GV90+ gas-fired water boiler — <strong>Boiler</strong> <strong>Manual</strong>Troubleshooting (continued)CHART 7LIMIT light flashing and POWER light on steadyElectrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to followinstructions could result in severe personal injury, death or substantial property damage.• This is NOT a lockout mode. The IBC should only be signalingthat the water temperature sensor is either shorted orthere is an open circuit across the sensor terminals.• This situation is usually corrected by replacing the sensor,as described below.• Remove SENSOR plug from receptacle on IBC (Figure 93, page 78, Item 6).• Then re-insert.Does LIMIT light still flash?NoYes• Replace sensor and harness.Does LIMIT light still flash?NoYes• <strong>Boiler</strong> may now be operating correctly. Verify per normalsequence of operation (Figure 75, page 65).• Replace IBC (IBC).• Retest.Part number 550-142-054/1211 87