge2 Recombination3 Transmission4 Reflection <strong>and</strong> shading of the front contacts4NegativeelectrodeN Layer1Positivecontact211P layerP-N region3100% of the incident solar energy- 3% reflection losses <strong>and</strong> shading of the front contacts- 23% photons with high wavelength, with insufficient energy to freeelectrons; heat is generated- 32% photons with short wavelength, with excess energy (transmission)- 8.5% recombination of the free charge carriers- 20% electric gradient in the cell, above all in the transition regions- 0.5% resistance in series, representing the conduction losses= 13% usable electric energyUnder st<strong>and</strong>ard operating conditions (1W/m 2 irradiance at a temperature of25°C) a PV cell generates a current of about 3A with a voltage of 0.5V <strong>and</strong> apeak power equal to 1.5-1.7Wp.On the market there are photovoltaic modules for sale constituted by an assemblyof cells.The most common ones comprise 36 cells in 4 parallel row connected in series,with an area ranging from 0.5 to 1m 2 .Several modules mechanically <strong>and</strong> electrically connected form a panel, that is acommon structure which can be anchored to the ground or to a building.Several panels electrically connected in series constitute an array <strong>and</strong> severalarrays, electrically connected in parallel to generate the required power, constitutethe generator or photovoltaic field.466 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.2 Main components of a photovoltaic plants5.2.2 InverterThe power conditioning <strong>and</strong> <strong>control</strong> system is constituted by an inverter thatconverts direct current to alternating current <strong>and</strong> <strong>control</strong>s the quality of theoutput power to be delivered to the grid, also by means of an L-C filter insidethe inverter itself.The transistors, used as static switches, are <strong>control</strong>led by an opening-closingsignal which, in the simplest mode, would result in an output square waveform.Principle scheme of a single-phase inverter+L-NTo obtain a waveform as sinusoidal as possible, a more sophisticated technique– Pulse Width Modulation (PWM) – is used; PWM technique allows aregulation to be achieved on the frequency as well as on the r.m.s. value ofthe output waveform.The power delivered by a PV generator depends on the point where it operates.In order to maximize the energy supply by the plant, the generator shall adaptto the load, so that the operating point always corresponds to the maximumpower point. To this purpose, inside the inverter a <strong>control</strong>led chopper calledMaximum Power Point Tracker (MPPT) is used; the MPPT calculates instantby instant the pair of values “voltage-current” of the generator at which themaximum available power is produced.The MPPT systems commercially used identify the maximum power point onthe characteristic curve of the generator by causing, at regular intervals, smallvariations of loads which determine deviations of the voltage-current values <strong>and</strong>evaluating if the new product I x V is higher or lower then the previous one. Incase of a rise, the load conditions are kept varying in the considered direction.In the other case, the conditions are modified in the opposite direction.Due to the characteristics of the required performances the inverters forst<strong>and</strong>-alone plants <strong>and</strong> for grid-connected plants shall have different characteristics:• in the st<strong>and</strong>-alone plants the inverters shall be able to supply a voltageAC side. as constant as possible at the varying of the production of thegenerator <strong>and</strong> of the load dem<strong>and</strong>;• in the grid-connected plants the inverters shall reproduce, as exactly aspossible, the network voltage <strong>and</strong> at the same time try to optimize <strong>and</strong>maximize the energy output of the PV panels.<strong>ABB</strong> | <strong>Electrical</strong> devices 467


5.3 Typologies of photovoltaic plants5 Photovoltaic plants5.3.1 St<strong>and</strong>-alone plantsSt<strong>and</strong>-alone plants are plants which are not connected to the grid <strong>and</strong> consist ofPV panels <strong>and</strong> of a storage system which guarantees electric energy supply alsowhen lighting is poor or when it is dark. Since the current delivered by the PVgenerator is DC power, if the user plant needs AC current an inverter becomesnecessary. Such plants are advantageous from a technical <strong>and</strong> financial pointof view whenever the electric network is not present or whenever it is not easyto reach, by replacing motor generator sets.Besides, in a st<strong>and</strong>-alone configuration, the PV field is over-dimensioned sothat, during the insolation hours, both the load supply as well as the rechargeof the storing batteries can be guaranteed with a certain safety margin to takeinto account the days of poor insolation.At present the most common applications are used to supply:• pumping water equipment;• radio repeaters, weather or seismic observation <strong>and</strong> data transmissionstations;• lightning systems;• systems of signs for roads, harbors <strong>and</strong> airports;• service supply in campers;• advertising <strong>installation</strong>s;• refuges at high altitudes.5.3.2 Grid-connected plantsPermanently grid-connected plants draw power from the grid during the hourswhen the PV generator cannot produce the energy necessary to satisfy theneeds of the consumer.On the contrary, if the PV system produces excess electric power, the surplusis put into the grid, which therefore can operate as a big accumulator: as aconsequence, grid-connected systems don’t need accumulator banks.These plants offer the advantage of distributed - instead of centralized – generation:in fact the energy produced near the consumption area has a value higherthan that produced in traditional large power plants, because the transmissionlosses are limited <strong>and</strong> the expenses of the big transport <strong>and</strong> dispatch electricsystems are reduced. In addition, the energy production in the insolation hoursallows the requirements to the grid to be reduced during the day, that is whenthe dem<strong>and</strong> is higher.468 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.4 Earthing <strong>and</strong> protection againstindirect contactThe concept of earthing applied to a photovoltaic (PV) system may involve boththe exposed conductive parts (e.g. metal frame of the panels) as well as thegeneration power system (live parts of the PV system e.g. the cells).A PV system can be earthed only if it is galvanically separated (e.g. by meansof a transformer) from the electrical network by means of a transformer. A PVinsulated system could seem apparently safer for the people touching a livepart; as a matter of fact, the insulation resistance to earth of the live parts is notinfinite <strong>and</strong> then person is passed through by a current returning through suchresistance. This current rises when the voltage to earth of the plant <strong>and</strong> theplant size increase since the insulation resistance to earth decreases. Besides,the physiological decay of the insulators, due to the passage of time <strong>and</strong> thepresence of humidity, reduces the insulation resistance itself. Consequently, invery big plants, the current passing through a person in touch with the live partmay cause electrocution <strong>and</strong> therefore the advantage over the earthed systemsis present only in case of small plants.5.4.1 Plants with transformerIn the plants with transformer, in addition to the analysis of the PV system eitherinsulated or earthed, for the protection against indirect contacts it is necessaryto make a difference between the exposed conductive parts upstream <strong>and</strong>downstream the transformer 2 .5.4.1.1 Exposed conductive parts on the load side of the transformerPlant with IT systemIn this type of plant the live parts result insulated from earth, whereas the exposedconductive parts are earthed 3 (Figure 2).Figure 2A+ - + - + -BIdLoadRe2In this case upstream <strong>and</strong> downstream are referred to the direction of the electric powerproduced by the PV plant.3For safety reasons the earthing system of the PV plant results to be in common with theconsumer’s one.<strong>ABB</strong> | <strong>Electrical</strong> devices 469


5 Photovoltaic plants5.4 Earthing <strong>and</strong> protection against indirect contactIn this case the earthing resistance R eof the exposed conductive parts shallmeet the condition (CEI 64-8):R e≤ 120I d(1)where I dis the current of first fault to earth, which is not known in advance, butwhich is generally very low in small-sized plants.As a consequence, the earthing resistance Re of the consumer plant, which isdefined for a fault in the network, usually satisfies only the relation (1).In case of a double earth fault, since the PV generator is a current generator, thevoltage of the interconnected exposed conductive parts shall be lower than:I sc . R eqp≤ 120V (2)where I scis the short-circuit current of the cells involved, whereas R eqpis theresistance of the conductor interconnecting the exposed conductive parts affectedby fault. For instance, if R eqp= 1Ω (value approximated by excess), therelation (2) is fulfilled for I scnot exceeding 120A, which is usual in small-sizedplants; therefore the effective touch voltage in case of a second earth fault doesnot result hazardous.On the contrary, in large-sized plants it is necessary to reduce to acceptable limitsthe chance that a second earth fault occurs, by eliminating the first earth faultdetected by the insulation <strong>control</strong>ler (either inside the inverter or external).Plant with TN systemIn this type of plant the live parts <strong>and</strong> the exposed conductive parts are connectedto the same earthing system (earthing system of the consumer’s plant).Thus a TN system on the DC side is obtained (Figure 3).Figure 3A+ - + - + -BIdLoadRe470 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.4 Earthing <strong>and</strong> protection against indirect contactIn the presence of an earth fault, a short-circuit occurs as in the usual TN systems,but such current cannot be detected by the maximum current devicessince the characteristic of the PV plants is the generation of fault currents withvalues not much higher than the rated current.Therefore, as regards the dangerousness of this fault, the considerations madein the previous paragraph 4 on the second fault for an IT system are valid.4The Std. IEC 60364-7 recommends that the whole <strong>installation</strong> on the DC side (switchboards,cables, <strong>and</strong> terminal boards) is erected by use of class II devices or equivalentinsulation.5.4.1.2 Exposed conductive parts on the supply side of the transformerTake into consideration the network-consumer system of TT type.The exposed conductive parts belonging to the consumer’s plant protected bya residual current circuit-breakers positioned at the beginning of the consumer’splant (Figure 4), result protected both towards the network as well as towardsthe PV generator.Figure 4A+ -IdPVIdrGridBRnIdLoadReThere must not be an exposed conductive part between the parallel pointA-B <strong>and</strong> the network because in such case the normative requirement that allthe exposed conductive parts of a consumer’s plant in a TT system must beprotected by a residual current circuit-breaker.<strong>ABB</strong> | <strong>Electrical</strong> devices 471


5 Photovoltaic plantsAs regards the exposed conductive parts upstream the parallel point A-B,such as for instance the exposed conductive part of the transformer or of theinverter when the transformer is incorporated, a residual current device 5 shall beinterposed as Figure 5 shows; this residual current device detects the leakagecurrents coming both from the network as well as from the PV generator.When the residual current device trips due to an earth fault current, the invertergoes in st<strong>and</strong> by due to lack of network voltage.Figure 55.4 Earthing <strong>and</strong> protection against indirect contactA+ -IdBIdrGridRnReIdIdPVLoad5The rated residual current shall be coordinated with the earth resistance Re, in compliancewith the usual relation of the TT systems: R e≤ 50I dn472 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.4 Earthing <strong>and</strong> protection against indirect contactOn the contrary, if the network-consumer system is type TN, for both the supplypossibilities, either from the network or from the PV generator, residual currentcircuit-breakers are not needed provided that the fault current on the AC sidecauses the tripping of the overcurrent devices by the times prescribed in theStd. (Figure 6).Figure 6A+ -IdPVBIdrGridRnLoad5.4.2 Plants without transformerIn case of absence of the separation transformer between the PV <strong>installation</strong><strong>and</strong> the network, the PV <strong>installation</strong> itself shall be insulated from earth in itsactive parts becoming an extension of the supply network, generally with apoint connected to earth (TT or TN system).As regards the exposed conductive parts of the consumer’s plant <strong>and</strong> upstreamthe parallel point A-B, from a conceptual point of view, what described inclause 6.4.1.2 is still valid.On the DC side an earth fault on the exposed conductive parts determinesthe tripping of the residual current circuit-breaker positioned downstream theinverter (Figure 7). After the tripping of the residual current device, the invertergoes in st<strong>and</strong> by due to the lack of network voltage, but the fault is suppliedby the PV generator. Since the PV system is type IT, the considerations madein clause 6.4.1.1.1 are valid.<strong>ABB</strong> | <strong>Electrical</strong> devices 473


5 Photovoltaic plants5.4 Earthing <strong>and</strong> protection against indirect contactFor earth faults on the DC side <strong>and</strong> on the exposed conductive parts upstreamthe parallel point A-B, the residual current circuit-breaker on the load side ofthe inverter is passed through by a residual current which is not alternating.Therefore such device must be of type B 6 , unless the inverter is by constructionsuch as not to inject DC earth fault currents (IEC 60364-7) 7 .Figure 7IdPVAIdrIdtype BGrid+ - + - + -BRnLoadRe6The residual current device of type B detects the following typologies of earth faultcurrents:• alternating (also at frequency exceeding the network one, e.g. up to 1000 Hz);• pulsating unidirectional;• direct.7The Std. CEI EN 62040-1 prescribes that the protection of the UPS (including an inverter)against earth faults is realized by using residual current devices type B (for three-phaseUPS) <strong>and</strong> type A (for single-phase UPS), whenever an earth fault current with DC componentsmay be possible according to the UPS design.474 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.5 Protectin against overcurrents<strong>and</strong> overvoltagesWhen defining the layout of a photovoltaic plant it is necessary to provide,where needed, for the protection of the different sections of the plant againstovercurrents <strong>and</strong> overvoltages of atmospheric origin.Here are given, at first, the conditions for the protection against overcurrentsin the PV plant on the supply (DC side) <strong>and</strong> on the load side of the inverter(AC side), then the methods for the protection of the plant against any damagecaused by possible direct or indirect fulmination 8 .5.5.1 <strong>Protection</strong> against overcurrents on DC side5.5.1.1 Cable protectionsFrom the point of view of the protection against overloads, it is not necessary toprotect the cables (CEI 64-8/7) if they are chosen with a current carrying capacitynot lower than the maximum current which might affect them (1.25 Isc) 9 .9Isc is the short-circuit current in the module under st<strong>and</strong>ard test conditions <strong>and</strong> thetwenty-five per cent rise takes the insolation values exceeding 1kW/m2 into account.As regards the short-circuit, the cables on the DC side are affected by suchovercurrent in case of:• fault between the polarity of the PV system;• fault to earth in the earthed systems;• double fault to earth in the earth-insulated systems.A short-circuit on a cable for the connection string to subfield switchboard(fault 1 of Figure 8) is supplied simultaneously upstream of the load side of thestring under consideration (I cc1= 1.25 . I sc) downstream of the other x-1 stringsconnected to the same inverter (I cc2= (x-1) . 1.25 . I sc).If the PV plant is small-sized with two strings only (x=2), it results thatI cc2= 1.25 . I sc= I cc1<strong>and</strong> therefore it is not necessary to protect the string cablesagainst short-circuit. On the contrary, when three or more strings (x≥3) areconnected to the inverter, the current I cc2is higher than the service current <strong>and</strong>therefore the cables must be protected against the short-circuit when theircurrent carrying capacity is lower than I cc2, that is I z< (x-1) . 1.25 . I sc.A short-circuit between a subfield switchboard <strong>and</strong> the inverter switchboard(fault 2 of the Figure 8) is supplied upstream by the y strings in parallel of thesubfield (I cc3) <strong>and</strong> downstream by the remaining (x-y) strings relevant to thesame inverter switchboard.The short-circuit current I cc3= y . 1.25 . I sccoincides with the service current ofthe circuit between the subfield switchboard <strong>and</strong> inverter, whereas the currentI cc4= (x-y) . 1.25 . I scis higher than the service current if x-y > y ⇒ x > 2y.In this case it is necessary to protect the cable against the short-circuit if itscurrent carrying capacity is lower than I sc4, that is I z


