7979k0/Ausgabe 11.2004<br />

WAREMA <strong>Control</strong>s<br />

<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-channel Central<br />

<strong>Control</strong> <strong>Unit</strong> <strong>EWFS</strong> ®<br />

User guide<br />

(Please save these instructions for future use)<br />

Valid as from November 1, 2004<br />

93280680•816755•7979k0•08.10.2004


General remarks<br />

General Remarks<br />

The publication of this manual<br />

supercedes all previous corresponding<br />

documentation.<br />

We reserve the right to make<br />

alterations in the interests of technical<br />

progress.<br />

Considerable care was taken in<br />

producing the text and graphics in this<br />

documentation but it is impossible to<br />

rule out errors completely.<br />

WAREMA provides you with a<br />

complete range of sun protection<br />

systems for windows, facades and<br />

glazed structures. Please contact the<br />

export department if you need any<br />

documentation on:<br />

– sun protection control systems<br />

– outside venetian blinds<br />

– inside venetian blinds<br />

– roller shutters<br />

– facade awnings<br />

– vertical awnings<br />

– markisolettes<br />

– conservatory awnings<br />

– articulated arm awnings<br />

– cassette awnings<br />

– basket awnings<br />

– Dutch canopy awning<br />

– insect screens<br />

– sun protections for roof windows<br />

– vertical louvre blinds<br />

– pleated blinds<br />

– roller blinds<br />

– black-out systems<br />

Safety Instructions<br />

Electrical installation work must be left<br />

strictly to qualified electricians. Only<br />

then is there any guarantee that your<br />

country´s statutory regulations are<br />

complied with and that the installation<br />

provisions of your local power supply<br />

company are properly observed. The<br />

user may be placed at serious risk if<br />

the equipment is wrongly installed.<br />

For further information please refer the<br />

the available user and installation<br />

guides.<br />

Imprint<br />

WAREMA Renkhoff GmbH<br />

Hans-Wilhelm-Renkhoff Strasse 2<br />

D-97828 Marktheidenfeld/Main<br />

2<br />

Headquarter<br />

WAREMA Renkhoff SE<br />

Hans-Wilhelm-Renkhoff Strasse 2<br />

D-97828 Marktheidenfeld/Main<br />

P.o. box 13 55<br />

D-97822 Marktheidenfeld/Main<br />

Phone:+49 (0) 9391/20-0<br />

Fax: +49 (0) 9391/20-4299<br />

http://www.warema.com<br />

Sales Department (Sun protection<br />

control systems):<br />

Phone:+49 (0) 9391/20-3730;<br />

Fax: +49 (0) 9391/20-3739<br />

Application technique:<br />

Phone:+49 (0) 9391/20-6720;<br />

Fax: +49 (0) 9391/20-6729<br />

Service:<br />

Phone:+49 (0) 9391/20-6760;<br />

Fax: +49 (0) 9391/20-6769<br />

WAREMA and the WAREMA logo are trademarks of WAREMA Renkhoff SE.<br />

All other brand names or product names mentioned in this documentation are<br />

trade marks or registered trade marks of their respective owners.<br />

© 2004, WAREMA Renkhoff SE<br />

93280680•816755•7979k0•08.10.2004


Table of contents<br />

1. General ................................................................................................................. 6<br />

2. For your safety ..................................................................................................... 7<br />

2.1 Usage to the intended purpose ....................................................................... 8<br />

2.2 Target group ..................................................................................................... 8<br />

2.3 General safety instructions .............................................................................. 9<br />

2.4 Software version .............................................................................................. 9<br />

3. Introduction ....................................................................................................... 10<br />

3.1 The control field ............................................................................................. 10<br />

3.2 Basic functions .............................................................................................. 11<br />

3.2.1 Display of the room temperature ............................................................. 11<br />

3.2.2 Display of the position and cause/manual operation ................................ 11<br />

3.2.3 Operating with the remote control........................................................... 12<br />

3.2.4 Initial menu "User settings" ...................................................................... 12<br />

3.2.5 Initial menu "Service settings" .................................................................. 12<br />

3.2.6 Initial menu "Functions ON/OFF" .............................................................. 12<br />

3.2.7 Initial menu "Display measured values" .................................................... 15<br />

3.2.8 Displaying the date and time.................................................................... 16<br />

3.3 Facades and channels.................................................................................... 17<br />

4. The menu structure ........................................................................................... 18<br />

4.1 <strong>Channel</strong>-dependent or non-channel-dependent? ........................................... 18<br />

4.2 Safety and comfort functions ........................................................................ 18<br />

4.3 Explanation of the most Important symbols used ......................................... 20<br />

4.3.1 Symbols: Manual operation...................................................................... 20<br />

4.3.2 Symbols: Menu change, modifying values .............................................. 20<br />

4.3.3 Symbols: Activation of safety and comfort functions .............................. 21<br />

4.3.4 Symbols: Cause of a move command ..................................................... 23<br />

4.3.5 Symbols: Position and movements of the sunblind ................................. 24<br />

4.3.6 Symbols: Displaying movements at windows ......................................... 24<br />

4.3.7 Symbols: Displaying movements at locks................................................ 25<br />

5. Getting started .................................................................................................. 26<br />

5.1 Display level and manual operation ............................................................... 26<br />

5.2 Setting the time and date .............................................................................. 27<br />

5.3 Overview of the control system .................................................................... 29<br />

6. <strong>Channel</strong>-dependent user settings .................................................................... 30<br />

6.1 Sun control ..................................................................................................... 31<br />

6.1.1 Sun control ON/OFF ................................................................................. 32<br />

6.1.2 Sun control limit "DOWN"......................................................................... 33<br />

6.1.3 Sun control delay "DOWN" ....................................................................... 33<br />

6.1.4 Sun control position "DOWN" ................................................................... 33<br />

6.1.5 Sun control limit "UP" ............................................................................... 34<br />

6.1.6 Sun control delay "UP" .............................................................................. 34<br />

6.1.7 Sun control limit "OPEN" .......................................................................... 35<br />

6.1.8 Sun control delay "OPEN" ......................................................................... 35<br />

6.1.8.1 The "OPEN" limit ................................................................................. 35<br />

6.1.9 Slat angle after moving down .................................................................. 36<br />

6.1.10 Using the sun control correctly ................................................................ 37<br />

6.1.11 The sun control during wind, rain or ice alert ........................................... 37<br />

6.2 Dawn/dusk control ......................................................................................... 38<br />

6.2.1 Dawn/dusk control ON/OFF ..................................................................... 39<br />

6.2.2 Dawn/dusk control limit "UP".................................................................... 40<br />

6.2.3 Dawn/dusk control limit "DOWN" ............................................................. 40<br />

6.2.4 Slat angle after moving down .................................................................. 41<br />

6.2.5 Using the dawn/dusk control correctly..................................................... 42<br />

6.2.6 The dawn/dusk control during wind,- rain or ice alert .............................. 42<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 3


Table of contents<br />

4<br />

We reserve the right to carry out improvements<br />

6.3 Temperature control....................................................................................... 43<br />

6.3.1 Basic functions ......................................................................................... 44<br />

6.3.2 Temperature control ON/OFF ................................................................... 45<br />

6.3.3 Selecting the operating modes of the temperature control ..................... 46<br />

6.3.3.1 Direct control ...................................................................................... 46<br />

6.3.3.2 Enable sun .......................................................................................... 46<br />

6.3.3.3 Difference temperature ...................................................................... 46<br />

6.3.4 Changing the operating mode .................................................................. 46<br />

6.3.5 Temperature control in the "Direct control" operating mode .................... 47<br />

6.3.5.1 Temperature control limit "UP" ............................................................ 47<br />

6.3.5.2 Temperature control limit "DOWN" ..................................................... 48<br />

6.3.6 Temperature control in the "Enable sun" operating mode ........................ 49<br />

6.3.6.1 Temperature control limit "ON" ........................................................... 49<br />

6.3.6.2 Temperature control limit "OFF" .......................................................... 50<br />

6.3.7 Temperature control in the "Difference temperature" operating mode .... 51<br />

6.3.7.1 Temperature limit "ON" ....................................................................... 52<br />

6.3.7.3 Difference temperature limit "OPEN" ................................................. 53<br />

6.3.7.2 Temperature limit "OFF" ...................................................................... 53<br />

6.3.7.4 Difference temperature limit "CLOSE" ............................................... 54<br />

6.4 Rain monitoring.............................................................................................. 55<br />

6.4.1 Rain monitoring ON/OFF .......................................................................... 55<br />

6.5 Humidity control ............................................................................................ 57<br />

6.5.1 Humidity control ON/OFF......................................................................... 58<br />

6.5.2 Humidity limit "OPEN" .............................................................................. 59<br />

6.5.3 Humidity limit "CLOSE" ............................................................................ 59<br />

6.6 Timer switch .................................................................................................. 60<br />

6.6.1 Timer switch ON/OFF .............................................................................. 61<br />

6.6.2 Timer switch Mo - Fr "UP" ........................................................................ 62<br />

6.6.3 Timer switch Mo - Fr "DOWN" ................................................................. 62<br />

6.6.4 Timer switch Sa - Su "UP" ......................................................................... 62<br />

6.6.5 Timer switch Sa - Su "DOWN" .................................................................. 63<br />

6.6.6 Slat angle after moving down .................................................................. 63<br />

6.7 Comfort timer ................................................................................................ 65<br />

6.7.1 Comfort timer ON/OFF ............................................................................ 67<br />

6.7.2 Comfort timer Mo - Fr "ON"...................................................................... 68<br />

6.7.3 Comfort timer Mo - Fr "OFF" .................................................................... 68<br />

6.7.4 Comfort timer Sa - Su "ON" ...................................................................... 69<br />

6.7.5 Comfort timer Sa - Su "OFF"..................................................................... 69<br />

6.8 Manual operation ........................................................................................... 70<br />

6.8.1 "Dead man’s mode" .................................................................................. 70<br />

6.8.2 "Time mode" ............................................................................................. 70<br />

6.8.3 "Permanent mode" ................................................................................... 70<br />

6.8.4 "Continuous mode" ................................................................................... 70<br />

6.8.5 Changing the control mode ...................................................................... 71<br />

6.8.6 Slat angle after moving down .................................................................. 72<br />

6.8.7 Reversing the direction of movement during manual operation .............. 73<br />

6.8.8 The possibilities of manual operation ....................................................... 74<br />

6.8.8.1 Function keys / function dial ............................................................... 74<br />

6.8.8.2 Remote control ................................................................................... 74<br />

6.8.8.3 External channel buttons .................................................................... 74<br />

6.8.8.4 External master switch ....................................................................... 74<br />

6.9 Learning/deleting the remote control ............................................................ 75<br />

6.9.1 Displaying the assignment ....................................................................... 75<br />

6.9.2 Learning a remote control ........................................................................ 77<br />

6.9.3 Building a group ....................................................................................... 77<br />

6.9.4 Deleting a remote control ........................................................................ 79<br />

6.9.5 Deleting all the remote controls ............................................................... 80<br />

6.10 Resetting alerts.............................................................................................. 81<br />

6.10.1 Resetting the ice alert manually ............................................................... 81<br />

6.10.2 Enabling the ice alert again ...................................................................... 82<br />

93280680•816755•7979k0•08.10.2004


Table of contents<br />

7. Non-channel-dependent user settings ............................................................ 84<br />

7.1 Setting the time and date .............................................................................. 84<br />

7.2 Display contrast ............................................................................................. 86<br />

7.3 Dimming the backlight of the display ............................................................ 87<br />

7.4 Reset "Wind Sensor Failure" alert .................................................................. 88<br />

8. <strong>Channel</strong>-dependent service settings ............................................................... 89<br />

8.1 Password ....................................................................................................... 90<br />

8.2 The "Product" menu ....................................................................................... 91<br />

8.2.1 Product type ............................................................................................. 96<br />

8.2.2 Runtimes .................................................................................................. 96<br />

8.2.2.1 Runtime "UP" ...................................................................................... 97<br />

8.2.2.2 Runtime "DOWN" ............................................................................... 97<br />

8.2.3 Turn time .................................................................................................. 98<br />

8.2.4 Maximum slat angle ................................................................................. 99<br />

8.2.5 Minimum slat angle.................................................................................. 99<br />

8.2.6 <strong>Control</strong> type............................................................................................ 101<br />

8.2.6.1 Drive direct ....................................................................................... 101<br />

8.2.6.2 Drive with motor control units .......................................................... 101<br />

8.2.7 Interlocks................................................................................................ 102<br />

8.3 Wind Monitoring .......................................................................................... 103<br />

8.3.1 Wind monitoring ON/OFF ...................................................................... 105<br />

8.3.2 Wind monitoring limit "UP" ..................................................................... 106<br />

8.3.3 Wind monitoring delay "UP" ................................................................... 107<br />

8.3.4 Wind monitoring „OFF“ delay ............................................................... 107<br />

8.4 Ice monitoring .............................................................................................. 108<br />

8.4.1 Ice monitoring ON/OFF .......................................................................... 108<br />

8.4.2 Ice monitoring limit "UP"......................................................................... 109<br />

8.4.3 Resetting the ice alert automatically ...................................................... 109<br />

8.5 Allocating a sensor ....................................................................................... 110<br />

9. Non-channel-dependent service settings ..................................................... 112<br />

9.1 System settings ........................................................................................... 112<br />

9.1.1 Internal temperature offset .................................................................... 112<br />

9.1.2 Duration of the wind sensor test ........................................................... 113<br />

9.1.3 Querying the software version............................................................... 114<br />

9.2 Changing the user language ........................................................................ 115<br />

10. Maintenance .................................................................................................... 115<br />

11. Liability ............................................................................................................. 115<br />

12. Cleaning ........................................................................................................... 116<br />

13. Disposal ............................................................................................................ 116<br />

14. User Information ............................................................................................. 116<br />

15. Trouble shooting ............................................................................................. 117<br />

16. Index ................................................................................................................. 118<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 5


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

1. General<br />

6<br />

We reserve the right to carry out improvements<br />

With the <strong>Wisotronic</strong> <strong>dialog</strong> you now own a multifunctional sun protection control<br />

unit which can control various sun protection products (slat products, cloth<br />

products, roller shutters, window drives, etc.) intelligently in accordance with the<br />

respective weather conditions. The <strong>Wisotronic</strong> <strong>dialog</strong> is available in 2 basic<br />

variants:<br />

® 2-channel module<br />

® 3-channel module<br />

The control panel and power unit can be mounted separately and only have to be<br />

connected by means of a 4-wire line. Drives, sensors, lock switches, and<br />

pushbuttons are connected to the power unit. Various modules of the power unit<br />

are available to suit the respective control panel:<br />

® As a REG / DIN rail-mounted device (REG, 12 modular spacings)<br />

® In a flush-type housing<br />

® In a surface-type housing<br />

You can either operate your sun protection products manually or leave the<br />

operation completely to the automatic control products. The <strong>Wisotronic</strong> <strong>dialog</strong><br />

protects your sun/view protection against harmful weather influences and offer<br />

extensive comfort and safety functions. The <strong>Wisotronic</strong> <strong>dialog</strong> can furthermore be<br />

operated via an <strong>EWFS</strong> radio remote control unit (1 or 8 channels), whereby the<br />

radio receiver is integrated in the control panel.<br />

The <strong>Wisotronic</strong> <strong>dialog</strong> evaluates the data for:<br />

® Wind,<br />

® Rain,<br />

® Brightness,<br />

® Internal and external temperature,<br />

® Relative humidity<br />

® Time (DCF-77 reception)<br />

and correspondingly controls the corrected sun protection products, such as slat<br />

products (outside venetian blinds, internal venetian blinds), cloth products<br />

(awnings, pleated blinds), vertical venetian blinds, darkening units, roller shutter<br />

and window drives.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

2. For your safety<br />

We have developed, manufactured and tested the <strong>Wisotronic</strong> under observance<br />

of the fundamental safety requirements.<br />

Residual risks nevertheless remain!<br />

■ Therefore read these instructions before you operate the control system the<br />

first time. They help you to get to know the functions of the device and to use<br />

them optimally.<br />

■ Therefore keep these instructions at a place which is accessible at all times for<br />

all users!<br />

Hierarchic warnings are used in these instructions.<br />

They are identified by a warning sign in the margin and graded hierarchically as<br />

follows:<br />

1. WARNING<br />

2. ATTENTION<br />

3. CAUTION<br />

WARNING<br />

ATTENTION<br />

CAUTION<br />

The term WARNING is used as a warning against immediate<br />

imminent danger.<br />

Death or serious injuries may result (damage to persons)<br />

The term ATTENTION is used as a warning against a possible<br />

imminent danger.<br />

Death, serious or minor injuries (damage to persons), damage to<br />

property or damage to the environment may result.<br />

The term CAUTION is used as an application<br />

recommendation.<br />

Damage to property may result from non-observance.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 7


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

2.1 Usage to the intended<br />

purpose<br />

2.2 Target group<br />

8<br />

We reserve the right to carry out improvements<br />

In addition to the hierarchic warnings described above we use the following<br />

symbols:<br />

TIP<br />

■ This sign identifies<br />

This is used to mark text sections which contain additional<br />

explanations, information or hints.<br />

- Activities which you must carry out, or<br />

- Instructions which must be observed.<br />

ATTENTION<br />

The control system allows the connection of a conventional<br />

sun protection drive with a single-phase a.c. motor per<br />

channel. Alternatively several sun protection drives can be<br />

connected together via motor control units.<br />

When window drives are used, the installer of the system<br />

must ensure that the safety requirements and regulations of<br />

DIN EN 60335-2-103 "Special requirements for drives of gates,<br />

doors and windows" as well as of ZH 1/494 "Guideline for<br />

power-driven windows, doors and gates" are observed.<br />

The approval of the manufacturer has to be obtained if the device<br />

is to be used to a purpose different to that described here. Usage<br />

which is not to the intended purpose can result in damage to the<br />

user or third parties as well as damage to the device itself, the<br />

connected devices or to the moving mechanical parts of the<br />

complete system.<br />

■ Therefore always use our product to the intended purpose only!<br />

These instructions are intended for all those persons who operate the device. If<br />

you require additional information, please contact your specialist dealer.<br />

ATTENTION<br />

Operation by persons who are not sufficiently qualified and<br />

informed can cause severe damage to the system or even<br />

damage to persons!<br />

■ Mounting and commissioning may therefore only be carried out by<br />

correspondingly trained specialists! This personnel must be able to recognize<br />

dangers which can be caused by the mechanical, electrical or electronic<br />

equipment!<br />

ATTENTION<br />

If it is to be assumed that safe operation is not possible, the<br />

device may not be taken into operation or it must be shut<br />

down.<br />

■ This assumption is justified if the device or the connecting cables show<br />

damage or if the device no longer functions.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

2.3 General safety<br />

instructions<br />

2.4 Software version<br />

The <strong>Wisotronic</strong> controls your sun/view protection automatically. You must<br />

therefore observe the following safety instructions:<br />

ATTENTION<br />

An automatically controlled mechanism can start moving<br />

unexpectedly!<br />

■ Therefore never place any objects in the area of movement of an automatically<br />

controlled mechanism!<br />

■ If measuring or test work has to be carried out on the active system, ensure<br />

that existing accident prevention regulations are observed under all<br />

circumstances.<br />

CAUTION<br />

CAUTION<br />

ATTENTION<br />

An automatically controlled sunblind (for example roller<br />

shutters at balcony doors) can move downwards<br />

automatically and lock you out! If the <strong>Wisotronic</strong> controls<br />

such sunblinds via an automatic system, you should "play it<br />

safe" and de-activate these temporarily when you leave the<br />

house!<br />

The complete system cannot function if the power fails.<br />

Therefore move your sunblind to a safe position in time if a<br />

storm is imminent!<br />

Children must not play with this product. Remote control<br />

units of all types must not fall into the hands of children!<br />

The following documents are available in addition to these instructions:<br />

® Installation guide Art. 816 756<br />

® Anschlusspläne für MSE, Netzteile und GA Art. 816 345 (German)<br />

These instructions were drawn up on the basis of the software version<br />

CP 1954111x<br />

PU 1771111x<br />

Please refer to Section 9 for further information about establishing the software<br />

version of your device.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 9


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

3. Introduction<br />

3.1 The control field<br />

10<br />

We reserve the right to carry out improvements<br />

The <strong>Wisotronic</strong> <strong>dialog</strong> is distinguished by its particularly user-friendly user<br />

interface. All the setting steps and measured values are displayed in clear text in a<br />

clearly structured display window which is simply called "Display" in this<br />

document. Programming of the control system is carried out by means of four<br />

function buttons. Menu items are selected and information is called up by means<br />

of a function dial.<br />

<strong>Wisotronic</strong><br />

<strong>dialog</strong> 3CH<br />

Th 01.01.2004<br />

04 : 04: 04<br />

Fig. 3-1: Operating and display elements of the <strong>Wisotronic</strong> <strong>dialog</strong><br />

1. Clearly-structured 4-line display: This display informs you about all the<br />

elements that you can set or read on the <strong>Wisotronic</strong>. You can, for example,<br />

read the current measured values of the outdoor brightness and temperature<br />

or the current time.<br />

2. Function buttons: Various processes can be triggered by using the function<br />

buttons, depending on what is displayed. You can, for example, save your<br />

settings, change menu displays and modify limits. Manual operation of the<br />

sunblind is also carried out by means of the function buttons. The assignment<br />

of the individual buttons is indicated by symbols which can be viewed above<br />

the buttons in the display.<br />

3. Function dial: This dial with latching function allows the easy selection of<br />

menus or the display of current weather data and measured values in the<br />

display. If the dial is pressed, the move command currently being executed is<br />

interrupted and the connected sunblind is stopped immediately.<br />

TIP<br />

1<br />

2<br />

3<br />

Move commands which were triggered by safety functions<br />

(wind, rain or ice monitoring) cannot be stopped!<br />

4. Display of the device variant: 3CH = 3-channel; 2CH = 2-channel<br />

93280680•816755•7979k0•08.10.2004<br />

4


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

3.2 Basic functions<br />

3.2.1 Display of the room<br />

temperature<br />

3.2.2 Display of the position and<br />

cause/manual operation<br />

Operation of the <strong>Wisotronic</strong> is easy to understand and self-explanatory to a great<br />

extent. If the control system was commissioned and set by your specialist dealer,<br />

you usually do not have to modify anything. You can access the following displays<br />

by turning the function dial.<br />

TIP<br />

The displays shown in these instructions are examples of the<br />

3-channel variant. The displayed entries which can be<br />

modified may therefore differ from those on the display of<br />

your <strong>Wisotronic</strong>. If you only have the 2-channel variant, the<br />

third channel is therefore not displayed on your display.<br />

This standard display always consists of the display of the current room<br />

temperature and is displayed automatically when the <strong>Wisotronic</strong> has not been<br />

operated for three minutes.<br />

Temperature<br />

X 23° C<br />

H! T H #T<br />

If the buttons under the "UP" or "DOWN" symbols are pressed, the sunblind (here<br />

connected to <strong>Channel</strong>s 1 and 2) is moved in the corresponding direction. (Instead<br />

of the room temperature the cause and direction of movement are then<br />

displayed.)<br />

The next menu is accessed by turning the dial clockwise:<br />

uh rh<br />

H! T H #T<br />

The next menu is accessed by turning the dial clockwise:<br />

wh<br />

H§ßT<br />

Upper half: Shows whether the sunblind is being moved currently and which<br />

action triggered a move command.<br />

Lower half: If the buttons under the "UP" or "DOWN" symbols are pressed, the<br />

sunblind (here connected to <strong>Channel</strong> 1 or 2) is moved in the corresponding<br />

direction.<br />

■ Press the button T and the sunblind at the corresponding channel moves<br />

down. If you want to stop the movement, press the button of the opposite<br />

direction, in this case H. Alternatively you can press the function dial. This<br />

always has a higher priority and also stops the movement, even if the arrows<br />

