DATAKOM<strong>DKG</strong>-<strong>705</strong> User’s Manual7. LOAD TRANSFER MODESversa.The <strong>DKG</strong>-<strong>705</strong> has more than one ways of transferring the load from genset to mains and viceThese modes are:-transfer with interruption,-no break transfer, (with or without synchronization)-soft transfer.7.1 Transfer with InterruptionThis is the most conventional way of transferring the load between the genset and mains. Therewill be a power interruption period duration during the transfer. Note that the program parameters P_508and P_509 define the power interruption period.If this transfer method is used, it is advised to make an electrical interlockbetween the two contactors to prevent a phase to phase short circuit.Transfer from genset to mains:-The generator contactor releases,-The unit waits for Mains Contactor Timer (P_508)-The mains contactor is energized.Transfer from mains to genset:-The mains contactor releases,-The unit waits for Generator Contactor Timer (P_509)-The generator contactor is energized.<strong>705</strong>-UE.doc - 22 -