5 Photovoltaic plants5.5 Protectin against overcurrents on DC sideFigure 8String+–Cable 1SubfieldswitchboardAy+–Cable 2Fault 1Isc3Isc1Isc2Fault 2SubfieldswitchboardIsc4x+––B++–parallel pointwith the gridInverterswitchboard+–“A” represents the protective device in the subfield switchboard for the protectionof the “cable 1” connecting the string to the switchboard itself.“B” represents the protection device installed in the inverter switchboard to protectthe “cable 2” for the connection between the inverter <strong>and</strong> the subfieldswitchboard.“y” number of strings connected to the same subfield switchboard.“x” total number of strings connected to the same inverter.476 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.5 Protectin against overcurrents on DC side5.5.1.2 <strong>Protection</strong> of the strings against reverse currentDue to shading or fault a string becomes passive, absorbing <strong>and</strong> dissipating theelectric power generated by the other strings connected in parallel to the sameinverter through a current which flows through the string under considerationin a reverse direction with respect to that of st<strong>and</strong>ard operation, with possibledamages to the modules. These are able to withst<strong>and</strong> a reverse current rangingfrom 2.5 <strong>and</strong> 3 I sc(IEC TS 62257-7-1).Since with x strings in parallel connected to the same inverter the highest reversecurrent is equal to I inv= (x-1) . 1.25 . I sc, it is not necessary to protect the stringsI inv≤ 2.5 . I scif that is (x-1) . 1.25 ≤ 2.5 ⇒ x ≤ 3 10 .5.5.1.3 Behaviour of the inverterThe contribution to the short-circuit on the DC side of the inverter may comefrom the grid <strong>and</strong> from the discharge of the capacitors inside the inverter.The grid current is due to the recirculating diodes of the bridge inverter whichin this case act as a bridge rectifier. Such current is limited by the impedancesof the transformer <strong>and</strong> of the inductors belonging to the output circuit <strong>and</strong> bythe protection fuses of the inverter on the AC side chosen so that they can limitthe thermal effects of possible internal faults on the semiconductors.As a consequence the I 2 t passing through will be normally reduced. Indicativelya final current value (internal capacitors completely discharged) of 10In can bean upper limit value. This current is present in case of inverter with galvanicinsulation at 50Hz, while it is null in case of inverter without transformer.In fact these inverters usually have an input DC/DC converter so that the operationon a wide voltage range of the PV generator is guaranteed; this converter,due to its constructive typology, includes at least one blocking diodes whichprevents the contribution of the grid current to the short-circuit.The discharge current of the capacitors is limited by the cables between inverter<strong>and</strong> fault <strong>and</strong> exhausts itself with exponential trend: the lowest the impedance ofthe cable stretch, the highest the initial current, but the lowest the time constantof the discharge. The energy which flows is limited to that one initially stored inthe capacitors. Moreover, if a blocking diode or other similar device is in serieswith one of the two poles, this contribution to the short-circuit is null.In each case, the short-circuit on the DC side causes a drop of the direct voltage,the inverter certainly shuts down <strong>and</strong> probably is disconnected from the grid.Normally the shut down times of the inverter are of the order of some milliseconds,while the disconnection times may be of the order of some dozens ofmilliseconds. In the interval between the shut down <strong>and</strong> the disconnection, thegrid might cause the above mentioned effect, while the internal capacitors, ifinvolved, participate up to their complete discharge.10The blocking diodes can be used, but they do not replace the protections againstovercurrent (IEC TS 62257-7-1), since it is taken into consideration the possibility thatthe blocking diode does not work properly <strong>and</strong> is short-circuited. Moreover the diodesintroduce a loss of power due to the voltage drop on the junction, a loss which can bereduced by using Schottky diodes with 0.4V drop instead of 0.7V of conventional diodes.However the rated reverse voltage of the diodes shall be ≥ 2 U oc<strong>and</strong> the rated current≥ 1.25 I sc(CEI Guide 82-25).<strong>ABB</strong> | <strong>Electrical</strong> devices 477


5 Photovoltaic plants5.5 Protectin against overcurrents on DC sideHowever, the influences of both the grid <strong>and</strong> the internal capacitors on theshort-circuit have only a transient nature <strong>and</strong> they are not such as to affectthe sizing of the protection, switching <strong>and</strong> disconnection devices position onthe DC side.5.5.1.4 Choice of the protective devicesAs regards the protection against the short-circuits on the DC side, the devicesshall be obviously suitable for DC use <strong>and</strong> have a rated service voltage U eequalor higher than the maximum voltage of the PV generator which is equal to 1.2U oc11(IEC TS 62257-7-1).Moreover the protection devices shall be positioned at the end of the circuit tobe protected, proceeding from the strings towards the inverter, that is in thevarious subfield switchboards <strong>and</strong> inverter switchboards since the short-circuitcurrents come from the other strings, that is from the load side <strong>and</strong> not fromthe supply side (IEC TS 62257-7-1).In order to avoid unwanted tripping under st<strong>and</strong>ard operation conditions, the protectivedevices positioned in the subfield switchboards (device A in the Figure 8)shall have a rated current I n12:I n≥ 1.25 . I sc(3)These devices shall protect:• every single string against the reverse current;• the connection cable 13 string to subswitchboard (cable 1 of Figure 6.7) ifthe latter has a current carrying capacity lower than the maximum shortcircuitcurrent of the other x-1 strings connected to the same inverterswitchboard 14 , i.e. if:I z< I cc2= (x - 1) . 1.25 . I sc(4)To the purpose of protection for the string, the rated current of the protectivedevice (either thermomagnetic circuit-breaker or fuse) must not exceed thatone declared by the manufacturer for the panel protection (clause 6.5.1.2); ifno indications are given by the manufacturer, the following is assumed (IECTS 62257-7-1):1.25 . I sc≤ I n≤ 2 . I sc(5)11Uoc is the no load voltage coming out of the strings.12For thermomagnetic circuit-breakers the [6.1] becomes I 1≥ 1.25 . I sc, while for magneticonly circuit-breakers I u≥ 1.25 . I scso that their overheating can be avoided.13<strong>Protection</strong> against short-circuit only since I z≥ 1.25 . I sc.14The short-circuit I cc1= 1.25 . I sc(Figure 6.1) is unimportant because the string cable hasa current carrying capacity not lower than 1.25 . I sc.478 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.5 Protectin against overcurrents on DC sideTo the purpose of protection for the connection cable, the protective devicemust be chosen so that the following relation is satisfied for each value of shortcircuit(IEC 60364) 15 up to a maximum of (x-1) . 1.25 . I sc:I 2 t ≤ K 2 S 2 (6)The breaking capacity of the device must not be lower than the short-circuitcurrent of the other n-1 strings, that is:I cu≥ (x-1) . 1.25 . I sc(7)The devices in the inverter switchboard must protect against the short-circuit theconnection cables subfield switchboard-inverter switchboard when these cableshave a current carrying capacity lower than I cc4= (x-y) . 1.25 . I sc(Figure 8).In this case these devices shall satisfy the relations (3) <strong>and</strong> (6), while their currentcarrying capacity shall not be lower than the short-circuit current of the othern-m strings, that is:I cu≥ (x-y) . 1.25 . I sc(8)In short, the cable for the connection inverter switchboard to inverter must notbe protected if its current carrying capacity is chosen at least equal to (CEI64-8/7):I cu≥ (x-y) . 1.25 . I sc(9)15For the magnetic only circuit-breaker it is necessary, if possible, to set I3 at a value equalto the value Iz of the cable in order to determine the tripping of the device when the shortcircuit current exceeds the current carrying capacity of the protected cable. Besides, itis possible to use a magnetic only circuit-breaker if the number of strings connected tothe same inverter is maximum 3; otherwise for the protection of the string it is necessaryto use a thermomagnetic circuit-breaker chosen according to (5).16The short-circuit current I sc3= y . 1.25 . I sc(Figure 8) is unimportant since the string cablehas a current carrying capacity not lower than y . 1.25 . I sc.<strong>ABB</strong> | <strong>Electrical</strong> devices 479


5 Photovoltaic plants5.5 Protectin against overcurrents on DC side5.5.2 <strong>Protection</strong> against overcurrents on AC sideSince the cable connecting the inverter to the point of connection with the gridis usually dimensioned to obtain a current carrying capacity higher than themaximum current which the inverter can deliver, a protection against overloadis not needed. However the cable must be protected against a short circuitsupplied by the grid 17 through a protective device positioned near the point ofconnection with the grid.To protect such cable the main circuit-breaker of the consumer plant can beused if the specific let-through energy is withstood by the cable. However, the tripof the main circuit-breaker put all the consumer plant out of service. In the multiinverterplants, (Figure 9) the presence of one protection for each line allows, incase of fault on an inverter, the functioning of the other ones, provided that thecircuit-breakers on each line are selective with the main circuit-breaker.Figure 9Point ofparallel withthe grid17Generally, the inverter limits the output current to a value which is the double of its ratedcurrent <strong>and</strong> goes in st<strong>and</strong>-by in few tenths of seconds due to the trip of the internalprotection. As a consequence, the contribution of the inverter to the short-circuit currentis negligible in comparison with the contribution of the grid.480 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.5 Protectin against overcurrents on DC side5.5.3 Choice of the switching <strong>and</strong> disconnecting devicesThe <strong>installation</strong> of a disconnecting device on each string is suitable in order toallow verification or maintenance interventions on the string without putting outof service other parts of the PV plant (CEI Guide 82-25 II ed.) 18 .The disconnection of the inverter must be possible both on the DC side as wellas on the AC side so that maintenance is allowed by excluding both the supplysources (grid <strong>and</strong> PV generator) (CEI 64-8/7).On the DC side of the inverter a disconnecting device shall be installed whichcan be switched under load, such as a switch-disconnector. On the AC sidea general disconnecting device shall be provided.The protective device installed in the point of connection with the grid canbe used; if this device is not close to the inverter, it is advisable to position adisconnecting device immediately on the load side of the inverter.5.5.4 <strong>Protection</strong> against overvoltagesThe PV <strong>installation</strong>s, since they usually are outside the buildings, may be subjectto overvoltages of atmospheric origin, both direct (lightning striking the structure)as well as indirect (lightning falling near to the structure of the building or affectingthe energy or signaling lines entering the structure) through resistive or inductivecoupling. The resistive coupling occurs when lightning strikes the electrical lineentering the building. The lightning current, through the characteristic impedanceof the line, originates an overvoltage which may exceed the impulse withst<strong>and</strong>voltage of the equipment, with consequent damaging <strong>and</strong> fire hazard.The inductive coupling occurs because the lightning current is impulsive <strong>and</strong>therefore it generates in the surrounding space an electromagnetic field highlyvariable.As a consequence, the variation in the magnetic field generates some overvoltagesinduced on the electric circuits nearby. In addition to the overvoltagesof atmospheric origin, the PV plant may be exposed to internal switchingovervoltages.5.5.4.1 Direct lightningBuilding without LPS 19Generally, the erection of a PV plant does not change the outline of a building<strong>and</strong> therefore the frequency of the fulminations; therefore no specific measuresagainst the risk of fulmination are necessary (CEI Guide 82-25,II ed.).On the contrary, in case the PV <strong>installation</strong> changes significantly the outline ofthe building, it is necessary to reconsider the frequency of fulminations on it<strong>and</strong> consequently to take into consideration the necessity of realizing an LPS(CEI Guide 82-25 II ed.).18When an automatic circuit-breaker is used the switching <strong>and</strong> disconnecting function isalready included.19Lightning <strong>Protection</strong> System: it is constituted by the protective systems both external(detectors, lightning conductors <strong>and</strong> ground electrodes) as well as internal (protectivemeasures in order to reduce the electromagnetic effects of the lightning current enteringthe structure to be protected).<strong>ABB</strong> | <strong>Electrical</strong> devices 481


5 Photovoltaic plants5.5 Protectin against overcurrents on DC sideBuilding with LPSIn case of presence of a protection system against atmospheric discharges 20 ,if the PV plant does not alter the outline of the building <strong>and</strong> if the minimumdistance d between the PV plant <strong>and</strong> the LPS plant is higher than the safetydistances (EN 62305-3) other additional measures for the protection of the newplant (CEI Guide 82-25 II ed.) are not required.On the contrary, if the PV plant does not alter the outline of the building, butthe minimum distance d is lower than the distance s it is appropriate to extendthe LPS plant <strong>and</strong> connect it to the metal structures of the PV <strong>installation</strong> (CEIGuide 82-25, II ed.).Finally, if the PV plant alters the outline of the building a new risk evaluation <strong>and</strong>/or a modification of the LPS are necessary (CEI Guide 82-25, II ed.).PV plant on the groundIf a PV plant is erected on the ground there is no fire risk due to direct fulmination<strong>and</strong> the only hazard for human beings is represented by the step <strong>and</strong>touch voltages.When the surface resistivity exceeds 5 kΩm (e.g. rocky asphalted ground, atleast 5 cm thickness or laid with gravel for minimum 15 cm), it is not necessaryto take any particular measure since the touch <strong>and</strong> step voltage values are negligible(CEI 81-10). Instead, if the ground resistivity were equal to or lower than5 kΩm, it would be necessary to verify theoretically whether some protectivemeasures against the step <strong>and</strong> touch voltages are necessary; however, in thiscase, the probability of lightning strikes is very small <strong>and</strong> therefore the problemoccurs only with very large plants.Indirect lightningAlso in case lightning does not strike directly the structure of the PV plant, it isnecessary to take some measures to minimize the overvoltages caused by anylikely indirect strike of lightning:• shielding of the circuits in order to reduce the magnetic field inside theenclosure with a consequent reduction of the induced overvoltages 21 ;• reduction of the area of the turn of the induced circuit obtained by connectingsuitably the modules one to the other, by twisting the conductors together<strong>and</strong> bringing the live conductor as much as possible near to the PE.20It is advisable that the protection grounding plant is connected to that for the protectionagainst lightning.21The shielding effect of a metal enclosure originates thanks to the currents induced inthe enclosure itself; they create a magnetic field which by Lenz’s law opposes the causegenerating them, that is the magnetic field of the lightning current; the higher the currentsinduced in the shield (i.e. the higher its conductance), the better the shielding effect.482 <strong>Electrical</strong> devices | <strong>ABB</strong>


