DATAKOM<strong>DKG</strong>-<strong>705</strong> User’s Manual5 522 Mains Freq Low Limit Hz 0 60 If the mains frequency goes under thislimit, it means that the mains are offand it starts the transfer to the gensetin AUTO and TEST modes. In parallelwith mains operation it will cause themains contactor to deenergize and awarning given.5 523 Mains Freq High Lim Hz 44 70 If the mains frequency goes over thislimit, it means that the mains are offand it starts the transfer to the gensetin AUTO and TEST modes. In parallelwith mains operation it will cause themains contactor to deenergize and awarning given.5 524 Genset Voltage FailTimerSec 0 30 This is the period between the gensetvoltages go outside limits (defined byP_514, P_515, P_620) and the GensetLow/High Voltage alarm occurs.<strong>705</strong>-UE.doc - 38 -