H and T are not visible on the display or if the move commands were<br />

triggered by the remote control.<br />

TIP<br />

Move commands which were triggered by safety functions<br />

(wind, rain or ice monitoring) cannot be stopped!<br />

Note: The move behavior and the operation depend on the set sunblind product.<br />

For further information please read the "Manual Operation" section in section 6.8.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 11


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

3.2.3 Operating with the remote<br />

control<br />

3.2.4 Initial menu "User<br />

settings"<br />

3.2.5 Initial menu "Service<br />

settings"<br />

3.2.6 Initial menu "Functions<br />

ON/OFF"<br />

12<br />

We reserve the right to carry out improvements<br />

The supplied radio remote control allows the <strong>Wisotronic</strong> to be controlled remotely.<br />

First read the user instructions of your remote control in order to familiarize<br />

yourself with all the functions. If the control system nevertheless does not react<br />

to the remote control, please refer to Section 6.9 "Learning/Deleting the Remote<br />

<strong>Control</strong>".<br />

ATTENTION<br />

Never press the buttons on your remote control if you cannot<br />

see the sunblind!<br />

The next menu is accessed by turning the dial clockwise:<br />

User<br />

settings<br />

1 2 3 0<br />

From this menu you can branch to the "User settings" submenu of the respective<br />

channel by selecting a channel. Alternatively you can access the non-channeldependent<br />

user settings "Date, display or reset alerts" by pressing the 0 button.<br />

The next menu is accessed by turning the dial clockwise:<br />

Service<br />

settings<br />

1 2 3 0<br />

From this menu you can branch to the "Service settings" submenu of the<br />

respective channel by selecting a channel. Alternatively you can access the nonchannel-dependent<br />

service settings "System or user language" by pressing the 0<br />

button.<br />

The next menu is accessed by turning the dial clockwise:<br />

Functions<br />

ON/OFF<br />

{<br />

From this menu you can branch to the "Functions ON/OFF" submenu.<br />

There you can activate/de-activate comfort functions together or switch<br />

individual functions on and off. The menu is accessed by pressing the { button:<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

Functions<br />

Comfort<br />

6 5 5 }<br />

If the comfort functions are active, a check mark is displayed in the square. If the<br />

comfort functions are de-activated, the square is empty. You can use this function,<br />

for example, if you want to clean your windows and the sunblind should not be<br />

moved automatically.<br />

ATTENTION<br />

The safety functions (wind, rain and ice monitoring) can<br />

nevertheless move your sunblind!<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 13


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

14<br />

We reserve the right to carry out improvements<br />

When you turn the dial clockwise you can access further menus consecutively.<br />

Here you can use the function buttons to activate/de-activate the following<br />

comfort functions individually.<br />

Functions<br />

Sun<br />

6 6 5 }<br />

Functions<br />

Dawn/Dusk<br />

6 5 6 }<br />

Functions<br />

Temperature<br />

6 6 5 }<br />

Functions<br />

Rain<br />

5 6 5 }<br />

Functions<br />

Humidity<br />

6 5 6 }<br />

Functions<br />

Timer switch<br />

6 5 5 }<br />

Functions<br />

Comfort timer<br />

6 6 6 }<br />

Functions<br />

Wind<br />

6 6 6 }<br />

Functions<br />

Ice<br />

6 5 5 }<br />

This is a safety function. The current<br />

state is therefore only displayed and<br />

cannot be modified. For further<br />

information please refer to section<br />

8.3.<br />

This is a safety function. The current<br />

state is therefore only displayed and<br />

cannot be modified. For further<br />

information please refer to section<br />

8.4.<br />

You can exit the menu at any time by pressing the } button.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

3.2.7 Initial menu "Display<br />

measured values"<br />

The next menu is accessed by turning the dial clockwise:<br />

Display<br />

measured values<br />

{<br />

From this menu you can branch to the "Display measured values" submenu. There<br />

you can read the measured values of all the connected sensors. You access the<br />

menu by pressing the { button: By turning the dial clockwise you access further<br />

menus where you can read the following measured values (provided that the<br />

required sensors are connected):<br />

Measured values<br />

Wind 2m/s<br />

Rain NO<br />

}<br />

Measured values<br />

Photo 1 0lx<br />

Photo 2 0klx<br />

}<br />

Measured values<br />

Photo 3 0klx<br />

Humidity 45%RH<br />

}<br />

Measured values<br />

Temp int 22° C<br />

Temp out 15° C<br />

}<br />

Measured values<br />

Temp 1 15° C<br />

Temp 2 --° C<br />

}<br />

Measured values<br />

Temp 3 --° C<br />

You can exit the menu at any time by pressing the } button.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 15<br />

}<br />

Display of the current wind speed and<br />

status of the rain monitoring function<br />

(no = no rain).<br />

Display of the current brightness values<br />

of the "Photo" 1 and 2 sensors.<br />

Display of the current brightness value<br />

of "Photo" 3 sensor, display of the relative<br />

humidity.<br />

Display of the current temperature value<br />

(of the device-internal sensor), display of<br />

the outside temperature.<br />

Display of further temperature values (if<br />

further sensors are connected).<br />

Display of further temperature values (if<br />

further sensors are connected).


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

3.2.8 Displaying the date and<br />

time<br />

16<br />

We reserve the right to carry out improvements<br />

The next menu is accessed by turning the dial clockwise:<br />

<strong>Wisotronic</strong><br />

<strong>dialog</strong> 3CH<br />

Th 04.01.2004<br />

09:10:38<br />

The current date and time are displayed in this menu. if the unit is not operated<br />

for a period of three minutes, this screen is displayed automatically:<br />

TIP<br />

Temperature<br />

23° C<br />

H! T H #T<br />

Familiarize yourself with these basic functions, turn the<br />

function dial and watch how the display changes whenever<br />

the function dial is turned.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

3.3 Facades and channels<br />

Because the term "Facade" is often misunderstood in the field of sun protection<br />

control systems, this term will be examined in more detail here:<br />

The <strong>Wisotronic</strong> <strong>dialog</strong> disposes of two or three channels, also called "Outputs".<br />

Each output can control either an individual sun protection product (for example<br />

an awning), or a whole group of similar sun protection products (for example a<br />

group of roller shutters).<br />

The individual channels can be controlled completely independently of each other.<br />

<strong>Wisotronic</strong><br />

<strong>dialog</strong> 3K<br />

Mo 01.01.2004<br />

04 : 04: 04 Uhr<br />

Fig. 3-2: <strong>Channel</strong>s of the <strong>Wisotronic</strong> <strong>dialog</strong><br />

In the example shown above <strong>Channel</strong> 1 controls the awning (Facade 1), <strong>Channel</strong> 2<br />

the conservatory awnings (Facade 2) and <strong>Channel</strong> 3 the outside venetian blinds of<br />

the conservatory (Facade 2). It is obvious that it is not possible to differentiate<br />

according to the building facades in this example but rather according to the<br />

individual channels.<br />

A different example: The <strong>Wisotronic</strong> controls all the roller shutters on the West<br />

facade with <strong>Channel</strong> 1, all the roller shutters on the South facade with <strong>Channel</strong> 2<br />

and all the roller shutters on the East facade with <strong>Channel</strong> 3. Since controlling is<br />

carried by facades in this example, it would also be possible to use the term<br />

"Facade" instead of "<strong>Channel</strong>" here.<br />

TIP<br />

In these instructions we will always use the term "<strong>Channel</strong>".<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 17


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

4. The menu structure<br />

4.1 <strong>Channel</strong>-dependent or nonchannel-dependent?<br />

4.2 Safety and comfort<br />

functions<br />

18<br />

We reserve the right to carry out improvements<br />

The representation of the menu structure on the next page is intended to help<br />

you learn to operate the <strong>Wisotronic</strong> rapidly. Whenever you need help or are<br />

looking for a specific menu item, look it up here. The section numbers of this<br />

manual are printed next to the individual menu items. Refer to the section where<br />

you will immediately find the desired function.<br />

When operating the <strong>Wisotronic</strong> it is necessary to differentiate between channeldependent<br />

and non-channel-dependent functions:<br />

<strong>Channel</strong>-dependent functions can be activated and set separately for each<br />

individual channel of the <strong>Wisotronic</strong>. <strong>Channel</strong>-dependent functions can always be<br />

recognized by the channel symbols:<br />

1 2 3 and<br />

Non-channel-dependent functions are higher-level functions. These apply either<br />

for all the channels simultaneously or apply to general settings such as for<br />

example the time or display contrast. Non-channel specific functions can always<br />

be recognized by this symbol:<br />

0<br />

We furthermore differentiate between safety and comfort functions:<br />

Safety functions:<br />

® Wind monitoring<br />

® Ice monitoring<br />

® Rain monitoring<br />

Comfort functions:<br />

® Sun control<br />

® Dawn/dusk control<br />

® Temperature control<br />

® Humidity control<br />

® Timer switch<br />

® Comfort timer<br />

¡“¶<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

Sect. 5.1<br />

Main menu<br />

Fig. 4-1: Menu Structure<br />

Display of the position and<br />

cause/manual operation<br />

(channel 1 and 2)<br />

Display of the position and<br />

cause/manual operation<br />

(channel 3) *<br />

Initial menu<br />

User settings<br />

Initial menu<br />

Service settings<br />

Initial menu<br />

Functions ON/OFF<br />

Initial menu<br />

"Display measured values"<br />

Wind<br />

Rain<br />

Photo 1<br />

Photo 2<br />

Photo 3<br />

Humidity<br />

Temp int.<br />

Temp out.<br />

Temp 1<br />

Temp 2<br />

Temp 3<br />

*<br />

Activate/deactivate all the<br />

comfort functions together<br />

Activate/deactivate the<br />

comfort function<br />

"Sun"<br />

Activate/deactivate the<br />

comfort function<br />

"Dawn/Dusk"<br />

Activate/deactivate the<br />

comfort function<br />

"Temperature"<br />

Activate/deactivate the<br />

safety function<br />

"Rain"<br />

Activate/deactivate the<br />

comfort function<br />

"Humidity"<br />

Activate/deactivate the<br />

comfort function<br />

"Timer switch"<br />

Activate/deactivate the<br />

comfort function<br />

"Comfort timer"<br />

Activate/deactivate the<br />

safety function<br />

"Wind"<br />

Activate/deactivate the<br />

safety function<br />

"Ice"<br />

3.2.2<br />

3.2.2<br />

{<br />

{<br />

{<br />

3.2.6<br />

{<br />

3.2.7<br />

3.2.6<br />

3.2.6<br />

3.2.6<br />

3.2.6<br />

3.2.6<br />

3.2.6<br />

3.2.6<br />

3.2.6<br />

3.2.6<br />

3.2.6<br />

1<br />

2<br />

3<br />

0<br />

Sect. 6<br />

1<br />

2<br />

3<br />

User settings<br />

Sect. 7<br />

0<br />

Sect. 8<br />

1<br />

2<br />

3<br />

Service settings<br />

Sect. 9<br />

0<br />

*<br />

*<br />

* 3-channel variant only<br />

} <strong>Channel</strong>-dependent Settings<br />

Sun control<br />

Dawn/Dusk control<br />

Temperature control<br />

Rain monitoring<br />

Humidity control<br />

Timer switch<br />

Comfort timer<br />

Manual operation<br />

Remote control<br />

learn / delete<br />

Reset alerts:<br />

Ice alert<br />

Date / Time<br />

Display<br />

Reset alerts:<br />

Wind sensor test<br />

Product settings<br />

Wind monitoring<br />

Ice monitoring<br />

Allocation<br />

sensor<br />

Non-<strong>Channel</strong>-dependent Settings<br />

Ssystem settings<br />

Language<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 19<br />

6.1<br />

6.2<br />

6.3<br />

6.4<br />

6.5<br />

6.6<br />

6.7<br />

6.8<br />

6.9<br />

6.10<br />

7.1<br />

7.2<br />

7.3<br />

7.4<br />

8.2<br />

8.3<br />

8.4<br />

8.5<br />

9.1<br />

9.2<br />

Integr. temp<br />

sensor offset<br />

Duration Wind<br />

sensor test<br />

Software version<br />

9.1.1<br />

9.1.2<br />

9.1.3


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

4.3 Explanation of the most<br />

Important symbols used<br />

4.3.1 Symbols: Manual<br />

operation<br />

4.3.2 Symbols: Menu change,<br />

modifying values<br />

20<br />

We reserve the right to carry out improvements<br />

You will be confronted with certain symbols time and again when operating the<br />

<strong>Wisotronic</strong>.<br />

The following symbols are always positioned in the lower line of the display. The<br />

buttons below these symbols are used to operate your sunblind manually:<br />

H<br />

T<br />

F<br />

f<br />

If the button below this symbol is pressed, your sunblind moves<br />

up or an awning moves in.<br />

If the button below this symbol is pressed, your sunblind moves<br />

down or an awning moves out.<br />

If the button below this symbol is pressed, your window is<br />

opened.<br />

If the button below this symbol is pressed, your window is closed.<br />

The following symbols are always positioned in the lower line of the display. The<br />

buttons below these symbols are used to move through the menus or modify the<br />

setting values:<br />

1<br />

2<br />

3<br />

0<br />

{<br />

}<br />

—+<br />

*<br />

¡<br />

“<br />

¶<br />

|<br />

If the button below this symbol is pressed, you can carry out the<br />

settings for <strong>Channel</strong> 1.<br />

If the button below this symbol is pressed, you can carry out the<br />

settings for <strong>Channel</strong> 2.<br />

If the button below this symbol is pressed, you can carry out the<br />

settings for <strong>Channel</strong> 3.<br />

The button below this symbol is used to carry out the non-channeldependent<br />

settings.<br />

If the button below this symbol is pressed, the system moves one<br />

menu level down.<br />

If the button below this symbol is pressed, the system moves one<br />

menu level up.<br />

If the buttons below the plus or minus sign is pressed, the setting<br />

values are modified.<br />

If the button below this symbol is pressed, the cursor changes to<br />

the next decimal place<br />

This symbol reminds you that you are currently carrying out the<br />

settings for <strong>Channel</strong> 1.<br />

This symbol reminds you that you are currently carrying out the<br />

settings for <strong>Channel</strong> 2.<br />

This symbol reminds you that you are currently carrying out the<br />

settings for <strong>Channel</strong> 3.<br />

If the button below the floppy disk symbol is pressed, your<br />

settings are saved.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

4.3.3 Symbols: Activation of<br />

safety and comfort<br />

functions<br />

The following symbols are always positioned in the lower line of the display.<br />

They always refer to the text additionally displayed in the display. The functions at<br />

the respective channels can be switched on and off by pressing the buttons<br />

below the symbols.<br />

Functions<br />

Comfort<br />

5 6 5 }<br />

5<br />

6<br />

All the comfort functions at the respective channel are deactivated.<br />

All the comfort functions at the respective channel are activated.<br />

Functions<br />

Sun<br />

5 6 8 }<br />

5<br />

6<br />

8<br />

The sun control is de-activated at the respective channel.<br />

The sun control is activated at the respective channel.<br />

The sun control is activated at the respective channel, but is<br />

currently being blocked, because<br />

Either all the comfort functions for this channel are de-activated<br />

Or because the sun control is blocked by the temperature control<br />

Or because the comfort timer is activated at the respective<br />

channel, but it is in the OFF phase at present. This blocks the sun<br />

control.<br />

Functions<br />

Dawn/Dusk<br />

5 6 8 }<br />

5<br />

6<br />

8<br />

The dawn/dusk control is de-activated at the respective channel.<br />

The dawn/dusk control is activated at the respective channel.<br />

The dawn/dusk control is activated at the respective channel, but<br />

is currently being blocked<br />

Either because all the comfort functions for this channel are deactivated<br />

Or because the comfort timer is activated at the respective<br />

channel, but it is in the OFF phase at present. This blocks the<br />

dawn/dusk control.<br />

This also applies correspondingly for the functions "Rain",<br />

"Humidity" and "Timer switch".<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 21


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

22<br />

We reserve the right to carry out improvements<br />

Functions<br />

Temperature<br />

5 6 7 }<br />

5<br />

6<br />

7<br />

The temperature control is de-activated at the respective channel.<br />

The temperature control is activated at the respective channel.<br />

The temperature control is activated at the respective channel, but<br />

is in the "Enable sun" operating mode. The sun control is being<br />

blocked at present because the limit for activating the sun control<br />

has not been reached yet.<br />

Functions<br />

Comfort timer<br />

5 6 7 }<br />

5<br />

6<br />

7<br />

The comfort timer is de-activated at the respective channel.<br />

The comfort timer is activated at the respective channel.<br />

The comfort timer is activated at the respective channel, but is in<br />

the OFF phase at present. This blocks all the comfort functions.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

4.3.4 Symbols: Cause of a move<br />

command<br />

The following symbols are always positioned in the upper line of the display. They<br />

inform you about the current status of the control system and show the cause of<br />

a move command. This means that you can always follow what the control<br />

system is currently doing or last did. Furthermore you can observe the control<br />

behavior exactly and adapt it if necessary.<br />

TIP<br />

m<br />

S<br />

b<br />

w<br />

d<br />

X<br />

^<br />

r<br />

R<br />

u<br />

Z<br />

W<br />

e<br />

The symbol display depends on the connected sensors and<br />

the sunblind product which is set.<br />

Your sunblind was moved manually. The cause was manual<br />

operation via the buttons of the <strong>Wisotronic</strong>, the remote control or<br />

via local control buttons.<br />

Your sunblind was moved. The cause was the sun control because<br />

the brightness exceeded the "Sun DOWN" limit.<br />

Your sunblind was moved. The cause was the sun control because<br />

the brightness dropped below the "Sun TURN OPEN" limit.<br />

Your sunblind was moved. The cause was the sun control because<br />

the brightness dropped below the "Cloud UP" limit.<br />

Your sunblind was moved. The cause was the dawn/dusk control<br />

because the brightness dropped below the "Dusk DOWN" limit or<br />

exceeded the "Dawn UP" limit.<br />

Your sunblind was moved. The cause was the temperature control<br />

because the temperature dropped below the "UP" limit or<br />

exceeded the "DOWN" limit.<br />

Your sunblind was moved. The cause was the difference<br />

temperature control because the temperature difference between<br />

the outside and inside temperatures dropped below the "HIGH"<br />

limit or exceeded the "DOWN" limit.<br />

Your sunblind was moved. The cause was the rain monitoring<br />

function because the sensor recognized rain.<br />

(RH = Relative humidity) Your sunblind was moved. The cause was<br />

the humidity control because the humidity dropped below the "Limit<br />

UP (dry)" limit or exceeded the "Limit DOWN (wet)" limit.<br />

Your sunblind was moved. The cause was the timer switch.<br />

Your sunblind was moved. The cause was a move command via<br />

the external master switch.<br />

Your sunblind was moved. The cause was the wind monitoring<br />

function.<br />

Your sunblind was moved. The cause was the ice monitoring<br />

function.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 23


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

4.3.5 Symbols: Position and<br />

movements of the<br />

sunblind<br />

4.3.6 Symbols: Displaying<br />

movements at windows<br />

24<br />

We reserve the right to carry out improvements<br />

TIP<br />

I<br />

U<br />

l<br />

s<br />

f<br />

F<br />

s<br />

Your sunblind was moved upwards during the last movement and<br />

is positioned in the upper end position.<br />

Your sunblind was moved downwards during the last movement<br />

and is positioned in the lower end position. If a slat product is<br />

connected to the respective channel, the slats remain closed after<br />

the downward movement has been completed.<br />

Your sunblind was moved downwards during the last movement<br />

and is positioned in the lower end position. If a slat product is<br />

connected to the respective channel, the slats were turned open<br />

after the downward movement had been completed.<br />

Your sunblind was stopped during the last movement and is in an<br />

unspecific position.<br />

A flashing symbol always means that a move command is<br />

being carried out.<br />

Your window was closed during the last movement.<br />

Your window was opened during the last movement.<br />

Your window was stopped during the last movement and is in an<br />

unspecific position.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

4.3.7 Symbols: Displaying<br />

movements at locks<br />

ª<br />

†<br />

@<br />

‚<br />

g<br />

G<br />

‚<br />

The lock switch is open, so that movement of the sunblind is<br />

blocked.<br />

Static symbol: The sunblind is in the upper end position and is<br />

blocked by the open lock switch.<br />

Flashing symbol: The displayed cause is trying to move the<br />

sunblind up. However, the sunblind is blocked by the open lock<br />

switch.<br />

The lock switch is open, so that movement of the sunblind is<br />

blocked.<br />

Static symbol: The sunblind is in the lower end position and is<br />

blocked by the open lock switch.<br />

Flashing symbol: The displayed cause is trying to move the<br />

sunblind down. However, the sunblind is blocked by the open lock<br />

switch.<br />

The lock switch is open, so that movement of the sunblind is<br />

blocked.<br />

Static symbol: The sunblind is in the lower end position. In case of<br />

slat products the slats are turned open. The sunblind is blocked by<br />

the open lock switch.<br />

Flashing symbol: The displayed cause is trying to move the<br />

sunblind down and to turn it open at the bottom position.<br />

However, the sunblind is blocked by the open lock switch.<br />

The lock switch is open, so that movement of the sunblind is<br />

blocked. The sunblind is in an unspecific position.<br />

The lock switch is open, so that movement of the window is<br />

blocked.<br />

Static symbol: The window is closed and is blocked by the open<br />

lock switch.<br />

Flashing symbol: The displayed cause is trying to close the<br />

window. However, this is blocked by the open lock switch.<br />

The lock switch is open, so that movement of the window is<br />

blocked.<br />

Static symbol: The window is opened completely and is blocked<br />

by the open lock switch.<br />

Flashing symbol: The displayed cause is trying to open the<br />

window. However, this is blocked by the open lock switch.<br />

The lock switch is open, so that movement of the window is<br />

blocked. The window is in an unspecific position.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 25


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

5. Getting started<br />

5.1 Display level and manual<br />

operation<br />

Important information!<br />

26<br />

We reserve the right to carry out improvements<br />

The default menu is displayed automatically after the power is applied to the<br />

<strong>Wisotronic</strong> or if no operation has been carried out for a duration of three minutes.<br />

You can access the following menus by turning the function dial.<br />

The following menus can be called up:<br />

Fig. 5-1: Main menu level: The section numbers are listed on the right in the boxes.<br />