5 Photovoltaic plants5.5 Protectin against overcurrents on DC sideThe overvoltages, even if limited, which may be generated must be dischargedtoground by means of SPD (Surge Protective Device) to protect the equipment.In fact, SPDs are devices with impedance variable according to the voltageapplied: at the rated voltage of the plant they have a very high impedance,whereas in the presence of an overvoltage they reduce their impedance, derivingthe current associated to the overvoltage <strong>and</strong> keeping the latter withina determined range of values. According to their operation modalities SPDscan be divided into:• switching SPDs, such as spinterometers or <strong>control</strong>led diodes, when thevoltage exceeds a defined value, reduce instantaneously their impedance<strong>and</strong> consequently the voltage at their ends;• limitation SPDs, such as varistors or Zener diodes, have an impedancewhich decreases gradually at the increase of the voltage at their ends;• combined SPDs which comprise the two above mentioned devicesconnected in series or in parallel.<strong>Protection</strong> on DC sideFor the protection on the DC side it is advisable to use varistors SPDs or combinedSPDs. Inverters usually have an internal protection against overvoltages,but if SPDs are added to the inverter terminals, its protection is improved <strong>and</strong> atthe same time it is possible to avoid that the tripping of the internal protectionsput out of service the inverter, thus causing suspension of energy production<strong>and</strong> making necessary the intervention of skilled personnel.These SPDs should have the following characteristics:• Type 2• Maximum rated service voltage Ue > 1.25 Uoc22• <strong>Protection</strong> level Up ≤ U inv• Nominal discharge current In ≥ 5 kA• Thermal protection with the capability of estinguishing the short-circuitcurrent at the end of life <strong>and</strong> coordination with suitable back-up protection.Since the modules of the strings generally have an impulse withst<strong>and</strong> voltagehigher than that of the inverter, the SPDs installed to protect the inverter generallyallow the protection of the modules too, provided that the distance betweenmodules <strong>and</strong> inverter is shorter than 10 m 23 .22U invis the impulse withst<strong>and</strong> voltage of the inverter DC side.23The SPD shall be installed on the supply side (direction of the energy of the PV generator)of the disconnecting device of the inverter so that it protects the modules also when thedisconnecting device is open.<strong>ABB</strong> | <strong>Electrical</strong> devices 483


5 Photovoltaic plants5.5 Protectin against overcurrents on DC side<strong>Protection</strong> on AC sideA PV plant connected to the grid is subject also to the overvoltages comingfrom the line itself. If a separation transformer is present, with earthed metalshield, the inverter is protected against the overvoltages of the transformer itself.If the transformer is not present or in case of a transformer without shield, it isnecessary to install a suitable SPD immediately downstream the inverter.This SPDs should have the following characteristics:• Type 2• Maximum rated service voltage Ue > 1.1 Uo 2425• <strong>Protection</strong> level Up ≤ U inv• Nominal discharge current In ≥ 5 kA• Thermal protection with the capability of estinguishing the short-circuitcurrent at the end of life <strong>and</strong> coordination with suitable back-up protection.If the risk analysis for the building prescribes the <strong>installation</strong> of an outside LPS, itis necessary to position an SPD for the protection against direct lightning at thepower delivery point. Such SPD should have the following characteristics:• Type 1• Maximum rated service voltage Ue > 1.1 Uo• <strong>Protection</strong> level Up ≤ U inv• Impulse current Iimp ≥ 25 kA for each pole• Extinction of the follow-up current Ifi exceeding the short-circuit currentat the <strong>installation</strong> point <strong>and</strong> coordination with a suitable back-up protection.24Uo is the voltage to earth for TT <strong>and</strong> TN systems; in case of an IT system it is Ue > 1.73 Uo.25U invis the impulse withst<strong>and</strong> voltage of the inverter on the AC side.484 <strong>Electrical</strong> devices | <strong>ABB</strong>


6 Calculation of short-circuit current6.1 General aspectsA short-circuit is a fault of negligible impedance between live conductors havinga difference in potential under normal operating conditions.6.2 Fault typologiesIn a three-phase circuit the following types of fault may occur:• three-phase fault;• two-phase fault;• phase to neutral fault;• phase to PE fault.In the formulas, the following symbols are used:• I kshort-circuit current;• U rrated voltage;• Z Lphase conductor impedance;• Z Nneutral conductor impedance;• Z PEprotective conductor impedance.The following table briefly shows the type of fault <strong>and</strong> the relationships betweenthe value of the short-circuit current for a symmetrical fault (three phase) <strong>and</strong>the short-circuit current for asymmetrical faults (two phase <strong>and</strong> single phase)in case of faults far from generators.Three-phase faultZ LI kLLLZ LI kLLLZ LI kLLLZ NTwo-phase faultZ LZ LZ LI kLLZ N<strong>ABB</strong> | <strong>Electrical</strong> devices 485


6 Calculation of short-circuit current6.2 Fault typologiesPhase to neutral faultZ LZ LZ LZ NI kLNPhase to PE faultZ LZ LZ LZ PEI kLPEThe following table allows the approximate value of a short-circuit current tobe found quickly.NoteThree-phaseshort-circuitTwo-phaseshort-circuitPhase to neutralshort-circuitPhase to PE short-circuit(TN system)I kLLLI kLLI kLNI kLLL-I kLLL=1.16I kLLI kLLL=2I kLN(Z L= Z N)I kLLL=3I kLN(Z L= 0,5Z N)I kLLL=I kLN(Z N≅ 0)I kLLI kLL=0.87I kLLL-I kLL=1.73I kLN(Z L= Z N)I kLL=2.6I kLN(Z L= 0,5Z N)I kLL=0.87I kLN(Z N≅ 0)I kLNI LN=0.5I kLLL(Z L= Z N)I LN=0.33I kLLL(Z L= 0,5Z N)I LN=I kLLL(Z N≅ 0)I kLN=0.58I kLL(Z L= Z N)I kLN=0.38I kLL(Z L= 0,5Z N)I kLN=1.16I kLL(Z N≅ 0)-I kLPEI LPE=0.5I kLLL(Z L= Z PE)I LPE=0.33I kLLL(Z L= 0.5Z PE)I LPE=I kLLL(Z PE≅ 0)I kLPE=0.58I kLL(Z L= Z PE)I kLPE=0.38I kLL(Z L= 0.5Z PE)I kLPE=1.16I kLL(Z PE≅ 0)486 <strong>Electrical</strong> devices | <strong>ABB</strong>


6.3 Determination of the short-circuitcurrent: “short-circuit power method”6 Calculation of short-circuit currentThe short-circuit current can be determined by using the “short-circuit powermethod”. This method allows the determination of the approximate short-circuitcurrent at a point in an <strong>installation</strong> in a simple way; the resultant value is generallyacceptable. However, this method is not conservative <strong>and</strong> gives more accuratevalues, the more similar the power factors of the considered components are(network, generators, transformers, motors <strong>and</strong> large section cables etc.).The “short-circuit power method” calculates the short-circuit current I kbasedon the formula:Three-phase short-circuitTwo-phase short-circuitwhere:• S kis the short-circuit apparent power seen at the point of the fault;• U ris the rated voltage.To determine the short-circuit apparent power S k, all the elements of the networkshall be taken into account, which may be:• elements which contribute to the short-circuit current:network, generators, motors;• elements which limit the value of the short-circuit current:conductors <strong>and</strong> transformers.The procedure for the calculation of the short-circuit current involves thefollowing steps:1. calculation of the short-circuit power for the different elements of the<strong>installation</strong>;2. calculation of the short-circuit power at the fault point;3. calculation of the short-circuit current.6.3.1 Calculation of the short-circuit power for the different elements of the<strong>installation</strong>The short-circuit apparent power S kshall be determined for all the componentswhich are part of the <strong>installation</strong>:NetworkAn electrical network is considered to include everything upstream of the pointof energy supply.<strong>ABB</strong> | <strong>Electrical</strong> devices 487


6.3 Determination of the short-circuit current: “short-circuit power method”6 Calculation of short-circuit currentGenerally, the energy distribution authority supplies the short-circuit apparentpower (S knet) value at the point of energy supply. However, if the value of theshort-circuit current I knetis known, the value of the power can be obtained byusing, for three-phase systems, the following formula:where U ris the rated voltage at the point of energy supply.If the aforementioned data are not available, the values for S knetgiven in thefollowing table can be taken as reference values:Net voltage U r[kV] Short-circuit power S knet[MVA]Up to 20 500Up to 32 750Up to 63 1000GeneratorThe short-circuit power is obtained from:⋅where X * d% is the percentage value of the subtransient reactance (X d”) or of thetransient reactance (X d’) or of the synchronous reactance (X d), according to theinstant in which the value of the short-circuit power is to be evaluated.In general, the reactances are expressed in percentages of the rated impedanceof the generator (Z d) given by:where U r<strong>and</strong> S rare the rated voltage <strong>and</strong> power of the generator.Typical values can be:- X d”from 10 % to 20 %;- X d’ from 15 % to 40 %;- X dfrom 80 % to 300 %.Normally, the worst case is considered, that being the subtransient reactance.The following table gives the approximate values of the short-circuit power ofgenerators (X d”= 12.5 %):S r[kVA] 50 63 125 160 200 250 320 400 500 630 800 1000 1250 1600 2000 2500 3200 4000S kgen[MVA] 0.4 0.5 1.0 1.3 1.6 2.0 2.6 3.2 4.0 5.0 6.4 8.0 10.0 12.8 16.0 20.0 25.6 32.0488 <strong>Electrical</strong> devices | <strong>ABB</strong>


6.3 Determination of the short-circuit current: “short-circuit power method”6 Calculation of short-circuit currentAsynchronous three-phase motorsUnder short-circuit conditions, electric motors contribute to the fault for a briefperiod (5-6 periods).The power can be calculated according to the short-circuit current of the motor(I k), by using the following expression:Typical values are:S kmot= 5÷7 S rmot(I kis about 5÷7 I rmot: 5 for motors of small size, <strong>and</strong> 7 for larger motors).TransformersThe short-circuit power of a transformer (S ktrafo) can be calculated by using thefollowing formula:The following table gives the approximate values of the short-circuit power oftransformers:S r[kVA] 50 63 125 160 200 250 320 400 500 630 800 1000 1250 1600 2000 2500 3200 4000u k% 4 4 4 4 4 4 4 4 4 4 5 5 5 6 6 6 6 6S ktrafo[MVA] 1.3 1.6 3.1 4 5 6.3 8 10 12.5 15.8 16 20 25 26.7 33.3CablesA good approximation of the short-circuit power of cables is:where the impedance of the cable (Z c) is:The following table gives the approximate values of the short-circuit power ofcables, at 50 <strong>and</strong> 60 Hz, according to the supply voltage (cable length = 10 m):<strong>ABB</strong> | <strong>Electrical</strong> devices 489


6.3 Determination of the short-circuit current: “short-circuit power method”6 Calculation of short-circuit current230 [V] 400 [V] 440 [V] 500 [V] 690 [V] 230 [V] 400 [V] 440 [V] 500 [V] 690 [V]S [mm 2 ] S kcable[MVA] @50 Hz S kcable[MVA] @60 Hz1.5 0.44 1.32 1.60 2.07 3.94 0.44 1.32 1.60 2.07 3.942.5 0.73 2.20 2.66 3.44 6.55 0.73 2.20 2.66 3.44 6.554 1.16 3.52 4.26 5.50 10.47 1.16 3.52 4.26 5.50 10.476 1.75 5.29 6.40 8.26 15.74 1.75 5.29 6.40 8.26 15.7310 2.9 8.8 10.6 13.8 26.2 2.9 8.8 10.6 13.7 26.216 4.6 14.0 16.9 21.8 41.5 4.6 13.9 16.9 21.8 41.525 7.2 21.9 26.5 34.2 65.2 7.2 21.9 26.4 34.1 65.035 10.0 30.2 36.6 47.3 90.0 10.0 30.1 36.4 47.0 89.650 13.4 40.6 49.1 63.4 120.8 13.3 40.2 48.7 62.9 119.870 19.1 57.6 69.8 90.1 171.5 18.8 56.7 68.7 88.7 168.895 25.5 77.2 93.4 120.6 229.7 24.8 75.0 90.7 117.2 223.1120 31.2 94.2 114.0 147.3 280.4 29.9 90.5 109.5 141.5 269.4150 36.2 109.6 132.6 171.2 326.0 34.3 103.8 125.6 162.2 308.8185 42.5 128.5 155.5 200.8 382.3 39.5 119.5 144.6 186.7 355.6240 49.1 148.4 179.5 231.8 441.5 44.5 134.7 163.0 210.4 400.7300 54.2 164.0 198.4 256.2 488.0 48.3 146.1 176.8 228.3 434.7With n cables in parallel, it is necessary to multiply the value given in the tableby n. If the length of the cable (L act) is other than 10 m, it is necessary to multiplythe value given in the table by the following coefficient:6.3.2 Calculation of the short-circuit power at the fault pointThe rule for the determination of the short-circuit power at a point in the<strong>installation</strong>, according to the short-circuit power of the various elements ofthe circuit, is analogue to that relevant to the calculation of the equivalentadmittance. In particular:• the power of elements in series is equal to the inverse of the sum of theinverses of the single powers (as for the parallel of impedances);• the short-circuit power of elements in parallel is equal to the sum of the singleshort-circuit powers (as for the series of impedances).The elements of the circuit are considered to be in series or parallel, seeing thecircuit from the fault point.In the case of different branches in parallel, the distribution of the current betweenthe different branches shall be calculated once the short-circuit current at thefault point has been calculated. This must be done to ensure the correct choiceof protection devices installed in the branches.490 <strong>Electrical</strong> devices | <strong>ABB</strong>


