Table of ContentsPage #Access Doors 11Assembly Instructions 16-17Cleats 4Coiled Hanging Strap 6Corners 5Cut-To-Length 10Duct Construction Standards 19-271/2'' W.G. Static 191'' W.G. Static 202'' W.G. Static 213'' W.G. Static 224'' W.G. Static 236'' W.G. Static 2410'' W. G. Static 25<strong>Dyn</strong>-O-<strong>Mate</strong> Components 16<strong>Dyn</strong>-O-Wrap 13<strong>Dyn</strong>-O-Wrap Dispenser 13Flange 3Flat Drive 9Flat Hanging Strap 6Flat S 9<strong>Product</strong> Information▪ All <strong>Dyn</strong>-O-<strong>Mate</strong> Flange, Corners & Cleats are manufactured with yellow label.▪ Hollow Turning Vane, Vane Rail, Flat S, Flat Drive, & Standing S are manufactured with yellow label.▪ All weights shown in this catalog are approximate.▪ All Flat Drive, Flat S, Flat Hanger Straps and Flange have painted ends to designate the metal gaugecolor coding is as follows:▪ 16 gauge: Yellow▪ 22 gauge: White▪ 18 gauge: Black▪ 24 gauge: Green▪ 20 gauge: Blue▪ 26 gauge: Orange or Red▪ J Flange: Blue▪ H Flange: White▪ All <strong>Duro</strong> <strong>Dyn</strong>e products are warranted against defects in quality or workmanship. Defectivematerial will be repaired or replaced at the manufacturer’s option. Liability resulting from defectsin quality or workmanship is limited to the value of that material.Contact UsDURO DYNE EAST81 Spence St.Bay Shore, NY 11706Tel: (631) 249-9000Fax: (631) 249-8346Toll Free: 800-899-3876PAGE 2Important Ordering Information<strong>Product</strong> Gauge IdentificationDURO DYNE MIDWEST3825 Symmes RoadFairfield, OH 45011Tel: (513) 870-6000Fax: (513) 870-6005Toll Free: 800-966-6446WarrantyPage #Grille Masking 13Nuts & Bolts 8<strong>Product</strong> Information 2Ordering Information 2<strong>Product</strong> Gauge Identification 2Warranty 2Punched Angle Iron 6Smacna Policy 18Standing S 9Threaded Rod & Accessories 7-8Tool & Accessories 14-15Cleat Tool 14Crimper 14<strong>Dyn</strong>-O-Claw 15<strong>Dyn</strong>-O-Loc 15Gasket 14Nosing 15Pittsburgh Lock Opening Tool 15Vane Dimpler 14Vane and Rail 12All dimensions shown throughout this<strong>Product</strong> <strong>Catalog</strong> are approximate.DURO DYNE WEST10837 Commerce Way, Unit CFontana, CA 92337Tel: (562) 926-1774Fax: (562) 926-5778Toll Free: 800-899-3963DURO DYNE CANADA5030 Francois-CussonLachine, QuebecCanada H8T 1B3Tel: (514) 422-9760Fax: (514) 636-0328


J Flange1.41.40SealantPocket<strong>Dyn</strong>-O-<strong>Mate</strong> FlangesFlangeDOMJ Flange▪ Designed to strengthen the duct wall and connect duct sections together.▪ Furnished with an integrated sealant pocket for a secure air tight fit.▪ Manufactured from 20-gauge steel in both 12ft. & 20ft. lengths.▪ DOMJ is designed for large commercial and high-pressure applications.▪ Bundles of 20ft. lengths available only with a Full Truckload order.▪ Specialty metal available upon request.H Flange.96.3763/64"1.341.34SealantPocketJ SpeedFlange1-23/64"DOMH Flange▪ Designed to strengthen the duct wall and connect duct sections together.▪ Furnished with an integrated sealant pocket for a secure air tight fit.▪ Manufactured from 22-gauge steel in both 12ft. & 20ft. lengths.▪ DOMH is designed for low to medium pressure or residential applications.▪ Bundles of 20ft. lengths available only with a Full Truckload.