DATAKOM<strong>DKG</strong>-<strong>705</strong> User’s ManualGroup Parameter DefinitionUnit Min Max Description6 629 Emergency Backup - 0 1 If this parameter is set to 1, in the TESTmode, the load will be transferred to thegenset if the mains fail.6 630 Frequency VoltageOffsetV 5 50 This parameter adjusts the sensitivity forgenset frequency reading. If the gensetfrequency appears to be a non-zero valuewhile the engine is at rest, increase this6 631 Load Shedding LowLimit6 632 Load Shedding HighLimit6 633 Mains CurrentTransformersparameter. The standard value is 20V.KW 0 5000 If the genset active power output goesbelow this limit, then the Load Sheddingrelay will be deactivated.KW 0 5000 If the genset active power output goesabove this limit, then the Load Sheddingrelay will be activated.- 0 1 0: Mains current transformers are notconnected. All mains current, power andcos? values are zeros, peak lopping andsoft transfer to genset are not allowed1: Mains current transformers areconnected and used. All mains current,power and cos? measurements are valid,peak lopping and soft transfer to gensetare allowed.6 634 Modem Connection - 0 1 0: No modem connection, the serial port isconnected to PC1: Modem connected.<strong>705</strong>-UE.doc - 42 -