6.3 Determination of the short-circuit current: “short-circuit power method”6 Calculation of short-circuit current6.3.3 Calculation of the short-circuit currentTo determine the short-circuit current in an <strong>installation</strong>, both the fault point aswell as the configuration of the system which maximize the short-circuit currentinvolving the device shall be considered. If appropriate, the contribution of themotors shall be taken into account.For example, in the case detailed below, for circuit-breaker CB1, the worstcondition occurs when the fault is right upstream of the circuit-breaker itself.To determine the breaking capacity of the circuit-breaker, the contribution oftwo transformers in parallel must be considered.Fault right downstream of CB1CB1 CB2 CB3Fault1SDC010050F0001Fault right upstream of CB1(worst condition for CB1)FaultCB1 CB2 CB31SDC010051F0001Once the short-circuit power equivalent at the fault point has been determined,the short-circuit current can be calculated by using the following formula:Three-phase short-circuitTwo-phase short-circuit<strong>ABB</strong> | <strong>Electrical</strong> devices 491


6.3 Determination of the short-circuit current: “short-circuit power method”6 Calculation of short-circuit currentAs a first approximation, by using the following graph, it is possible to evaluatethe three-phase short-circuit current downstream of an object with short-circuitpower (S kEL) known; corresponding to this value, knowing the short-circuitpower upstream of the object (S kUP), the value of I kcan be read on the y-axis,expressed in kA, at 400 V.Figure 1: Chart for the calculation of the three-phase short-circuitcurrent at 400 VI k [kA]1501401301201101009080S kUPS kUP = °S kELI kS kUP = 1000 MVAS kUP = 750 MVAS kUP = 500 MVAS kUP = 250 MVA7060504030S kUP = 100 MVAS kUP = 50 MVAS kUP = 40 MVAS kUP = 30 MVA20100S kUP = 20 MVAS kUP = 10 MVA0 10 20 30 40 50 60 70 80 90 100 S kEL [MVA]1SDC010052F0001492 <strong>Electrical</strong> devices | <strong>ABB</strong>


6.3 Determination of the short-circuit current: “short-circuit power method”6 Calculation of short-circuit current6.3.4 ExamplesThe following examples demonstrate the calculation of the short-circuit currentin some different types of <strong>installation</strong>.Example 1Upstream network: U r= 20000 VS knet= 500 MVAUATransformer:S r= 1600 kVAu k% = 6%U 1r/ U 2r=20000/400CB1Motor:Generic load:P r= 220 kWI kmot/I r= 6.6cosϕ r= 0.9η = 0.917I rL= 1443.4 Acosϕ r= 0.9MCB2LBCB31SDC010053F0001Calculation of the short-circuit power of different elementsNetwork:S knet= 500 MVATransformer:Motor:S kmot= 6.6.S rmot= 1.76 MVA for the first 5-6 periods (at 50 Hz about 100 ms)Calculation of the short-circuit current for the selection of circuitbreakersSelection of CB1For circuit-breaker CB1, the worst condition arises when the fault occurs rightdownstream of the circuit-breaker itself. In the case of a fault right upstream,the circuit-breaker would be involved only by the fault current flowing from themotor, which is remarkably smaller than the network contribution.<strong>ABB</strong> | <strong>Electrical</strong> devices 493


6.3 Determination of the short-circuit current: “short-circuit power method”6 Calculation of short-circuit currentThe circuit, seen from the fault point, is represented by the series of the networkwith the transformer. According to the previous rules, the short-circuit power isdetermined by using the following formula:⋅the maximum fault current is:The transformer LV side rated current is equal to 2309 A; therefore the circuitbreakerto select is an Emax E3N 2500.Using the chart shown in Figure 1, it is possible to find I kCB1from the curve withS kUP= S knet= 500 MVA corresponding to S kEL= S ktrafo= 26.7 MVA:I k [kA]150140130120110S kUP = 500 MVA1009080706050I k = 36.5 kA4030201000 10 20 30 40 50 60 70 80 90 100S S kEL [MVA]kUP = 26.7 MVA1SDC010054F0001494 <strong>Electrical</strong> devices | <strong>ABB</strong>


6.3 Determination of the short-circuit current: “short-circuit power method”6 Calculation of short-circuit currentSelection of CB2For circuit-breaker CB2, the worst condition arises when the fault occurs rightdownstream of the circuit-breaker itself. The circuit, seen from the fault point, isrepresented by the series of the network with the transformer. The short-circuitcurrent is the same used for CB1.The rated current of the motor is equal to 385 A; the circuit-breaker to selectis a Tmax T5H 400.Selection of CB3For CB3 too, the worst condition arises when the fault occurs right downstreamof the circuit-breaker itself.The circuit, seen from the fault point, is represented by two branches in parallel:the motor <strong>and</strong> the series of the network <strong>and</strong> transformer. According to theprevious rules, the short-circuit power is determined by using the followingformula:Motor // (Network + Transformer)The rated current of the load L is equal to 1443 A; the circuit-breaker to selectis a Tmax T7S1600 or an Emax X1B1600.Example 2The circuit shown in the diagram is constituted by the supply, two transformersin parallel <strong>and</strong> three loads.UAUpstream network: U r1=20000 VS knet= 500 MVATransformers 1 <strong>and</strong> 2: S r= 1600 kVAu k% = 6%U 1r/U 2r=20000/400Load L1: S r= 1500 kVA; cosϕ = 0.9;Load L2: S r= 1000 kVA; cosϕ = 0.9;Load L3: S r= 50 kVA; cosϕ = 0.9.L1Trafo 1 Trafo 2CB1 CB2BCB3 CB4 CB5L2 L31SDC010055F0001<strong>ABB</strong> | <strong>Electrical</strong> devices 495


6.3 Determination of the short-circuit current: “short-circuit power method”6 Calculation of short-circuit currentCalculation of the short-circuit powers of different elements:NetworkTransformers 1 <strong>and</strong> 2Selection of CB1 (CB2)For circuit-breaker CB1 (CB2) the worst condition arises when the fault occursright downstream of the circuit-breaker itself. According to the previous rules,the circuit seen from the fault point, is equivalent to the parallel of the twotransformers in series with the network: Network + (Trafo 1 // Trafo 2).The short-circuit current obtained in this way corresponds to the short-circuitcurrent at the busbar. This current, given the symmetry of the circuit, is distributedequally between the two branches (half each). The current which flows throughCB1 (CB2) is therefore equal to half of that at the busbar.⋅+The circuit-breakers CB1(CB2) to select, with reference to the rated current ofthe transformers, are Emax E3N 2500.Selection of CB3-CB4-CB5For these circuit-breakers the worst condition arises when the fault occurs rightdownstream of the circuit-breakers themselves. Therefore, the short-circuitcurrent to be taken into account is that at the busbar:I kCB3= I kbusbar= 69.56 kAThe circuit-breakers to select, with reference to the current of the loads, are:CB3: Emax E3S 2500CB4: Emax E2S 1600CB5: Tmax T2H 160496 <strong>Electrical</strong> devices | <strong>ABB</strong>


6.4 Determination of the short-circuitcurrent I kdownstream of a cable as afunction of the upstream oneCablesection6 Calculation of short-circuit currentThe table below allows the determination, in a conservative way, of the threephaseshort-circuit current at a point in a 400 V network downstream of a singlepole copper cable at a temperature of 20 °C. Known values:- the three-phase short-circuit current upstream of the cable;- the length <strong>and</strong> cross section of the cable.Length[mm 2 ][m]1.5 0.9 1.1 1.4 1.8 2.5 3.5 5.3 7 9.4 142.5 0.9 1 1.2 1.5 1.8 2.3 2.9 4.1 5.9 8.8 12 16 244 0.9 1.2 1.4 1.6 1.9 2.3 2.8 3.7 4.7 6.6 9.4 14 19 25 386 0.8 1.1 1.4 1.8 2.1 2.5 2.8 3.5 4.2 5.6 7 10 14 21 28 38 5610 0.9 1.2 1.4 1.9 2.3 2.9 3.5 4.1 4.7 5.8 7 9.4 12 16 23 35 47 63 9416 0.9 1.1 1.5 1.9 2.2 3 3.7 4.7 5.6 6.5 7.5 9.3 11 15 19 26 37 56 75 100 15025 0.9 1.2 1.4 1.7 2.3 2.9 3.5 4.6 5.8 7.2 8.7 10 12 14 17 23 29 41 58 87 116 155 23335 1.2 1.6 2 2.4 3.2 4 4.8 6.4 8 10 12 14 16 20 24 32 40 56 80 121 161 216 32450 1.1 1.7 2.3 2.8 3.4 4.5 5.7 6.8 9 11 14 17 20 23 28 34 45 57 79 113 170 226 303 45570 0.8 1.5 2.3 3.1 3.8 4.6 6.2 7.7 9.2 12 15 19 23 27 31 38 46 62 77 108 154 231 308 41395 1 2 3 4 5 6 8 10 12 16 20 25 30 35 40 50 60 80 100 140 200 300 400120 1.2 2.4 3.6 4.8 6 7.2 10 12 14 19 24 30 36 42 48 60 72 96 120 168 240 360 481150 1.4 2.8 4.2 5.6 7 8.4 11 14 17 23 28 35 42 49 56 70 84 113 141 197 281 422185 1.6 3.2 4.8 6.4 8 10 13 16 19 26 32 40 48 56 64 80 96 128 160 224 320 480240 1.8 3.7 5.5 7.3 9.1 11 15 18 22 29 37 46 55 64 73 91 110 146 183 256 366 549300 2 4 6 8 10 12 16 20 24 32 40 50 60 70 80 100 120 160 200 280 4002x120 2.4 4.8 7.2 10 12 14 19 24 29 38 48 60 72 84 96 120 144 192 240 336 4812x150 2.8 5.6 8.4 11 14 17 23 28 34 45 56 70 84 98 113 141 169 225 281 394 5632x185 3.2 6.4 10 13 16 19 26 32 38 51 64 80 96 112 128 160 192 256 320 4483x120 3.6 7.2 11 14 18 22 29 36 43 58 72 90 108 126 144 180 216 288 360 5053x150 4.2 8.4 13 17 21 25 34 42 51 68 84 105 127 148 169 211 253 338 4223x185 4.8 10 14 19 24 29 38 48 58 77 96 120 144 168 192 240 288 384 480I kupstreamI kdownstream[kA][kA]100 96 92 89 85 82 78 71 65 60 50 43 36 31 27 24 20 17 13 11 7.8 5.6 3.7 2.7 2.0 1.390 86 83 81 78 76 72 67 61 57 48 42 35 31 27 24 20 17 13 11 7.8 5.6 3.7 2.7 2.0 1.380 77 75 73 71 69 66 62 57 53 46 40 34 30 27 24 20 17 13 10 7.7 5.5 3.7 2.7 2.0 1.370 68 66 65 63 62 60 56 53 49 43 38 33 29 26 23 19 16 13 10 7.6 5.5 3.7 2.7 2.0 1.360 58 57 56 55 54 53 50 47 45 40 36 31 28 25 23 19 16 12 10 7.5 5.4 3.7 2.7 2.0 1.350 49 48 47 46 45 44 43 41 39 35 32 29 26 23 21 18 15 12 10 7.3 5.3 3.6 2.6 2.0 1.340 39 39 38 38 37 37 35 34 33 31 28 26 24 22 20 17 15 12 10 7.1 5.2 3.6 2.6 2.0 1.335 34 34 34 33 33 32 32 31 30 28 26 24 22 20 19 16 14 11 10 7.1 5.1 3.5 2.6 2.0 1.330 30 29 29 29 28 28 28 27 26 25 23 22 20 19 18 16 14 11 9.3 7.0 5.0 3.5 2.6 1.9 1.325 25 24 24 24 24 24 23 23 22 21 21 19 18 17 16 14 13 11 9.0 6.8 5.0 3.4 2.6 1.9 1.320 20 20 20 19 19 19 19 18 18 18 17 16 15 15 14 13 12 10 8.4 6.5 4.8 3.3 2.5 1.9 1.315 15 15 15 15 15 14 14 14 14 14 13 13 12 12 12 11 10 8.7 7.6 6.1 4.6 3.2 2.5 1.9 1.312 12 12 12 12 12 12 12 11 11 11 11 11 10 10 10 9.3 8.8 7.8 7.0 5.7 4.4 3.1 2.4 1.9 1.310 10 10 10 10 10 10 10 9.5 9.4 9.2 9.0 8.8 8.5 8.3 8.1 7.7 7.3 6.5 5.9 5.0 3.9 2.9 2.3 1.8 1.28.0 8.0 7.9 7.9 7.9 7.8 7.8 7.7 7.7 7.6 7.5 7.4 7.2 7.1 6.9 6.8 6.5 6.2 5.7 5.2 4.5 3.7 2.8 2.2 1.7 1.26.0 6.0 5.9 5.9 5.9 5.9 5.8 5.8 5.8 5.7 5.6 5.5 5.4 5.3 5.2 5.1 4.9 4.8 4.4 4.1 3.6 3.1 2.4 2.0 1.6 1.13.0 3.0 3.0 3.0 3.0 3.0 3.0 2.9 2.9 2.9 2.9 2.9 2.8 2.8 2.8 2.7 2.7 2.6 2.5 2.4 2.2 2.0 1.7 1.4 1.2 0.9<strong>ABB</strong> | <strong>Electrical</strong> devices 497