TIP<br />

5.1<br />

Display of the position and<br />

cause/manual operation<br />

(channel 1 and 2)<br />

5.1<br />

Main menu<br />

* 3-channel variant only<br />

Display of the position and<br />

cause/manual operation<br />

(channel 3)<br />

*<br />

Initial menu<br />

User settings<br />

Initial menu<br />

Service settings<br />

Initial menu<br />

Functions ON/OFF<br />

Initial menu<br />

"Display measured values"<br />

The displays shown in these instructions are examples of the<br />

3-channel variant. The displayed entries which can be<br />

modified may therefore differ from those on the display of<br />

your <strong>Wisotronic</strong>. If you only have the 2-channel variant, the<br />

third channel is therefore not displayed on your display.<br />

5.1<br />

{<br />

{<br />

{<br />

{<br />

Default menu<br />

Bypass into<br />

the menu<br />

"User settings"<br />

Bypass into<br />

the menu<br />

"Service settings"<br />

Bypass into<br />

the menu<br />

"Functions<br />

ON/OFF"<br />

Bypass into<br />

the menu<br />

"Display measured<br />

values"<br />

Sect. 6<br />

Sect. 8<br />

3.2.6<br />

3.2.7<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

5.2 Setting the time and<br />

date<br />

If the <strong>Wisotronic</strong> was commissioned by one of our specialist partners and adapted<br />

optimally to your sunblind, no further product-dependent settings are required<br />

after the supply voltage has been switched on. If modifications nevertheless have<br />

to be carried out, please refer to Section 8 for further information.<br />

If the date and time are not displayed correctly, you can correct this simply:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the menu item 0 . The following display appears:<br />

Date/Time<br />

{ }<br />

■ The following date and time displays are examples and may deviate from the<br />

display on your <strong>Wisotronic</strong>. Select the menu item (button {). The following<br />

display appears:<br />

Date/Time<br />

Time<br />

15:00<br />

— + | }<br />

■ Set the current time by using the buttons — + and then press the button |<br />

(save)<br />

■ Turn the function dial until the following display appears:<br />

Date/Time<br />

Year<br />

2004<br />

— + | }<br />

■ Set the current year by using the buttons — + and then press the button |<br />

(save)<br />

■ Turn the function dial until the following display appears:<br />

Date/Time<br />

Month<br />

July<br />

— + | }<br />

■ Set the current month by using the buttons — + and then press the button<br />

| (save)<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 27


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

28<br />

We reserve the right to carry out improvements<br />

■ Turn the function dial until the following display appears:<br />

Date/Time<br />

Day<br />

23<br />

— + | }<br />

■ Set the current day by using the buttons — + and then press the button |<br />

(save).<br />

■ Turn the function dial until the following display appears:<br />

Date/Time<br />

Weekday<br />

Friday<br />

— + | }<br />

■ Set the current weekday by using the buttons — + and then press the<br />

button | (save). Quit the setting menu by pressing the } button.<br />

This completes the process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

5.3 Overview of the control<br />

system<br />

The <strong>Wisotronic</strong> encompasses four function blocks: Safety and comfort functions,<br />

a timer switch and the possibility of manual operation. The following graphic<br />

explains the properties of the safety functions: When a safety function has been<br />

triggered, move commands are not executed - all the switches are open.<br />

Exception: An ice alert can be resetted temporarily. For further information please<br />

refer to Section 6.10.<br />

Comfort functions<br />

Sun control<br />

Dawn/Dusk control<br />

Temperature control<br />

Humidity control<br />

Comfort timer<br />

Timer switch<br />

Timer switch<br />

Manual operation<br />

Manual UP/DOWN<br />

Remote control UP/DOWN<br />

Function dial STOP<br />

Fig. 5-2: Safety functions active - switches are open, move commands are blocked.<br />

If no safety function has triggered, all the functions of the <strong>Wisotronic</strong> can be used<br />

to the full extent. This is illustrated in the following graphic: All the switches are<br />

closed. Exception: The comfort timer. For further information on this function<br />

please refer to Section 6.7.<br />

Comfort functions<br />

Sun control<br />

Dawn/Dusk control<br />

Temperature control<br />

Humidity control<br />

Comfort timer<br />

Timer switch<br />

Timer switch<br />

Manual operation<br />

Safety functions<br />

Wind monitoring<br />

Rain monitoring<br />

Ice monitoring<br />

Manual UP/DOWN<br />

Remote control UP/DOWN<br />

Function dial STOP<br />

Safety functions<br />

Wind monitoring<br />

Rain monitoring<br />

Ice monitoring<br />

Move<br />

command<br />

Move<br />

command<br />

Fig. 5-3: Comfort functions active: Switches are closed, move commands are enabled.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 29


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6. <strong>Channel</strong>-dependent<br />

user settings<br />

30<br />

We reserve the right to carry out improvements<br />

When you turn the function dial you access the User settings menu. Here you can<br />

carry out various user-defined settings specifically for each channel.<br />

■ Turn the function dial until the following display is shown:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (button 1, 2 or 3) or the function 0. You can then access<br />

the following menus by turning the function dial, where you can then carry out<br />

your settings:<br />

* 3-channel variant only<br />

1<br />

}<br />

2<br />

3<br />

0<br />

Sect. 6<br />

1<br />

2<br />

User settings<br />

Sect. 7<br />

0<br />

<strong>Channel</strong>-dependent Settings<br />

3 *<br />

Non-<strong>Channel</strong>-dependent Settings<br />

Sun control<br />

Dawn/Dusk control<br />

Temperature control<br />

Rain monitoring<br />

Humidity control<br />

Timer switch<br />

Comfort timer<br />

Manual operation<br />

Remote control<br />

learn / delete<br />

Reset alerts:<br />

Ice alert<br />

Date / Time<br />

Display<br />

Reset alerts:<br />

Wind monitoring<br />

Fig. 6-1: User settings: The section numbers are listed on the right in the boxes.<br />

6.1<br />

6.2<br />

6.3<br />

6.4<br />

6.5<br />

6.6<br />

6.7<br />

6.8<br />

6.9<br />

6.10<br />

7.1<br />

7.2<br />

7.3<br />

7.4<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.1 Sun control<br />

TIP<br />

Changing the user settings can impair the safety of the<br />

system or reduce its effectiveness! If you are not sure what<br />

effect a change has, consult an expert.<br />

The sun control is one of the most important comfort functions of the <strong>Wisotronic</strong><br />

because the most important control mode for sun protection products is that of<br />

controlling as a function of the brightness. The sensors "Wind/Photo", "Wind/Photo/Radio<br />

clock" or the sensor "Photo" (180°) can be used to detect the brightness.<br />

If the brightness exceeds the set "Down" limit, a move command is triggered and<br />

the sunblind is moved downwards. If the "Photo" measured value drops below the<br />

set "Up" limit, the sunblind is moved upwards again.<br />

The following values can be changed for each channel:<br />

Sun control<br />

Sun control ON/OFF<br />

Sun limit UP<br />

Sun delay UP<br />

Sun limit OPEN<br />

Only meanfully in case of selected<br />

product type "slat products"<br />

Sun delay OPEN<br />

Only meanfully in case of selected<br />

product type "slat products"<br />

Sun limit DOWN<br />

Sun delay DOWN<br />

Sun position DOWN<br />

Sun angle DOWN<br />

Only meanfully in case of selected<br />

product type "slat products"<br />

ON/OFF<br />

0...99<br />

klx<br />

0...99<br />

Minutes<br />

0...99<br />

klx<br />

0...99<br />

Minutes<br />

0...99<br />

klx<br />

0...99<br />

Minutes<br />

0...<br />

100%<br />

—80...<br />

+80°<br />

Fig. 6-2: Sun control: Values which can be changed. The "Sun angle DOWN" setting range<br />

depends on the settings described in Sections 8.2.3 to 8.2.5.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 31


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.1.1 Sun control ON/OFF<br />

32<br />

We reserve the right to carry out improvements<br />

Here you can specify whether the sun control is to be activated or not. Proceed as<br />

follows in order to change the setting value:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Sun<br />

control<br />

ON<br />

— + ¡ | }<br />

■ Activate or de-activate the sun control by using the buttons — + and then<br />

press the button | (save). The symbol ¡ reminds you that you are carrying<br />

out the settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the }button twice consecutively. This completes the process.<br />

TIP<br />

Sun<br />

control<br />

If you want to carry out the settings for further channels, you<br />

can press the button below the channel number to select the<br />

next channel in all the displays with channel designations, for<br />

example:<br />

CH 1 { }<br />

■ You can also change the channels directly by repeatedly pressing the button<br />

below the channel number.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.1.2 Sun control limit "DOWN"<br />

6.1.3 Sun control delay "DOWN"<br />

6.1.4 Sun control position<br />

"DOWN"<br />

The limit "DOWN" specifies the intensity of brightness from which the sunblind is<br />

to be moved down. The setting range is from 0 - 99 klx. If you do not want to<br />

evaluate the limit "DOWN", you can also set the value "0" (---) here. Proceed<br />

as follows in order to change the setting value:<br />

■ Change to the sun control menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Sun<br />

limit DOWN<br />

35 klx<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

A delay can be assigned to the limit "DOWN" so that the sun protection does not<br />

move down immediately whenever the brightness changes (for example when<br />

the sun shines temporarily through an otherwise heavy layer of cloud). This<br />

smooths the movement behavior of the sun protection and thus increases the<br />

comfort. If the limits are reached or exceeded for the duration of this delay period,<br />

the "DOWN" command is triggered and the sun protection is moved down. The<br />

setting range is from 0 - 99 minutes. Proceed as follows in order to change the<br />

setting value:<br />

■ Change to the sun control menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Sun<br />

delay DOWN<br />

2 minutes<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

The limit "Position" specifies the position to which the sunblind is to be moved<br />

down when the sun control limit is exceeded. The setting range is from 0-100%,<br />

whereby a value of 0% corresponds to the upper end position and a value of<br />

100% to the lower end position. Proceed as follows in order to change the setting<br />

value:<br />

■ Change to the sun control menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Sun<br />

position DOWN<br />

100%<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 33


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.1.5 Sun control limit "UP"<br />

6.1.6 Sun control delay "UP"<br />

34<br />

We reserve the right to carry out improvements<br />

The limit "UP" specifies the intensity of brightness at which the sunblind is to be<br />

moved up. The setting range is from 0 - 99 klx. If you do not want to evaluate the<br />

limit "UP", you can also set the value "0" (---) here. Proceed as follows in order<br />

to change the setting value:<br />

■ Change to the sun control menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Sun<br />

limit UP<br />

15 klx<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

A delay can be assigned to the limit "UP" so that the sun protection does not<br />

move up immediately whenever the brightness changes (for example when the<br />

sun is covered temporarily by a cloud). This smoothens the move behavior of the<br />

sun protection and thus increases the comfort. If the limits are reached or<br />

exceeded for the duration of this delay period, the "UP" command is triggered and<br />

the sun protection is moved up. The setting range is from 0 - 99 minutes. Proceed<br />

as follows in order to change the setting value:<br />

■ Change to the sun control menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Sun<br />

delay UP<br />

20 minutes<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

TIP<br />

If the sun control is used in combination with the dawn/dusk<br />

control, you have to set the "Sun delay UP" and the "Sun<br />

delay OPEN" periods of the sun control to longer than 5<br />

minutes, because the delay periods of the dawn/dusk control<br />

are fixed internally at 5 minutes. Otherwise the Dawn/dusk<br />

control does not work properly.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.1.7 Sun control limit "OPEN" This function only makes sense if you have selected a slat product (external<br />

venetian blind or internal venetian blind) as the product type. This specifies the<br />

brightness from which the slats of external or internal venetian blinds are to be<br />

turned to a horizontal position, for example in order to let more light into the room<br />

when the sky is covered but bright. The setting range is from 0 - 99 klx. If you do<br />

not want to evaluate the limit "OPEN", you can also set the value "0"<br />

(---) here. Proceed as follows in order to change the setting value:<br />

6.1.8 Sun control delay "OPEN"<br />

6.1.8.1 The "OPEN" limit<br />

■ Change to the sun control menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Sun<br />

limit OPEN<br />

28 klx<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

This function only makes sense if you have selected a slat product (external<br />

venetian blind or internal venetian blind) as the product type. A delay period can<br />

be assigned to the "OPEN" limit so that the slats are not turned open immediately<br />

whenever the intensity of brightness changes (for example if the clouds only<br />

become denser temporarily). This smooths the move behavior of the sun<br />

protection and thus increases the comfort. The turn command is triggered and the<br />

slats are turned open if the limits are reached or if the value drops below these<br />

limits for the duration of the delay period. The setting range is from 0 - 99<br />

minutes. Proceed as follows in order to change the setting value:<br />

■ Change to the sun control menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Sun<br />

delay OPEN<br />

0 minutes<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

The following instructions for the setting of the "DOWN", "OPEN" and "UP" limits<br />

have to be observed in order for the sun control to function properly in connection<br />

with the "OPEN" limit:<br />

■ The lowest value must always be the value for "UP", for example 5 klx<br />

■ The highest value must always be the value for "DOWN", for example 30 klx<br />

■ The value for "OPEN" must be set between these values, for example 10 klx.<br />

TIP<br />

In order to find the optimal setting for your sun protection<br />

system you should test various values on a bright day with<br />

varying cloud situations. This is the only way of obtaining the<br />

optimum result.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 35


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.1.9 Slat angle after moving<br />

down<br />

36<br />

We reserve the right to carry out improvements<br />

This function only makes sense if you have selected a slat product (external<br />

venetian blind or internal venetian blind) as the product type. If you have<br />

connected slat products such as external venetian blinds to a channel, you can<br />

specify how the slats are to be set after the movement down has been<br />

completed. This makes sense in particular if you prefer a particular setting. In<br />

addition, you do not have to turn the slats open manually after an automatic<br />

movement down. The sun control takes over the task of turning open the slats for<br />

you automatically if a corresponding programming exists. The slat setting for<br />

automatic operation has been set to a value of 38° in our works.<br />

The following fig. illustrates the setting of the slat angle:<br />

Positive value: Slats are turned outwards<br />

Negative value: Slats are turned inwards<br />

Setting 0°: The slats remain in a horizontal position<br />

Fig. 6-3: Slat angle of external venetian blinds and internal venetian blinds<br />

TIP<br />

Outside<br />

+80° 0°<br />

The product-typical turning time as well as the producttypical<br />

turning angle (refer to Section 8.2.3 to 8.2.5) have to be<br />

set first.<br />

Note: The setting range of the slat angle depends on the settings made in<br />

Section 8.2.3 to 8.2.5. Proceed as follows in order to change the setting value:<br />

■ Change to the sun control menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Sun<br />

angle DOWN<br />

38°<br />

— + ¡ | }<br />

Inside<br />

-80°<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the ¡ button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.1.10 Using the sun control<br />

correctly<br />

6.1.11 The sun control during<br />

wind, rain or ice alert<br />

The following section describes the effects of the setting values for the sun control<br />

described above in more detail. The graphic below explains how the outdoor<br />

brightness can change during the course of a certain period by means of an<br />

example diagram:<br />

Fig. 6-4: Course of brightness and movement behavior<br />

The thick black curve represents the course of brightness. The two horizontal<br />

lines are the limits specified by you for moving the sun protection up or down.<br />

The vertical dashed lines mark the delay periods for activating and de-activating.<br />

Let us assume that you have set 2 minutes for this delay period, then the sun<br />

protection reacts as follows:<br />

The outdoor brightness increases until Point 1 of the curve is reached. The<br />

"DOWN" limit is reached here. The "DOWN" delay period now begins but your sun<br />

protection is not yet moved down. The brightness drops below the "DOWN" limit<br />

at Point 2 of the curve before the "DOWN" delay period has expired. Your sun<br />

protection has remained at the top position.<br />

Later on the brightness increases again and exceeds the "DOWN" limit once more<br />

at Point 3. The "DOWN" delay period now begins but your sun protection is not<br />

yet moved down. However, the "DOWN" delay period has already expired at Point<br />

4 and the limit is still exceeded - the sun protection now moves down.<br />

Now a cloud moves in front of the sun and your rooms slowly become too dark.<br />

The limit "UP" is dropped at point 5. Nothing happens yet, because the "UP" delay<br />

period now first starts - the sun protection therefore does not move up yet. The<br />

"UP" delay period has finally expired at Point 6 and the brightness still lies below<br />

the "UP" limit. The sun protection now moves up again.<br />

The correct setting of the delay periods thus results in a comfortable control of<br />

the sun protection. It contributes to "smoothening" the reaction behavior of the<br />

control system. This ensures that the sun protection is not moved immediately<br />

whenever the outside brightness changes.<br />

TIP<br />

Brightness (klx)<br />

Adjusted DOWN limit<br />

Adjusted OPEN limit<br />

Adjusted UP limit<br />

Course of brightness<br />

1 2 3 4 5 6<br />

< 2 Min = 2 Min = 2 Min<br />

The graphic also illustrates clearly that the "DOWN" limit<br />

always has to be set higher than the "UP" limit - otherwise<br />

the sun control does not function.<br />

The sun control is inactive during a wind, rain or ice alert. After the alert has been<br />

canceled, the sun control becomes active again and starts again with the<br />

brightness evaluation.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 37<br />

Delay DOWN<br />

Delay DOWN<br />

Delay UP<br />

Time


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.2 Dawn/dusk control<br />

38<br />

We reserve the right to carry out improvements<br />

The dawn/dusk control is a further comfort function of the <strong>Wisotronic</strong> which<br />

allows you to control the sun protection or mainly view protection depending on<br />

the dawn or dusk situation. The brightness is detected by Photo sensors. If the<br />

brightness drops below the set "DOWN" limit for the duration of 5 minutes, a<br />

move command is triggered which moves the sun/view protection down. If the<br />

"Photo" measured value exceeds the set "UP" limit for the duration of 5 minutes,<br />

the sun protection is moved up again.<br />

The following values can be changed for each channel:<br />

Dawn/Dusk control<br />

ON/OFF<br />

Dawn limit UP<br />

Dusk limit DOWN<br />

Dusk<br />

angle DOWN<br />

Only meanfully in case of selected<br />

product type "slat products"<br />

Fig. 6-5: Dawn/dusk control: Values which can be changed. The "Dusk angle DOWN"<br />

setting range depends on the settings described in Sections 8.2.3 to 8.2.5.<br />

TIP<br />

Dawn/dusk control<br />

ON/OFF<br />

0...99<br />

lx<br />

0...99<br />

lx<br />

— 80 ...<br />

+ 80 °<br />

The dawn/dusk control uses the "Photo 1" sensor connection<br />

to evaluate the brightness. This applies for all the channels.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.2.1 Dawn/dusk control ON/OFF<br />

Here you can specify whether the dawn/dusk control is to be activated or not.<br />

Proceed as follows in order to change the setting value:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Dawn/Dusk<br />

control<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Dawn/Dusk<br />

control<br />

ON<br />

— + ¡ | }<br />

■ Activate or de-activate the dawn/dusk control by using the buttons — + and<br />

then press the button | (save). The symbol ¡ reminds you that you are<br />

carrying out the settings for <strong>Channel</strong> 1. If you want to exit the menu without<br />

saving the changes, press the } button twice consecutively. This completes<br />

the process.<br />

TIP<br />

Dawn/dusk<br />

control<br />

If you want to carry out the settings for further channels, you<br />

can press the button below the channel number to select the<br />

next channel in all the displays with channel designations, for<br />

example:<br />

CH 1 { }<br />

■ You can also change the channels directly by repeatedly pressing the button<br />

below the channel number.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 39


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.2.2 Dawn/dusk control limit<br />

"UP"<br />

6.2.3 Dawn/dusk control limit<br />

"DOWN"<br />

40<br />

We reserve the right to carry out improvements<br />

The limit "UP" specifies the brightness from which the sunblind is to be moved up<br />

in the morning. The setting range is from 0 - 99 lx. If you do not want to evaluate<br />

the limit "UP", you can also set the value "0" (---) here. Proceed as follows in<br />

order to change the setting value:<br />

■ Change to the dawn/dusk control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Dawn<br />

limit UP<br />

30 lx<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button |(save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> ¡. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

The limit "DOWN" specifies the brightness from which the sunblind is to be<br />

moved down in the evening. The setting range is from 0 - 99 lx. If you do not<br />

want to evaluate the limit "DOWN", you can also set the value "0" (---) here.<br />

Proceed as follows in order to change the setting value:<br />

■ Change to the dawn/dusk control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Dusk<br />

limit DOWN<br />

80 lx<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button |(save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> ¡. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

TIP<br />

If the sun control is used in combination with the dawn/dusk<br />

control, you have to set the "Sun delay UP" and the "Sun<br />

delay OPEN" periods of the sun control to longer than 5<br />

minutes, because the delay periods of the dawn/dusk control<br />

are fixed internally at 5 minutes. Otherwise the Dawn/dusk<br />

control does not work properly.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.2.4 Slat angle after moving<br />

down<br />

This function only makes sense if you have selected a slat product (external<br />

venetian blinds or internal venetian blinds) as the product type. After moving<br />

down has been completed by the dawn/dusk control, the slats are turned open to<br />

the set angle. You can ensure that the sunblind is turned either to let the light<br />

through (horizontal, setting 0°) or to protect against viewing from the outside (for<br />

example +80°).<br />

The following fig. illustrates the setting of the slat angle:<br />

Positive value: Slats are turned outwards<br />

Negative value: Slats are turned inwards<br />

Setting 0°: The slats remain in a horizontal position<br />

Fig. 6-6: Slat angle at external venetian blinds and internal venetian blinds<br />

TIP<br />

Outside<br />

+80° 0°<br />

The product-typical turning time as well as the producttypical<br />

turning angle (refer to Section 8.2.3 to 8.2.5) have to be<br />

set first.<br />

Note: The setting range of the slat angle depends on the settings made in<br />

Section 8.2.3 to 8.2.5.<br />

■ Change to the dawn/dusk control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Dusk<br />

angle DOWN<br />

80°<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button |(save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> ¡. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 41<br />

Inside<br />

-80°


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.2.5 Using the dawn/dusk control<br />

correctly<br />

6.2.6 The dawn/dusk control<br />

during wind,- rain or ice<br />

alert<br />

42<br />

We reserve the right to carry out improvements<br />

The following section describes the effects of the setting values for the dawn/<br />

dusk control described above in more detail. The graphic below explains how the<br />

outdoor brightness can change during the course of the dawn/dusk by means of<br />

an example diagram:<br />

Brightness (lx)<br />

Adjusted limit dawn DOWN<br />

Adjusted limit dusk UP<br />

Course of brightness<br />

1 2 3 4<br />

Fig. 6-7: Course of brightness and movement behavior<br />

Delay UP<br />

5 Min 5 Min<br />

The thick black curve represents the course of brightness. The two horizontal<br />

lines are the limits specified by you for moving the sunblind up or down.<br />

During dawn the outdoor brightness increases until Point 1 of the curve is<br />

reached. Here the limit "Dawn UP" is reached and then exceeded. The delay<br />

period of 5 minutes (which cannot be changed) now begins to run. At Point 2 of<br />

the curve this period has expired and the limit is still exceeded - the sunblind now<br />

moves up.<br />

During dusk the outdoor brightness decreases until Point 3 of the curve is<br />

reached. Here the limit "Dusk DOWN" is reached, after which the brightness<br />

drops below the limit. The delay period of 5 minutes (which cannot be changed)<br />

now begins to run. At Point 4 of the curve this period has expired and the<br />

brightness still lies below the limit - the sunblind now moves down.<br />

The dawn/dusk control is inactive during a wind,- rain or ice alert. After the alert<br />

has been canceled, the dawn/dusk control becomes active again and starts again<br />

with the brightness evaluation.<br />

Delay DOWN<br />

Time<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3 Temperature control<br />

