EXTENDED REGISTER GROUPS<br />
Reg, PID regulator<br />
Compensate for viscous friction. It produces a feed forward torque<br />
proportional to speed reference.<br />
Reg.ViscSF 23 0..255 RW<br />
Scale factor for viscous friction compensation.<br />
Reg.TorqCLim 24 0..8191 RW<br />
Continuous torque or (for PM-synchronous-motors: current) limit.<br />
100% Torque = 8191.<br />
This limit will be used after Reg.TorqTime has expired.<br />
Reg.TorqTime 25 0..8191 RW<br />
Timer for activation <strong>of</strong> REG.TorqCLim.<br />
Reg.DerrFltSF 26 0..7 RW<br />
Low pass filter limiting the noise at the SpdErr signal.<br />
Reg.DerrFltSF = 0,<br />
y(n) = x(n). Default at startup, which means no filter.<br />
Reg.DerrFltSF = 1,<br />
y(n) = 0.5*y(n-1)+0.5*x(n), time const ~ 2,5 ms.<br />
Reg.DerrFltSF = 2,<br />
y(n) = 0.75*y(n-1)+0.25*x(n) time const ~ 8 ms.<br />
Reg.DerrFltSF = 3,<br />
y(n) = 0.875*y(n-1)+0.125x(n) time const ~ 18 ms.<br />
Reg.DerrFltSF = 4, ~ 40 ms.<br />
Reg.DerrFltSF = 5, ~ 75 ms.<br />
Reg.TrqLimFlgs 27 0..3 R<br />
Bit information on Torqlimit status. Bit 0 (1) indicates if the output<br />
torque is limited by Reg.TorqLim. Bit 1(2) indicates if the<br />
dynamic limit has been activated, that is if the output is limited by<br />
Reg.TorqCLim.<br />
Reg.PosRef 28 -2 31 ..2 31 -1 R<br />
The actual reference value used by the regulator. Normally this is the<br />
sum <strong>of</strong> PG.Apos and Gear.PosRef. In the case<br />
<strong>of</strong> disconnected<br />
Pr<strong>of</strong>ile Generator, the Pg.DconnAPos is used instead.<br />
User's Manual 5.1 Inmotion Technologies AB<br />
Doc. No.9032 0027 01 (B), Rev. 11.07.2001<br />
85