6.4 Determination of the short-circuit current I kdownstream of a cable as a functionof the upstream one6 Calculation of short-circuit currentNote:• In the case of the I kupstream <strong>and</strong> the length of the cable not being includedin the table, it is necessary to consider:- the value right above I kupstream;- the value right below for the cable length.These approximations allow calculations which favour safety.• In the case of cables in parallel not present in the table, the length must bedivided by the number of cables in parallel.ExampleDataRated voltage = 400 VCable section = 120 mm 2Conductor = copperLength = 29 mUpstream short-circuit current = 32 kA400 VIk upstream = 32 kAQF A120 mm 2Cu/PVCL = 29 mQF BIk downstream = ?QF C1SDC010056F0001ProcedureIn the row corresponding to the cable cross section 120 mm 2 , it is possible tofind the column for a length equal to 29 m or right below (in this case 24). Inthe column of upstream short-circuit current it is possible to identify the rowwith a value of 32 kA or right above (in this case 35). From the intersection ofthis last row with the previously identified column, the value of the downstreamshort-circuit current can be read as being equal to 26 kA.498 <strong>Electrical</strong> devices | <strong>ABB</strong>


6.5 Algebra of sequences6 Calculation of short-circuit current6.5.1 General aspectsFigure 1It is possible to study a symmetrical, balanced three-phase network in quite asimple way by reducing the three-phase network to a single-phase one havingthe same value of rated voltage as the three-phase system line-to-neutralvoltage.Asymmetric networks cannot be reduced to the study of a single-phase networkjust because of this unbalance. In this case, being impossible any simplification,it is necessary to proceed according to the analysis methods typical for thesolution of electrical systems.The modelling technique allowing the calculation of an asymmetric <strong>and</strong>unbalanced network by converting it to a set of three balanced networks thateach can be represented by a single-phase equivalent circuit easily solvable isthe method of symmetrical components.This method derives from mathematical considerations according to whichany set of three phasors 1 can be divided into three sets of phasors with thefollowing characteristics:- a balanced set, called positive sequence, formed by three phasors of equalmagnitude shifted by 120° <strong>and</strong> having the same phase sequence as theoriginal system- a balanced set, called negative sequence, formed by three phasors of equalmagnitude shifted by 120° <strong>and</strong> having inverse phase sequence to that of theoriginal system- a zero sequence set formed by three phasors of equal magnitude in phase.Unbalanced setPositive sequence setNegative sequence setZero sequence setV1ViV2V3=VdVdVdVi+ +ViV0V0V01The phasor is a vectorial representation of magnitude which varies in time. A signal oftypeis represented by the phasor<strong>ABB</strong> | <strong>Electrical</strong> devices 499


6 Calculation of short-circuit current6.5.2 Positive, negative <strong>and</strong> zero sequence systems6.5 Algebra of sequencesThe following relationships* represent the link between the quantities of thethree-phase balanced network <strong>and</strong> the positive, negative <strong>and</strong> zero sequencesystems:* In the formulas, the subscripts relevant to positive-sequence, negative-sequence <strong>and</strong>zero-sequence components are indicated by “d”, “i” <strong>and</strong> “0” respectively.The complex constant is a versor which, multiplied by a vector,rotates the vector by 120° in a positive direction (counterclockwise).The complex constant operates a -120° rotation.Some useful properties of this set of three vectors are:Figure 2Therefore, it is possible to state that a real three-phase network may be replacedby three single-phase networks related to the three positive, negative <strong>and</strong> zerosequences, by substituting each component with the corresponding equivalentcircuit. If generators can be considered symmetrical as it occurs in plant practice,by considering as a positive sequence set the one they generate, the threesingle-phase networks are defined by the following circuits <strong>and</strong> equations:Figure 3Where:- E dis the line-to-neutral voltage of the section upstream the fault- Z is the system impedance upstream the fault location- I is the fault current- V is the voltage measured at the fault location.500 <strong>Electrical</strong> devices | <strong>ABB</strong>


6 Calculation of short-circuit current6.5.3 Calculation of short-circuit current with the algebra of sequencesWithout going into the details of a theoretical treatment, it is possible to show theprocedure to semplify <strong>and</strong> resolve the electrical network under a pre-estabilishedfault condition thruogh an example.Isolated line-to line faultThe diagram showing this fault typology <strong>and</strong> the link between currents <strong>and</strong>voltages, may be represented as follows:Figure 46.5 Algebra of sequencesBy using the given fault conditions <strong>and</strong> the formula 1), it follows that:V d= V iI d= -I iI o= 0 therefore V o= 0(4)These relationships applied to the three sequence circuits of Figure 3 allowthe definition of the sequence network equivalent to the three-phase networkunder study <strong>and</strong> representing the initial fault condition. This network may berepresented as follows:Figure 5<strong>ABB</strong> | <strong>Electrical</strong> devices 501


6 Calculation of short-circuit current6.5 Algebra of sequencesBy solving this simple network (constituted by series-connected elements) inrelation to the current I d, the following is obtained:By using formulas 2) referred to the current, <strong>and</strong> formulas 4), it follows that:5)Since results to be equal to , the value of the line-to-line short-circuitcurrent in the two phases affected by the fault can be expressed as follows:Using formulas 2) referred to the voltage, <strong>and</strong> formulas 4) previously found, thefollowing is obtained:6) for the phase not affected by the fault7) for the phases affected by the faultThrough the negative sequence circuit, relation 6) can be written as.Further to the above, <strong>and</strong> since , the phase not affected by the faultshall be:.For the phases affected by the fault, being, it results:Making reference to the previous example, it is possible to analyse all faulttypologies <strong>and</strong> to express the fault currents <strong>and</strong> voltages as a function of theimpedances of the sequence components.502 <strong>Electrical</strong> devices | <strong>ABB</strong>


6 Calculation of short-circuit currentA summary is given in Table 1 below:6.5 Algebra of sequencesType of faultFaultconditions: Current Voltage on phasesThree-phase short-circuitI 1I 2V 1 = V 2 = V 3=IV 13I 1 + I 2 + I 3 =0V 2V 3Line-to-line short-circuitI 1I 2V 2 = V 3IVI 2 = - I 313V 2V 3Line-to-line short-circuit withearth connectionI 1I 2 = U n.Zd . ZiI 2V 2 = V 3 =0 I 3 = U n.IV 1 I 1 = 0Zd . Zi3V 2.V 3Single line short-circuitI 1I 2V 1 =0I k1 = I 1 =IIV 2 =I 3 =013V 2V 3UI k3 I 1 = nV3 . 1 = V 2 = V 3 =0ZdI k2 = I 2 = U nZ d +Z i2V 1 = . Un . Z i3 Z d +Z iU nZ iV 2 = V 3 = .3 Z d+Z i( 1+α 2 ). Z i +Z o+ Z i. Zo + Z o. ZdV 2 = V 3 =0( 1+α). Z i +Z o+ Z i. Zo + Z o. ZZd V 1 = 3. i.Un .Z oZ d. Z i + Z i. Z o + Z o.ZI =U iground =I 2 +I 3 nZd . Zi + Z i. Zo + Z o. Zd3 . UnZ d+ Z i+Z oV 2 = U n.V 1 = 0Z iZ d. Zo- α+ Z i + Z oZ i- α. ZV o3 = U n. +Z d + Z i + Z oZ d<strong>ABB</strong> | <strong>Electrical</strong> devices 503


6 Calculation of short-circuit current6.5 Algebra of sequences6.5.4 Positive, negative <strong>and</strong> zero sequence short-circuit impedances ofelectrical equipmentEach component of an electrical network (utility – transformer – generator– cable) may be represented by a positive, negative <strong>and</strong> zero sequenceimpedance value.UtilityBy utility it is meant the distribution supply network (usually MV) from which theplant is fed. It is characterized by positive <strong>and</strong> negative sequence elements,whereas the zero sequence impedance is not taken into consideration sincethe delta-connected windings of the primary circuit of the transformer impedethe zero sequence current. As regards the existing impedances, it can bewritten:TransformerIt is characterized by positive <strong>and</strong> negative sequence elements; besides, as afunction of the connection of the windings <strong>and</strong> of the distribution system on theLV side, the zero sequence component may be present too.Thus, it is possible to say that:whereas the zero sequence component can be expressed as:Z o=Z Τwhen the flow of zero sequence currents in the two windings is possibleZ o=∞ when the flow of zero sequence currents in the two windings is impossibleCableIt is characterized by positive, negative <strong>and</strong> zero sequence elements which varyas a function of the return path of the short-circuit current.As regards the positive <strong>and</strong> negative sequence components, it is possible tosay that:Z d= Z i= Z C=R C+ j X CTo evaluate the zero sequence impedance, it is necessary to know the returnpath of the current:Return through the neutral wire (phase-to-neutral fault)Return through PE (phase-to-PE conductor fault in TN-S system)Return through ground (phase-to-ground fault in TT system)where:• Z C, R C<strong>and</strong> X Crefer to the line conductor• Z nC, R nC<strong>and</strong> X nCrefer to the neutral conductor• Z PEC, R PEC<strong>and</strong> X PECrefer to the protection conductor PE• Z EC, R EC<strong>and</strong> X ECrefer to the ground.504 <strong>Electrical</strong> devices | <strong>ABB</strong>


6 Calculation of short-circuit current6.5 Algebra of sequencesSynchronous generatorsGenerally speaking, positive, negative <strong>and</strong> zero sequence reactances of synchronousgenerators (<strong>and</strong> also of rotating machines) have different values.”For the positive sequence, only the sub transient reactance X d is used, since,in this case, the ” calculation of the fault current gives the highest””X value.d XThe negative sequence reactance is very variable, ranging between qX dthe valuesof”X d <strong>and</strong> X ” ” ””X q . In the initial instants of the short-circuit, X d <strong>and</strong> X q do not differd ””very much <strong>and</strong> therefore we may consider X””X i= X d . On the contrary if Xq Xd <strong>and</strong>”X q q are remarkably different, it is possible to use a”value equal to the average”X q Xvalue of the two reactances; it follows that:qThe zero sequence reactance is very variable too <strong>and</strong> results to be lower thanthe other two above mentioned reactances. For this reactance, a value equal to0.1 to 0.7 times the negative or positive sequence reactances may be assumed<strong>and</strong> can be calculated as follows:where x o% is a typical parameter of the machine. Besides, the zero sequencecomponent results to be influenced also by the grounding modality of thegenerator through the introduction of the parameters R G<strong>and</strong> X G,which represent,respectively, the grounding resistance <strong>and</strong> the reactance of the generator.If the star point of the generator is inaccessible or anyway non-earthed, thegrounding impedance is ∞.To summarize, the following expressions are to be considered for the sequenceimpedances:where R ais the stator resistance defined astime constant., with T aas stator<strong>ABB</strong> | <strong>Electrical</strong> devices 505


6 Calculation of short-circuit current6.5 Algebra of sequencesLoadsIf the load is passive, the impedance shall be considered as infinite.If the load is not passive, as it could be for an asynchronous motor, it is possibleto consider the machine represented by the impedance Z Mfor the positive <strong>and</strong>negative sequence, whereas for the zero sequence the value Z oMmust be givenby the manufacturer. Besides, if the motors are not earthed, the zero sequenceimpedance shall be ∞.Therefore:with Z Mequal towhere:I LRis the current value when the rotor is blocked by the motoris the rated current of the motorI ris the rated apparent power of the motorThe ratio is often known; for LV motors, this ratio can be considered equalto 0.42 with, from which X M=0.922.Z Mcan be determined.506 <strong>Electrical</strong> devices | <strong>ABB</strong>


6 Calculation of short-circuit current6.5 Algebra of sequences6.5.5 Formulas for the calculation of the fault currents as a function of theelectrical parameters of the plantThrough Table 1 <strong>and</strong> through the formulas given for the sequence impedancesexpressed as a function of the electrical parameters of the plant components,it is possible to calculate the different short-circuit currents.In the following example, a network with a MV/LV transformer with delta primarywinding <strong>and</strong> secondary winding with grounded star point is taken into consideration<strong>and</strong> a line-to-line fault is assumed downstream the cable distribution line.Figure 6Z NETZ LZ NETZ LZ NETZ TZ LZ NZ PEApplying the algebra of sequences:the impedances relevant to the positive <strong>and</strong> negative sequences underexamination are:considering that, the following is obtained:where:U ris the rated voltage on the LV sideZ Tis the impedance of the transformerZ Lis the impedance of the phase conductorZ NETis the impedance of the upstream network.By making reference to the previous example, it is possible to obtain Table 2below, which gives the expressions for the short-circuit currents according tothe different typologies of fault.<strong>ABB</strong> | <strong>Electrical</strong> devices 507


6 Calculation of short-circuit current6.5 Algebra of sequencesTable 2Three-phasefaultI k3Z NETZ NETZ LZ LI k3=Z NETU r3. ( +Z T +Z L )Z NETZ LZ TZ NZ PELine-to-linefaultI k2Z NETZ NETZ LZ L= I k2U r2.( Z NET +Z T +Z L )Z NETZ LZ TZ NZ PESingle-phasefaultI k1 (line-to-neutral orline-to-PE)Z NETZ NETZ LZ L= I k1U r23 . + Z PE3. ( Z NET +Z T + Z L(Z NETZ TZ LZ NZ PE= I k1U r23 . + Z N3. ( Z NET +Z T + Z L(Where:U ris the rated voltage on the LV sideZ Tis the impedance of the transformerZ Lis the impedance of the phase conductorZ NETis the impedance of the upstream networkZ PEis the impedance of the protection conductor (PE)Z Nis the impedance of the neutral conductor508 <strong>Electrical</strong> devices | <strong>ABB</strong>


6 Calculation of short-circuit current6.5 Algebra of sequencesTable 3Table 3 below summarizes the relations for the fault currents, taking into accountthe upstream defined or infinite power network values <strong>and</strong> the distance of thefault from the transformer.Upstream defined power network Upstream infinite power network Z NET 0Far-from thetransformerNear thetransformerZ L 0, Z PE (o Z N ) 0Far-from thetransformerNear thetransformerZ L 0, Z PE (o Z N ) 0I k3 =I k3I k3 =3. ( +Z T + Z L )Z NETU rU r3. ( +Z T )Z NETI k3=U r3. ( +Z L )Z TI k3=U r3. ( )Z TU rI k2 =I k2 =2.( Z NET +Z T + Z L )2.( Z NET +Z T )I k2U r= I k2U r2.( +Z L )Z T= I k2U r2.( Z T )I k2 < I k3 I k2 = 0.87.I k3 I k2 = 0.87.I k3 I k2 = 0.87.I k3I k1 =I k1U r2( Z NET +Z T +Z L3.3 . +Z PE)I k1=U r2( Z NET +Z T3.3 . )I k1=U r3. ( Z T +Z L + Z PE )I k1 > I k3ifZ NET > 3 . Z PEI k1 > I k3 I k1 ʺ I k3 I k1 =I k1=U r3. ( )I k3Z T<strong>ABB</strong> | <strong>Electrical</strong> devices 509


