10In order to achieve minimum response time, the Weather Protectionmust be oriented with the flow direction indicator facing into the airflow. See procedure in section 2.1.3.The sensor must be mounted in straight parts of the duct withundisturbed airflow. Avoid areas with possible turbulent flow e.g.immediately after sharp bends or junctions.Figure 2.1Ventilation duct or pipe mounting using Duct MountingFlange KitRefer to: Figure 2.2 for details.
11Figure 2.2Exploded view, Duct Mount Flange Kit2.1.3 OrientationThe detector should be mounted so that the longitudinal axis of thedetector is horizontal. This will prevent accumulation of water and duston the optics. The Weather Protection must always be orientedcorrectly for optimal performance.NOTE: When the GD10P is mounted outdoors, the flow directionindicator must point upwards.See “Flow Direction Indicator” in Fig. 2.3 below. Orientation of theWeather Protection is performed as follows:• Use a screwdriver to loosen the two screws on the WeatherProtection• Rotate the Weather Protection to correct position• Tighten the screw with a torque of max. 0.5 NmFlow directionindicatorFlowdirectionFigure 2.3Orientation of GD10P weather housing in relation toflow direction
- Page 1: SIMRAD GD10P - IR GASDETECTOROPERAT
- Page 4 and 5: 5.4 GAS DETECTION SYSTEM...........
- Page 6 and 7: 41.2 ConstructionA complete GD10P G
- Page 8 and 9: 6- Electrical connection 3 wires (M
- Page 10 and 11: 8EN 61779-4/IEC 61779-4EN 50081-1EN
- Page 14 and 15: 122.1.4 Mounting the GD10PThe detec
- Page 16 and 17: 142.2.2.2 Retrofit mountingFor retr
- Page 18 and 19: 163. OPERATION3.1 Start-up procedur
- Page 20 and 21: 18• If there is an air movement o
- Page 22 and 23: 20Figure 4.3Test procedure
- Page 24 and 25: 22Refer to Figure 5.2 below.Radiati
- Page 26 and 27: 24Converting % LEL to % v/v is base
- Page 28: 261 21: Plate Adapter (junctionbox/
11Figure 2.2Exploded view, Duct Mount Flange Kit2.1.3 OrientationThe detector should be mounted so that the longitudinal axis of thedetector is horizontal. This will prevent accumulation of water and duston the optics. The Weather Protection must always be orientedcorrectly for optimal performance.NOTE: When the <strong>GD10P</strong> is mounted outdoors, the flow directionindicator must point upwards.See “Flow Direction Indicator” in Fig. 2.3 below. Orientation of theWeather Protection is performed as follows:• Use a screwdriver to loosen the two screws on the WeatherProtection• Rotate the Weather Protection to correct position• Tighten the screw with a torque of max. 0.5 NmFlow directionindicatorFlowdirectionFigure 2.3Orientation of <strong>GD10P</strong> weather housing in relation toflow direction