▪ Specialty metal available upon request.SpeedFlangeSpeedFlange from <strong>Duro</strong> <strong>Dyn</strong>e drastically reduced installation time due to theaddition of pre-punched drill holes. The pre-punched holes are aligned at 1’’centers and allow for the use of any common drill gun eliminating the need for CClamps or special tools.▪ Installation in half the time as conventional flange.▪ Designed to strengthen the duct wall and connect duct sections together.SPEED FLANGE ▪ - HFurnished with an integrated sealant pocket for a secure air tight fit.▪ Manufactured in 10ft., 12ft. & 20ft. lengths.▪ Available in J Style (20 gauge) for large commercial and high-pressure applicationsand H Style (22 gauge) for low to medium pressure or residential applications.▪ Meets SMACNA rigidity class J for transverse joints (steel) or class H for transversejoints (Aluminum).▪ Bundles of 20ft. lengths available only with a Full Truckload order.▪ Specialty metal available upon request.1-43/32" 1-13/32"SPEED FLANGE - JSEALANT POCKET FOR ALL FLANGEFlame Spread - 5Smoke Density - 0Fuel Contribution - 0Life Expectancy - 20yr minimum1-23/64" 1-11/32"H Speed Flange1"1"1-11/32"1-3/8"Item # Code Description Packaging Weight (lbs.)21230 DOMJ20 J Flange - 20ft 1000ft./Bundle 74021231 DOMH20 H Flange 5- 20ft 1000ft./Bundle 53021003 SFJ20 J SPEED Flange - 20FT 1000ft./Bundle 69021006 SFH20 H SPEED Flange - 20FT 1000ft./Bundle 49521234 DOMJ12 J Flange - 12ft 1200ft./Bundle 89021235 DOMH12 H Flange - 12ft 1200ft./Bundle 64021002 SFJ12 J SPEED Flange - 12FT 1200ft./Bundle 84021005 SFH12 H SPEED Flange - 12FT 1200ft./Bundle 59521233 DOMJ10 J Flange - 10ft 500ft/Bundle 37021001 SFJ10 J SPEED Flange - 10FT 500ft/Bundle 34521004 SFH10 H SPEED Flange - 10FT 500ft./Bundle 24821236 DOMJ20SS J Flange - 20ft Stainless Steel 1000ft./Bundle 74021238 DOMJ20AL J Flange - 20ft Aluminum 1000ft./Bundle 259FLANGE PAGE 3


Cleats<strong>Dyn</strong>-O-<strong>Mate</strong> Cleats▪ DOM-CLT and DOM-PCLT for use with DOMJ & DOMH 20 gauge flanges forairtight duct connections.▪ DOM-CLT is manufactured from 20 gauge galvanized steel 6” pieces.▪ DOM-PCLT is extruded .070” PVC and designed for breakaway connection needs.▪ DOM-QCLT is compatible with <strong>Dyn</strong>-O-<strong>Mate</strong> J, Ductmate 35, CL Ward J, WardIndustries J, Hardcast flanges, TDC, TDF and TDX Connections, and is manufacturedfrom 22 gauge steel.<strong>Dyn</strong>-O-<strong>Mate</strong> Cleats0.300.770.43Item # Code Description Packaging Weight (lbs.)21250 DOMCLT 6in. Metal Cleat 500/Box (250ft.) 4021256 DOMCLTSS 6in. Stainless Steel Cleat 500/Box (250ft.) 4321252 DOMPCLT 6in. Plastic Cleat 500/Box (250ft.) 1021259 DOMQCLT 6in. Metal Quad Cleat ® 500/Box (250ft.) 40Quad Cleat ®.420.8501.290TDC/TDF Cleats▪ TDF-CLT is used with TDF connection, TDC-CLT is used with TDC connection.▪ TDC/TDF-2230 is 22 gauge steel formed into lengths of 30” long and divided into five6” cleats that are partially cut through allowing them to be easily separated into 6” pieces.▪ TDF-PCLT is extruded .070” PVC and designed for breakawayconnection needs.TDC/TDF CleatItem # Code Description Packaging Weight (lbs.)30" Pieces13230 TDC223013231 TDF22306" PiecesTDC 6in. Metal(Pre-Scored Cleat)TDF 6in. Metal(Pre-Scored Cleat)60-30in. pcs. (150ft.) 3360-30in. pcs. (150ft.) 3321257 BDCCLT TDC 6 in. Metal 500/Box (250ft.) 5521258 BTDFCLT TDF 6in. Metal 500/Box (250ft.) 5521253 TDFPCLT TDF 6in. Plastic 500/Box (250ft.) 10BreakawayADimensionsTDC TDFA .400 .450B .840 .975C 1.150 1.075BCInstallation Recommendations1/2'' to 2''sp - 1 piece on 24''centers2'' to 3'' sp - 1 piece on 18'' centers4'' to 6'' sp - 1 piece on 12'' centersOver 10'' sp - continuous cleatPAGE 4CLEATS