6.6 Calculation of the peak value of theshort-circuit current6 Calculation of short-circuit currentThe electrodynamical effects of the short-circuit currents are particularlydangerous for the bus ducts, but they can also damage cables.The peak current is important also to evaluate the I cmvalue of the circuitbreaker.The I cmvalue is also bound to the I cuvalue, according to Table 16 of the St<strong>and</strong>ardIEC 60947-1. With reference to the short-circuit current of the plant, it shallbe I cm> I kp.The peak current of a plant may be calculated by the following formula (seeStd. IEC 60909-0):where:- I” kis the short-circuit current (rms value) at the initial instant of the shortcircuit- R is the resistive component of the short-circuit impedance at the faultlocation- X is the reactive component of the short-circuit current at the fault locationWhen the power factor cosϕ kis known, it is possible to write:510 <strong>Electrical</strong> devices | <strong>ABB</strong>


6.7 Considerations about UPS(Uninterruptible Power Supplies)contribution to short-circuit currents6 Calculation of short-circuit currentIn the following considerations particular attention is given to a doubleconversionor UPS on-line, belonging to the category VFI (Voltage <strong>and</strong> FrequencyIndependent), for which the output voltage is independent of the mains voltagevariations <strong>and</strong> frequency variations are <strong>control</strong>led by this device within thest<strong>and</strong>ard limits prescribed by the St<strong>and</strong>ards; this system is characterised bythe following operating modalities:- under normal operating conditions, in the presence of the network voltage,the load is fed by the network itself through the UPS;- under emergency conditions (lack of network), power to the load is suppliedby the battery <strong>and</strong> by the inverter (“isl<strong>and</strong> supply” with UPS disconnectedfrom the mains);- in case of temporary overcurrent required by the load (e.g. motor start-up),power supply to the load is guaranteed by the network through the staticswitch which excludes the UPS;- in case of maintenance, for example due to a fault on the UPS, the load is fedby the network through a manual bypass switch, by temporarily giving up theavailability of emergency power supply.As regards the dimensioning of the protections on the supply side of the UPS,it is necessary to know the characteristics of the network voltage <strong>and</strong> of theshort-circuit current; for the dimensioning of the protections on the load side,it is necessary to know the current values let through by the UPS.If power supply of the loads is provided directly from the network through manualbypass, also the circuit-breaker on the load side must have a breaking capacity(Icu) suitable for the short-circuit current of the supply-side network.Furthermore, if required, an evaluation of the protection co-ordination in relationto the operating conditions is necessary.<strong>ABB</strong> | <strong>Electrical</strong> devices 511


6 Calculation of short-circuit current6.7 Calculation of short-circuit currentHowever, in order to choose the suitable protections, it is important to distinguishbetween two operating conditions for UPS:1) UPS under normal operating conditionsa) Overload condition:- if due to a possible fault on the battery, this condition affects only the circuitbreakeron the supply-side of the UPS (also likely the intervention of theprotections inside the battery);- if required by the load, this condition might not be supported by the UPS,which is bypassed by the static converter.b) Short-circuit condition:The short-circuit current is limited by the dimensioning of the thyristors ofthe bridge inverter. In the practice, UPS may supply a maximum short-circuitcurrent equal to 150 to 200% of the rated value. In the event of a short-circuit,the inverter supplies the maximum current for a limited time (some hundredsof milliseconds) <strong>and</strong> then switches to the network, so that power to the loadis supplied by the bypass circuit.In this case, selectivity between the circuit-breaker on the supply side <strong>and</strong>the circuit-breaker on the load side is important in order to disconnect onlythe load affected by the fault.The bypass circuit, which is also called static switch, <strong>and</strong> is formed by thyristorsprotected by extrarapid fuses, can feed the load with a higher current than theinverter; this current results to be limited by the dimensioning of the thyristorsused, by the power installed <strong>and</strong> by the provided protections.The thyristors of the bypass circuit are usually dimensioned to withst<strong>and</strong> thefollowing overload conditions:125% for 600 seconds150% for 60 seconds700% for 600 milliseconds1000% for 100 millisecondsGenerally, more detailed data can be obtained from the technical informationgiven by the manufacturer.512 <strong>Electrical</strong> devices | <strong>ABB</strong>


6 Calculation of short-circuit current2) UPS under emergency operating conditions6.7 Calculation of short-circuit currenta) Overload condition:this condition, involving the load-side circuit-breaker only, is supported by thebattery with inverter, which presents an overload condition usually calculablein the following orders of magnitude:1.15 x In for indefinite time1.25 x In for 600 seconds1.5 x In for 60 seconds2 x In for 1 secondsGenerally, more detailed data can be obtained from the technical informationgiven by the manufacturer.b) Short-circuit condition:the maximum current towards the load is limited by the inverter circuit only(with a value from 150 to 200% of the nominal value). The inverter feeds theshort-circuit for a certain period of time, usually limited to some milliseconds,after which the UPS unit disconnects the load leaving it without supply. In thisoperating modality, it is necessary to obtain selectivity between the circuitbreakeron the load side <strong>and</strong> the inverter, which is quite difficult due to thereduced tripping times of the protection device of the inverter.Figure 7 Figure 8Manual bypassStatic bypass~ ~~ == ~~ == ~UPSUPS on-line with static switchUPS off-line: loads directly fed by the network<strong>ABB</strong> | <strong>Electrical</strong> devices 513


Annex A: Calculation of load current I bGeneric loadsThe formula for the calculation of the load current of a generic load is:where:• P is the active power [W];• k is a coefficient which has the value:- 1 for single-phase systems or for direct current systems;- for three-phase systems;• U ris the rated voltage [V] (for three-phase systems it is the line voltage, forsingle-phase systems it is the phase voltage);• cosϕ is the power factor.Table 1 allows the load current to be determined for some power values accordingto the rated voltage. The table has been calculated considering cosϕto be equal to 0.9; for different power factors, the value from Table 1 must bemultiplied by the coefficient given in Table 2 corresponding to the actual valueof the power factor (cosϕ act).Table 1: Load current for three-phase systems with cosϕ = 0.9U r[V]P [kW]230 400 415 440 500 600 690I b[A]0.03 0.08 0.05 0.05 0.04 0.04 0.03 0.030.04 0.11 0.06 0.06 0.06 0.05 0.04 0.040.06 0.17 0.10 0.09 0.09 0.08 0.06 0.060.1 0.28 0.16 0.15 0.15 0.13 0.11 0.090.2 0.56 0.32 0.31 0.29 0.26 0.21 0.190.5 1.39 0.80 0.77 0.73 0.64 0.53 0.461 2.79 1.60 1.55 1.46 1.28 1.07 0.932 5.58 3.21 3.09 2.92 2.57 2.14 1.865 13.95 8.02 7.73 7.29 6.42 5.35 4.6510 27.89 16.04 15.46 14.58 12.83 10.69 9.3020 55.78 32.08 30.92 29.16 25.66 21.38 18.5930 83.67 48.11 46.37 43.74 38.49 32.08 27.8940 111.57 64.15 61.83 58.32 51.32 42.77 37.1950 139.46 80.19 77.29 72.90 64.15 53.46 46.4960 167.35 96.23 92.75 87.48 76.98 64.15 55.7870 195.24 112.26 108.20 102.06 89.81 74.84 65.0880 223.13 128.30 123.66 116.64 102.64 85.53 74.3890 251.02 144.34 139.12 131.22 115.47 96.23 83.67100 278.91 160.38 154.58 145.80 128.30 106.92 92.97110 306.80 176.41 170.04 160.38 141.13 117.61 102.27120 334.70 192.45 185.49 174.95 153.96 128.30 111.57130 362.59 208.49 200.95 189.53 166.79 138.99 120.86140 390.48 224.53 216.41 204.11 179.62 149.68 130.16150 418.37 240.56 231.87 218.69 192.45 160.38 139.46200 557.83 320.75 309.16 291.59 256.60 213.83 185.94514 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex A: Calculation of load curremt I bAnnex A: Calculation of load current I bU r[V]230 400 415 440 500 600 690P [kW]I b[A]250 697.28 400.94 386.45 364.49 320.75 267.29 232.43300 836.74 481.13 463.74 437.39 384.90 320.75 278.91350 976.20 561.31 541.02 510.28 449.05 374.21 325.40400 1115.65 641.50 618.31 583.18 513.20 427.67 371.88450 1255.11 721.69 695.60 656.08 577.35 481.13 418.37500 1394.57 801.88 772.89 728.98 641.50 534.58 464.86550 1534.02 882.06 850.18 801.88 705.65 588.04 511.34600 1673.48 962.25 927.47 874.77 769.80 641.50 557.83650 1812.94 1042.44 1004.76 947.67 833.95 694.96 604.31700 1952.39 1122.63 1082.05 1020.57 898.10 748.42 650.80750 2091.85 1202.81 1159.34 1093.47 962.25 801.88 697.28800 2231.31 1283.00 1236.63 1166.36 1026.40 855.33 743.77850 2370.76 1363.19 1313.92 1239.26 1090.55 908.79 790.25900 2510.22 1443.38 1391.21 1312.16 1154.70 962.25 836.74950 2649.68 1523.56 1468.49 1385.06 1218.85 1015.71 883.231000 2789.13 1603.75 1545.78 1457.96 1283.00 1069.17 929.71Table 2: Correction factors for load current with cosϕ other than 0.9cosϕ act1 0.95 0.9 0.85 0.8 0.75 0.7k cosϕ*0.9 0.947 1 1.059 1.125 1.2 1.286*For cosϕ actvalues not present in the table,Table 3 allows the load current to be determined for some power values accordingto the rated voltage. The table has been calculated considering cosϕto be equal to 1; for different power factors, the value from Table 3 must bemultiplied by the coefficient given in Table 4 corresponding to the actual valueof the power factor (cosϕ act).Table 3: Load current for single-phase systems with cosϕ = 1 or dc systemsU r[V]230 400 415 440 500 600 690P [kW]I b[A]0.03 0.13 0.08 0.07 0.07 0.06 0.05 0.040.04 0.17 0.10 0.10 0.09 0.08 0.07 0.060.06 0.26 0.15 0.14 0.14 0.12 0.10 0.090.1 0.43 0.25 0.24 0.23 0.20 0.17 0.140.2 0.87 0.50 0.48 0.45 0.40 0.33 0.290.5 2.17 1.25 1.20 1.14 1.00 0.83 0.721 4.35 2.50 2.41 2.27 2.00 1.67 1.452 8.70 5.00 4.82 4.55 4.00 3.33 2.905 21.74 12.50 12.05 11.36 10.00 8.33 7.2510 43.48 25.00 24.10 22.73 20.00 16.67 14.4920 86.96 50.00 48.19 45.45 40.00 33.33 28.99<strong>ABB</strong> | <strong>Electrical</strong> devices 515


Annex A: Calculation of load curremt I bAnnex A: Calculation of load current I bP [kW]U r[V]230 400 415 440 500 600 690I b[A]30 130.43 75.00 72.29 68.18 60.00 50.00 43.4840 173.91 100.00 96.39 90.91 80.00 66.67 57.9750 217.39 125.00 120.48 113.64 100.00 83.33 72.4660 260.87 150.00 144.58 136.36 120.00 100.00 86.9670 304.35 175.00 168.67 159.09 140.00 116.67 101.4580 347.83 200.00 192.77 181.82 160.00 133.33 115.9490 391.30 225.00 216.87 204.55 180.00 150.00 130.43100 434.78 250.00 240.96 227.27 200.00 166.67 144.93110 478.26 275.00 265.06 250.00 220.00 183.33 159.42120 521.74 300.00 289.16 272.73 240.00 200.00 173.91130 565.22 325.00 313.25 295.45 260.00 216.67 188.41140 608.70 350.00 337.35 318.18 280.00 233.33 202.90150 652.17 375.00 361.45 340.91 300.00 250.00 217.39200 869.57 500.00 481.93 454.55 400.00 333.33 289.86250 1086.96 625.00 602.41 568.18 500.00 416.67 362.32300 1304.35 750.00 722.89 681.82 600.00 500.00 434.78350 1521.74 875.00 843.37 795.45 700.00 583.33 507.25400 1739.13 1000.00 963.86 909.09 800.00 666.67 579.71450 1956.52 1125.00 1084.34 1022.73 900.00 750.00 652.17500 2173.91 1250.00 1204.82 1136.36 1000.00 833.33 724.64550 2391.30 1375.00 1325.30 1250.00 1100.00 916.67 797.10600 2608.70 1500.00 1445.78 1363.64 1200.00 1000.00 869.57650 2826.09 1625.00 1566.27 1477.27 1300.00 1083.33 942.03700 3043.48 1750.00 1686.75 1590.91 1400.00 1166.67 1014.49750 3260.87 1875.00 1807.23 1704.55 1500.00 1250.00 1086.96800 3478.26 2000.00 1927.71 1818.18 1600.00 1333.33 1159.42850 3695.65 2125.00 2048.19 1931.82 1700.00 1416.67 1231.88900 3913.04 2250.00 2168.67 2045.45 1800.00 1500.00 1304.35950 4130.43 2375.00 2289.16 2159.09 1900.00 1583.33 1376.811000 4347.83 2500.00 2409.64 2272.73 2000.00 1666.67 1449.28Table 4: Correction factors for load current with cosϕ other than 1cosϕ act1 0.95 0.9 0.85 0.8 0.75 0.7k cosϕ*1 1.053 1.111 1.176 1.25 1.333 1.429*For cosϕ actvalues not present in the table,Lighting circuitsThe current absorbed by the lighting system may be deduced from the lightingequipment catalogue, or approximately calculated using the following formula:516 <strong>Electrical</strong> devices | <strong>ABB</strong>where:• P Lis the power of the lamp [W];• n Lis the number of lamps per phase;• k Bis a coefficient which has the value:- 1 for lamps which do not need any auxiliary starter;- 1.25 for lamps which need auxiliary starters;• k Nis a coefficient which has the value:- 1 for star-connected lamps;- for delta-connected lamps;• U rLis the rated voltage of the lamps;• cosϕ is the power factor of the lamps which has the value:- 0.4 for lamps without compensation;- 0.9 for lamps with compensation.


