EXTENDED REGISTER GROUPS<br />

Int, Interrupt control<br />

Termistor input in Motor connector event Bit 3 (bitvalue =8),<br />

should be set if automatic trip on Motor temp high is<br />

wanted.<br />

In.PTC eventBit 2 (bitvalue = 4), should be set if automatic<br />

trip on In.PTC “low” is wanted.<br />

If no PL program is running when an event occurs, the<br />

power stage will be shut <strong>of</strong>f on the conditions specified in<br />

Bit2, 3 and 4.<br />

If a program is running and Vector.TempErr = 0 (default<br />

value), the power stage will be shut <strong>of</strong> on the conditions<br />

specified in Bit2, 3 and 4.<br />

If Vector.TempErr 0,<br />

the program must handle this<br />

event by using the system interrupt on this vector, (enable<br />

by setting bit 5 in Int.SysMask). These conditions are<br />

checked with the rate set in SysIo.ChkTmr.<br />

Int.TempMask is set to a default value defined in<br />

EEprom.5, bit 4, 3 and 2 at startup, If EEprom.0 matches<br />

the revision number <strong>of</strong> the firmware.<br />

Bit2 (4) = 1 Enable In.PTC interrupt.<br />

Bit3 (8) = 1 Enable interrupt on motor over temperature.<br />

Bit4 (16) = 1 Enable interrupt on drive over temperature.<br />

Int.BleedLim 7 0 8191 RW<br />

Limit for bleeder monitoring.<br />

The default value for this 0.<br />

The function is disabled.<br />

If set > 0 the function monitors the bleeder load,<br />

SysIo.ADC6, with the rate set in SysIo.ChkTmr.<br />

A value <strong>of</strong> 400 allows a load equal to 0.5 seconds <strong>of</strong><br />

continuous bleeding <strong>of</strong> the DC-bus.<br />

A value <strong>of</strong> 8000 allows a load equal to 10 seconds <strong>of</strong><br />

continuos bleeding <strong>of</strong> the DC-bus.<br />

If the program (interpreter) is stopped, the power stage will<br />

be shut <strong>of</strong> when the bleeder load reaches this limit. If the<br />

program (interpreter) is running and the<br />

Vector.BLeedErr = 0 (the<br />

default value), the power stage<br />

will be shut <strong>of</strong> when the bleeder load reaches this limit.<br />

If the Vector.BLeedErr is 0 then the<br />

program is<br />

supposed to handle the condition by using the system<br />

interrupt on this vector, (enabled by setting bit 6 in<br />

Int.SysMask).<br />

The shunt regulator resistors can withstand a defined<br />

amount <strong>of</strong> energy from the regenerative power stage. This<br />

amount can be translated to a time <strong>of</strong> constant operation. A<br />

value in this parameter <strong>of</strong> 400 is equal to 500 ms <strong>of</strong><br />

continuous operation. The internal resistors in the DMC 2<br />

can be used for 500 ms continuous shunting.<br />

Int.Mode 8 0..1 RW<br />

=0 Normal mode. This is the default at startup.<br />

=1<br />

INT.IntMask and INT.SysMask on the stack<br />

When an interrupt is detected the firmware will push the<br />

content <strong>of</strong><br />

and then clear them, (disabling all interrupts). On leaving an<br />

User's Manual 5.1 Inmotion Technologies AB<br />

Doc. No.9032 0027 01 (B), Rev. 11.07.2001<br />

107