I&O Manual - Solaris Water Heaters - Categories On Thermal ...
I&O Manual - Solaris Water Heaters - Categories On Thermal ... I&O Manual - Solaris Water Heaters - Categories On Thermal ...
D. SETUP MENUDisplayWWSDLL StartTriggerLL StopTriggerWaterheater OnDelayWaterheater OffDelayHigh FireLimitRotationRotationAfterOutdoorSensorOutdoorSet UpWaterheater SetUpOutdoorDesignWaterheaterDesignFactorySettingsOffRange/ChoicesOffWWSD of WaterheaterWWSD of SysPumpBoth90 50 to 10025 0 to 50120 0 to 900120 0 to 900100 40 to 100DisableDisableEnable168 8 to 720NoNoDisplay OnlyOutdoor Reset55°F 40°F to 100°F140°F 80°F to 180°F30°F -20°F to 50°F180°F 80°F to 220°FDescriptionWWSDSpecifies Warm Weather Shut-Down (WWSD) control of water heater and/or system pump:Ignores Warm Weather setpointWhen Outside Air Temperature (OAT) is higher than the WWSD setpoint, inhibits water heater startWhen OAT is higher than the WWSD setpoint de-energize System Pump output (SO)When OAT is higher than the WWSD setpoint, inhibit Call for Heat and de-energized system pumpoutput (SO)LL Start TriggerSpecifies the percent of maximum modulation rate the running water heater(s) must reach beforecalling upon additional water heaters for help.LL Stop TriggerSpecifies the percent of modulation rate that the running water heater(s) must be below before shuttingdown a lag water heater.Water heater On DelayTime Delay after the On Point setpoint before starting the next water heater. Short time delay to preventnuisance starts due to momentary temperature and modulation rate swings.Water heater Off DelayTime Delay after the Off Point setpoint before stopping the next water heater. Short time delay toprevent nuisance stops due to momentary temperature and modulation rate swings.High Fire LimitHigh modulation rate limit for all water heaters on the peer-to-peer network as long as at least onewater heater is still not running. After the last water heater has started the modulation rate is releasedup to 100%.RotationSpecifies number of hours (cumulative) a lead water heater runs before passing the lead to anotherwater heater.Lead rote will be surrendered earlier if the lead water heater is placed into manual mode, is runningremotely (mode 6), fails to start, is “blind” (all input sensors failed), or is satisfying a DHWP request.Rotate AfterSpecifies number of hours (cumulative) a lead water heater runs before passing the lead to anotherwater heater.Outdoor SensorEnables the Outside Air Temperature sensor and display and control logic:Outside Air Input (O+O-) is ignored.Do Not Calculate setpoint based on outdoor temperature, Display Outside Air TemperatureCalculate the temperature setpoint based on outdoor temperature using a reset curve defined byOutdoor Set Up, Water heater Set Up, Outdoor Design and water heater Design parameters.Outdoor Set UpThe Outdoor Set Up temperature is the outdoor temperature at which the Water heater Set Up temperatureis supplied. Only visible when Outdoor Sensor is set to Outdoor Reset.Water heater Set UpThe Water heater Set Up temperature is the starting water heater water temperature of the resetratio. If the building feels cool during mild outdoor conditions, the Water heater Set Up setting shouldbe increased. Only visible when Outdoor Sensor is set to Outdoor Reset.Outdoor DesignThe Outdoor Design temperature is the outdoor temperature at which the Water heater Design temperatureis supplied.Only visible when Outdoor Sensor is set to Outdoor ResetWater heater DesignThe Water heater Design setting is the water temperature required to satisfy the building heat lossduring the Outdoor Design temperature. If the building feels cool during cold outside conditions, theWater heater Design setting should be increased.Only visible when Outdoor Sensor is set to Outdoor Reset.52
