<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171New Standards for the Small <strong>Electric</strong> Quarter-turn MarketControl Panel offers easysetting of all functions fromone locationSeparate terminal block forsafe and easy field wiringterminationsSelf-locking, epi-cyclical internalgearing ensures a smooth andreliable operationCopyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-02753


<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171Option ModulesOM1 - Servoamp andRetransmission Module (availablewith integral Bluetooth ® NonintrusiveConfiguration)Analog Position INPUT of 4 to 20 mA or0 to 10 VDC (selectable).Analog Position OUTPUT of 4 to 20 mAor 0 to 10 VDC (selectable).Monitor Relay Alarm contact to indicateloss of power, torque alarm, overtemperature of motor or electronics andloss of analog signal.Motor Running output contact.Four additional SPST Output Contactsset independently at one of 10 pointsalong the stroke.Contacts are configurable (make orbreak).Non-intrusive Configuration ofServoamp/RetransmissionOptional - OM1 module may bespecified with integral, non-intrusive,configuration using Bluetooth ® wirelesstechnology protocol.OM2 - Battery Backup ModuleProvides power so that the remotecontacts will update whenever the mainpower supply to the actuator is lost.OM3 - Local InterfaceIntegral pushbutton panel withLocal/Remote Selector, Open/Closepushbuttons and 2 LED's (Red/Green)for local indication.OM4 - Non-intrusiveConfiguration ToolA module with Bluetooth ® wirelesstechnology allows non-intrusiveconfiguration of on-off actuators.OM13 - Three-wire interfacecontrol moduleConverts unit to three-wire configurationwhere power and directional control arethe same.BUS Communication - NetworkInterfaceOptional network interface modules toallow communication with BUS systems.These modules are plug and play.OM8 - AS-interface ® Module(available with integral Bluetooth ®Non-intrusive Configuration)ASi 2.1/2.2 module.OM9 - PROFIBUS ® DPV0 andDPV1 (available with integralBluetooth ® Non-intrusiveConfiguration)PROFIBUS ® DPV0 cycliccommunication and acycliccommunication as per PROFIBUS ®DPV1 extension.OM10 - FOUNDATION fieldbus(available with integral Bluetooth ®Non-intrusive Configuration)FF interface module.OM11 - DeviceNet Module(available with integral Bluetooth ®Non-intrusive Configuration)DeviceNet interface module.Notes1. AS-interface ® is a registered trademark ofAS-International.2. The Bluetooth word mark and logos areowned by the Bluetooth SIG, Inc. and anyuse of such marks by Tyco Flow Control isunder license.3. Foundation fieldbus is a registeredtrademark of the Fieldbus Foundation.4. PROFIBUS ® is a registered trademark ofPROFIBUS International.5. DeviceNet is a registered trademark ofODVA.®®Copyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-02754


<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171<strong>Keystone</strong> Direct Mount SystemThe same direct mounting brought to themarket place by <strong>Keystone</strong> for valves andactuators, with even more flexibility.<strong>Keystone</strong> Valve pioneered the directmounting compact valve actuatorsystem. The EPI 2 continues thiscustomer oriented system withadditional flexibility aimed at allowing thecustomer more actuator with everypurchase. The EPI 2 has dual mountingbolt circles and dual shaft acceptancewith most units. This feature allowscoverage of more valve sizes and typeswith less actuator models.CDFABEShaft Inserts<strong>Actuator</strong> BaseDimensions (inches)Standard Bore Bolt Circle Standard Shaft InsertsDouble D Keyed DepthA B C D E F KeyModel Bore Dia. Key Depth Dia. Holes Dia. Holes SizeE006 1.125 1/4 x 1 /4 1.34 1.75 1/4" - 20 UNC 3.25 3/8" - 16 UNC 0.5 0.75 – – 1.37E013 – – 2.12 – – 3.25 3/8" - 16 UNC – – 1.125 1/4 x 1 /4 2.12E025 1.875 1/2 x 3 /8 2.12 3.25 3/8" - 16 UNC 5.00 1/2" - 13 UNC – – 1.125 1/4 x 1 /4 2.12E051 1.875 1/2 x 3 /8 2.12 3.25 3/8" - 16 UNC 5.00 1/2" - 13 UNC – – 1.125 1/4 x 1 /4 2.12E091 2.250 1/2 x 3 /8 4.80 5.00 1/2" - 13 UNC 6.50 3/4" - 10 UNC – – 1.875 1/2 x 3 /8 4.25E171 2.250 1/2 x 3 /8 4.80 5.00 1/2" - 13 UNC 6.50 3/4" - 10 UNC – – 1.875 1/2 x 3 /8 4.25NotesStandard Bore - W1, W2, X1, and X2 on modelsE013 and E025 are 35 mm bore with 8 mm x 10mm key. W5, W8, and X5 are as listed above.Insert - W1, W2, X1, and X2 on model ModelE051 is 1.625 with 3/8 x 3/8 key. W5, W8, andX5 are as listed above.Copyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-02755


