escape of air trapped in the water heater.To perform a long term pressure test including thewater heater, ALL trapped air must first be removedfrom the water heater.A loss of pressure during such a test, with novisible water leakage, is an indication that thewater heater contained trapped air.WARNINGFailure to operate the unit with the properwater flow rate can lead to appliance failure.Always install water flow switch so that theunit stops operating if improper water flowis present.Safety relief valve discharge piping mustbe piped such that the potential of severeburns is eliminated. DO NOT pipe in anyarea where freezing could occur. DO NOTinstall any shut-off valves, plugs or caps.Consult Local Codes for proper dischargepiping arrangement.Do not operate water heater with flow ratesin excess of the maximum flow rates listedin Table 2. Water heater tube erosion andpitting will occur. Thermal Solutions StandardWarranty does not cover problemscaused by excessive water flow rates.If a high head system pump is installed,assure that the water heater relief valveand system piping are capable of operatingproperly at the combined pressure of thesystem fill pressure plus the pump statichead pressure.22
Table 2 - Solaris Water heater Flow and Pressure DropWaterHeaterModel20° ΔT (max) 40° ΔT (min)Δ P (ft)Flow(GPM)Δ P (ft)Flow(GPM)Supply/ReturnPipe (in. dia.)SOL-500 6.9 41 1.4 20 2Figure 12: Water Piping (Single Water heater)23
- Page 1 and 2: INSTALLATION, OPERATING ANDSERVICE
- Page 3 and 4: WARNINGThis water heater requires r
- Page 5 and 6: WaterheaterModelNumberINPUT(MBH)GRO
- Page 7 and 8: 5. For water heater located in an u
- Page 9 and 10: B. General Guidelines1. Vent system
- Page 12 and 13: 12Figure 4: Recommended Separate Ho
- Page 14 and 15: E. Optional Separate Horizontal Ven
- Page 16 and 17: SEE TABLE 0Figure 8: Separate Horiz
- Page 18 and 19: 18Figure 9: Vertical Vent Installat
- Page 20 and 21: IV. Water Piping and Trim1. WATER T
- Page 24 and 25: 24Figure 13: Safety & Drain Valve I
- Page 26 and 27: Table 5: Maximum Capacity of Schedu
- Page 28 and 29: SolarisLadder DiagramNOTES:1. IF LO
- Page 30 and 31: VII. Modular InstallationA. General
- Page 32 and 33: Figure 17: Modular Water heater Con
- Page 34 and 35: VIII. System Start-upA. Safe operat
- Page 36 and 37: FOR YOUR SAFETY READ BEFORE OPERATI
- Page 38 and 39: Figure 22: SOL500-1500 Pilot Valve1
- Page 40 and 41: Secondsfor OneRevolutionTable 7:
- Page 42 and 43: A. General Guidelines1. A thorough
- Page 44 and 45: I. Check Combustion and Safety Cont
- Page 46 and 47: C. Trouble Shooting GuideAlarm Mess
- Page 48 and 49: X. Thermal Solutions Water heater C
- Page 50 and 51: Label 101175-04RJ-11(6 pin)Boiler P
- Page 52 and 53: D. SETUP MENUDisplayWWSDLL StartTri
- Page 54 and 55: E. Boiler Configuration MenuDisplay
- Page 56 and 57: G. Setpoints MenuDisplayOperational
- Page 58 and 59: XI. Repair PartsAll Solaris ® Seri
- Page 60 and 61: 63159847311SIDE VIEW OFGAS VALVE102
- Page 62 and 63: 12KeyNo.Manifold Orifice AssemblyDe
- Page 64 and 65: 6 59738412Key No. Description Quant
- Page 66 and 67: SERVICE RECORDDateService Performed
- Page 68: LIMITED WARRANTYSubject to the term
escape of air trapped in the water heater.To perform a long term pressure test including thewater heater, ALL trapped air must first be removedfrom the water heater.A loss of pressure during such a test, with novisible water leakage, is an indication that thewater heater contained trapped air.WARNINGFailure to operate the unit with the properwater flow rate can lead to appliance failure.Always install water flow switch so that theunit stops operating if improper water flowis present.Safety relief valve discharge piping mustbe piped such that the potential of severeburns is eliminated. DO NOT pipe in anyarea where freezing could occur. DO NOTinstall any shut-off valves, plugs or caps.Consult Local Codes for proper dischargepiping arrangement.Do not operate water heater with flow ratesin excess of the maximum flow rates listedin Table 2. <strong>Water</strong> heater tube erosion andpitting will occur. <strong>Thermal</strong> Solutions StandardWarranty does not cover problemscaused by excessive water flow rates.If a high head system pump is installed,assure that the water heater relief valveand system piping are capable of operatingproperly at the combined pressure of thesystem fill pressure plus the pump statichead pressure.22