The temperature control of the <strong>Wisotronic</strong> allows temperature-dependent control<br />

of your sunblind in connection with temperature detectors ("Temperature"<br />

sensors). A sensor for the room temperature is already integrated into the device<br />

itself (device-internal sensor). Three further "Temperature" (inside) sensors and<br />

one "Temperature" (outside) sensor can be connected additionally to the<br />

<strong>Wisotronic</strong>.<br />

TIP<br />

Application example:<br />

<strong>Channel</strong> 2:<br />

Outside<br />

venetian<br />

blind<br />

The temperature control can evaluate either the deviceintegrated<br />

sensor OR a sensor connected to the power unit,<br />

but not several ones simultaneously (for each individual<br />

channel of the <strong>Wisotronic</strong>).<br />

<strong>Channel</strong> 1:<br />

conservatory<br />

awning<br />

Fig. 6-8: Temperature control: Application example<br />

The <strong>Wisotronic</strong> is mounted in the living room.<br />

<strong>Channel</strong> 1 controls the conservatory awning depending on the temperature in the<br />

conservatory, measured with Sensor A (connected to the input "Temperature<br />

inside 1").<br />

<strong>Channel</strong> 2 controls the external venetian blind at the conservatory depending on<br />

the temperature in the conservatory, also measured with Sensor A.<br />

<strong>Channel</strong> 3 controls the roller shutters in the living room depending on the<br />

temperature in the living room, measured with the sensor integrated into the control<br />

panel of the <strong>Wisotronic</strong> ("Temperature (integrated)").<br />

The outside temperature is measured with Sensor B. The external venetian blind,<br />

conservatory awning and roller shutters are subject to ice monitoring and are<br />

moved up before they freeze solid.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 43<br />

X<br />

X<br />

e<br />

Sensor A:<br />

Temperature<br />

(inside) sensor<br />

Sensor B:<br />

Temperature<br />

(outside) sensor<br />

<strong>Channel</strong> 3:<br />

Roller shutter


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.1 Basic functions<br />

44<br />

We reserve the right to carry out improvements<br />

The temperature control allows the comfortable control of your sunblind<br />

depending on the internal and external temperature. Window drives can be<br />

controlled additionally.<br />

1. The temperature control can be activated or de-activated completely channelby-channel.<br />

2. The <strong>Wisotronic</strong> controls your system by constantly comparing the temperature<br />

limits set by you with the local prevailing temperatures. If the temperature<br />

exceeds or drops below the limit, move commands are then triggered.<br />

Prerequisite: The required sensors have to be connected and assigned<br />

correctly.<br />

3. Three operating modes are available for the temperature control:<br />

The "Direct control" operating mode simply only triggers move commands<br />

when the temperature exceeds or drops below the limit.<br />

The "Enable sun" operating mode can be used to activate/de-activate the sun<br />

control.<br />

The "Difference temperature" operating mode can be used to control window<br />

drives depending on the internal and external temperature.<br />

4. Limits have to be specified in order for <strong>Wisotronic</strong> to fulfill all these control<br />

tasks. The temperature control can then be adapted optimally to your<br />

requirements.<br />

The following graphic provides an overview of the temperature control menu.<br />

The following values can be changed for each channel:<br />

Direct<br />

control<br />

Temp.<br />

limit<br />

UP<br />

Temp.<br />

limit<br />

DOWN<br />

Diff.<br />

Temp.<br />

limit<br />

UP<br />

Diff.<br />

temp.<br />

limit<br />

DOWN<br />

—24...<br />

+74°C<br />

—24...<br />

+74°C<br />

1...<br />

+20°C<br />

1...<br />

+20°C<br />

Temperature control<br />

Temperature control ON/OFF<br />

Temperature mode<br />

Enable<br />

sun<br />

Temp.<br />

limit<br />

OFF<br />

Temp.<br />

limit<br />

ON<br />

Diff.<br />

temp.<br />

limit<br />

UP<br />

Diff.<br />

temp.<br />

limit<br />

DOWN<br />

—24...<br />

+74°C<br />

—24...<br />

+74°C<br />

1...<br />

+20°C<br />

1...<br />

+20°C<br />

Fig. 6-9: Temperature control: Values which can be changed.<br />

Diff.<br />

temp.<br />

Temp.<br />

limit<br />

OFF<br />

Temp.<br />

limit<br />

ON<br />

Diff.<br />

temp.<br />

limit<br />

UP<br />

Diff.<br />

temp.<br />

limit<br />

DOWN<br />

—24...<br />

+74°C<br />

—24...<br />

+74°C<br />

1...<br />

+20°C<br />

1...<br />

+20°C<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.2 Temperature control<br />

ON/OFF<br />

Here you can specify for each channel whether the temperature control is to be<br />

activated or not. Proceed as follows in order to change the setting value:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

<strong>Channel</strong> 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Temperature<br />

control<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Temperature<br />

control<br />

ON<br />

— + ¡ | }<br />

■ Activate or de-activate the temperature control by using the buttons — +<br />

and then press the button | (save). The symbol ¡ reminds you that you are<br />

carrying out the settings for <strong>Channel</strong> 1. If you want to exit the menu without<br />

saving the changes, press the }button twice consecutively. This completes<br />

the process.<br />

TIP<br />

Temperature<br />

control<br />

If you want to carry out the settings for further channels, you<br />

can press the button below the channel number to select the<br />

next channel in all the displays with channel designations, for<br />

example:<br />

CH 1 { }<br />

■ You can also change the channels directly by repeatedly pressing the button<br />

below the channel number.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 45


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.3 Selecting the operating<br />

modes of the<br />

temperature control<br />

6.3.3.1 Direct control<br />

6.3.3.2 Enable sun<br />

6.3.3.3 Difference temperature<br />

6.3.4 Changing the operating<br />

mode<br />

46<br />

We reserve the right to carry out improvements<br />

Three operating modes are available for the temperature control:<br />

® Direct control<br />

® Enable sun<br />

® Difference temperature<br />

This operating mode simply only triggers move commands when limits are<br />

exceeded.<br />

This operating mode can be used to activate/de-activate the sun control.<br />

Example: On a cold clear winter day you want the sun to first heat up your<br />

conservatory before the sun protection becomes active. After all, the sun is the<br />

most inexpensive heating source. You can therefore program the <strong>Wisotronic</strong> so<br />

that the sun control is not activated until a certain inside temperature has been<br />

reached. The "Enable sun" operating mode is used to this purpose.<br />

In this operating mode the control system compares the internal and external<br />

temperature. If the temperature exceeds or drops below the limit, move<br />

commands are then triggered.<br />

Example: You wish to maintain your ideal temperature in a living room with builton<br />

conservatory. To this purpose you have connected window drives to the control<br />

system. You can now specify a limit which represents your "cozy"<br />

temperature, for example 22°C. If the sun shines into the conservatory in the<br />

morning, the room temperature also rises and at some point reaches your ideal<br />

value of 22°C. When this value is exceeded, the control system opens a window<br />

and lets cool air into the room. When your ideal temperature is reached again, the<br />

window is closed automatically again. However, if the external temperature<br />

reaches values of, for example, 30°C in the course of the day, it would not make<br />

any sense to let this hot air into the room. The control system recognizes this fact<br />

and therefore keeps the window closed. The window is not opened again until<br />

the external air has cooled down.<br />

Proceed as follows in order to change the operating mode:<br />

■ Change to the temperature control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Temperature<br />

mode<br />

Direct control<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button |(save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.5 Temperature control in the<br />

"Direct control" operating<br />

mode<br />

6.3.5.1 Temperature control<br />

limit "UP"<br />

This operating mode simply only triggers move commands when limits are<br />

exceeded. Continue here if you have selected this operating mode. Otherwise<br />

skip this section. The following values can be changed for each channel:<br />

Temp.<br />

limit<br />

UP<br />

Temp.<br />

limit<br />

DOWN<br />

Diff.<br />

temp.<br />

limit<br />

UP<br />

Diff.<br />

temp.<br />

limit<br />

DOWN<br />

Fig. 6-10: Temperature control: Values which can be changed in the "Direct control"<br />

operating mode<br />

The limit "UP" specifies the temperature from at the sunblind is to be moved up.<br />

Example: You want the sun to support the process of heating your conservatory<br />

on cold clear winter days. You can therefore specify for the control system from<br />

which temperature the sun protection is to be moved up in order to let the<br />

sunlight into the conservatory. The setting range is from –24°C to 74°C. If you do<br />

not want to evaluate the limit "UP", you can also set the value<br />

"0" (---) here. Proceed as follows in order to change the setting value:<br />

■ Change to the temperature control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Temperature<br />

limit UP<br />

22° C<br />

— + ¡ | }<br />

Operating mode:<br />

Direct control<br />

—24...<br />

+74°C<br />

—24...<br />

+74°C<br />

1...<br />

+20°C<br />

1...<br />

+20°C<br />

■ Change the setting values by using the buttons — + and then press the<br />

button |(save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 47


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.5.2 Temperature control<br />

limit "DOWN"<br />

48<br />

We reserve the right to carry out improvements<br />

The limit "DOWN" specifies the temperature at which the sunblind is to be moved<br />

down. Example: You want to keep the inside temperature of your conservatory at<br />

a bearable level on hot midsummer days. You can therefore specify for the<br />

<strong>Wisotronic</strong> at which temperature the sunblind is to be moved down in order to<br />

shade the conservatory. The setting range is from –24°C to 74°C. If you do not<br />

want to evaluate the limit "DOWN", you can also set the value "0" (---) here.<br />

Proceed as follows in order to change the setting value:<br />

■ Change to the temperature control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Temperature<br />

limit DOWN<br />

26° C<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the }button twice consecutively. This completes the<br />

process.<br />

TIP<br />

The menu items "Difference temperature "UP" and "DOWN""<br />

are not evaluated in this operating mode. It is therefore not<br />

necessary to carry out settings here.<br />

If "Window" was selected as the connected product, the<br />

displays deviate from those shown here: "CLOSE" is displayed<br />

instead of "UP".<br />

"OPEN" is displayed instead of "DOWN".<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.6 Temperature control in the<br />

"Enable sun" operating<br />

mode<br />

6.3.6.1 Temperature control<br />

limit "ON"<br />

This operating mode influences the way the sun control works. Continue here if<br />

you have selected this operating mode. Otherwise skip this section. The following<br />

values can be changed for each channel:<br />

Fig. 6-11: Temperature control: Values which can be changed in the "Enable sun" operating<br />

mode<br />

The limit "ON" specifies the temperature at which the sun control is to be enabled<br />

again. Example: The sun control may become active again after the sun has<br />

heated up your conservatory and your ideal temperature has been reached. You<br />

can therefore specify for the <strong>Wisotronic</strong> at which temperature the sun control is<br />

to be enabled again in order to shade the conservatory. The setting range is from<br />

–24° to 74°C. If you do not want to evaluate the limit "ON", you can also set the<br />

value "0" (---) here. Proceed as follows in order to change the setting value:<br />

■ Change to the temperature control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Temperature<br />

limit ON<br />

26° C<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

TIP<br />

Temp.<br />

limit<br />

OFF<br />

Temp.<br />

limit<br />

ON<br />

Diff.<br />

temp.<br />

limit<br />

UP<br />

Diff.<br />

temp.<br />

limit<br />

DOWN<br />

Operating mode:<br />

Enable sun<br />

—24...<br />

+74°C<br />

—24...<br />

+74°C<br />

1...<br />

+20°C<br />

1...<br />

+20°C<br />

The menu items "Difference temperature "UP" and "DOWN""<br />

are not evaluated in this operating mode. It is therefore not<br />

necessary to carry out settings here.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 49


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.6.2 Temperature control<br />

limit "OFF"<br />

50<br />

We reserve the right to carry out improvements<br />

The limit "OFF" specifies the temperature at which the sun control is to be<br />

disabled. Example: On a cold clear winter day you want the sun to first heat up<br />

your conservatory before the sun protection becomes active. After all, the sun is<br />

the most inexpensive heating source. However, if the sun control is activated at<br />

the same time, this could move the sun protection down before your ideal<br />

temperature has been reached. You can therefore program the control system so<br />

that the sun control is not activated until a certain inside temperature has been<br />

reached. The setting range is from –24°C to 74°C. If you do not want to evaluate<br />

the limit "OFF", you can also set the value "0" (---) here. Proceed as follows in<br />

order to change the setting value:<br />

■ Change to the temperature control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Temperature<br />

limit OFF<br />

22° C<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

Sun control<br />

Operating mode:<br />

Enable sun<br />

Move<br />

command<br />

Fig. 6-12: The sun control in the "Enable sun" operating mode: The switch does not close<br />

and the sun control is not enabled until the temperature is reached in the room.<br />

When the room temperature drops below the limit "OFF" again, the switch opens<br />

and the sun control is disabled, the sunblind moves up.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.7 Temperature control in the<br />

"Difference temperature"<br />

operating mode<br />

You can use this operating mode to cool and ventilate a room by controlling your<br />

windows depending on the internal and external temperatures. The difference<br />

temperature modes operates with four adjustable limits:<br />

1. Limit "ON" (maximum cozy temperature): If the internal temperature<br />

exceeds this limit, it is too warm inside. The difference temperature control is<br />

activated in order to ventilate and cool the room.<br />

2. Limit "OFF" (minimum cozy temperature): If the internal temperature drops<br />

below this limit, it is too cold inside. The difference temperature control is deactivated<br />

again and the windows are closed again.<br />

3. Limit difference temperature "OPEN" (outside cooler than inside): If the<br />

external temperature lies under the internal temperature by at least the set<br />

difference temperature, the windows are opened to ventilate and cool the<br />

room.<br />

4. Limit difference temperature "CLOSE" (outside too hot): If the external<br />

temperature is not significant lower than the internal temperature, the room<br />

can no longer be cooled by the hot external air. The necessary difference<br />

temperature limit "CLOSE" can be set. The windows are closed again so that<br />

the room is not heated up further by the increasingly hot external air.<br />

Example: In the morning it is initially too cool in the room. The sun shines<br />

through the windows into the room and heats it up. When the internal<br />

temperature exceeds the maximum cozy temperature, the difference<br />

temperature control is activated. Because it is cooler outside than inside, the<br />

windows are opened.<br />

The ventilation cools the room. If the room temperature drops below the<br />

minimum cozy temperature, the windows are closed again in order to prevent the<br />

room from cooling down. If the internal temperature rises again above the<br />

maximum cozy temperature and it is still cooler outside than inside, the windows<br />

are opened again.<br />

In the course of the day the external temperature rises further due to the sun<br />

irradiation. If it becomes too hot outside in order to cool the room by ventilating it,<br />

the windows are closed again.<br />

During the evening the external temperature drops again and at some stage it is<br />

cooler outside than inside again. The windows are opened again in order to<br />

ventilate and cool again, until the minimum cozy temperature in the room is<br />

reached. Then the windows are closed again in order to protect the room against<br />

cooling down.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 51


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.7 Temperature control in the<br />

"Difference temperature"<br />

operating mode<br />

6.3.7.1 Temperature limit "ON"<br />

52<br />

We reserve the right to carry out improvements<br />

This operating mode only makes sense if the connected product is a window<br />

drive. A "window" must therefore also be set as the product type. In this operating<br />

mode the control system compares the internal and external temperature. If the<br />

temperature exceeds or drops below the limit, move commands are triggered.<br />

The following values can be changed for each channel:<br />

Temp.<br />

limit<br />

OFF<br />

Temp.<br />

limit<br />

ON<br />

Fig. 6-13: Temperature control: Values which can be changed in the "Difference<br />

temperature" operating mode<br />

The limit "ON" specifies the room temperature above which the window is<br />

opened for ventilating and cooling. Example: You wish to maintain your maximum<br />

cozy temperature to a great extent in a living room with a built-on conservatory. To<br />

this purpose you have connected window drives to the control system. You can<br />

now specify a limit which represents your cozy temperature, for example 24°C. If<br />

the sun shines into the conservatory in the morning, the room temperature also<br />

rises and at some point reaches your ideal value of 24°C. The control system may<br />

not open the window for cooling and ventilating until this temperature has been<br />

reached. The setting range is from –24°C to 74°C. If you do not want to evaluate<br />

the limit "ON", you can also set the value "0" (---) here. Proceed as follows in<br />

order to change the setting value:<br />

■ Change to the temperature control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Temperature<br />

limit ON<br />

24° C<br />

— + ¡ | }<br />

Difference temperature<br />

operating mode<br />

Difference<br />

Temp.<br />

limit<br />

CLOSE<br />

Difference<br />

Temp.<br />

limit<br />

OPEN<br />

—24...<br />

+74°C<br />

—24...<br />

+74°C<br />

1...<br />

+20°C<br />

1...<br />

+20°C<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.7.2 Temperature limit "OFF"<br />

6.3.7.3 Difference temperature<br />

limit "OPEN"<br />

The limit "OFF" specifies the minimum cozy temperature at which the<br />

temperature control is to be disabled and the window is to be closed again.<br />

Example: If the room temperature drops to a value of, for example 20°C through<br />

ventilating, the temperature control is disabled and the window is closed again in<br />

order to protect the room against cooling down. The setting range is from<br />

–24°C to 74°C. If you do not want to evaluate the limit "OFF", you can also set the<br />

value ---here. Proceed as follows in order to change the setting value:<br />

■ Change to the temperature control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Temperature<br />

limit OFF<br />

20° C<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

The limit "OPEN" specifies by how many degrees the external temperature has to<br />

be lower than the internal temperature so that the window is opened. If the value<br />

is exceeded, the window is opened. Example: Your max. cozy temperature is<br />

from 24°C, which has already been reached. If the external temperature lies lower<br />

than the internal temperature by the set difference temperature limit "OPEN", the<br />

window is opened for ventilating and cooling. If you set 5°C here, the window is<br />

not opened again until the external temperature has dropped<br />

24°C - 5°C = 19°C. The setting range is from 1 to 20°C. If you do not want to<br />

evaluate the limit "OPEN", you can also set the value "0" (---) here. Proceed as<br />

follows in order to change the setting value:<br />

■ Change to the temperature control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Diff. temp.<br />

limit OPEN<br />

5° C<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

TIP<br />

Correct setting of the limits "OPEN" and "CLOSE" thus<br />

smoothens the move behavior of the window drive and<br />

therefore means that the window is not opened or closed<br />

immediately whenever the temperature changes.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 53


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.3.7.4 Difference temperature<br />

limit "CLOSE"<br />

54<br />

We reserve the right to carry out improvements<br />

The limit "CLOSE" specifies by how many degrees the external temperature has<br />

to be lower than the internal temperature so that the window remains opened. If<br />

the difference temperature drops below the limit "CLOSE", the window is closed.<br />

Example: Your maximum coszy temperature is from 24°C which has already<br />

been reached. The window has already been opened automatically. The external<br />

temperature increases and the difference temperature between outside and<br />

inside drops below the limit of the difference temperature limit "CLOSE". The<br />

window is now closed. If you set 5°C as limit "CLOSE" and the increasing external<br />

temperature is only to 5°C or less lower than the internal temperature, then the<br />

window is closed.The setting range is from 1 to 20°C. If you do not want to<br />

evaluate the limit "CLOSE", you can also set the value "0" (---) here. Proceed<br />

as follows in order to change the setting value:<br />

■ Change to the temperature control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Diff. temp.<br />

limit CLOSE<br />

2° C<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.4 Rain monitoring<br />

6.4.1 Rain monitoring ON/OFF<br />

Although external venetian blinds and roller shutters are relatively insensitive<br />

against rain, all cloth products such as articulated arm awnings and conservatory<br />

awnings have to be protected against rain. If you have set one of these cloth<br />

products as a product in your <strong>Wisotronic</strong>, the rain monitoring function is set<br />

automatically for this product as a safety function. Prerequisite for this safety<br />

function is the connection of a sensor for rain. If you wish, you can naturally also<br />

activate the rain monitoring function for other sun protection products specifically<br />

for each channel. If precipitation (rain or snow) falls on the "Rain" sensor, the sun<br />

protection is moved up. The preselected comfort functions and manual moving<br />

are then blocked. After the "Rain" sensor has dried again and the delay period<br />

which is set in the sensor has expired, the preselected comfort functions and<br />

manual moving are enabled again.<br />

The following values can be changed for each channel:<br />

Rain<br />

monitoring<br />

Fig. 6-14: Rain monitoring: Values which can be changed.<br />

Proceed as follows to activate or de-activate the rain monitoring specifically for<br />

each channel:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Rain<br />

monitoring<br />

CH 1 { }<br />

Rain monitoring<br />

ON/OFF<br />

■ Select this menu item (button {). The following display appears:<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 55


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

56<br />

We reserve the right to carry out improvements<br />

Rain<br />

monitoring<br />

ON<br />

— + ¡ | }<br />

■ Activate or de-activate the rain monitoring by using the buttons — + and<br />

then press the button | (save). The symbol ¡ reminds you that you are<br />

carrying out the settings for <strong>Channel</strong> 1. If you want to exit the menu without<br />

saving the changes, press the } button twice consecutively. This completes<br />

the process.<br />

TIP<br />

Rain<br />

monitoring<br />

If you want to carry out the settings for further channels, you<br />

can press the button below the channel number to select the<br />

next channel in all the displays with channel designations, for<br />

example:<br />

CH 1 { }<br />

■ You can also change the channels directly by repeatedly pressing the button<br />

below the channel number.<br />

TIP<br />

If the rain monitoring function has recognized rain, all the<br />

comfort functions and the manual operation are blocked at<br />

the corresponding channel.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.5 Humidity control<br />

The humidity control is a further comfort function of the <strong>Wisotronic</strong>. This is used<br />

to open a motor-driven window or to activate a ventilation device when an<br />

adjustable humidity limit is exceeded or to activate an air humidifying device (for<br />

example an indoor spring) if the humidity drops below a limit. The combined<br />

"Temperature/humidity" (inside) sensor can be used to detect the humidity.<br />

CAUTION<br />

Non-sun-protection devices may only be integrated into a sun<br />

protection system if certain regulations are observed. Should<br />

you have any questions about connecting non-sun-protection<br />

devices, please contact your specialist dealer!<br />

The following values can be changed for each channel:<br />

Fig. 6-15: Humidity control: Values which can be changed, set product = "Window".<br />

TIP<br />

TIP<br />

Humidity<br />

control<br />

Humidity control<br />

ON/OFF<br />

Humidity limit CLOSE<br />

Humidity limit OPEN<br />

ON/OFF<br />

1...99<br />

%RH<br />

1...99<br />

%RH<br />

If a sun/view protection was selected as the connected<br />

product, the displays deviate from those shown here: "UP" is<br />

displayed instead of "CLOSE".<br />

"DOWN" is displayed instead of "OPEN".<br />

A delay period is not required here since the humidity only<br />

changes very slowly.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 57


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.5.1 Humidity control ON/OFF<br />

