DATAKOM<strong>DKG</strong>-<strong>705</strong> User’s ManualSynchronization failure:Check the parameters P_A02, P_A04, P_A15 and P_A16. If Dual Genset mode is used then check alsoP_A39 and P_A40. If one of them is defined too low, this may delay or disable the synchronizationprocess.Check the synchronization fail timeout parameter (P_A07), if necessary increase. A typical delay may be20 seconds.Check the synchronization limits (P_A10, P_A11, P_A12), If necessary widen the limits. A typicalapplication may be P_A10=0.5Hz, P_A11=5V, P_A12=5ºOne of the protection functions is too sensitive.Check protection specific warning on the ALARM LIST menu of the unit and reduce the sensitivity of thecorresponding protection using the programming menu.19. DECLARATION OF CONFORMITYThe unit conforms to the EU directives-73/23/EEC and 93/68/EEC (low voltage)-89/336/EEC, 92/31/EEC and 93/68/EEC (electro-magnetic compatibility)Norms of reference:EN 61010 (safety requirements)EN 50081-2 (EMC requirements)EN 50082-2 (EMC requirements)The CE mark indicates that this product complies with the European requirements for safety, healthenvironmental and customer protection.<strong>705</strong>-UE.doc - 55 -