Annex A: Calculation of load curremt I bAnnex A: Calculation of load current I bMotorsTable 5 gives the approximate values of the load current for some three-phasesquirrel-cage motors, 1500 rpm at 50 Hz, according to the rated voltage.Note: these values are given for information only, <strong>and</strong> may vary according to the motor manifacturer<strong>and</strong> depending on the number of polesMotor powerTable 5: Motor load currentRated current of the motor at:[kW]0.060.090.120.180.250.370.550.751.11.52.22.533.7455.56.57.5891112.51518.520222530374045515559758090100110129132140147160180184200220250257295315355400450475500560600670PS = hp1/121/81/61/41/31/23/411.5233.4455.56.87.58.8101112.51517202527303440505460707580100110125136150175180190200220245250270300340350400430480545610645680760810910220-230 V[A]0.380.550.761.11.42.12.73.34.96.28.79.811.614.215.318.920.623.727.428.83239.243.852.664.969.375.284.4101124134150168181194245260292325358420425449472502578590626700803826948990108012501410149015701750––240 V[A]0.350.500.6811.381.932.33.14.15.67.98.910.6131417.218.921.824.826.429.335.340.248.258.763.46877.292.7114123136154166178226241268297327384393416432471530541589647736756868927101011301270134014201580––380-400 V[A]0.220.330.420.640.881.221.522.63.555.76.68.28.510.511.513.815.516.718.3222530374044506072798597105112140147170188205242245260273295333340370408460475546580636710800850890100010801200415 V[A]0.200.300.400.600.851.151.4022.53.555.56.57.58.4101112.51415.417212328353740475566728090961051351381651822002302422502602803203253403854254505005355806507407808309209901100440 V[A]0.190.280.370.550.761.061.251.672.263.034.314.95.87.17.69.410.31213.514.415.819.321.926.33234.637.142.150.161.96773.983.890.396.91231311461621782092142272362562892953213534014124735055496116887307708609201030500 V[A]0.160.240.330.460.590.851.201.482.12.63.84.35.16.26.58.18.910.411.912.713.916.71922.528.530.6333844546064.573.77985.3106112128143156184186200207220254259278310353363416445483538608645680760810910600 V[A]0.120.210.270.400.560.771.021.221.662.223.163.594.255.25.66.97.58.79.910.611.614.116.119.323.525.427.230.937.145.449.154.261.466.271.190.396.3107119131153157167173188212217235260295302348370405450508540565630680760660-690 V[A]–––––0.70.91.11.522.93.33.54.44.966.78.199.710.6131517.52123252833424449566066828698107118135140145152170190200215235268280320337366410460485510570610680<strong>ABB</strong> | <strong>Electrical</strong> devices 517


Annex B: HarmonicsWhat are they?The harmonics allow to represent any periodic waveform; in fact, accordingto Fourier’s theorem, any periodic function of a period T may be representedas a summation of:- a sinusoid with the same period T;- some sinusoids with the same frequency as whole multiples of the fundamental;- a possible continuous component, if the function has an average value notnull in the period.The harmonic with frequency corresponding to the period of the originalwaveform is called fundamental <strong>and</strong> the harmonic with frequency equal to “n”times that of the fundamental is called harmonic component of order “n”.A perfectly sinusoidal waveform complying with Fourier’s theorem does notpresent harmonic components of order different from the fundamental one.Therefore, it is underst<strong>and</strong>able how there are no harmonics in an electricalsystem when the waveforms of current <strong>and</strong> voltage are sinusoidal. On thecontrary, the presence of harmonics in an electrical system is an index of thedistortion of the voltage or current waveform <strong>and</strong> this implies such a distributionof the electric power that malfunctioning of equipment <strong>and</strong> protective devicescan be caused.To summarize: the harmonics are nothing less than the components of adistorted waveform <strong>and</strong> their use allows us to analyse any periodic nonsinusoidalwaveform through different sinusoidal waveform components.Figure 1 below shows a graphical representation of this concept.Figure 1Caption:nonsinusoidal waveformfirst harmonic (fundamental)third harmonicfifth harmonic518 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex B: HarmonicsAnnex B: HarmonicsHow harmonics are generated?Harmonics are generated by nonlinear loads. When we apply a sinusoidalvoltage to a load of this type, we shall obtain a current with non-sinusoidalwaveform. The diagram of Figure 2 illustrates an example of nonsinusoidalcurrent waveform due to a nonlinear load:Figure 2IItvtvtLinear loadtNonlinear loadAs already said, this nonsinusoidal waveform can be deconstructed intoharmonics. If the network impedances are very low, the voltage distortionresulting from a harmonic current is low too <strong>and</strong> rarely it is above the pollutionlevel already present in the network. As a consequence, the voltage can remainpractically sinusoidal also in the presence of current harmonics.To function properly, many electronic devices need a definite current waveform<strong>and</strong> thus they have to ’cut’ the sinusoidal waveform so as to change its rmsvalue or to get a direct current from an alternate value; in these cases the currenton the line has a nonsinusoidal curve.The main equipment generating harmonics are:- personal computer- fluorescent lamps- static converters- continuity groups- variable speed drives- welders.In general, waveform distortion is due to the presence, inside of these equipment,of bridge rectifiers, whose semiconductor devices carry the current only for afraction of the whole period, thus originating discontinuous curves with theconsequent introduction of numerous harmonics.<strong>ABB</strong> | <strong>Electrical</strong> devices 519


Annex B: HarmonicsAnnex B: HarmonicsAlso transformers can be cause of harmonic pollution; in fact, by applyinga perfectly sinusoidal voltage to a transformer, it results into a sinusoidalmagnetizing flux, but, due to the phenomenon of the magnetic saturation ofiron, the magnetizing current shall not be sinusoidal. Figure 3 shows a graphicrepresentation of this phenomenon:Figure 3The resultant waveform of the magnetizing current contains numerousharmonics, the greatest of which is the third one. However, it should be notedthat the magnetizing current is generally a little percentage of the rated currentof the transformer <strong>and</strong> the distortion effect becomes more <strong>and</strong> more negligiblethe most loaded the transformer results to be.EffectsThe main problems caused by harmonic currents are:1) overloading of neutrals2) increase of losses in the transformers3) increase of skin effect.The main effects of the harmonics voltages are:4) voltage distortion5) disturbances in the torque of induction motors520 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex B: HarmonicsAnnex B: Harmonics1) Overloading of neutralsIn a three phase symmetric <strong>and</strong> balanced system with neutral, the waveformsbetween the phases are shifted by a 120° phase angle so that, when thephases are equally loaded, the current in the neutral is zero. The presence ofunbalanced loads (phase-to-phase, phase-to-neutral etc.) allows the flowingof an unbalanced current in the neutral.Figure 4L1 L2 L3NFigure 4 shows an unbalanced system of currents (phase 3 with a load 30%higher than the other two phases), <strong>and</strong> the current resultant in the neutral ishighlighted in red. Under these circumstances, the St<strong>and</strong>ards allow the neutralconductor to be dimensioned with a cross section smaller than the phase conductors.In the presence of distortion loads it is necessary to evaluate correctlythe effects of harmonics.In fact, although the currents at fundamental frequency in the three phases canceleach other out, the components of the third harmonic, having a period equal toa third of the fundamental, that is equal to the phase shift between the phases(see Figure 5), are reciprocally in phase <strong>and</strong> consequently they sum in the neutralconductor adding themselves to the normal unbalance currents.The same is true also for the harmonics multiple of three (even <strong>and</strong> odd, althoughactually the odd ones are more common).<strong>ABB</strong> | <strong>Electrical</strong> devices 521


Annex B: HarmonicsAnnex B: HarmonicsFigure 5Phase 1:fundamental harmonic <strong>and</strong> 3 rd harmonicPhase 2:fundamental harmonic <strong>and</strong> 3 rd harmonicPhase 3:fundamental harmonic <strong>and</strong> 3 rd harmonicResultant of the currents of the three phases522 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex B: HarmonicsAnnex B: Harmonics2) Increase of losses in the transformersThe effects of harmonics inside the transformers involve mainly three aspects:• a) increase of iron losses (or no-load losses)• b) increase of copper losses• c) presence of harmonics circulating in the windingsa) The iron losses are due to the hysteresis phenomenon <strong>and</strong> to the lossescaused by eddy currents; the losses due to hysteresis are proportional to thefrequency, whereas the losses due to eddy currents depend on the squareof the frequency.b) The copper losses correspond to the power dissipated by Joule effect inthe transformer windings. As the frequency rises (starting from 350 Hz) thecurrent tends to thicken on the surface of the conductors (skin effect); underthese circumstances, the conductors offer a smaller cross section to thecurrent flow, since the losses by Joule effect increase.These two first aspects affect the overheating which sometimes causes aderating of the transformer.c) The third aspect is relevant to the effects of the triple-N harmonics (homopolarharmonics) on the transformer windings. In case of delta windings, theharmonics flow through the windings <strong>and</strong> do not propagate upstreamtowards the network since they are all in phase; the delta windings thereforerepresent a barrier for triple-N harmonics, but it is necessary to pay particularattention to this type of harmonic components for a correct dimensioningof the transformer.3) Increase of skin effectWhen the frequency rises, the current tends to flow on the outer surface of aconductor. This phenomenon is known as skin effect <strong>and</strong> is more pronouncedat high frequencies. At 50 Hz power supply frequency, skin effect is negligible,but above 350 Hz, which corresponds to the 7th harmonic, the cross section forthe current flow reduces, thus increasing the resistance <strong>and</strong> causing additionallosses <strong>and</strong> heating.In the presence of high-order harmonics, it is necessary to take skin effect intoaccount, because it affects the life of cables. In order to overcome this problem,it is possible to use multiple conductor cables or busbar systems formed bymore elementary isolated conductors.4) Voltage distortionThe distorted load current drawn by the nonlinear load causes a distortedvoltage drop in the cable impedance. The resultant distorted voltage waveformis applied to all other loads connected to the same circuit, causing harmoniccurrents to flow in them, even if they are linear loads.The solution consists in separating the circuits which supply harmonic generatingloads from those supplying loads sensitive to harmonics.5) Disturbances in the torque of induction motorsHarmonic voltage distortion causes increased eddy current losses in themotors, in the same way as seen for transformers. The additional losses aredue to the generation of harmonic fields in the stator, each of which is tryingto rotate the motor at a different speed, both forwards (1 st , 4 th , 7 th , ...) as wellas backwards (2 nd , 5 th , 8 th , ...). High frequency currents induced in the rotorfurther increase losses.<strong>ABB</strong> | <strong>Electrical</strong> devices 523


Annex B: HarmonicsAnnex B: HarmonicsMain formulasThe definitions of the main quantities typically used in a harmonic analysis aregiven hereunder.Frequency spectrumThe frequency spectrum is the classic representation of the harmonic content ofa waveform <strong>and</strong> consists of a histogram reporting the value of each harmonicas a percentage of the fundamental component. For example, for the followingwaveform:100the frequency spectrum is:90807060504030201001234567891011 12 13 141516 17 18192021 22 23 2425 26 27282930 31The frequency spectrum provides the size of the existing harmonic components.Peak factorThe peak factor is defined as the ratio between the peak value <strong>and</strong> the rmsvalue of the waveform:in case of perfectly sinusoidal waveforms, it is worth , but in the presenceof harmonics it can reach higher values.High peak factors may cause the unwanted tripping of the protectiondevices.Rms valueThe rms value of a periodical waveform e(t) is defined as:where T is the period.524 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex B: HarmonicsAnnex B: HarmonicsIf the rms values of the harmonic components are known, the total rms valuecan be easily calculated by the following formula:Total harmonic distortion THDThe total harmonic distortion is defined as:THD in currentTHD in voltageThe harmonic distortion ratio is a very important parameter, which givesinformation about the harmonic content of the voltage <strong>and</strong> current waveforms<strong>and</strong> about the necessary measures to be taken should these values be high.For THD i< 10% <strong>and</strong> THD u< 5%, the harmonic content is considered negligible<strong>and</strong> such as not to require any provisions.St<strong>and</strong>ard references for circuit-breakersIEC 60947 Low-voltage switchgear <strong>and</strong> <strong>control</strong>gearAnnex F of the St<strong>and</strong>ard IEC 60947-2 (third edition 2003) gives informationabout the tests to check the immunity of the overcurrent releases againstharmonics.In particular, it describes the waveform of the test current, at which, incorrespondence with determinate values of injected current, the release shallhave a behaviour complying with the prescriptions of this St<strong>and</strong>ard.Hereunder, the characteristics of the waveform of the test current are reported,which shall be formed, in alternative, as follows:1) by the fundamental component <strong>and</strong> by a 3rd harmonic variable between72% <strong>and</strong> 88% of the fundamental, with peak factor equal to 2 or by a 5thharmonic variable between 45% <strong>and</strong> 55% of the fundamental, with peak factorequal to 1.9or2) by the fundamental component <strong>and</strong> by a 3rd harmonic higher than 60% ofthe fundamental, by a 5th harmonic higher than 14% of the fundamental <strong>and</strong>by a 7th harmonic higher than 7% of the fundamental. This test current shallhave a peak factor > 2.1 <strong>and</strong> shall flow for a given time < 42% of the periodfor each half period.<strong>ABB</strong> | <strong>Electrical</strong> devices 525