58<br />

We reserve the right to carry out improvements<br />

Proceed as follows to activate or de-activate the humidity control specifically for<br />

each channel:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Humidity<br />

control<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Humidity<br />

control<br />

ON<br />

— + ¡ | }<br />

■ Activate or de-activate the humidity control by using the buttons — + and<br />

then press the button | (save). The symbol ¡ reminds you that you are<br />

carrying out the settings for <strong>Channel</strong> 1. If you want to exit the menu without<br />

saving the changes, press the } button twice consecutively. This completes<br />

the process.<br />

TIP<br />

Humidity<br />

control<br />

If you want to carry out the settings for further channels, you<br />

can press the button below the channel number to select the<br />

next channel in all the displays with channel designations, for<br />

example:<br />

CH 1 { }<br />

■ You can also change the channels directly by repeatedly pressing the button<br />

below the channel number.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.5.2 Humidity limit "OPEN"<br />

6.5.3 Humidity limit "CLOSE"<br />

The limit "OPEN" specifies the humidity as from which the move command is to<br />

be initiated. Example: A motor-driven window is to be opened as from a relative<br />

humidity of 75%. The setting range is from 1 to 99%RH (relative humidity). If you<br />

do not want to evaluate the limit "OPEN", you can also set the value "0" (---)<br />

here. Proceed as follows in order to change the setting value:<br />

■ Change to the humidity control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Humidity<br />

limit OPEN<br />

70%RH<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

The limit "CLOSE" specifies the humidity above which the move command is to<br />

be initiated. Example: The window has already been opened for a certain period<br />

so that the relative humidity in the room has already sunk again. The window is to<br />

be closed again as from a relative humidity of 45%. The setting range is from 1 to<br />

99%RH. If you do not want to evaluate the limit "CLOSE", you can also set the<br />

value "0" (---) here. Proceed as follows in order to change the setting value:<br />

■ Change to the humidity control menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Humidity<br />

limit CLOSE<br />

40%RH<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

TIP<br />

If a sunblind was selected as the connected product, the<br />

displays deviate from those shown here: "UP" is displayed<br />

instead of "CLOSE".<br />

"DOWN" is displayed instead of "OPEN".<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 59


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.6 Timer switch<br />

60<br />

We reserve the right to carry out improvements<br />

The timer switch is a further comfort function of the <strong>Wisotronic</strong> which allows the<br />

sunblind to be moved up or down at a certain moment specifically for each<br />

channel. Move commands can be programmed:<br />

® Together for a complete working week (Monday to Friday)<br />

® For the weekend (Saturday and Sunday).<br />

In case of down movements the subsequent turning up of the slats of a slat<br />

product can be programmed with different slat angles.<br />

The following values can be changed:<br />

Fig. 6-16: Timer switch: Values which can be changed.<br />

TIP<br />

Timer switch<br />

Timer switch ON/OFF<br />

Timer switch Mo-Fr UP<br />

Timer switch Mo-Fr DOWN<br />

Timer switch Sa-Su UP<br />

Timer switch angle DOWN<br />

Only meanfully in case of selected<br />

product type "slat products"<br />

ON/OFF<br />

hrs:min<br />

hrs:min<br />

hrs:min<br />

Timer switch Sa-Su DOWN hrs:min<br />

— 80 ...<br />

+ 80 °<br />

If "Window" was selected as the connected product, the<br />

displays deviate from those shown here: "CLOSE" is displayed<br />

instead of "UP". "OPEN" is displayed instead of "DOWN".<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.6.1 Timer switch ON/OFF<br />

Here you can specify for each channel whether the timer switch is to be activated<br />

or not. Proceed as follows in order to change the setting value:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Timer switch<br />

<strong>Channel</strong> 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Timer switch<br />

ON<br />

— + ¡ | }<br />

■ Activate or de-activate the timer switch by using the buttons — + and then<br />

press the button | (save). The symbol ¡ reminds you that you are carrying<br />

out the settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

TIP<br />

Timer switch<br />

If you want to carry out the settings for further channels, you<br />

can press the button below the channel number to select the<br />

next channel in all the displays with channel designations, for<br />

example:<br />

CH 1 { }<br />

■ You can also change the channels directly by repeatedly pressing the button<br />

below the channel number.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 61


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.6.2 Timer switch Mo - Fr "UP"<br />

6.6.3 Timer switch Mo - Fr<br />

"DOWN"<br />

6.6.4 Timer switch Sa - Su "UP"<br />

62<br />

We reserve the right to carry out improvements<br />

If the sunblind is to be moved up on every day of a working week at the same<br />

time, you can set this switching instant here. The setting range is from 00:01 to<br />

23:59. If you do not wish to move the sunblind up from Mo. to Fr., you can also<br />

set the value "00:00" ( --:--) here. Proceed as follows in order to change the<br />

setting:<br />

■ Change to the timer switch menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Timer switch<br />

Mo - Fr UP<br />

18:00<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

If the sunblind is to be moved down on every day of a working week at the same<br />

time, you can set this switching instant here. The setting range is from 00:01 to<br />

23:59. If you do not wish to move the sunblind down from Mo. to Fr., you can<br />

also set the value "00:00" ( --:--) here. Proceed as follows in order to<br />

change the setting:<br />

■ Change to the timer switch menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Timer switch<br />

Mo - Fr DOWN<br />

8:00<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

If the sunblind is to be moved up on Saturdays and Sundays at the same time,<br />

you can set this switching instant here. The setting range is from 00:01 to 23:59.<br />

If you do not wish to move the sunblind up from Sa. to Su., you can also set the<br />

value "00:00" ( --:--) here. Proceed as follows in order to change the<br />

setting:<br />

■ Change to the timer switch menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Timer switch<br />

Sa - Su UP<br />

18:00<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.6.5 Timer switch Sa - Su<br />

"DOWN"<br />

6.6.6 Slat angle after moving<br />

down<br />

If the sunblind is to be moved down on Saturdays and Sundays at the same time,<br />

you can set this switching instant here. The setting range is from 00:01 to 23:59.<br />

If you do not wish to move the sunblind down from Sa. to Su., you can also set<br />

the value "00:00" ( --:--) here. Proceed as follows in order to change the<br />

setting:<br />

■ Change to the timer switch menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Timer switch<br />

Sa - Su DOWN<br />

8:00<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

This function only makes sense if you have selected a slat product (external<br />

venetian blind or internal venetian blind) as the product type. After moving down<br />

has been completed by the timer switch, the slats are turned open to the set angle.<br />

You can ensure that the sunblind is turned either to let the light through (horizontal,<br />

setting 0°) or to protect against viewing from the outside (for example<br />

+80°).<br />

The following fig. illustrates the setting of the slat angle:<br />

Positive value: Slats are turned outwards<br />

Negative value: Slats are turned inwards<br />

Setting 0°: The slats remain in a horizontal position<br />

Fig. 6-17: Slat angle at external venetian blinds and internal venetian blinds<br />

TIP<br />

Outside<br />

+80° 0°<br />

The product-typical turn time as well as the product-typical<br />

turning angle (refer to Section 8.2.3 to 8.2.5) have to be set<br />

first.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 63<br />

Inside<br />

-80°


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

64<br />

We reserve the right to carry out improvements<br />

Note: The setting range of the slat angle always depends on the settings made in<br />

Section 8.2.3 to 8.2.5. Proceed as follows in order to change the setting:<br />

■ Change to the timer switch menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Timer switch<br />

Angle DOWN<br />

0°<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.7 Comfort timer<br />

The comfort timer is used to activate or de-activate the comfort functions (sun,<br />

humidity, dawn/dusk and temperature control) at a certain time specifically for<br />

each channel. The times can be programmed:<br />

® Together for a complete working week (Monday to Friday)<br />

® For the weekend (Saturday and Sunday).<br />

The comfort timer switches all the comfort functions together. It is not possible<br />

to influence individual functions separately. The timer switch is not affected. It<br />

operates separately from the comfort timer. The following graphics help to explain<br />

how the comfort timer functions: It is easy to recognize that the comfort<br />

functions first have to be "enabled" by the comfort timer before move commands<br />

can be executed. It also becomes clear that manual operation and the timer<br />

switch operate independently.<br />

Comfort functions<br />

Sun control<br />

Dawn/Dusk control<br />

Temperature control<br />

Humidity control<br />

Comfort timer<br />

Timer switch<br />

Timer switch<br />

Manual operation<br />

Manual UP/DOWN<br />

Remote control UP/DOWN<br />

Function dial STOP<br />

Safety functions<br />

Wind monitoring<br />

Rain monitoring<br />

Ice monitoring<br />

Fig. 6-18: OFF phase: Comfort timer has not enabled the comfort functions (comfort<br />

functions are disabled) - the switch is opened. Move commands can only be<br />

initiated by the safety functions, by the timer switch or manually.<br />

Comfort functions<br />

Sun control<br />

Dawn/Dusk control<br />

Temperature control<br />

Humidity control<br />

Comfort timer<br />

Timer switch<br />

Timer switch<br />

Manual operation<br />

Manual UP/DOWN<br />

Remote control UP/DOWN<br />

Function dial STOP<br />

Safety function<br />

Wind monitoring<br />

Rain monitoring<br />

Ice monitoring<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 65<br />

enabled<br />

disabled<br />

Move<br />

command<br />

Move<br />

command<br />

Fig. 6-19: ON phase: The comfort timer has enabled the comfort functions - the switch is<br />

now closed.


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

66<br />

We reserve the right to carry out improvements<br />

Fig. 6-20: Comfort timer de-activated. The comfort functions are always enabled.<br />

TIP<br />

If you do de-activate the comfort timer (if you do not use it),<br />

the comfort functions are always enabled.<br />

The following values can be changed for each channel:<br />

Comfort timer<br />

Comfort functions<br />

Sun control<br />

Dawn/Dusk control<br />

Temperature control<br />

Humidity control<br />

Comfort timer<br />

Timer switch<br />

Timer switch<br />

Manual operation<br />

Manual UP/DOWN<br />

Remote control UP/DOWN<br />

Function dial STOP<br />

Safety function<br />

Wind monitoring<br />

Rain monitoring<br />

Ice monitoring<br />

Comfort timer ON/OFF<br />

Comfort timer<br />

Mo-Fr ON<br />

Comfort timer<br />

Mo-Fr OFF<br />

Comfort timer<br />

Sa-Su ON<br />

Comfort timer<br />

Sa-Su OFF<br />

Fig. 6-20: Comfort timer: Values which can be changed.<br />

ON/OFF<br />

hrs:min<br />

hrs:min<br />

hrs:min<br />

hrs:min<br />

Move<br />

command<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.7.1 Comfort timer ON/OFF<br />

Here you can specify for each channel whether the comfort timer is to be<br />

activated or not. Proceed as follows in order to change the setting value:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Comfort timer<br />

<strong>Channel</strong> 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Comfort timer<br />

OFF<br />

— + ¡ | }<br />

■ Activate or de-activate the timer control by using the buttons — + and then<br />

press the button | (save). The symbol ¡ reminds you that you are carrying<br />

out the settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

TIP<br />

Comfort timer<br />

If you want to carry out the settings for further channels, you<br />

can press the button below the channel number to select the<br />

next channel in all the displays with channel designations, for<br />

example:<br />

CH 1 { }<br />

■ You can also change the channels directly by repeatedly pressing the button<br />

below the channel number.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 67


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.7.2 Comfort timer Mo - Fr<br />

"ON"<br />

6.7.3 Comfort timer Mo - Fr<br />

"OFF"<br />

68<br />

We reserve the right to carry out improvements<br />

Activate the comfort functions for a working week (Monday to Friday) together:<br />

The set time specifies when the comfort functions may be enabled. The setting<br />

range is from 00:01 to 23:59. If you do not wish to activate the comfort timer<br />

from Mo. to Fr., you can also set the value "00:00" ( --:--) here. Proceed as<br />

follows in order to change the setting:<br />

■ Change to the comfort timer menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Comfort timer<br />

Mo - Fr ON<br />

08:00<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

De-activate the comfort functions for a working week (Monday to Friday)<br />

together:<br />

The set time specifies when the comfort functions are to be disabled. The setting<br />

range is from 00:01 to 23:59. If you do not wish to de-activate the comfort timer<br />

from Mo. to Fr., you can also set the value "00:00" ( --:--) here. Proceed as<br />

follows in order to change the setting:<br />

■ Change to the comfort timer menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Comfort timer<br />

Mo - Fr OFF<br />

18:00<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.7.4 Comfort timer Sa - Su<br />

"ON"<br />

6.7.5 Comfort timer Sa - Su<br />

"OFF"<br />

Activate the comfort functions for the weekend (Saturday and Sunday) together:<br />

The set time specifies when the comfort functions may be enabled. The setting<br />

range is from 00:01 to 23:59. If you do not wish to activate the comfort timer<br />

from Sa. to Su., you can also set the value "00:00" ( --:--) here. Proceed as<br />

follows in order to change the setting:<br />

■ Change to the comfort timer menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Comfort timer<br />

Sa - Su ON<br />

08:00<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

De-activate the comfort functions for the weekend (Saturday and Sunday)<br />

together:<br />

The set time specifies when the comfort functions are to be disabled. The setting<br />

range is from 00:01 to 23:59. If you do not wish to de-activate the comfort timer<br />

from Sa. to Su., you can also set the value "00:00" ( --:--) here. Proceed as<br />

follows in order to change the operating mode:<br />

■ Change to the comfort timer menu as described above and select a channel.<br />

Turn the function dial until the following display appears:<br />

Comfort timer<br />

Sa - Su OFF<br />

18:00<br />

— + ¡ | }<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 69


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.8 Manual operation<br />

6.8.1 "Dead man’s mode"<br />

6.8.2 "Time mode"<br />

6.8.3 "Permanent mode"<br />

6.8.4 "Continuous mode"<br />

70<br />

We reserve the right to carry out improvements<br />

In this section you learn how your sun protection can be operated manually. Different<br />

sun protection products also require different control behaviors. For example,<br />

it makes sense at external venetian blinds to be able to adjust the slat angle by<br />

means of a short move command, whereas this does not make much sense at<br />

awnings or roller shutters. Depending on the sun protection product which is to<br />

be controlled, you can choose between the following control modes:<br />

® Dead man’s mode<br />

® Time mode<br />

® Permanent mode<br />

® Continuous mode<br />

In this setting the sunblind moves in the desired direction until the button is<br />

released again.<br />

This control mode is particularly suitable for slat products such as external<br />

venetian blinds or internal venetian blinds: The sunblind moves in the<br />

corresponding direction after the button has been pressed. If the button is<br />

pressed for longer than 2.5 seconds, the control system remains locked. The<br />

button can then be released. The sun protection moves until the set runtime has<br />

expired. In order to de-activate the lock mode and stop the motor, the button with<br />

the opposite move command has to be pressed briefly. The slats are turned up<br />

after the "DOWN" runtime has expired.<br />

If you only want to turn the slats, just press one of the buttons briefly.<br />

If you want the slats to remain closed after moving down, press the "Down"<br />

button once more during the "DOWN" runtime. The sunblind moves until the end<br />

of the runtime - the slats do not turn up.<br />

This control mode is suitable for, for example, roller shutters and cloth products.<br />

The runtime starts immediately after the "Up" button has been pressed. The<br />

sunblind is moved up. If the "Down" button is pressed during the up movement,<br />

the drive stops. The adjustable runtime is started immediately after the "Down"<br />

button has been pressed. The sun protection is moved down. If the "Up" button is<br />

pressed during the down movement, the drive stops.<br />

This control mode is particularly suitable for lighting equipment: Brief pressing of<br />

the "Up" button - the connected device is switched on and the runtime is set to<br />

"endless". Brief pressing of the "Down" button - the device is switched off again.<br />

TIP<br />

The set control mode also operates with the remote control.<br />

The movement can also be stopped by pressing the function<br />

dial.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.8.5 Changing the control<br />

mode<br />

If you have set the connected sunblind correctly (as described in Section 8.2),<br />

advisable setting values have already been set for each of these products, for<br />

example:<br />

® For slat products "Time mode"<br />

® For cloth products and roller shutters "Permanent mode"<br />

We recommend that you do not change these values. If you nevertheless want to<br />

carry out changes because, for example, you have connected other devices (e.g.<br />

windows, facade awnings) to the <strong>Wisotronic</strong>, proceed as follows:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Manual<br />

operation<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Manual<br />

operation<br />

Time mode<br />

— + ¡ | }<br />

■ Change the mode by using the buttons — + and then press the button |<br />

(save). The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 71


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.8.6 Slat angle after moving<br />

down<br />

72<br />

We reserve the right to carry out improvements<br />

This function only makes sense if you have selected a slat product (external<br />

venetian blinds or internal venetian blinds) as the product type. You can specify<br />

how the slats are to be set after the down movement has been completed. You<br />

can ensure that the sunblind is turned either to let the light through (horizontal,<br />

setting 0°) or to view protection (for example +80°). If you move down the<br />

sunblind manually you do not have to wait until the sunblind has reached the<br />

"Down" position in order to set the slats. The <strong>Wisotronic</strong> takes over the task of<br />

turning open the slats for you automatically if a corresponding programming<br />

exists.<br />

The following fig. illustrates the setting of the slat angle:<br />

Positive value: Slats are turned outwards<br />

Negative value: Slats are turned inwards<br />

Setting 0°: The slats remain in a horizontal position<br />

Fig. 6-21: Slat angle at external venetian blinds and internal venetian blinds<br />

TIP<br />

Outside<br />

+80° 0°<br />

The product-typical turn time as well as the product-typical<br />

turning angle (refer to Section 8.2.3 to 8.2.5) have to be set<br />

first.<br />

Note: The setting range of the slat angle depends on the settings made in<br />

Section 8.2.3 to 8.2.5. Proceed as follows in order to change the operating mode:<br />

■ Change to the manual operation menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Manual<br />

angle DOWN<br />

0°<br />

— + ¡ | }<br />

Inside<br />

■ Change the setting values by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

-80°<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.8.7 Reversing the direction of<br />

movement during manual<br />

operation<br />

You can reverse the direction of movement during manual operation specifically<br />

for each channel. This has an effect on the following operating elements:<br />

® Function buttons of the <strong>Wisotronic</strong><br />

® Operating buttons of the remote control<br />

® External operating buttons connected to the <strong>Wisotronic</strong><br />

Example: You want an awning to be moved in and not out when the "Down"<br />

button is pressed.<br />

TIP<br />

ATTENTION<br />

The reversal of the direction of movement ...<br />

only has an effect on the manual operation of the sunblind.<br />

only has an effect on external operating buttons if these are<br />

connected directly to the power unit of the <strong>Wisotronic</strong>.<br />

Never press buttons on your remote control, on the<br />

<strong>Wisotronic</strong> or at local operating elements indiscriminately, if<br />

you cannot see the sunblind.<br />

Proceed as follows in order to reverse the direction of movement:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select a channel (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Manual<br />

operation<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Manual<br />

operation<br />

Time mode<br />

— + | }<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 73


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.8.8 The possibilities of manual<br />

operation<br />

6.8.8.1 Function keys / function<br />

dial<br />

6.8.8.2 Remote control<br />

6.8.8.3 External channel buttons<br />

6.8.8.4 External master switch<br />

74<br />

ATTENTION<br />

We reserve the right to carry out improvements<br />

■ Turn the function dial until the following display appears:<br />

Manual<br />

Direction<br />

Normal<br />

— + ¡ | }<br />

■ Change the direction of movement by using the buttons — + and then<br />

press the button | (save). The symbol ¡ reminds you that you are carrying<br />

out the settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the } button twice consecutively. This completes the<br />

process.<br />

ATTENTION<br />

This function may not be used to reverse the direction of<br />

movement at drives with polarity reversal!<br />

Via the function keys and with the function dial:<br />

® If a comfort function has triggered a move command, it is possible to<br />

counteract or stop it.<br />

® If a safety function has triggered, it is not possible to either counteract or stop<br />

it.<br />

Operation is possible at any time, irrespective of the control system display.<br />

® If a comfort function has triggered a move command, it is possible to<br />

counteract or stop it.<br />

® If a safety function has triggered, it is not possible to either counteract or stop<br />

it.<br />

® As long as a function key at the control system or an external channel button<br />

is pressed, operation with the remote control is not possible.<br />

If external channel buttons are connected to the control system, the sun<br />

protection can be operated via these buttons, irrespective of the display on the<br />

control system.<br />

® If a comfort function has triggered a move command, it is possible to<br />

counteract or stop it.<br />

® If a safety function has triggered, it is not possible to either counteract or stop<br />

it.<br />

This switch is used to operate all the channels simultaneously (dead man’s mode).<br />

® If a comfort function has triggered a move command, it is possible to<br />

counteract or stop it.<br />

® If a safety function has triggered, it is not possible to either counteract or stop<br />

it.<br />

® The latched switch can be latched in the "UP" or "DOWN" position. The sun<br />

protection then remains in this position. The function and external channel<br />

button, the remote control or a comfort function can no longer trigger a move<br />

command.<br />

The safety functions (Wind- Rain- and Ice monitoring) can<br />

nevertheless move your sun protection!<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.9 Learning/deleting the<br />

remote control<br />

6.9.1 Displaying the assignment<br />

The <strong>Wisotronic</strong> <strong>dialog</strong> is supplied with an 8-channel radio remote control. This can<br />

be used to operate the connected sunblind. Read the corresponding user<br />

instructions before using the remote control for the first time. If you want to use<br />

several remote controls, you can teach several remote controls, assign channels<br />

or delete remote controls.<br />

The assignment of all the remote controls "known" (learned) to the <strong>Wisotronic</strong> can<br />

be displayed specifically for the channels:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the desired channel of the <strong>Wisotronic</strong> (in this example <strong>Channel</strong> 1). The<br />

following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Remote control<br />

learn/delete<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Remote control<br />

memory<br />

1:ID 09747 C1<br />

— + ¡ | }<br />

The third line has the following meaning here:<br />

Fig. 6-22: Identification of remote controls<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 75<br />

1<br />

2<br />

3<br />

1:ID 09747 C1


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

76<br />

We reserve the right to carry out improvements<br />

1. Number of the learned memory space. You can have all the learned remote<br />

controls displayed consecutively by pressing the — + buttons. 16 remote<br />

controls can be taught for each channel of the <strong>Wisotronic</strong>. If the line is empty<br />

after the colon, the place is still free. A new remote control can be learned<br />

here.<br />

2. ID (code number) of the learned remote control.<br />

3. <strong>Channel</strong> of the learned remote control. If you have learned an 8-channel<br />

remote control, the channel of the remote control which you have assigned is<br />

displayed here.<br />

TIP<br />

If you want to carry out the settings for further channels, you<br />

can press the button below the channel number to select the<br />

next channel in all the displays with channel designations, for<br />

example:<br />

Remote control<br />

learn/delete<br />

CH 1 { }<br />

■ You can also change the channels directly by repeatedly pressing the button<br />

below the channel number.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.9.2 Learning a remote control<br />