<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171Models E006, E013, E025, E051, E091BRG F EWWCPNMWKHLJA1AHDD1With optional local interface module OM3Dimensions (inches)Weight 3Model A A1 B C D D1 E F G H J K L M N P R 1 W 2 (lbs)E006 9.4 11.3 10.7 8.3 4.5 6.3 3.3 4.7 2.7 3.1 2.5 1.3 1.4 2.6 2.7 4.9 6.9 1" NPT 19.8E013 9.4 11.3 10.7 9.0 4.5 6.3 3.3 4.7 2.7 3.1 2.5 1.3 2.1 3.4 3.4 4.9 6.9 1" NPT 20.9E025 11.6 13.4 13.1 11.3 5.1 6.9 4.3 6.1 2.7 3.7 3.0 1.3 2.5 3.7 3.6 7.1 9.1 1" NPT 34.2E051 11.6 13.4 13.1 11.3 5.1 6.9 4.3 6.1 2.7 3.7 3.0 1.3 2.5 3.7 3.6 7.1 9.1 1" NPT 37.5E091 13.4 15.3 13.7 14.3 5.5 7.3 4.3 6.8 2.7 4.1 3.2 1.3 5.5 6.8 6.5 9.5 9.1 1" NPT 57.0Notes1. Space required for cover removal2. 4 total conduit connections3. Add 1.1 lbs. for Option Module OM3 Local InterfaceCopyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-02756


<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171Model E171RG F EWWPN L M CWKKHBAJHDD1A1With optional local interface module OM3Dimensions (inches)Weight 3Model A A1 B C D D1 E F G H J K L M N P R 1 W 2 (lbs)E171 13.4 15.3 19.9 18.3 5.5 7.3 10.5 6.8 2.7 4.1 3.2 1.3 9.5 10.7 10.4 9.5 9.1 1" NPT 99.2Notes1. Space required for cover removal2. 4 total conduit connections3. Add 1.1 lbs. for Option Module OM3 Local InterfaceCopyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-02757


<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171PerformanceAdjustable torque and stroke time offersflexibility in performance and valveprotection unsurpassed in the smallelectric quarter-turn market.Torque output at selected setting (lb. in.)Model 100% 40%E006 600 560 520 480 440 400 360 320 280 240E013 1300 1214 1127 1040 954 867 780 693 607 520E025 2500 2334 2167 2001 1834 1667 1500 1334 1167 1000E051 5100 4761 4421 4081 3741 3401 3061 2720 2380 2040E091 9100 8496 7889 7282 6675 6068 5461 4854 4247 3640E171 17700 16525 15344 14164 12983 11802 10622 9441 8261 7080Position 9 8 7 6 5 4 3 2 1 0Output torque is independently adjustable from 40% to 100% in both directions of travel. Adjustments are in increments of 1 from 0 to 9. The default setting is100%, position 9 on the rotary selector used for configuration.Operating Time at selected setting (sec’s/90)Model 100% 10%E006 12 15 18 26 38 48 60 75 85 110E013 12 15 18 26 38 48 60 75 85 110E025 12 15 18 26 38 48 60 75 85 110E051 12 15 18 26 38 48 60 75 85 110E091 20 24 30 45 60 80 100 120 140 180E171 44 53 66 100 132 180 220 264 310 400Position 9 8 7 6 5 4 3 2 1 0Output speed is adjustable from 10% to 100% in both directions of travel. Adjustments are in increments of 1 from 0 to 9. The default settings are: 18 secondsfor the E006, E013, E025 & E051 - 30 seconds for the E091 - and 66 seconds for the E171. The tolerance is +/- 10% of nominal.Copyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-02758


