CONVENTIONAL DETECTORS<br />

256 •<br />

1043/143<br />

1043/228<br />

CONVENTIONAL BUTTONS<br />

1043/143 Manual break-glass button<br />

1043/144 Manual rearming button<br />

Fire alarm buttons are used to manually trip the alarm. The 1043/143 is of the<br />

break-glass type: simply apply pressure to the middle of the glass to break it and<br />

operate and internal switch. Replace the glass to reset (spare part code 1043/247).<br />

The 1043/144 can be rearmed: press the central part of the glass to actuate<br />

the switch. A test tool is provided to test the device and rearm the glass.<br />

A red LED on the buttons indicates alarm state.<br />

EN 54 - 11 compliant.<br />

The main features are:<br />

- Power voltage: 11 - 29Vdc<br />

- Alarm consumption: 50 mA@24Vdc<br />

- Weight: 150 g<br />

- Dimensions (W x H x D) mm: 110 x 100 x 40<br />

CONVENTIONAL BUTTON ACCESSORIES<br />

1043/145 Manual break-glass button hammer<br />

1043/247 Spare glass<br />

Spare glass for 1043/143, 1043/243 and 1043/506 buttons.<br />

Special conventional detectors<br />

GAS DETECTORS<br />

1043/228 Low profile methane gas detector with relay output<br />

1043/229 Low profile LPG gas detector with relay output<br />

These detectors indicate the presence of methane and LPG gas in concentrations<br />

lower than the minimum explosivity limit (LEL), i.e. 10%, well before an explosive<br />

mixture is formed. They are provided with a relay alarm output (NO and NC<br />

contacts), an optoisolated NC fault output and two terminals for connecting<br />

to a current line for conventional control units.<br />

The main features are:<br />

- Power voltage: 11 - 29 Vdc<br />

- Stand-by consumption: 50 mA @ 27.6 Vdc<br />

- Alarm consumption: 100 mA @ 27.6 Vdc<br />

- Alarm delay: 20 sec<br />

- Alarm line consumption: 50 mA @ 27.6 Vdc<br />

- Working temperature range: from -5° to +50° C<br />

- Humidity: < 95 %<br />

- Relay output: NO - NC 1A @30Vdc<br />

- Alarm threshold of the detector: 15% LEL - 0.75% by volume<br />

- Casing: white ABS<br />

- Degree of protection: IP 40<br />

- Dimensions (Ø x H) mm: 115 x 45