6.9.3 Building a group<br />

If you learn an 8-channel remote control for the <strong>Wisotronic</strong>, you must first select<br />

the channel which you want to learn at the remote control. You have to imagine<br />

that each individual channel can be viewed as a separate remote control. This<br />

recognizes the <strong>Wisotronic</strong> automatically. You can assign up to 16 remote controls<br />

to each channel of the <strong>Wisotronic</strong>. The learn procedure essentially consists of four<br />

steps:<br />

■ Selecting a channel of the <strong>Wisotronic</strong>.<br />

■ Selecting a channel at the remote control.<br />

■ Pressing the learn button at the remote control. The remote control has been<br />

learned.<br />

■ Pressing the save button | of the <strong>Wisotronic</strong>. The remote control has been<br />

saved.<br />

Example: You have a <strong>Wisotronic</strong> 3-channel <strong>EWFS</strong> and an 8-channel remote control.<br />

You want to<br />

® Operate <strong>Channel</strong> 1 of the <strong>Wisotronic</strong> with <strong>Channel</strong> 1 of the remote control<br />

® Operate <strong>Channel</strong> 2 of the <strong>Wisotronic</strong> with <strong>Channel</strong> 2 of the remote control<br />

® Operate <strong>Channel</strong> 3 of the <strong>Wisotronic</strong> with <strong>Channel</strong> 3 of the remote control<br />

® Operate <strong>Channel</strong> 1, 2 and 3 of the <strong>Wisotronic</strong> together with <strong>Channel</strong> 4 of the<br />

remote control.<br />

Procedure:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the desired channel of the <strong>Wisotronic</strong> (in this example first <strong>Channel</strong> 1).<br />

The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Remote control<br />

learn/delete<br />

CH 1 { }<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 77


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

78<br />

We reserve the right to carry out improvements<br />

■ Select the menu item (button {). The following display appears:<br />

Remote control<br />

memory<br />

1:ID 09747 C1<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Remote control<br />

learn<br />

1:ID 09747 C1<br />

— + ¡ | }<br />

■ Now select <strong>Channel</strong> 1 on your remote control and then press the "L" button on<br />

your remote control. As soon as the display of the <strong>Wisotronic</strong> has changed,<br />

the remote control has been recognized. At the same time the learned<br />

channel and the code number of the remote control are displayed. Now press<br />

the button | (save). The remote control has been saved. <strong>Channel</strong> 1 of the<br />

<strong>Wisotronic</strong> can now be operated with <strong>Channel</strong> 1 of the remote control.<br />

■ Now repeat the steps shown above for <strong>Channel</strong> 2 (also learn <strong>Channel</strong> 2 of the<br />

remote control to memory space 2 and <strong>Channel</strong> 3 of the remote control to<br />

memory space 3)<br />

Now learn <strong>Channel</strong> 4 of the remote control on all three channels of the<br />

<strong>Wisotronic</strong>. To do so, call up the following display:<br />

Remote control<br />

learn<br />

1:ID 09740 C1<br />

— + ¡ | }<br />

■ Press the button + (in order to select memory space 2). The following display<br />

is shown:<br />

Remote control<br />

learn<br />

2:<br />

— + ¡ | }<br />

■ Now select <strong>Channel</strong> 4 on your remote control and then press the "L" button on<br />

your remote control. As soon as the display of the <strong>Wisotronic</strong> has changed,<br />

the remote control has been recognized. At the same time the learned<br />

channel and the code number of the remote control are displayed. Now press<br />

the button |(save). The remote control has been saved. <strong>Channel</strong> 1 of the<br />

<strong>Wisotronic</strong> can now also be operated with <strong>Channel</strong> 4 of the remote control.<br />

■ Now repeat the steps shown above for <strong>Channel</strong> 2 (also learn <strong>Channel</strong> 4 of the<br />

remote control to memory space 2)<br />

■ Now repeat the steps shown above for <strong>Channel</strong> 3 (also learn <strong>Channel</strong> 4 of the<br />

remote control to memory space 2)<br />

TIP<br />

If, as is shown in this example, a remote control is already<br />

displayed in the display, this is overwritten during saving. You<br />

can learn up to 16 different remote controls to each channel of<br />

the <strong>Wisotronic</strong>, if required.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.9.4 Deleting a remote control<br />

You can delete an individual remote control memory.<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the desired channel of the <strong>Wisotronic</strong> (in this example <strong>Channel</strong> 1). The<br />

following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Remote control<br />

learn/delete<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Remote control<br />

memory<br />

1:ID 09747 C1<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Remote control<br />

delete<br />

1:ID 09747 C1<br />

— + ¡ | }<br />

■ The symbol ¡ reminds you that you are carrying out the settings for <strong>Channel</strong><br />

1. Select the remote control to be deleted by using the buttons — + and<br />

then press the button | (save). The remote control has been deleted. Press<br />

the } button twice successively. This completes the process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 79


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.9.5 Deleting all the remote<br />

controls<br />

80<br />

We reserve the right to carry out improvements<br />

You can delete all the remote controls which were learned to a channel of the<br />

<strong>Wisotronic</strong> together. Example: On <strong>Channel</strong> 1 you have learned different remote<br />

controls on the memory spaces "1" to "5". You do not have to delete each<br />

individual memory space separately. Proceed as follows:<br />

■ Change to the remote control settings menu as described above and select a<br />

channel. Turn the function dial until the following display appears:<br />

Remote control<br />

memory<br />

1:ID 09747 C1<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Remote control<br />

Delete all<br />

1:ID 09747 C1<br />

— + ¡ | }<br />

■ The symbol ¡ reminds you that you are carrying out the settings for <strong>Channel</strong><br />

1. Now press the button |(save). All the remote controls taught to this<br />

channel have been deleted. Press the } button twice successively. This<br />

completes the process.<br />

TIP<br />

This procedure does not delete all the remote controls, but, as<br />

is shown in this example, only the remote controls taught to<br />

<strong>Channel</strong> 1. If the remote controls taught to <strong>Channel</strong>s 2 and 3<br />

are to be deleted as well, repeat the steps specified above for<br />

the channels and .<br />

2 3<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.10 Resetting alerts<br />

6.10.1 Resetting the ice alert<br />

manually<br />

In case of an ice alert those channels at which the ice monitoring function (service<br />

settings) has been activated are blocked, so that your sunblind cannot be moved<br />

either manually or automatically. This ice alert remains stored in the <strong>Wisotronic</strong><br />

until it has been reset manually or automatically. The function "Ice alert reset" has<br />

to be used to reset an active ice alert, after you have convinced yourself that<br />

there is no danger of damage to the controlled sunblind.<br />

TIP<br />

CAUTION<br />

An ice alert can be reset either manually or automatically. This<br />

section explains how the ice alert is reset manually. The steps<br />

required to reset an ice alert automatically are explained in<br />

Section 8.4.<br />

First ensure that your sunblind cannot be damaged by the<br />

movement: External venetian blinds and roller shutters,<br />

cassette awnings and conservatory awnings can be frozen<br />

tight. If you nevertheless operate them, damage to property<br />

may result! If the sunblind is operated during icing, all<br />

guarantees and liabilities expire!<br />

To reset an ice alert manually:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the desired channel of the <strong>Wisotronic</strong> at which an ice alert is active (in<br />

this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Reset<br />

alerts<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Ice alert<br />

man. reset<br />

NO<br />

— + ¡ | }<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 81


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

6.10.2 Enabling the ice alert<br />

again<br />

82<br />

We reserve the right to carry out improvements<br />

■ The symbol ¡ reminds you that you are carrying out the settings for <strong>Channel</strong><br />

1. Press the button +. The text<br />

CAUTION! is displayed. You now have to press the button + as often<br />

as is required to have read the following text completely: CAUTION!<br />

Resetting the ice alert enables the control<br />

of the channel. Movement commands<br />

could destroy frozen windows or<br />

sunblinds. The user is responsible for<br />

damage to frozen windows or sunblinds.<br />

RESET? Yes<br />

Ice alert<br />

man. reset<br />

YES<br />

— + ¡ | }<br />

■ Now press the button |(save). The ice alert has now been reset. The text<br />

Ice alert enable is displayed and the sunblind can be operated<br />

again. Then press the } button twice successively. This completes the<br />

process.<br />

CAUTION<br />

The ice alert now remains reset until the conditions for an ice<br />

alert exist again: If the external temperature drops below the<br />

set limit AND rain falls, the ice alert is activated again.<br />

We therefore recommend that you enable the ice alert in due<br />

course, in particular if your sunblind is not observed<br />

constantly (for example in your absence).<br />

An ice alert is saved in the <strong>Wisotronic</strong> for the duration of the ice condition. An<br />

example: Because the external temperature dropped below the freezing point<br />

during the night and freezing rain fell briefly afterwards, the ice alert is triggered,<br />

the sunblind is moved up and operation blocked. When you wanted to operate<br />

your sunblind the next morning, you found the ice alert. Because you wanted to<br />

operate the sunblind nevertheless, you reset the ice alert and have, for example,<br />

moved your external venetian blinds down. In the evening you want to enable the<br />

ice alert again, because the frost still exists. Because the ice condition continues<br />

to exist, the sunblind moves up again immediately after the ice alert has been<br />

enabled!<br />

CAUTION<br />

Therefore first ensure that your sun protection cannot be<br />

damaged by the movement: External venetian blinds and<br />

roller shutters, cassette awnings and conservatory awnings<br />

can be frozen tight in their guide rails. If the ice alert is<br />

enabled nevertheless while frost continues, damage to<br />

property may result! If the sunblind is operated during icing,<br />

all guarantees and liabilities expire!<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

To enable an ice alert again:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the desired channel of the <strong>Wisotronic</strong> at which you have reset the ice<br />

alert (in this example <strong>Channel</strong> 1). The following display is shown:<br />

Sun<br />

control<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Reset<br />

alerts<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Ice alert<br />

enable<br />

NO<br />

— + ¡ | }<br />

■ The symbol ¡ reminds you that you are carrying out the settings for <strong>Channel</strong><br />

1. Press the button +. The text<br />

CAUTION! is displayed. You now have to press the button + as often<br />

as is required to have read the following text completely: CAUTION!<br />

Enabling the ice alert enables ice<br />

monitoring of the channel. Movement<br />

commands caused by an Ice Alert could<br />

damage frozen blinds or windows. The<br />

user<br />

YES<br />

is responsible for damage. ENABLE?<br />

Ice alert<br />

enable<br />

YES<br />

— + ¡ | }<br />

■ Now press the button | (save). The ice alert has now been enabled again.<br />

The text ice alert man. reset is displayed and the sunblind<br />

can be operated again. Then press the } button twice successively. This<br />

completes the process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 83


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

7. Non-channeldependent<br />

user<br />

settings<br />

7.1 Setting the time and date<br />

84<br />

We reserve the right to carry out improvements<br />

If the <strong>Wisotronic</strong> was commissioned by one of our specialist partners and adapted<br />

optimally to your sunblind, no further settings are required after the supply voltage<br />

has been switched on.<br />

If the date and time are not displayed correctly nevertheless, you can correct this<br />

simply:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the menu item 0 . The following display appears:<br />

Date/Time<br />

{ }<br />

■ The following date and time displays are examples and may deviate from the<br />

display on your <strong>Wisotronic</strong>. Select the menu item (button {). The following<br />

display appears:<br />

Date/Time<br />

Time<br />

15:00<br />

— + | }<br />

■ Set the current time by using the buttons — + and then press the button<br />

|(save).<br />

■ Turn the function dial until the following display appears:<br />

Date/Time<br />

Year<br />

2004<br />

— + | }<br />

■ Set the current year by using the buttons — + and then press the button<br />

|(save).<br />

■ Turn the function dial until the following display appears:<br />

Date/Time<br />

Month<br />

July<br />

— + | }<br />

■ Set the current month by using the buttons — + and then press the button<br />

|(save)<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

■ Turn the function dial until the following display appears:<br />

Date/Time<br />

Day<br />

23<br />

— + | }<br />

■ Set the current day by using the buttons — + and then press the button<br />

| (save).<br />

■ Turn the function dial until the following display appears:<br />

Date/Time<br />

Weekday<br />

Friday<br />

— + | }<br />

■ Set the current weekday by using the buttons — + and then press the<br />

button | (save). Quit the setting menu by pressing the } button. This<br />

completes the process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 85


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

7.2 Display contrast<br />

86<br />

We reserve the right to carry out improvements<br />

You can adjust the contrast of the display to your requirements: If you prefer a<br />

low-contrast, unobtrusive display, set a low value here. If you prefer a high<br />

contrast, which also allows the display to be read from a larger distance, set a<br />

higher value. Proceed as follows in order to change the setting value:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the function 0 (non-channel-dependent settings). The following display<br />

appears:<br />

Date/Time<br />

{ }<br />

■ Turn the function dial until the following display appears:<br />

Display<br />

{ }<br />

■ Select this menu item (button {). The following display appears:<br />

Display<br />

Contrast<br />

50%<br />

— + | }<br />

■ Adjust the value by using the buttons — + until you like the setting. Then<br />

press the button | (save). If you want to exit the menu without saving the<br />

changes, press the }button twice consecutively. This completes the process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

7.3 Dimming the backlight of<br />

the display<br />

You can adjust the backlight brightness of the display while non-operative to your<br />

requirements: If you prefer an unobtrusive display, which shines unobtrusively<br />

and does not blind during darkness, set a low value. If you prefer a bright display<br />

which also allows reading at a higher ambient brightness, set a higher value.<br />

Proceed as follows in order to change the setting value:<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the function 0 (non-channel-dependent settings). The following display<br />

appears:<br />

Date/Time<br />

{ }<br />

■ Turn the function dial until the following display appears:<br />

Display<br />

{ }<br />

■ Select this menu item (button {). The following display appears:<br />

Display<br />

Contrast<br />

50%<br />

— + | }<br />

■ Turn the function dial until the following display appears:<br />

Display backlight<br />

dimmed<br />

50%<br />

— + | }<br />

■ Change the value by using the buttons — + and then press the button<br />

|(save). If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

TIP<br />

When the <strong>Wisotronic</strong> is operated, the display switches to the<br />

maximum backlight brightness. If it is not operated for a<br />

duration of three minutes, the display switches over to the<br />

dimmed brightness set by you.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 87


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

7.4 Reset "Wind Sensor<br />

Failure" alert<br />

88<br />

We reserve the right to carry out improvements<br />

If the sensor failure check is activated for the "Wind" sensor (refer to Section<br />

9.1.2), the following text can be displayed:<br />

Alert<br />

Wind sensor<br />

H! T H #T<br />

In this case the sunblind of all the channels with activated wind monitoring is<br />

moved up automatically and can no longer be operated. This alert has to be reset<br />

manually.<br />

■ Turn the function dial until the following display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the function 0 (non-channel-dependent settings). The following display<br />

appears:<br />

Date/Time<br />

{ }<br />

■ Turn the function dial until the following display appears:<br />

Reset<br />

alerts<br />

{ }<br />

■ Select this menu item (button {). The following display appears:<br />

Reset alert<br />

wind sensor<br />

test<br />

| }<br />

■ Press the button | (save). This resets the alert and the system can be<br />

operated again. If you want to exit the menu without saving the changes,<br />

press the }button twice consecutively. This completes the process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8. <strong>Channel</strong>-dependent<br />

service settings<br />

You can modify the service settings in order to adapt the <strong>Wisotronic</strong> <strong>dialog</strong><br />

optimally to your requirements. There you can carry out product settings,<br />

influence the wind and ice monitoring functions and assign sensors to the<br />

individual channels. Normally you do not have to change anything at these values.<br />

All the settings have already been carried out during commissioning by your sun<br />

protection specialist partners.<br />

CAUTION<br />

Changing these settings can impair the safety of the system<br />

or reduce its effectiveness! If you are not sure what effect a<br />

change has, consult an expert. In order to protect the system<br />

against unauthorized or unintentional modifications, access<br />

to the service settings is protected by a password.<br />

Service settings<br />

Product<br />

Wind monitoring<br />

Ice monitoring<br />

Assign sensors<br />

Fig. 7-1: <strong>Channel</strong>-dependent service settings with submenus.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 89<br />

8.2<br />

8.3<br />

8.4<br />

8.5


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.1 Password<br />

90<br />

We reserve the right to carry out improvements<br />

You first to have enter the password in order to open the service settings:<br />

■ Turn the function dial until the following display appears:<br />

Service<br />

settings<br />

1 2 3 0<br />

■ Select the desired channel of the <strong>Wisotronic</strong> (in this example <strong>Channel</strong> 1). The<br />

following display is shown:<br />

Enter<br />

password<br />

0000<br />

* + | }<br />

You now have to enter a password (if you have already entered a password, this<br />

menu is no longer displayed. Instead the "Product" menu is displayed<br />

immediately). Enter your password, if you don´t know your password ask your<br />

specialist dealer.<br />

■ Press the button + momentarily until the first number of the password is<br />

displayed at the first position. Change to the next position by pressing the<br />

button * momentarily. Enter all the numbers by the same method and then<br />

press the button {. The following display appears:<br />

Product<br />

CH 1 { }<br />

If the incorrect password was entered, 0000 is displayed again and you have<br />

to enter the password again.<br />

■ Select this menu item (button {). The following display appears:<br />

Product<br />

Product type<br />

Conserv. awning<br />

— + ¡ | }<br />

You can now call up the individual menus with the function dial.<br />

TIP<br />

After you have carried out your settings and have completed<br />

them, de-energize the device for approx. 5 seconds and then<br />

switch it on again. This blocks the access to the service<br />

settings again so that they can only be opened again by<br />

entering the password. This ensures that unauthorized<br />

persons do not have access to the service settings!<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.2 The "Product" menu In this menu you can set the sunblind (slat products, cloth products, roller<br />

shutters, etc.) used separately for each channel and modify individual parameters<br />

such as the runtime, turn time, etc. . The following values can be changed:<br />

Fig. 7-2: The "Product" menu: Values which can be changed.<br />

Each of these products has different properties. This means that they also react<br />

differently to wind, require other turn times and runtimes or are perhaps<br />

positioned inside and therefore do not require rain and wind protection, etc.. So<br />

that you do not have to enter all the product-dependent setting values and limits<br />

whenever you set a product in the <strong>Wisotronic</strong>, the <strong>Wisotronic</strong> <strong>dialog</strong> carries out<br />

this work for you. The required values are already stored for many products. All<br />

the product-dependent setting values are programmed by only pressing a button.<br />

The following settings are possible:<br />

Artic.arm awning<br />

Conserv. awning<br />

Outside V.blind<br />

Roller shutter<br />

Pleated blind<br />

Inside V.blind<br />

Window<br />

TIP<br />

Product<br />

Product type<br />

Runtime UP<br />

Runtime DOWN<br />

Turn time<br />

Only meanfully in case of selected<br />

product type "slat products"<br />

Product slat angle max.<br />

Only meanfully in case of selected<br />

product type "slat products"<br />

Product slat angle min.<br />

Only meanfully in case of selected<br />

product type "slat products"<br />

Product control type<br />

Select<br />

product<br />

type<br />

0...99<br />

Minutes<br />

0...99<br />

Minutes<br />

0 ...<br />

9.9 Sec<br />

— 128 ..<br />

+ 126 °<br />

— 128 ..<br />

+ 126 °<br />

Drive<br />

with MCU<br />

/direct<br />

Product lock switch ON/OFF<br />

The tables on the next pages provide information about the<br />

values which are set automatically when the product type is<br />

changed. If you want to record your own settings, you can<br />

enter your values in the two empty tables. This provides you<br />

with an overview of your personal settings.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 91


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

Setting step <strong>Unit</strong><br />

Sun control<br />

Fig. 7-3: Factory settings (User settings)<br />

92<br />

Articulated<br />

arm<br />

awning<br />

We reserve the right to carry out improvements<br />

Conserv.-/<br />

Facadeawning<br />

Outside<br />

venetian<br />

blind<br />

<strong>Channel</strong>-dependent user settings<br />

Roller<br />

shutter<br />

Pleated<br />

blind<br />

Inside<br />

venetian<br />

blind<br />

Sun control ON/OFF ON/OFF ON ON ON OFF ON ON OFF<br />

Window<br />

Limit UP klx 30 30 15 30 30 30 30<br />

Delay UP min 10 10 20 10 10 10 10<br />

Limit OPEN klx --- --- --- --- --- --- ---<br />

Delay OPEN min 0 0 0 0 0 0 0<br />

Limit DOWN klx 50 50 35 50 50 50 50<br />

Delay DOWN min 5 5 2 5 5 5 5<br />

Position DOWN % 100 100 100 100 100 100 100<br />

Angle DOWN<br />

Dawn/dusk control<br />

Degrees 0 0 38 0 0 38 0<br />

Dawn/Dusk control ON/OFF OFF OFF OFF ON OFF OFF OFF<br />

Limit UP lx 30 30 30 30 30 30 30<br />

Limit DOWN lx 80 80 80 80 80 80 80<br />

Angle DOWN<br />

Temperature control<br />

Degrees 0 0 80 0 0 80 0<br />

Temperature control ON/OFF OFF OFF OFF OFF OFF OFF OFF<br />

Operating mode<br />

Direct control<br />

Enable sun<br />

Difference Temp.<br />

Direct control Direct control Direct control Direct control Direct control Direct control<br />

Difference<br />

Temp.<br />

Limit UP/OFF ° C 22 22 22 22 22 22 22<br />

Limit DOWN/ON ° C 26 26 26 26 26 26 26<br />

Difference temp.<br />

limit UP<br />

° C 2 2 2 2 2 2 2<br />

Difference temp. limit<br />

DOWN<br />

° C 5 5 5 5 5 5 5<br />

Rain monitoring<br />

Rain monitoring<br />

Humidity control<br />

ON/OFF ON ON OFF OFF OFF OFF ON<br />

Humidity control ON/OFF OFF OFF OFF OFF OFF OFF OFF<br />

Limit UP %RH 40 40 40 40 40 40 40<br />

Limit DOWN<br />

Timer switch<br />

%RH 70 70 70 70 70 70 70<br />

Timer switch ON/OFF OFF OFF OFF OFF OFF OFF OFF<br />

Mo - Fr UP hrs:min 18:00 18:00 8:00 8:00 8:00 8:00 18:00<br />

Mo - Fr DOWN hrs:min 8:00 8:00 22:00 22:00 22:00 22:00 8:00<br />

Sa - Su UP hrs:min 18:00 18:00 8:00 8:00 8:00 8:00 18:00<br />

Sa - Su DOWN hrs:min 8:00 8:00 22:00 22:00 22:00 22:00 8:00<br />

Angle DOWN<br />

Comfort timer<br />

Degrees 0 0 80 0 0 80 0<br />

Comfort timer ON/OFF OFF OFF OFF OFF OFF OFF OFF<br />

Mo - Fr ON hrs:min 8:00 8:00 8:00 8:00 8:00 8:00 8:00<br />

Mo - Fr OFF hrs:min 18:00 22:00 22:00 22:00 22:00 22:00 18:00<br />

Sa - So ON hrs:min 8:00 8:00 8:00 8:00 8:00 8:00 8:00<br />

Sa - So OFF<br />

Manual operation<br />

hrs:min 18:00 22:00 22:00 22:00 22:00 22:00 18:00<br />

Mode<br />

Dead man´s mode<br />

Time mode<br />

Permanent mode<br />

Continuous mode<br />

Permanent mode Permanent mode Time mode Permanent mode Permanent mode Time Mode Permanent mode<br />

