SYSTEMA S.p.A.AIRTIGHT GAS-FIRED RADIANT TUBES INFRANOTEIf heat recovery systems are provided downstream from the generator, the hole must be on the length of ductfor evacuating combustion products leaving the recovery systems; this is a metal fumes duct, not insulatedand located inside the environment (see fig. 57), which loses heat to the environment by both convection andradiation.COMBUSTIONANALYSERSampling point located onthe flexible fumes elementFlexible fumeselementFig.57 Sampling hole for combustion analysis with heat recovery devices (point B)If the concentration of CO brought back to the condition of dry combustion products and without air is greater than 0.1%(1000 ppm) and it is not possible for the operator or the maintenance technician to reduce it below this value, the outcomeof combustion control must be considered negative, irrespective of the measured value of combustion performance.9.2.1 Measuring the temperature of the combustion airThis must be done at a suitable point of the combustion air feeding duct.At the end of measuring, the operator must close the hole securely, so as to guarantee the seal of the duct for evacuatingcombustion products during normal plant operation.Rev. 18GB061052