ADDJ CornerB<strong>Dyn</strong>-O-<strong>Mate</strong> CornersCornersDimensionsDDJ DDHA 1.15 .76B 1.88 1.50C 4.22 3.35DDH CornerC▪ DDJ corners are manufactured from 11-gauge steel. For use with DOMJ Flange.▪ DDH corners are manufactured from 12-gauge steel. For use with DOMH Flange.▪ Speed Corners have tapered coined corner tips for fast/easy handinsertion in to the Flange eliminating the need for a tinner’s hammer.▪ Speed Corners are formed from galvanized G 60 or better 12ga USAmade steel. For use with standard J Flange.▪ Nuts and Bolts are also sold separately. (See page 8)J Speed Corner4.2” sq29/64” sqItem # Code DescriptionPackagingWeight(lbs.)21240 DDJ Corner for DOMJ Flange 250/Box 7521241 DDH Corner for DOMH Flange 250/Box 3821247 DDJSS Stainless Steel Corner for DOMJSS Flange 250/Box 5821248 DDJAL Aluminum Corner for DOMJAL Flange 250/Box 2621242 DDJNB J Corner with 3/8 in. Nut & Bolt 250/Box 8021249 DDHNB H Corner with 1/2 in. Nut & Bolt 250/Box 4521094 DDJS J Speed Corner 250/Box 7021095 DDJSNB J Speed Corner with 3/8” Nuts & Bolts 250/Box 80ADOMC CornerBDimensionsDOMC DOMFA 1.225 1.275B 1.937 1.937C 4.055 4.055DOMF Corner1.2251.937DDFS StackableDDCS Stackable4.055Quad Corner ®CTDC/TDF Corners▪ DOMC and DOMF corners are manufactured from 16-gauge steel.▪ DDCS (TDC) & DDFS (TDF) corners are for use in corner insertion machines andare manufactured from 16-gauge steel.▪ Nuts and Bolts are sold separately. (See page 8)Item # Code Description Packaging Weight(lbs.)21254 DOMC TDC Corner 250/Box 4621255 DOMF TDF Corner 250/Box 4621280 DDC-SS TDC Stainless Steel Corner 300 Series 250/Box 3721281 DDC-AL TDC Aluminum Corner 250/Box 1421282 DDF-SS TDF Stainless Steel Corner 300 Series 250/Box 3721283 DDF-AL TDF Aluminum Corner 250/Box 1421284 DDC-316SS TDC Stainless Steel Corner 316 Series 250/Box 3721285 DDF-316SS TDF Stainless Steel Corner 316 Series 250/Box 3721245 DDCS TDC Stackable Cornermatic Corner 250/Box 3521264 DDCS-SS TDC Stainless Steel Stackable 250/Box 39Cornermatic Corner21265 DDCS-AL TDC Aluminum Stackable250/Box 16Cornermatic Corner21246 DDFS TDF Stackable Cornermatic Corner 250/Box 3521232 DDCSP TDC Stackable Corner 250/Box 3521237 DDFSP TDF Stackable Corner 250/Box 35Quad Corner ®1.2182.2344.094▪ Compatible with <strong>Dyn</strong>-O-<strong>Mate</strong> ® J, Ductmate 35, CL Ward J, Ward Industries J,and Hardcast flanges, TDC, TDF & TDX connections.▪ Quad corners are manufactured from 16-gauge steel.▪ Other gauges and materials available upon request.Item # Code Description Packaging Weight (lbs.)21270 DDEJ Quad Corner 250/Box 33CORNERS PAGE 5


Hangers & AngleCoiled & Flat Galvanized StrapCOILED DURO STRAP▪ Versatile product used for hanging ductwork.▪ Coiled <strong>Duro</strong> Strap is manufactured from 16, 18, 22, 24 and 26 gauge steel.▪ Coiled straps make it convenient to carry and easy to cut without wasting material.▪ Perforated Galvanized Strap has alternating hole sizes to accommodatesheet metal screws as well as nut & bolt combinations.Perforated Galvanized Strap* Perforated Galvanized Strap is made in Canada.Item # Code Description Packaging Weight(lbs.)13249 PGS24 24 ga. Perforated Galvanized Strap-3/4 in. 100ft./Box 413250 GS16 16ga. Galvanized <strong>Duro</strong> Strap-1in. 200ft./Box 4413251 GS18 18ga. Galvanized <strong>Duro</strong> Strap-1in. 200ft./Box 3613252 GS22 22ga. Galvanized <strong>Duro</strong> Strap-1in. 200ft./Box 2413253 GS24 24ga. Galvanized <strong>Duro</strong> Strap-1in. 200ft./Box 2013254 GS26 26ga. Galvanized <strong>Duro</strong> Strap-1in. 200ft./Box 20Coiled <strong>Duro</strong> StrapFLAT HANGING STRAP▪ Versatile product used for hanging ductwork.