Angle DOWN Degrees 0 0 38 0 0 38 0<br />

Manual direction Normal / reversed Normal<br />

Non-channel-dependent user settings<br />

Display<br />

Contrast % 40<br />

Backlight dimmed % 50<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

Setting step <strong>Unit</strong><br />

Product<br />

Product type -<br />

Fig.7-4: Factory settings (Service settings)<br />

Articulated<br />

arm<br />

awning<br />

Articulated<br />

arm<br />

awning<br />

Conserv.-/<br />

Facadeawning<br />

Outside<br />

venetian<br />

blind<br />

<strong>Channel</strong>-dependent service settings<br />

Conservatory<br />

awning<br />

Outside<br />

venetian<br />

blind<br />

Roller<br />

shutter<br />

Pleated<br />

blind<br />

Roller shutter Pleated blind<br />

Inside<br />

venetian<br />

blind<br />

Inside<br />

venetian<br />

blind<br />

Window<br />

Runtime UP min:sec 1:00 2:00 2:30 2:30 1:20 2:30 1:00<br />

Runtime DOWN min:sec 1:00 2:00 2:30 2:30 1:20 2:30 1:00<br />

Turn time sec 0 0 1,6 0 0 1,2 0<br />

Slat angle max. Degrees 0 0 80 0 0 80 0<br />

Slat angle min. Degrees 0 0 -80 0 0 -80 0<br />

<strong>Control</strong> type<br />

Drive direct/<br />

with MCU<br />

Drive with<br />

MCU<br />

Drive with<br />

MCU<br />

Drive with<br />

MCU<br />

Drive with<br />

MCU<br />

Drive with<br />

MCU<br />

Drive with<br />

MCU<br />

Lock switch OFF OFF OFF OFF OFF OFF OFF OFF<br />

Window<br />

Drive with<br />

MCU<br />

Wind monitoring<br />

Wind monitoring ON/OFF ON ON ON OFF OFF OFF ON<br />

Limit UP m/s 8 10 12 --- --- --- 6<br />

Delay UP sec 1 1 5 0 0 0 5<br />

Delay OFF<br />

Ice monitoring<br />

min 10 10 10 0 0 0 10<br />

Ice monitoring ON/OFF OFF OFF OFF OFF OFF OFF OFF<br />

Limit UP ° C 3 3 3 3 3 3 3<br />

Ice alert automatic reset<br />

Allocation sensor<br />

ON/OFF ON ON ON ON<br />

<strong>Channel</strong> 1:1<br />

ON ON ON<br />

Photo sensor 1/2/3/ 1-3<br />

Integrated/<br />

Inside 1<br />

<strong>Channel</strong> 2:2<br />

<strong>Channel</strong> 3:3<br />

Temperature sensor Inside 2<br />

Inside 3<br />

Outdoor<br />

Integrated<br />

Non-channel-dependent service settings<br />

System settings<br />

Integrated temperature<br />

offset<br />

° C 2<br />

Duration wind sensor<br />

test<br />

Hrs 99<br />

Software version - Dependent on the installed software<br />

Language<br />

Language Deutsch/English Deutsch<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 93


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

Fig. 7-5: Custom settings (User settings)<br />

94<br />

We reserve the right to carry out improvements<br />

Setting step <strong>Unit</strong> <strong>Channel</strong> 1 <strong>Channel</strong> 2 <strong>Channel</strong> 3<br />

<strong>Channel</strong>-dependent user settings<br />

Sun control<br />

Sun control<br />

ON/OFF<br />

ON/OFF<br />

Limit UP klx<br />

Delay UP min<br />

Limit OPEN klx<br />

Delay OPEN min<br />

Limit DOWN klx<br />

Delay DOWN min<br />

Position DOWN %<br />

Angle DOWN<br />

Dawn/dusk control<br />

Degrees<br />

Dawn/Dusk control ON/OFF<br />

Limit UP lx<br />

Limit DOWN lx<br />

Angle DOWN<br />

Temperature control<br />

Degrees<br />

Temperature contropl ON/OFF<br />

Direct control<br />

Operating mode<br />

Enable sun<br />

Difference Temp.<br />

Limit UP/OFF ° C<br />

Limit DOWN/ON ° C<br />

Difference temp.<br />

limit UP<br />

° C<br />

Difference temp. limit<br />

DOWN<br />

Rain monitoring<br />

° C<br />

Rain monitoring<br />

Humidity control<br />

ON/OFF<br />

Humidity control ON/OFF<br />

Limit UP %RH<br />

Limit DOWN<br />

Timer switch<br />

%RH<br />

Timer switch ON/OFF<br />

Mo - Fr UP hrs:min<br />

Mo - Fr DOWN hrs:min<br />

Sa - Su UP hrs:min<br />

Sa - Su DOWN hrs:min<br />

Angle DOWN<br />

Comfort timer<br />

Degrees<br />

Comfort timer ON/OFF<br />

Mo - Fr ON hrs:min<br />

Mo - Fr OFF hrs:min<br />

Sa - Su ON hrs:min<br />

Sa - Su OFF<br />

Manual operating<br />

hrs:min<br />

Dead man´s mode<br />

Operating mode<br />

Time mode<br />

Permanent mode<br />

Continuous mode<br />

Angle DOWN Degrees<br />

Direction of movement Normal / reversed<br />

Non-channel-dependent user settings<br />

Display<br />

Contrast %<br />

Backlight dimmed %<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

Fig. 7-6: Custom settings (Service settings)<br />

Setting step <strong>Unit</strong> <strong>Channel</strong> 1 <strong>Channel</strong> 2 <strong>Channel</strong> 3<br />

Product<br />

Articulated arm<br />

awning<br />

Conservatory<br />

awning<br />

Outside venetian<br />

Product type<br />

blind<br />

Roller shutter<br />

Pleated blind<br />

Inside venetian<br />

blind<br />

Window<br />

Runtime UP min:sec<br />

Runtime DOWN min:sec<br />

Turn time sec<br />

Slat angle max. Degrees<br />

Slat angle min. Degrees<br />

<strong>Control</strong> type<br />

<strong>Channel</strong>-dependent service settings<br />

Drive direct/<br />

with MCU<br />

Lock switch ON/OFF<br />

Wind monitoring<br />

Wind monitoring ON/OFF<br />

Limit UP m/s<br />

Delay UP sec<br />

Delay OFF<br />

Ice monitoring<br />

min<br />

Ice monitoring ON/OFF<br />

Limit UP ° C<br />

Ice alert automatic reset<br />

Allocation sensors<br />

ON/OFF<br />

Photo sensor 1/2/3/ 1-3<br />

Integrated/<br />

Inside 1<br />

Temperature sensor Inside 2<br />

Inside 3<br />

Outdoor<br />

Non-channel-dependent service settings<br />

System settings<br />

Integrated temperature<br />

° C<br />

offset<br />

Duration wind sensor<br />

hrs<br />

test<br />

Software version -<br />

Language<br />

Language Deutsch/English<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 95


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.2.1 Product type<br />

8.2.2 Runtimes<br />

96<br />

We reserve the right to carry out improvements<br />

Proceed as follows in order to change the product type specifically for each<br />

channel:<br />

■ Change to the product settings menu as described above and select a<br />

channel. The following display is shown:<br />

Product<br />

product type<br />

Conserv. awning<br />

— + ¡ | }<br />

TIP<br />

When you have selected the product type and saved it, the<br />

values from the two tables shown at the front are set<br />

automatically. If you have carried out changes to the settings<br />

beforehand, your values are overwritten completely during<br />

saving (this does not apply to the date and time or remote<br />

controls already learned).<br />

■ Change the product type by using the buttons — + and then press the<br />

button | (save). The symbol ¡ reminds you that you are carrying out the<br />

settings for <strong>Channel</strong> 1. If you want to exit the menu without saving the<br />

changes, press the }button twice consecutively. This completes the<br />

process.<br />

You have now changed the product type and together with this setting step the<br />

<strong>Wisotronic</strong> has carried out all the sensible settings for the sun protection product<br />

used. As a rule you do not have to carry out any further settings, unless you wish<br />

to optimize the control behavior further.<br />

The runtime of a sunblind is the time which the sunblind requires in order to move<br />

from one end setting to the other (for example from top to bottom). If a sun<br />

protection product is set as described above, sensible runtime and turn times are<br />

also set for this product in the <strong>Wisotronic</strong>. Normally it is not necessary to<br />

intervene here. This section describes how you can nevertheless carry out these<br />

adjustments.<br />

Experience shows that the runtimes of sunblind products differ. Thus a roller<br />

shutter with 150 cm length required a much shorter runtime than a folding arm<br />

awning with 300 cm extension. These runtimes can be adjusted to the connected<br />

product down to the second at the <strong>Wisotronic</strong>. You can also set separate runtimes<br />

for "UP" and "DOWN" because a sunblind requires more time to move up than to<br />

move down. Note: The runtimes are set to mean values in our works.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.2.2.1 Runtime "UP"<br />

8.2.2.2 Runtime "DOWN"<br />

The setting range is from 0 - 99 minutes. Proceed as follows in order to change<br />

the runtime "UP":<br />

■ Change to the product settings menu as described above and select a<br />

channel. The following display is shown:<br />

Product<br />

product type<br />

Outside V.blind<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Product<br />

runtime UP<br />

02:30 mm:ss<br />

— + ¡ | }<br />

■ Change the runtime by using the buttons — + and then press the button<br />

|(save). The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

The setting range is from 0 - 99 minutes. Proceed as follows in order to change<br />

the runtime "DOWN":<br />

■ Change to the product settings menu as described above and select a<br />

channel. The following display is shown:<br />

Product<br />

product type<br />

Outside V.blind<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Product<br />

runtime DOWN<br />

02:30 mm:ss<br />

— + ¡ | }<br />

■ Change the runtime by using the buttons — + and then press the button<br />

|(save). The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

TIP<br />

Always adapt the runtime as precisely as possible to the<br />

actual runtime of the sunblind. If you want to stop the<br />

sunblind automatically in a specific position by the sun control,<br />

do not use the runtime to this purpose, but rather the<br />

function "Position DOWN" as described in Section 6.1.4.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 97


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.2.3 Turn time<br />

98<br />

We reserve the right to carry out improvements<br />

The slat angle can be adjusted at outside venetian blinds and internal venetian<br />

blinds in order to change or optimize the light incidence in a room.<br />

The following fig. illustrates the setting of the slat angle:<br />

Positive value: Slats are turned outwards<br />

Negative value: Slats are turned inwards<br />

Setting 0°: The slats remain in a horizontal position<br />

Outside<br />

+80° 0°<br />

Inside<br />

Fig. 7-7: Slat angle at external venetian blinds and internal venetian blinds<br />

It is obvious that a drive motor requires a certain time when turning the slat until<br />

(as in our simple example) the slats have been turned from the position "+80°" to<br />

the position "-80°". In addition this turn time differs for various product types. For<br />

example, an internal venetian blind requires approximately 0.5 seconds, whereas<br />

this procedure can also take 1.6 seconds for an outside venetian blind, type<br />

E80A6. If this turn time is known, you only have to store it once in your<br />

<strong>Wisotronic</strong> together with the minimum and maximum possible turning angle.<br />

Afterwards the turning angles can be specified by simply entering angle degrees.<br />

Time-consuming determining of turn times and experimenting are superfluous.<br />

The following table shows the most common product types and their turn times/<br />

turning angles (only WAREMA products are listed here. If you want to control<br />

products of other manufacturers, please contact the respective manufacturer).<br />

If, for example, you have mounted external venetian blinds of the type E80A6,<br />

you have to set a value of 1.6 seconds for the turn time, a value of +80° for the<br />

maximum turning angle and -80° for the minimum turning angle.<br />

TIP<br />

-80°<br />

Slat type<br />

Description<br />

(slat)<br />

Max.<br />

angle (°)<br />

Min.<br />

angle (°)<br />

Turntime<br />

(Sec.)<br />

E80A6 flanged +80 -80 1,6<br />

E80AF Flat slat +80 0 0,8<br />

E60A6 flanged +75 -75 1,3<br />

E60A2 flanged +70 -70 1,3<br />

E100AF Flat slat +80 0 1,1<br />

E50A1 Flat slat +70 -70 1,0<br />

Minor adjustments may be necessary depending on the<br />

package weight and motor type.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.2.4 Maximum slat angle<br />

8.2.5 Minimum slat angle<br />

First set the turn time. The setting range for the turn time is from 0 to 9.9<br />

seconds. Proceed as follows in order to change the setting:<br />

■ Change to the product settings menu as described above and select a<br />

channel. The following display is shown:<br />

Product<br />

product type<br />

Outside V.blind<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Product<br />

turn time<br />

1.6 seconds<br />

— + ¡ | }<br />

■ Change the turn time by using the buttons — + and then press the button<br />

| (save). The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

Then set the maximum slat angle as specified in the table:<br />

■ Turn the function dial until the following display appears:<br />

Product<br />

slat angle max.<br />

80°<br />

— + ¡ | }<br />

■ Change the angle by using the buttons — + and then press the button |<br />

(save). If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

Then set the minimum slat angle as specified in the table:<br />

■ Turn the function dial until the following display appears:<br />

Product<br />

slat angle min.<br />

-80°<br />

— + ¡ | }<br />

■ Change the angle by using the buttons — + and then press the button |<br />

(save). The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 99


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

100<br />

We reserve the right to carry out improvements<br />

Subsequently you can use the function "Slat angle", as described in the following<br />

sections:<br />

® 6.1.9 (Slat angle after down movement by means of sun control)<br />

® 6.2.4 (Slat angle after down movement by means of dawn/dusk control)<br />

® 6.6.6 (Slat angle after down movement by means of timer switch)<br />

® 6.8.6 (Slat angle after down movement by means of manual operation)<br />

After the sunblind has reached its lower end position, a brief turn pulse is sent to<br />

the drive motor. This turns, for example, the slats of external venetian blinds or<br />

internal venetian blinds open. You can determine this angle yourself and specify it<br />

to one degree exactly.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.2.6 <strong>Control</strong> type<br />

8.2.6.1 Drive direct<br />

8.2.6.2 Drive with motor control<br />

units<br />

You can specify channel-by-channel to the <strong>Wisotronic</strong> which type of sun<br />

protection system is connected to its output.<br />

This setting is recommended if ...<br />

...only one drive is connected directly to a channel or<br />

...several drives are connected via motor control units (MCU),<br />

whereby no local operating buttons are connected to the<br />

MCU.<br />

Proceed as follows in order to change the setting:<br />

■ Change to the product settings menu as described above and select a<br />

channel. The following display is shown:<br />

Product<br />

Product type<br />

Outside V.blind<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Product<br />

<strong>Control</strong> type<br />

Drive with MCU<br />

— + ¡ | }<br />

■ Change the setting by using the buttons — + until the text Drive<br />

direct is displayed and then press the button | (save). The symbol ¡<br />

reminds you that you are carrying out the settings for <strong>Channel</strong> 1. If you want<br />

to exit the menu without saving the changes, press the }button twice<br />

consecutively. This completes the process.<br />

TIP<br />

When a comfort function has triggered a move command, the<br />

sun protection is moved directly to the set position without a<br />

reference movement.<br />

If you have connected one or several drives via motor control units with local<br />

operating elements, proceed as follows:<br />

■ Change to the product settings menu as described above and select a<br />

channel. The following display is shown:<br />

Product<br />

Product type<br />

Outside V.blind<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Product<br />

<strong>Control</strong> type<br />

Drive direct<br />

— + ¡ | }<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 101


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.2.7 Interlocks<br />

102<br />

We reserve the right to carry out improvements<br />

■ Change the setting by using the buttons — + until the text Drive<br />

with MCU is displayed and then press the button | (save). The symbol<br />

¡ reminds you that you are carrying out the settings for <strong>Channel</strong> 1. If you<br />

want to exit the menu without saving the changes, press the } button twice<br />

consecutively. This completes the process.<br />

TIP<br />

When a comfort function has triggered a move command, a<br />

reference movement DOWN is first carried out. Afterwards<br />

the sun protection is moved to the set position.<br />

If you have connected windows provided with lock switches (for example reed<br />

contacts) to the <strong>Wisotronic</strong>, you can connect these lock switches to the control<br />

system and evaluate them specifically by channel. For example, the moving of an<br />

internal venetian blind can be blocked if the window is not closed (prevention of<br />

damage). This control behavior is achieved through interlocking. If you want to<br />

evaluate the lock switches, proceed as follows:<br />

■ Change to the product settings menu as described above and select a<br />

channel. The following display is shown:<br />

Product<br />

Product type<br />

Outside V.blind<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Product<br />

lock switch<br />

OFF<br />

— + ¡ | }<br />

■ Change the setting by using the buttons — + until the text ON is displayed<br />

and then press the button |(save) The symbol ¡ reminds you that you are<br />

carrying out the settings for <strong>Channel</strong> 1. If you want to exit the menu without<br />

saving the changes, press the }button twice consecutively. This completes<br />

the process.<br />

TIP<br />

CAUTION<br />

If the lock switch detection is activated, the sunblind can only<br />

be moved if the lock switch is closed. See also section 4.3.<br />

If the lock switch is open, the sunblind cannot be moved -<br />

either not by the safety functions (wind, ice and rain<br />

monitoring)!<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.3 Wind Monitoring<br />

Strong wind can cause considerable damage to the sun protection. The<br />

<strong>Wisotronic</strong> therefore includes a permanent wind monitoring function which<br />

protects your sun protection against storm damage. In case of a wind alert the<br />

sun protection is moved up automatically and cannot be moved either manually or<br />

by a comfort function. The limits for a wind alert are already stored productspecifically<br />

in the <strong>Wisotronic</strong>. However, they can be changed and saved<br />

afterwards. Please ensure that you have already set the connected sun protection<br />

products correctly as described above. This means that usable setting values have<br />

already been stored for each sun protection product.<br />

The following values can be changed for each channel:<br />

Wind monitoring<br />

Wind monitoring ON/OFF<br />

Wind limit UP<br />

Wind delay UP<br />

Wind delay OFF<br />

Fig. 8-1: Wind monitoring: Values which can be changed.<br />

ON/OFF<br />

0...20<br />

m/s<br />

0...20<br />

Sek<br />

0...99<br />

Minutes<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 103


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

104<br />

We reserve the right to carry out improvements<br />

Wind speed (m/s)<br />

Adjusted limit UP<br />

Coarse of wind speed<br />

Fig. 8-2: Wind speed and move behavior<br />

1 2 3 4 5 6<br />

Delay UP<br />

< 5 Sec = 5 Sec = 2 Min<br />

The thick black curve represents the course of the wind speed. The horizontal line<br />

represents the limit set by you for moving the sun protection up. The vertical<br />

dashed lines mark the delay periods for activating and de-activating. Let us<br />

assume that you have set 5 seconds for the activation delay period and 2 minutes<br />

for de-activation delay period, then the sun protection reacts as follows:<br />

The wind speed increases until Point 1 of the curve is reached. The limit for<br />

moving the sun protection up is reached here. The "UP" delay period now begins<br />

to run so that your sun protection is not yet moved up. At Point 2 of the curve the<br />

speed drops below the limit for moving up. The delay period is now canceled<br />

before it has expired and your sun protection has remained below.<br />

Later on the wind speed increases again and exceeds the limit once more at Point<br />

3. The "UP" delay period now begins to run again so that your sun protection is not<br />

yet moved up. However, the delay period has already expired at Point 4 and the<br />

limit is still exceeded - the sun protection now moves up.<br />

The wind now drops again and its speed drops below the "Up" limit at Point 5.<br />

Nothing happens yet, because the de-activation delay period now first starts - the<br />

sun protection therefore does not travel down yet. At Point 6 the de-activation<br />

delay period has finally expired and the speed still lies below the limit. The wind<br />

monitoring function now enables the operation of the sun protection again.<br />

The correct setting of the delay periods thus results in a comfortable control of<br />

the sun protection. It contributes to "smoothening" the reaction behavior of the<br />

control system. This ensures that the sun protection is not moved immediately<br />

whenever the wind speed changes.<br />

Delay UP<br />

Delay OFF<br />

Time<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.3.1 Wind monitoring ON/OFF<br />

You can activate or de-activate the wind monitoring separately for each channel.<br />

However take into account the effect which the monitoring can have and observe<br />

the safety instructions in these instructions! Proceed as follows to activate or deactivate<br />

the wind monitoring:<br />

■ Change to the service settings menu as described above and select a channel.<br />

The following display is shown:<br />

Product<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Wind<br />

monitoring<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Wind<br />

monitoring<br />

OFF<br />

— + ¡ | }<br />

■ Change the settings by using the buttons — + and then press the button<br />

|(save) The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

CAUTION<br />

Changing the settings of the wind monitoring can impair the<br />

safety of the system or reduce its effectiveness! If you are not<br />

sure what effect a change has, consult an expert.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 105


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.3.2 Wind monitoring limit<br />

"UP"<br />

106<br />

We reserve the right to carry out improvements<br />

Here a wind speed limit above which the sunblind is to move up can be set<br />

separately for each channel. The setting range is from 1 to 20 m/s. If a wind<br />

evaluation is not desired, you can also set the value "0" (---) here. Proceed as<br />

follows in order to change the limit:<br />

■ Change to the wind monitoring menu as described above and select a<br />

channel. The following display is shown:<br />

Wind<br />

monitoring<br />

ON<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Wind<br />

limit UP<br />

12m/s<br />

— + ¡ | }<br />

■ Change the limit by using the buttons — + and then press the button |<br />

(save) The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

To estimate the wind speed you can use the following table:<br />

Windspeed in<br />

m/s<br />

Force Specifications for use on land<br />

0 - 0,2 0 Calm, smoke rises vertically<br />

0,3 - 1,5 1<br />

Light air, direction of wind shown by smoke<br />

drift, but not by wind vanes<br />

1,6 - 3,3 2 Light breeze, wind felt on face, leaves rustle<br />

3,4 - 5,4 3<br />

Gentle breeze, leaves and small twigs in<br />

constant motion, wind extends light flag<br />

5,5 -. 7,9 4<br />

Moderate breeze, raises dust and loose<br />

paper, small branches are moved.<br />

Fresh Breeze, small trees in leaf begin to<br />

8,0 - 10,7 5 sway; crested wavelets form on inland<br />

waters<br />

Strong Breeze, Large branches in motion;<br />

10,8 - 13,8 6 whistling heard in telegraph wires; umbrellas<br />

used with difficulty.<br />

Near Gale, whole trees in motion,<br />

13,9 - 17,1 7 inconvenience felt when walking against the<br />

wind.<br />

17,2 - 20,7 8<br />

Gale, breaks twigs off trees, generally<br />

impedes progress.<br />

20,8 - 24,4 9<br />

Severe Gale, slight structural damage occurs<br />

(chimney-pots and slates removed)<br />

Storm, seldom experienced inland; trees<br />

24,5 - 28,4 10 uprooted; considerable structural damage<br />

occurs.<br />

28,5 - 32,6 11<br />

Violent Storm, very rarely experienced,<br />

accompanied by wide-spread damage<br />

over 32,7 12 Hurricane<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.3.3 Wind monitoring delay<br />

