DATAKOM<strong>DKG</strong>-<strong>705</strong> User’s Manual4.2 Load Dump AlarmsDefinition Source DescriptionLow Oil Press.Switch Digital Input These load dump alarms are set depending on the digital inputHigh Eng.Temp.Switch Digital Input settings. The related program parameters are P_700 to P_776.Emergency Stop Digital InputLow Coolant Level Digital InputAlternator High Temp. Digital InputHigh Oil Temp. Digital InputOverloadDigital InputLow Fuel Level Digital InputBattery Charger Fail Digital InputSpare Alarm 7Digital InputSpare Alarm 6Digital InputSpare Alarm 5Digital InputSpare Alarm 4Digital InputSpare Alarm 3Digital InputSpare Alarm 2Digital InputSpare Alarm 1Digital InputGen Reverse Power Internal Set if the genset consumes active power (KW) from the mains andthis power goes over the Reverse Power Load Dump (P_618)limit.Gen Excess Power Internal Set if the genset power (KW) supplied to the load goes over theExcess Power Load Dump (P_617) limit for Overcurrent / ExcessPower Timer (P_511).Alternator Overcurrent Internal Set if at least one of the genset phase currents goes over theOvercurrent Limit (P_510) for Overcurrent / Excess PowerTimer (P_511).<strong>705</strong>-UE.doc - 15 -