D. Setup Menu (Continued)DisplayLocalPID ILocalPID DRemotePID PRemotePID IRemotePID DMixingValve PMixingValve IMixingValve DFactorySettingsRange/Choices30 0 to 100000 0 to 1000020 0 to 1000030 0 to 100000 0 to 1000015 0 to 1000040 0 to 100000 0 to 10000Max ΔT P 15 0 to 10000Max ΔT I 40 0 to 10000Max ΔT D 0 0 to 10000DescriptionLocal PID IIntegral Gain value for water heater outlet temperature sensor control Modes. A smaller value makesthe Integral ramp in less time (i.e.., faster). Integral is a secondary PID modulation rate tuning adjustmentthat ramps the output over time (typically minutes).Local PID DThe Derivative Gain value for water heater outlet temperature sensor control Modes. A larger Derivativegain value produces a larger PID output contribution proportional to the rate of change of theerror (Setpoint - Water heater Outlet Temperature). When set equal to zero it has no effect on theoutput.Remote PID PProportional Gain value for Remote System Temperature sensor control Modes. Refer to Local PID Pfor explanation.Remote PID IIntegral Gain term for Remote System Temperature sensor control Modes. Refer to Local PID I forexplanation.Remote PID DDerivative Gain term for Remote System Temperature sensor control Modes. Refer to Local PID D forexplanationMixing Valve PProportional Gain value for water heater Inlet Temperature sensor control mode. A larger gain valueresults in tighter, more active, PID control. Gain is the primary PID modulation rate tuning adjustmentand provides the immediate mixing valve modulation response.Only visible when mixing valve = yes.Mixing Valve IIntegral Gain value for water heater inlet Temperature sensor control mode. A smaller value makesthe Integral ramp in less time (i.e., faster). Integral is a secondary PID modulation rate tuning adjustmentthat ramps the output over time (typically minuets).Mixing Valve DThe Derivative Gain value for water heater Inlet Temperature sensor control mode. A larger Derivativegain value produces a larger PID output contribution proportional to the rate of change of the error(Setpoint - Water heater Inlet Temperature)When set equal to zero it has no effect on the output.Max ΔT PPromotional Gain value for water heater differential (water heater outlet minus inlet temperature sensor)temperature control mode. Refer to Local PID P for explanation.Only Visible when mixing valve = yes.Max ΔT IIntegral Gain value for water heater differential (water heater outlet minus inlet temperature sensor)temperature control mode. Refer to Local PID I for explanation.Only visible when mixing valve = yes.Max ΔT DDerivative gain term for water heater differential (water heater outlet minus inlet temperature sensor)temperature control mode. Refer to Local PID D for explanation. Only visible when mixing valve =yes.53
- Page 1 and 2: INSTALLATION, OPERATING ANDSERVICE
- Page 3 and 4: WARNINGThis water heater requires r
- Page 5 and 6: WaterheaterModelNumberINPUT(MBH)GRO
- Page 7 and 8: 5. For water heater located in an u
- Page 9 and 10: B. General Guidelines1. Vent system
- Page 12 and 13: 12Figure 4: Recommended Separate Ho
- Page 14 and 15: E. Optional Separate Horizontal Ven
- Page 16 and 17: SEE TABLE 0Figure 8: Separate Horiz
- Page 18 and 19: 18Figure 9: Vertical Vent Installat
- Page 20 and 21: IV. Water Piping and Trim1. WATER T
- Page 22 and 23: escape of air trapped in the water
- Page 24 and 25: 24Figure 13: Safety & Drain Valve I
- Page 26 and 27: Table 5: Maximum Capacity of Schedu
- Page 28 and 29: SolarisLadder DiagramNOTES:1. IF LO
- Page 30 and 31: VII. Modular InstallationA. General
- Page 32 and 33: Figure 17: Modular Water heater Con
- Page 34 and 35: VIII. System Start-upA. Safe operat