"UP"<br />

8.3.4 Wind monitoring „OFF“<br />

delay<br />

You can assign a delay period to the wind alert separately for each channel so that<br />

your sunblind is not moved up at each gust of wind. If the wind limits are reached<br />

or exceeded for the duration of this delay period, the wind alert is triggered and<br />

the sunblind is moved up. At a wind speed above 20 m/s a further safety function<br />

of the <strong>Wisotronic</strong> is activated. The sunblind is moved up immediately. The<br />

activation delay period is skipped in this case. The setting range is from 0 - 20<br />

seconds. Proceed as follows in order to change the limit:<br />

■ Change to the wind monitoring menu as described above and select a<br />

channel. The following display is shown:<br />

Wind<br />

monitoring<br />

ON<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Wind<br />

delay UP<br />

5 seconds<br />

— + ¡ | }<br />

■ Change the settings by using the buttons — + and then press the button |<br />

(save) The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

TIP<br />

If "Window" was selected as the connected product, the<br />

display deviates from that shown here: "CLOSE" is displayed<br />

instead of "UP".<br />

The wind alert remains active for a specific period for safety and comfort reasons.<br />

This smoothens the move behavior of your sunblind because the sunblind is not<br />

moved for the duration of the OFF delay, but remains in the "UP" position. After<br />

the OFF delay period has expired, the sunblind can be moved again by means of<br />

comfort functions or manual operation. The setting range is from 0 - 99 minutes.<br />

Proceed as follows in order to change the OFF delay period specifically for each<br />

channel:<br />

■ Change to the wind monitoring menu as described above and select a<br />

channel. The following display is shown:<br />

Wind<br />

monitoring<br />

ON<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Wind<br />

delay OFF<br />

10 minutes<br />

— + ¡ | }<br />

■ Change the settings by using the buttons — + and then press the button<br />

|(save) The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 107


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.4 Ice monitoring<br />

8.4.1 Ice monitoring ON/OFF<br />

108<br />

We reserve the right to carry out improvements<br />

The ice monitoring function ensures that your sunblind does not freeze solid while<br />

in the down position and can be damaged later by move commands. The<br />

<strong>Wisotronic</strong> therefore moves the sunblind up in case of cold weather in connection<br />

with rain before ice can form in the guide rails. Note: The ice monitoring function<br />

is de-activated in our works. During an ice alert both manual control and comfort<br />

control operation are blocked. Prerequisite for ice monitoring: A sensor for<br />

external temperature and a "Rain" sensor have to be connected. If the external<br />

temperature drops below an adjustable value and the "Rain" sensor signals<br />

precipitation, the sunblind is moved up and blocked up in the upper end position.<br />

The following values can be changed for each channel:<br />

Ice<br />

monitoring<br />

Fig. 8-3: Ice monitoring: Values which can be changed.<br />

Proceed as follows to activate or de-activate the ice monitoring:<br />

■ Change to the service settings menu as described above and select a channel.<br />

The following display is shown:<br />

Product<br />

CH 1 { }<br />

■ Turn the function dial until the following display appears:<br />

Ice<br />

monitoring<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Ice<br />

monitoring<br />

ON<br />

— + ¡ | }<br />

Ice monitoring ON/OFF<br />

Ice limit UP<br />

Ice alert<br />

autom. reset<br />

ON/OFF<br />

+2...<br />

+9°C<br />

ON/OFF<br />

■ Change the settings by using the buttons — + and then press the button |<br />

(save) The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.4.2 Ice monitoring limit "UP"<br />

8.4.3 Resetting the ice alert<br />

automatically<br />

You can specify exactly the temperature at which the ice alert is to be triggered. If<br />

rain falls and the temperature drops below the set limit, the sunblind is moved up<br />

and remains in this position until the ice alert has been canceled. For information<br />

on how to move the sunblind nevertheless, please refer to Section 6.10.1,<br />

"Resetting the ice alert".<br />

The setting range is from 0 - +9°C. Proceed as follows in order to change the<br />

limit:<br />

■ Change to the ice monitoring menu as described above and select a channel.<br />

The following display is shown:<br />

Ice<br />

monitoring<br />

ON<br />

— + ¡ | }<br />

■ Turn the function dial until the following display appears:<br />

Ice<br />

limit UP<br />

3° C<br />

— + ¡ | }<br />

■ Change the settings by using the buttons — + and then press the button |<br />

(save) The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press<br />

the }button twice consecutively. This completes the process.<br />

TIP<br />

An ice alert can also be de-activated (reset) manually. For further<br />

information please refer to Section 6.10.<br />

The control system can reset an ice alert automatically. If the outside temperature<br />

rises by 2°C above the "UP" limit set by you, the ice alert is reset automatically<br />

and the operation is enabled again.<br />

If an ice alert is to be reset automatically, proceed as follows:<br />

■ Change to the ice monitoring menu as described above and select a channel.<br />

The following display is shown<br />

Ice<br />

monitoring<br />

ON<br />

— + ¡ | }<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 109


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

8.5 Allocating a sensor<br />

110<br />

We reserve the right to carry out improvements<br />

■ Turn the function dial until the following display appears:<br />

Ice alert<br />

automatic reset<br />

OFF<br />

— + ¡ | }<br />

■ Change the setting by using the buttons — + and then press the button |<br />

(save). The symbol ¡ reminds you that you are carrying out the settings for<br />

<strong>Channel</strong> 1. If you want to exit the menu without saving the changes, press<br />

the }button twice consecutively. This completes the process.<br />

TIP<br />

The sensors have to be allocated in order for the control system to function<br />

correctly. (As a rule this was already carried out during commissioning). In the<br />

process you specify which sensors are used to control the individual channels.<br />

■ Turn the function dial until the following display appears:<br />

Service<br />

settings<br />

1 2 3 0<br />

■ Select the channel to which you want to allocate a sensor - in this example<br />

<strong>Channel</strong> 1: Press the button 1. The following display appears:<br />

Product<br />

The ON setting means: An ice alert is reset automatically, If<br />

the outside temperature rises by 2°C above the "UP" limit set<br />

by you. The OFF setting means: An ice alert has to be reset<br />

manually as described in Section 6.10.<br />

CH 1 { }<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

■ Turn the function dial until the following display appears:<br />

Allocation<br />

sensor<br />

CH 1 { }<br />

■ Select this menu item (button {). The following display appears:<br />

Allocation<br />

photo sensor<br />

1<br />

— + ¡ | }<br />

■ By turning the function dial the sensors to be allocated can now be selected.<br />

This example describes the allocation of the "Photo" sensor.<br />

■ The symbol ¡ reminds you that you are carrying out the allocation for <strong>Channel</strong><br />

1. Use the buttons — + to select the "Photo 1, 2, 3 or 1-3" sensor. As soon<br />

as you press the button | (save), <strong>Channel</strong> 1 is allocated to the selected<br />

sensor.<br />

■ Allocate a channel to each connected sensor.<br />

TIP<br />

CAUTION<br />

The sensor for relative humidity cannot be allocated!<br />

You can allocate the following sensors to any channel:<br />

3CH variant:<br />

- "Photo 1, 2, 3; 1-3" sensor<br />

- The temperature sensor integrated in the control panel<br />

- "Inside 1, 2, 3" temperature sensor<br />

- "Outside" temperature sensor<br />

2CH variant:<br />

- "Photo 1, 2, 3; 1-3" sensor<br />

- The temperature sensor integrated in the control panel<br />

- "Inside 1, 2, 3" temperature sensor<br />

- "Outside" temperature sensor<br />

Changing these settings can impair the safety of the system<br />

or reduce its effectiveness! If you are not sure what effect a<br />

change has, consult an expert.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 111


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

9. Non-channeldependent<br />

service<br />

settings<br />

9.1 System settings<br />

9.1.1 Internal temperature offset<br />

112<br />

We reserve the right to carry out improvements<br />

This section deals with the non-channel-dependent service settings.<br />

In this chapter we will describe the system settings.<br />

Depending on the position where your <strong>Wisotronic</strong> has been mounted, the<br />

temperature display of the <strong>Wisotronic</strong> may differ from a room thermometer<br />

mounted at a different position. Example: A room thermometer displays 24°C,<br />

but your <strong>Wisotronic</strong> displays 26°C. You can compensate this by setting an offset<br />

value amounting to the temperature difference, i.e. 2°C, at the <strong>Wisotronic</strong>.<br />

TIP<br />

Do not mount the <strong>Wisotronic</strong> in a position where influence<br />

from heat sources is to be expected (sun irradiation,<br />

radiators). This avoids faulty measurements!<br />

Proceed as follows in order to change the setting:<br />

■ Change to the service settings menu as described above. The following<br />

display appears:<br />

Service<br />

settings<br />

1 2 3 0<br />

■ Select the function 0 (non-channel-specific settings). The following display<br />

appears:<br />

System<br />

settings<br />

{ }<br />

■ Select this menu item (button {). The following display appears:<br />

Integr. temp<br />

sensor offset<br />

2° C<br />

— + | }<br />

■ Change the settings by using the buttons — + (enter 2°C for this example)<br />

and then press the button | (save) If you want to exit the menu without<br />

saving the changes, press the }button twice consecutively. This completes<br />

the process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

9.1.2 Duration of the wind<br />

sensor test<br />

If the "Wind" sensor or its connecting cable is damaged, the <strong>Wisotronic</strong> cannot<br />

evaluate wind measured values and the wind monitoring function does not<br />

function. In order to exclude damage to your sunblind in case of such a defect,<br />

you can activate the wind sensor test. If the <strong>Wisotronic</strong> does not receive a signal<br />

from the "Wind" sensor within a period which can be set (1 to 99 hours), it is<br />

assumed that the sensor is defective. The sunblind is moved up at those channels<br />

at which the wind monitoring function and the wind sensor test are activated. The<br />

following display is shown on the <strong>Wisotronic</strong>:<br />

Alert<br />

Wind sensor<br />

H! T H #T<br />

During this display the comfort functions are not activated. The local operating<br />

points do not have any function either. Take into account that sunblinds are no<br />

longer moved automatically during your absence (holiday, weekend, etc.). The<br />

setting range is from 1 - 99 hours. If a wind sensor test is not desired, you can<br />

also set the value "0" (---) here. The wind sensor test has to be reset<br />

manually. The procedure is described in Section 7.4. Proceed as follows in order<br />

to change the setting:<br />

■ Change to the service settings menu as described above. The following<br />

display appears:<br />

Service<br />

settings<br />

1 2 3 0<br />

■ Select the function 0 (non-channel-specific settings). The following display<br />

appears:<br />

System<br />

settings<br />

{ }<br />

■ Select this menu item (button {). The following display appears:<br />

Integr. temp<br />

sensor offset<br />

2° C<br />

— + | }<br />

■ Turn the function dial until the following display appears:<br />

Duration Wind<br />

sensor test<br />

99 hours<br />

— + | }<br />

■ Change the settings by using the buttons — + and then press the button |<br />

(save) If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 113


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

9.1.3 Querying the software<br />

version<br />

114<br />

We reserve the right to carry out improvements<br />

You may occasionally need to query the version of the operating software of your<br />

<strong>Wisotronic</strong>, for example if service is needed. Proceed as follows in order to query<br />

the software version:<br />

■ Change to the service settings menu as described above. The following<br />

display appears:<br />

User<br />

settings<br />

1 2 3 0<br />

■ Select the function 0 (non-channel-specific settings). The following display<br />

appears:<br />

System<br />

settings<br />

{ }<br />

■ Select this menu item (button {). The following display appears:<br />

Integr. temp<br />

sensor offset<br />

2° C<br />

— + | }<br />

■ Turn the function dial until the following display appears:<br />

Software vers.<br />

CP 1954110x<br />

PU 1771110x<br />

}<br />

■ Note the software version. In case of a fault you can supply this to our hotline.<br />

In order to exit the menu press the } button twice consecutively. This<br />

completes the process.<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

9.2 Changing the user<br />

language<br />

10. Maintenance<br />

11. Liability<br />

Proceed as follows in order to change the user language:<br />

■ Change to the service settings menu as described above. The following<br />

display appears:<br />

Service<br />

settings<br />

1 2 3 0<br />

■ Select the function 0 (non-channel-specific settings). The following display<br />

appears:<br />

System<br />

settings<br />

{ }<br />

■ Turn the function dial until the following display appears:<br />

Language<br />

{ }<br />

■ Select this menu item (button {). The following display appears:<br />

Language<br />

English<br />

— + | }<br />

■ Change the settings by using the buttons — + and then press the button |<br />

(save) If you want to exit the menu without saving the changes, press the<br />

}button twice consecutively. This completes the process.<br />

There are no parts to be maintained within the device. In case of a malfunction<br />

the installed miniature fuses may only be replaced by qualified electrical<br />

personnel. Also observe the specifications in the operating instructions of your<br />

sunblind.<br />

The manufacturer can reject the warranty for damage to the product if the product<br />

information given in these instructions is not observed, if it is used for purposes<br />

other than those specified or if used improperly. Liability for consequent damage<br />

to persons or property is also excluded in this case. Observe the specifications in<br />

the operating instructions of your sunblind. Liability for damage to the sunblind<br />

caused by operation during icing or icy conditions is also excluded.<br />

Note:<br />

The device fulfills the requirements on immunity to interference and emitted<br />

interference in residential and commercial areas.<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 115


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

12. Cleaning<br />

13. Disposal<br />

14. User Information<br />

116<br />

We reserve the right to carry out improvements<br />

Clean the device occasionally with a moist soft cloth. Vapor or high-pressure<br />

cleaning equipment, scouring sponges, scouring agents, solvents such as alcohol<br />

or naphtha may not be used!<br />

CAUTION<br />

If cleaning at the sun protection central unit, at the sun<br />

protection itself or immediately next to the sun protection is<br />

necessary, de-energize the system beforehand and secure it<br />

against being activated again.<br />

The device has to be disposed of or recycled in accordance with the statutory<br />

regulations.<br />

for use in:<br />

A, B, D, DK, E, F, FIN, GB, GR, I, IRL, L, NL, P, S, CH, IS, N.<br />

Receiver for sunblind remote control.<br />

The device complies at intended use with the essential requirements, which are<br />

fixed in the following EC-Guidelines and harmonized standards:<br />

- Directive on radio equipment and telecommunications terminal equipment and<br />

the mutual recognition of their conformity 1999/5/EC(R&TTE)<br />

- Directive on electromagnetic compability 89/336/EEC<br />

- Low voltage directive 73/23/EWG<br />

Link to declaration of conformity:<br />

http://www.warema.de<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

15. Trouble shooting<br />

<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> control<br />

unit <strong>EWFS</strong><br />

Remedy<br />

Type of Fault Possible cause Elimination of faults<br />

No Display Fuse has triggered<br />

Contact specialist dealer<br />

No supply voltage<br />

Switch on supply voltage<br />

Move command of remote control is<br />

not executed<br />

Remote control was not learned Learn remote control<br />

At 8-channel remote control: Incorrect Select correct channel, then repeat<br />

channel has been selected<br />

move command<br />

Button was pressed too briefly Repeat move command, keep button<br />

pressed a bit longer<br />

Interfering ambient influences Reduce distance to <strong>Wisotronic</strong><br />

Move commands of the remote control<br />

are only carried out sporadically<br />

Safety function: Wind, Ice or rain alert<br />

active, wind sensor test has recognized<br />

error<br />

Wait until wind, rain alert no longer<br />

exists, reset ice alert, reset wind<br />

sensor test<br />

Interfering ambient influences Reduce distance to <strong>Wisotronic</strong><br />

Sunblind can not be operated manually Safety function: Wind, ice or rain alert<br />

active, wind sensor test has recognized<br />

error<br />

Wind alert is not triggered even wind is<br />

weak<br />

Wind alert is triggered even wind is<br />

strong<br />

Interference through other transmitter Switch off other transmitter (e.g.<br />

baby intercom)<br />

Batteries in the remote control are weak Replace both batteries by new ones<br />

Wait until wind, rain alert no longer<br />

exists, reset ice alert, reset wind<br />

sensor test<br />

Lock switches not closed Close lock switches<br />

Wind limit set too low Increase wind limit, observe safety<br />

instructions<br />

Wind limit set too high Decrease wind limit, observe safety<br />

instructions<br />

Wind monitoring de-activated Activate wind monitoring<br />

Rain alert not triggered "Rain" sensor not connected, defective or<br />

soiled<br />

Check, clean sensor<br />

Rain monitoring function de-activated Activate function<br />

Ice alert not triggered Ice monitoring function de-activated Activate ice monitoring function<br />

Comfort functions Dawn/dusk, Sun,<br />

Humidity or Temperature control do not<br />

function as required<br />

Sunblind moves down too late at<br />

sunshine<br />

Temperature limit set too low Increase limit, observe safety<br />

instructions<br />

"Rain" sensor not connected, defective or<br />

soiled<br />

Check, clean sensor<br />

Comfort timer has not enabled the<br />

Modify the programming of the<br />

comfort functions<br />

comfort timer<br />

Time and date settings not correct Set the current time and date<br />

Sun control limit DOWN set too high Decrease limit<br />

Delay DOWN set too long Decrease limit<br />

Sunblind already moves down at low<br />

sun irradiation<br />

Sun control limit DOWN set too low Increase limit<br />

Sunblind moves up too late at cloud Sun control limit UP set too low Increase limit<br />

Sunblind does not move as a function<br />

of the sun irradication<br />

Sun control de-activated Activate sun control<br />

Delay UP set too long Decrease limit<br />

Sunblind does not move at dawn/dusk Dawn/dusk control de-activated Activate dawn/dusk control<br />

Limits of dawn/dusk control not<br />

programmed correctly<br />

Change limits<br />

"Photo" sensor not mounted correctly Check mounting site<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 117


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

16. Index<br />

A<br />

Alert<br />

-ice alert<br />

-reset automatically 109<br />

-reset manually 81<br />

-wind sensor failure 88<br />

Assigning sensors 110<br />

B<br />

Basic functions<br />

-function dial 10<br />

-operating 10<br />

-with remote control 12<br />

C<br />

Central switch<br />

-external 74<br />

<strong>Channel</strong> button 74<br />

-external 74<br />

Comfort functions 29<br />

-dawn/dusk control 39<br />

-dtemperature control 43<br />

-humidity control 57<br />

-manual operation 70<br />

-sun control 31<br />

-symbols 21<br />

Comfort timer 65<br />

-basic functions 65<br />

-on/off 65<br />

-programming 68<br />

<strong>Control</strong> mode 71<br />

-changes 71<br />

<strong>Control</strong> type<br />

-drive direct 101<br />

-with control units 101<br />

Custom settings<br />

-table 94, 95<br />

D<br />

Date, time<br />

-not displayed correctly 27<br />

-settings 27<br />

Dawn/dusk control 38<br />

-basic function 38<br />

-limit DOWN 40<br />

-on/off 39<br />

-slat angle 41<br />

Delay<br />

-humidity control 57<br />

-rain monitoring 55<br />

-sun control 34, 35<br />

-wind monitoring 104, 106, 107<br />

Devices<br />

-non-sun-protection 57<br />

-variants 6<br />

118<br />

We reserve the right to carry out improvements<br />

Difference temperature<br />

-how to use 51<br />

Direction of movement 73<br />

-safety 73<br />

Display<br />

-date and time 16<br />

-measured values 15<br />

-the software version 114<br />

Disposal 115<br />

F<br />

Facade<br />

-and channls 17<br />

-outputs 17<br />

Factory settings 92, 93<br />

Function buttons 10<br />

Function dial 10<br />

Functions<br />

-on/off 12, 14<br />

-safety 18, 29<br />

G<br />

Group 77<br />

-building a group 77<br />

H<br />

Humidity control<br />

-limit CLOSE 59<br />

-limit OPEN 59<br />

-on/off 58<br />

I<br />

Ice alert<br />

-resetting 81<br />

-automatically 109<br />

Ice monitoring<br />

-limit UP 109<br />

-on/off 108<br />

-resetting 108<br />

Interlocks 102<br />

-overview 102<br />

-symbols 24, 25<br />

M<br />

Manual operation 74<br />

-continous mode mode 70<br />

-properties 74<br />

-with ext. central switch 74<br />

-with ext. channel button 74<br />

-with function keys 74<br />

-with remote control 74<br />

Menue structure 18<br />

-overview 19<br />

O<br />

Operation 74<br />

-manual<br />

-ext. central switch 74<br />

-ext. channel button 74<br />

-function keys 74<br />

-remote control 74<br />

P<br />

Password 90<br />

Product<br />

-automatic preset 91<br />

-change settings 96<br />

-runtimes 96<br />

-type of 91<br />

Q<br />

Query<br />

-the software version 114<br />

R<br />

Rain monitoring 55<br />

-basic functions 55<br />

-on/off 55<br />

Remote control 75<br />

-channels 75<br />

-delete 77, 79<br />

-identification 75<br />

-learning 75<br />

Resetting<br />

-ice alert 81<br />

-"wind" sensor failure 88<br />

Runtime<br />

-product specific 97<br />

S<br />

Safety<br />

-functions 10<br />

-ice alert 81<br />

-rain monitoring 55<br />

-wind monitoring 103<br />

-"wind" sensor test 113<br />

-ice alert 81<br />

-instructions 7<br />

-intended purpose 8<br />

-interlocks 102<br />

-reversing the direction 74<br />

-target group 8<br />

-warning signs 7<br />

Service settings<br />

-channel-dependent 89<br />

-control type 101<br />

-ice monitoring 108<br />

-interlocks 102<br />

-overview 89<br />

-password 90<br />

-product settings 91<br />

-wind monitoring 103<br />

-non-channel-dependent 112<br />

-temperature offset 112<br />

-"wind" sensor test 113<br />

Slat angle 99<br />

Software version 9<br />

-query 114<br />

93280680•816755•7979k0•08.10.2004


<strong>Wisotronic</strong> <strong>dialog</strong> 2/3-<strong>Channel</strong> <strong>Control</strong> <strong>Unit</strong><br />

<strong>EWFS</strong> ®<br />

Sun control 31<br />

-delay OPEN 35<br />

-how to use 37<br />

-on/off 32<br />

-operating modes 50<br />

-overview 31<br />

-position DOWN 33<br />

-slat angle 36<br />

T<br />

Temperature control<br />

-difference temperature 52<br />

-example 43<br />

-limit DOWN 48<br />

-limit OFF 50<br />

-limit ON 49<br />

-limit UP 47<br />

-on/off 45<br />

-operating modes 46<br />

Timer switch<br />

-on/off 61<br />

-overview 60<br />

-programming 62<br />

-slat angle 63<br />

Turn time<br />

-typical 41, 63, 72<br />

U<br />

User settings<br />

-channel-dependent 30<br />

-comfort timer 65<br />

-dawn/dusk control 38<br />

-overview 30<br />

-sun control 31<br />

-temperature control 43<br />

-timer switch 60<br />

-wind sensor failure 88<br />

-non-channel-dependent 84<br />

-dimming the display 87<br />

-display contrast 86<br />

-time and date 84<br />

-safety 31<br />

W<br />

Wind monitoring<br />

-example 104<br />

-on/off 105<br />

-overview 103<br />

-reset "wind" sensor failure 88<br />

93280680•816755•7979k0•08.10.2004 We reserve the right to carry out improvements 119