Annex C: Calculation of the coefficient k forthe cables (k 2 S 2 )By using the formula (1), it is possible to determine the conductor minimumsection S, in the hypothesis that the generic conductor is submitted to an adiabaticheating from a known initial temperature up to a specific final temperature(applicable if the fault is removed in less than 5 s):where:• S is the cross section [mm 2 ];• I is the value (r.m.s) of prospective fault current for a fault of negligibleimpedance, which can flow through the protective device [A];• t is the operating time of the protective device for automatic disconnection[s];k can be evaluated using the tables 2÷7 or calculated according to the formula(2):where:• Q cis the volumetric heat capacity of conductor material [J/°Cmm 3 ] at 20 °C;• B is the reciprocal of temperature coefficient of resistivity at 0 °C for theconductor [°C];• ρ 20is the electrical resistivity of conductor material at 20 °C [Ωmm];• θ iinitial temperature of conductor [°C];• θ ffinal temperature of conductor [°C].Table 1 shows the values of the parameters described above.Table 1: Value of parameters for different materialsMaterial B Q cρ 20[°C] [J/°Cmm 3 ] [Ωmm]Copper 234.5 3.45⋅10 -3 17.241⋅10 -6 226Aluminium 228 2.5⋅10 -3 28.264⋅10 -6 148Lead 230 1.45⋅10 -3 214⋅10 -6 41Steel 202 3.8⋅10 -3 138⋅10 -6 78526 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex C: Calculation of the coefficient k forthe cables (k 2 S 2 )Table 2: Values of k for phase conductorAnnex C: calculation of short-circuit currentConductor insulationInitial temperature °CFinal temperature °CMaterial of conductor:copperaluminiumtin-soldered jointsin copper conductorsPVC≤ 300 mm 27016011576115PVC≤ 300 mm 27014010368-EPRXLPE9025014394-Rubber60 °C6020014193-MineralPVC Bare70105160 250115 135/115 a----aThis value shall be used for bare cables exposed to touch.Conductor insulation70 °C PVC90 °C PVC90 °C thermosetting60 °C rubber85 °C rubberSilicone rubberTable 3: Values of k for insulated protective conductors not incorporatedin cables <strong>and</strong> not bunched with other cablesTemperature °C bInitial303030303030Final160/140 a160/140 a250200220350Copper143/133 a143/133 a176159166201Material of conductorAluminiumValue for k95/88 a95/88 a116105110133Steel52/49 a52/49 aaThe lower value applies to PVC insulated conductors of cross section greater than300 mm 2 .bTemperature limits for various types of insulation are given in IEC 60724.64586073<strong>ABB</strong> | <strong>Electrical</strong> devices 527


Annex C: calculation of short-circuit currentAnnex C: Calculation of the coefficient k forthe cables (k 2 S 2 )Cable coveringPVCPolyethyleneCSPTable 4: Values of k for bare protective conductors in contact withcable covering but not bunched with other cablesTemperature °C aInitial303030Final200150220Copper159138166Material of conductorAluminiumValue for k10591110Steel585060aTemperature limits for various types of insulation are given in IEC 60724.Conductor insulation70 °C PVC90 °C PVC90 °C thermosetting60 °C rubber85 °C rubberSilicone rubberTable 5: Values of k for protective conductors as a core incorporated ina cable or bunched with other cables or insulated conductorsTemperature °C bInitial7090906085180Final160/140 a160/140 a250200220350Copper115/103 a100/86 a143141134132Material of conductorAluminiumValue for k76/68 a66/57 a94938987Steel42/37 a36/31 a52514847aThe lower value applies to PVC insulated conductors of cross section greater than300 mm 2 .bTemperature limits for various types of insulation are given in IEC 60724.528 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex C: calculation of short-circuit currentAnnex C: Calculation of the coefficient k forthe cables (k 2 S 2 )Conductor insulation70 °C PVC90 °C PVC90 °C thermosetting60 °C rubber85 °C rubberMineral PVC covered aMineral bare sheathTable 6: Values of k for protective conductors as a metallic layer of acable e.g. armour, metallic sheath, concentric conductor, etc.Temperature °CInitial608080557570105Final200200200200220200250Copper141128128144140135135Material of conductorAluminium LeadValue for kaThis value shall also be used for bare conductors exposed to touch or in contact withcombustible material.9385859593--2623232626--Steel5146465251--Conductor insulationVisible <strong>and</strong> in restricted areaNormal conditionsFire riskTable 7: Value of k for bare conductors where there is no risk of damageto any neighbouring material by the temperature indicatedInitialtemperature°C303030k value228159138CopperMaximumtemperature°C500200150Material of conductork value12510591AluminiumMaximumtemperature°C300200150k value825850SteelMaximumtemperature°C500200150<strong>ABB</strong> | <strong>Electrical</strong> devices 529


Annex D: Main physical quantities <strong>and</strong>electrotechnical formulasThe International System of Units (SI)SI Base UnitsQuantity Symbol Unit nameLength m metreMass kg kilogramTime s SecondElectric Current A ampereThermodynamic Temperature K kelvinAmount of Substance mol moleLuminous Intensity cd c<strong>and</strong>elaMetric Prefixes for Multiples <strong>and</strong> Sub-multiples of UnitsDecimal power Prefix Symbol Decimal power Prefix Symbol10 24 yotta Y 10 -1 deci d10 21 zetta Z 10 -2 centi c10 18 exa E 10 -3 milli m10 15 peta P 10 -6 mikro µ10 12 tera T 10 -9 nano n10 9 giga G 10 -12 pico p10 6 mega M 10 -15 femto f10 3 kilo k 10 -18 atto a10 2 etto h 10 -21 zepto z10 deca da 10 -24 yocto y530 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex D: Main physical quantities <strong>and</strong>electrotechnical formulasMain quantities <strong>and</strong> SI unitsAnnex D: Main physical quantitiesQuantity SI unit Other units ConversionSymbol Name Symbol Name Symbol NameLength, area, volumein inch 1 in = 25.4 mmft foot 1 ft = 30.48 cml length m metre fathom fathom 1 fathom = 6 ft = 1.8288 mmile mile 1 mile = 1609.344 msm sea mile 1 sm = 1852 myd yard 1 yd = 91.44 cmA area m 2 square metre a are 1 a = 10 2 m 2ha hectare 1 ha = 10 4 m 2l litre 1 l = 1 dm 3 = 10 -3 m 3V volume m 3 cubic metre UK pt pint 1 UK pt = 0.5683 dm 3UK gal gallon 1 UK gal = 4.5461 dm 3US gal gallon 1 US gal = 3.7855 dm 3Anglesα, β, γ plane angle rad radian ° degreesΩ solid angle sr steradianMassm mass, weight kg kilogram lb pound 1 lb = 0.45359 kgρ density kg/m 3 kilogramυ specific volume m 3 /kg cubic metrefor kilogramM moment of inertia kg⋅m 2 kilogram forsquare metreTimet duration s secondf frequency Hz Hertz 1 Hz = 1/sω angular 1/s reciprocal second ω = 2pffrequencyv speed m/s metre per second km/h kilometre 1 km/h = 0.2777 m/sper hourmile/h mile per hour 1 mile/h = 0.4470 m/sknot kn 1 kn = 0.5144 m/sg acceleration m/s 2 metre per secondsquaredForce, energy, powerF force N newton 1 N = 1 kg⋅m/s 2kgf1 kgf = 9.80665 Np pressure/stress Pa pascal 1 Pa = 1 N/m 2bar bar 1 bar = 10 5 PaW energy, work J joule 1 J = 1 W⋅s = 1 N⋅mP power W watt Hp horsepower 1 Hp = 745.7 WTemperature <strong>and</strong> heatT temperature K kelvin °C Celsius T[K] = 273.15 + T [°C]°F Fahrenheit T[K] = 273.15 + (5/9)⋅(T [°F]-32)Q quantity of heat J jouleS entropy J/K joule per kelvinPhotometric quantitiesI luminous intensity cd c<strong>and</strong>elaL luminance cd/m 2 c<strong>and</strong>ela per square metreΦ luminous flux lm lumen 1 lm = 1 cd⋅srE illuminance lux 1 lux = 1 lm/m 2<strong>ABB</strong> | <strong>Electrical</strong> devices 531


Annex D: Main physical quantitiesAnnex D: Main physical quantities <strong>and</strong>electrotechnical formulasMain electrical <strong>and</strong> magnetic quantities <strong>and</strong> SI unitsQuantity SI unit Other units ConversionSymbol Name Symbol Name Symbol NameI current A ampereV voltage V voltR resistance Ω ohmG conductance S siemens G = 1/RX reactance Ω ohm X L= ωLX C=-1/ωCB susceptance S siemens B L= -1/ωLB C= ωCZ impedance Ω ohmY admittance S siemensP active power W wattQ reactive power var reactive voltampereS apparent power VA volt ampereQ electric charge C coulomb Ah ampere/hour 1 C = 1 A⋅s1 Ah = 3600 A⋅sE electric field V/m volt per metrestrengthC electric capacitance F farad 1 F = 1 C/VH magnetic field A/m ampere per metreB magnetic induction T tesla G gauss 1 T = 1 V⋅s/m 21 G = 10 -4 TL inductance H henry 1 H = 1 Ω⋅sResistivity values, conductivity <strong>and</strong> temperature coefficient at20 °C of the main electrical materialsconductor conductivity temperatureresistivity ρ 20χ 20=1/ρ 20coefficient α 20[mm 2 Ω/m] [m/mm 2 Ω] [K -1 ]Aluminium 0.0287 34.84 3.8⋅10 -3Brass, CuZn 40 ≤ 0.067 ≥ 15 2⋅10 -3Constantan 0.50 2 -3⋅10 -4Copper 0.0175 57.14 3.95⋅10 -3Gold 0.023 43.5 3.8⋅10 -3Iron wire 0.1 to 0,15 10 to 6.7 4.5⋅10 -3Lead 0.208 4.81 3.9⋅10 -3Magnesium 0.043 23.26 4.1⋅10 -3Manganin 0.43 2.33 4⋅10 -6Mercury 0.941 1.06 9.2⋅10 -4Ni Cr 8020 1 1 2.5⋅10 -4Nickeline 0.43 2.33 2.3⋅10 -4Silver 0.016 62.5 3.8⋅10 -3Zinc 0.06 16.7 4.2⋅10 -3532 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex D: Main physical quantities <strong>and</strong>electrotechnical formulasMain electrotechnical formulasImpedanceAnnex D: Main physical quantitiesresistance of a conductor at temperature ϑconductance of a conductor at temperature ϑresistivity of a conductor at temperature ϑcapacitive reactanceinductive reactanceimpedancemodule impedancephase impedanceconductancecapacitive susceptanceinductive susceptanceadmittancemodule admittancephase admittance+ZjX LURX-jX CR+–Y+jB CUGB-jB LG+–<strong>ABB</strong> | <strong>Electrical</strong> devices 533


Annex D: Main physical quantitiesAnnex D: Main physical quantities <strong>and</strong>electrotechnical formulasImpedances in seriesZ = Z 1 + Z 2 + Z 3 + …Z 1 Z 2 Z 3Admittances in series1Y =1+ 1 + 1 + …Y 1 Y 2 Y 3Y 1 Y 2 Y 3Impedances in parallel1Z =1+ 1 + 1 + …Z 1 Z 2 Z 3Z 1Z 2 Z 3Admittances in parallelY = Y 1 + Y 2 + Y 3 + …Y 1Y 2 Y 3Delta-star <strong>and</strong> star-delta transformationsZ 131Z 1Z 122Z 30 Z 23Z 23Y→∆Z 12 = Z 1 + Z 2 + Z 1 ⋅ Z 2Z 3∆→YZ 1 =Z 12 ⋅ Z 13Z 12 + Z 13 + Z 23Z 23 = Z 2 + Z 3 + Z 2 ⋅ Z 3Z 1Z 2 =Z 12 ⋅ Z 23Z 12 + Z 13 + Z 23Z 13 = Z 3 + Z 1 + Z 3 ⋅ Z 1Z 2Z 3 =Z 23 ⋅ Z 13Z 12 + Z 13 + Z 23534 <strong>Electrical</strong> devices | <strong>ABB</strong>


Annex D: Main physical quantitiesAnnex D: Main physical quantities <strong>and</strong>electrotechnical formulasTransformersTwo-winding transformerrated currentI r =S rshort-circuit powershort-circuit currentS k =I k =S ru k % ⋅ 100S k I= r3 ⋅ U r u k % ⋅ 1003 ⋅ U ru k % S rlongitudinal impedancelongitudinal resistancelongitudinal reactanceU 2 rZ T =u k % ⋅ = 100 S r 100⋅R T =p U 2 k % r p ⋅ = k %100 S r 100⋅X T = Z T2 – R T23 ⋅ I 2 rS r3 ⋅ I 2 rThree-winding transformer1Z 1Z 2Z 332Z 12 = u 212100 ⋅ U rS r12Z 1 = 1 2 (Z 12 + Z 13 – Z 23 )Z 13 = u 213100 ⋅ U rS r13Z 2 = 1 2 (Z 12 + Z 23 – Z 13 )Z 23 = u 223100 ⋅ U rS r23Z 3 = 1 2 (Z 13 + Z 23 – Z 12 )<strong>ABB</strong> | <strong>Electrical</strong> devices 535


Annex D: Main physical quantities <strong>and</strong>electrotechnical formulasVoltage drop <strong>and</strong> powerAnnex D: Main physical quantitiesvoltage droppercentagevoltage dropactive powerreactive powerapparent powerpower factorpower lossCaptionρ 20resistivity at 20 °Ctotal length of conductorS cross section of conductorα 20temperature coefficient of conductor at 20 °Cθ temperature of conductorρθ resistivity against the conductor temperatureω angular frequencyf frequencyr resistance of conductor per length unitx reactance of conductor per length unitu k% short-circuit percentage voltage of the transformerrated apparent power of the transformerS rU rrated voltage of the transformerp k% percentage impedance losses of the transformer under short-circuitconditions536 <strong>Electrical</strong> devices | <strong>ABB</strong><strong>ABB</strong> SACE - <strong>Electrical</strong> devices


Contact us<strong>ABB</strong> SACEA division of <strong>ABB</strong> S.p.A.L.V. BreakersVia Baioni, 3524123 Bergamo - ItalyTel.: +39 035 395 111Fax: +39 035 395306-433The data <strong>and</strong> illustrations are not binding. We reservethe right to modify the contents of this document onthe basis of technical development of the products,without prior notice.Copyright 2010 <strong>ABB</strong>. All rights reserved.1SDC010002D0206 - 1000www.abb.com