<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171Current DrawA7.006.506.005.505.004.504.003.753.503.253.002.752.502.252.001.801.601.501.401.301.201.101.000.900.800.700.600.500.400.300.200.100.05Model E00624 VDC24 VAC48 VAC48 VDC120 VAC240 VAC120 VDC240 VDCtime (sec/90°)A7.006.506.005.505.004.504.003.753.503.253.002.752.502.252.001.801.601.501.401.301.201.101.000.900.800.700.600.500.400.300.200.100.05Model E01324 VDC24 VAC48 VAC48 VDC120 VAC240 VAC120 VDC240 VDCtime (sec/90°)8 12 15 22 30 40 50 60 75 908 12 15 22 30 40 50 60 75 90Model E025Model E051 - E091 - E171AA16.0015.0014.0013.0012.0011.0010.009.008.007.006.005.004.504.003.753.503.253.002.752.502.252.001.751.501.251.000.900.800.700.600.500.400.300.200.1024 VDC24 VAC48 VDC48 VAC120 VDC120 VAC240 VAC240 VDCtime (sec/90°)19.018.518.017.517.016.516.015.515.014.514.013.513.012.512.011.511.010.510.09.59.08.58.07.57.06.56.05.55.04.54.03.53.02.52.01.51.00.750.5024 VDC24 VAC48 VDC48 VAC120 VAC120 VDC240 VAC240 VDCtime (sec/90°)8 12 15 22 30 40 50 60 75 908 12 15 22 30 40 50 60 75 9015 24 30 45 60 90 100 120 150 190Model E051Model E091Notes1. A = current draw (Amp) at nominal conditions (output torque 100%)2. Max current (Amp) at stall conditions - 1.2 x A3. Current diagrams for VDC supplyCurrent diagrams for VAC/1-phase supply4. Power factor for VAC supply - 0.6033 53 66 100 132 180 220 264 330 400 Model E171Copyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-02759


<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171Wiring DiagramGeneral Arrangement with Base CardMPosition SensorConnector LConnector MDCDCCLC1 CLC2 OPC1 OPC2Power andProcessor CardConnector AConnector B Connector CL1 L2 L3 35 36 32 33 34Connector D20 21 22 23 24 25 26 27Connector E Connector F+ –28 29 30 31 10 11Ground(Note 1)Remote commands(Note 2)Output contacts(Note 3)Notes:1) Connection L1-L2 for VDC or VAC single phase motor supply from 24 to 240 voltConnection L1-L2-L3 for 3-phase motor supply from 208 to 575V2) Remote commands optionsLocal Interface(Optional Module 3)24VOC OVOptional externalsupply 24VDC3435363233OPOP3535OPCLCL3636CL3232Internal supply 24VDC External supply 24/120VAC External supply 24/120VDC+–3) Contacts shown in intermediate position CLC1-CLC2 end of travel signalling in CLOSINGContacts shown in intermediate position OPC1-OPC2 end of travel signalling in OPENINGCopyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-027510