- Page 36 and 37: FOR YOUR SAFETY READ BEFORE OPERATI
- Page 38 and 39: Figure 22: SOL500-1500 Pilot Valve1
- Page 40 and 41: Secondsfor OneRevolutionTable 7:
- Page 42 and 43: A. General Guidelines1. A thorough
- Page 44 and 45: I. Check Combustion and Safety Cont
- Page 46 and 47: C. Trouble Shooting GuideAlarm Mess
- Page 48 and 49: X. Thermal Solutions Water heater C
- Page 50 and 51: Label 101175-04RJ-11(6 pin)Boiler P
- Page 54 and 55: E. Boiler Configuration MenuDisplay
- Page 56 and 57: G. Setpoints MenuDisplayOperational
- Page 58 and 59: XI. Repair PartsAll Solaris ® Seri
- Page 60 and 61: 63159847311SIDE VIEW OFGAS VALVE102
- Page 62 and 63: 12KeyNo.Manifold Orifice AssemblyDe
- Page 64 and 65: 6 59738412Key No. Description Quant
- Page 66 and 67: SERVICE RECORDDateService Performed
- Page 68: LIMITED WARRANTYSubject to the term
D. Setup Menu (Continued)DisplayLocalPID ILocalPID DRemotePID PRemotePID IRemotePID DMixingValve PMixingValve IMixingValve DFactorySettingsRange/Choices30 0 to 100000 0 to 1000020 0 to 1000030 0 to 100000 0 to 1000015 0 to 1000040 0 to 100000 0 to 10000Max ΔT P 15 0 to 10000Max ΔT I 40 0 to 10000Max ΔT D 0 0 to 10000DescriptionLocal PID IIntegral Gain value for water heater outlet temperature sensor control Modes. A smaller value makesthe Integral ramp in less time (i.e.., faster). Integral is a secondary PID modulation rate tuning adjustmentthat ramps the output over time (typically minutes).Local PID DThe Derivative Gain value for water heater outlet temperature sensor control Modes. A larger Derivativegain value produces a larger PID output contribution proportional to the rate of change of theerror (Setpoint - <strong>Water</strong> heater Outlet Temperature). When set equal to zero it has no effect on theoutput.Remote PID PProportional Gain value for Remote System Temperature sensor control Modes. Refer to Local PID Pfor explanation.Remote PID IIntegral Gain term for Remote System Temperature sensor control Modes. Refer to Local PID I forexplanation.Remote PID DDerivative Gain term for Remote System Temperature sensor control Modes. Refer to Local PID D forexplanationMixing Valve PProportional Gain value for water heater Inlet Temperature sensor control mode. A larger gain valueresults in tighter, more active, PID control. Gain is the primary PID modulation rate tuning adjustmentand provides the immediate mixing valve modulation response.<strong>On</strong>ly visible when mixing valve = yes.Mixing Valve IIntegral Gain value for water heater inlet Temperature sensor control mode. A smaller value makesthe Integral ramp in less time (i.e., faster). Integral is a secondary PID modulation rate tuning adjustmentthat ramps the output over time (typically minuets).Mixing Valve DThe Derivative Gain value for water heater Inlet Temperature sensor control mode. A larger Derivativegain value produces a larger PID output contribution proportional to the rate of change of the error(Setpoint - <strong>Water</strong> heater Inlet Temperature)When set equal to zero it has no effect on the output.Max ΔT PPromotional Gain value for water heater differential (water heater outlet minus inlet temperature sensor)temperature control mode. Refer to Local PID P for explanation.<strong>On</strong>ly Visible when mixing valve = yes.Max ΔT IIntegral Gain value for water heater differential (water heater outlet minus inlet temperature sensor)temperature control mode. Refer to Local PID I for explanation.<strong>On</strong>ly visible when mixing valve = yes.Max ΔT DDerivative gain term for water heater differential (water heater outlet minus inlet temperature sensor)temperature control mode. Refer to Local PID D for explanation. <strong>On</strong>ly visible when mixing valve =yes.53