<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171Model Number DetailE 006 A 0 W5 00 0Model (1 digit)E – EPI 2 Quarter-turn <strong>Electric</strong>Size (3 digits)006 – 600 lb. in.013 – 1,300 lb. in.025 – 2,500 lb. in.051 – 5,100 lb. in.091 – 9,100 lb. in.171 – 17,700 lb. in.Local Indicator (1 digit)A – Standard WindowVoltage ratings (1 digit)0 – 24 to 240 VDC and24 to 240 VAC 1-ph 50/60 Hz1 – 208 to 240 VAC 3-ph 50/60 Hz2 – 380 to 480 VAC 3-ph 50/60 Hz3 – 500 to 575 VAC 3-ph 50/60 HzClassification & Temperature Rating (2 digit)W1 – NEMA 4/4X/6 (IP66/68M)Ambient Temp: -13°F to 158°F [-25°C to 70°C](Motor Pinion Reduction Gear - Reinforced Acetal Resin)W2 – NEMA 4/4X/6 (IP66/68M)Ambient Temp: -40°F to 158°F [-40°C to 70°C](Motor Pinion Reduction Gear - Reinforced Acetal Resin)W5 – CSA 139 (C-US)NEMA 4/4X/6 (IP66/68M)AWWAAmbient Temp: -40°F to 140°F [-40°C to 60°C](Motor Pinion Reduction Gear - Steel)X1 – FM/CSA per NEC 505 (Class 1, Zone 1 & 2)NEC 500 (Class 1, Div. 2)NEMA 4/4X/6 (IP66/68M)Ambient Temp: -13°F to 149°F [-25°C to 65°C](Motor Pinion Reduction Gear - Reinforced Acetal Resin)X2 – FM/CSA per NEC 505 (Class 1, Zone 1 & 2)NEC 500 (Class 1, Div. 2)NEMA 4/4X/6 (IP66/68M)Ambient Temp: -40°F to 149°F [-40°C to 65°C](Motor Pinion Reduction Gear - Reinforced Acetal Resin)X5 – FM/CSA per NEC 505 (Class 1, Zone 1 & 2)NEC 500 (Class 1, Div. 2)NEMA 4/4X/6 (IP66/68M)Ambient Temp: -40°F to 149°F [-40°C to 65°C](Motor Pinion Reduction Gear - Steel)Special Option Code (1 digit)0 – StandardOption Modules (2 digits)00 – NONE Standard On-Off ConfigurationP1 – Servo Amp w/Retransmission (OM1)P2 – Lithium Battery (OM2)P3 – Local Interface (OM3)P4 – Bluetooth ® Interface (OM4)P5 – Servo Amp w/Retransmission,Lithium Battery (OM1 + OM2)P6 – Servo Amp w/Retransmission, Local Interface (OM1+ OM3)P7 – Servo Amp w/Retransmission,Bluetooth ® Communication (OM1-B)P8 – Servo Amp w/Retransmission,Lithium Battery,Local Interface (OM1 + OM2 + OM3)P9 – Servo Amp w/Retransmission, Lithium Battery,Bluetooth ® communication (OM1-B + OM2)PA – Servo Amp w/Retransmission, Local Interface,Bluetooth ® communication (OM1-B + OM3)PC – Servo Amp w/Retransmission,Lithium Battery, Local Interface,Bluetooth ® communication (OM1-B + OM2 + OM3)PD – Local Interface, Bluetooth ® communication (OM3 + OM4)PF – Local Interface, Lithium Battery,Bluetooth ® communication (OM2 + OM3 + OM4)PJ – Local Interface,Lithium Battery (OM2 + OM3)3A – ASi 2.1 bus communication (OM8)4A – ASi 2.1 bus communication, Local Interface (OM8 + OM3)5A – ASi 2.1 bus communication,Bluetooth ® communication (OM8-B)6A – ASi 2.1 bus communication, Local Interface,Bluetooth ® communication (OM8-B + OM3)3D – DeviceNet bus communication4D – DeviceNet bus communication,Local Interface (OM11 + OM3)5D – DeviceNet bus communication,Bluetooth ® communication (OM11-B)6D – DeviceNet bus communication, Local Interface,Bluetooth ® Communication (OM11-B + OM3)3P – PDP V0/V1 bus communication (OM9)4P – PDP V0/V1 bus communication,Local Interface (OM9 + OM3)5P – PDP V0/V1 bus communication,Bluetooth ® communication (OM9-B)6P – PDP V0/V1 bus communication, Local InterfaceBluetooth ® communication (OM9-B + OM3)3F – Foundation Fieldbus communication (OM10)4F – Foundation Fieldbus communication,Local Interface (OM10 + OM3)5F – Foundation Fieldbus communication,Bluetooth ® communication (OM10-B)6F – Foundation Fieldbus communication, Local InterfaceBluetooth ® Communication (OM10-B + OM3)PG – 3-wire Interface Card (OM13)PH – 3-wire Interface Card, Lithium Battery (OM13 + OM2)Copyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-027511


<strong>Keystone</strong> EPI 2 <strong>Electric</strong> <strong>Actuator</strong>Models E006 to E171Also available for <strong>Keystone</strong> Direct Mounting ...<strong>Keystone</strong> 79U Pneumatic <strong>Actuator</strong>sRack and Pinion actuator available both double acting and spring return.Torques to 18,100 lb. in.<strong>Keystone</strong> MRP Pneumatic <strong>Actuator</strong>sRack and Pinion actuator available both double acting and spring return.Torques to 18,100 lb. in.www.tycoflowcontrol.comTyco Flow Control (TFC) provides the information herein in good faith but makes no representation as to its comprehensiveness or accuracy. This data sheet is intended only as a guide to TFC products and services.Individuals using this data sheet must exercise their independent judgment in evaluating product selection and determining product appropriateness for their particular purpose and system requirements. TFC MAKESNO REPRESENTATIONS OR WARRANTIES, EITHER EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION ANY WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITHRESPECT TO THE INFO<strong>RM</strong>ATION SET FORTH HEREIN OR THE PRODUCT(S) TO WHICH THE INFO<strong>RM</strong>ATION REFERS. ACCORDINGLY, TFC WILL NOT BE RESPONSIBLE FOR DAMAGES (OF ANY KIND ORNATURE, INCLUDING INCIDENTAL, INDIRECT, OR CONSEQUENTIAL DAMAGES) RESULTING FROM THE USE OF OR RELIANCE UPON THIS INFO<strong>RM</strong>ATION. Patents and Patents Pending in the U.S. andforeign countries. Tyco reserves the right to change product designs and specifications without notice.Copyright © 2007 Tyco Flow Control. All rights reserved.KEYMC-027512