▪ Flat Hanging Strap is manufactured from 16, 18, 22, and 24 gauge steel.▪ Flat Hanging Strap is sold in pre-cut lengths of 10ft.Flat Hanging StrapItem # Code Description Packaging Weight(lbs.)13270 HS1610 16ga. Galvanized Hanging Strap-1in. 10-10ft.50pcs./Bundle13271 HS1810 18ga. Galvanized Hanging Strap-1in. 10-10ft.40pcs./Bundle13272 HS2210 22ga. Galvanized Hanging Strap-1in. 10-10ft.30pcs./Bundle13273 HS2410 24ga. Galvanized <strong>Duro</strong> Strap-1in. 10-10ft.pcs./Bundle25Punched Angle Iron▪ Versatile product used for reinforcing & mounting duct.▪ Manufactured from 16 gauge galvanized steel.▪ 3/16" holes on 4" centers.▪ Available in 12' lengths.▪ Also available in aluminum & stainless steel.Punched Angle IronItem # Code Description Packaging Weight (lbs.)21221 PAI1612 1-1/2in x 1-1/2in x 12 ft600 ft / bundle 350 / bundle16ga Punched Angle IronPAGE 6HANGERS & ANGLE


Threaded Rod & AccessoriesThreaded RodThreaded RodHanging ductwork, equipment, wiring trays or other building componentsrequires secure structural assemblies. These assemblies are comprised ofsupport members attached to building anchor points with fasteners. Thesupport members are often lengths of strut or angle iron. The fastenerfrequently is threaded rod combined with washers and nuts.▪ Five diameters; 1/4”, 3/8”, 1/2”, 5/8", 3/4"▪ Shipped in sturdy cardboard tubes▪ Zinc PlatedItem # Code Description Packaging Weight(lbs.)21164 TR14ZP06 1/4in Threaded Rod 6ft 50 / Tube 3521165 TR38ZP06 3/8in Threaded Rod 6ft 25 / Tube 4321166 TR12ZP06 1/2in Threaded Rod 6ft 12 / Tube 3721161 TR58ZP06 5/8in Threaded Rod 6ft- Made in the U.S.A. 8 / Tube 4021162 TR34ZP06 3/4in Threaded Rod 6ft- Made in the U.S.A. 5 / Tube 3821167 TR14ZP10 1/4in Threaded Rod 10ft 50 / Tube 5921168 TR38ZP10 3/8in Threaded Rod 10ft 25 / Tube 7221169 TR12ZP10 1/2in Threaded Rod 10ft 12 / Tube 6221163 TR14ZP12USA 1/4in Threaded Rod 12ft - Made in the U.S.A. 50 / Tube 7021159 TR38ZP12USA 3/8in Threaded Rod 12ft - Made in the U.S.A. 25 / Tube 8621160 TR12ZP12USA 1/2in Threaded Rod 12ft - Made in the U.S.A. 12 / Tube 7821188 TR38ZP12 3/8in Threaded Rod 12ft 25 / Tube 8621189 TR12ZP12 1/2in Threaded Rod 12ft 12 / Tube 78AccessoriesFender WashersFlat WashersFender WashersItem # Code Description PackagingWeight(lbs.)21276 FDW12B 1/2in x 1.5in Fender Washer Bulk 50# Box 5021273 FDW12C 1/2in x 1.5in Fender Washer 100/Box 2.8121274 FDW14B 1/4in x 1.5in Fender Washer Bulk 50# Box 5021271 FDW14C 1/4in x 1.5in Fender Washer 100/Box 2.621275 FDW38B 3/8in x 1.5in Fender Washer Bulk 50# Box 5021272 FDW38C 3/8in x 1.5in Fender Washer 100/Box 2.68Flat WashersWeightItem # Code Description Packaging (lbs.)21106 FW12B 1/2in Flat Washer Bulk 50# Box 5021107 FW12C 1/2in Flat Washer 100/Box 3.3421133 FW14B 1/4in Flat Washer Bulk 50# Box 5021134 FW14C 1/4in Flat Washer 100/Box .5721140 FW38B 3/8in Flat Washer Bulk 50# Box 5021141 FW38C 3/8in Flat Washer 100/Box 1.44THREADED ROD & ACCESSORIES PAGE 7


Threaded Rod & AccessoriesNuts and BoltsItem # Code Description PackagingWeight(lbs.)21132 HN12B 1/2-13 Hex Nut 1800/Box 65.5221131 HN12C 1/2-13 Hex Nut 100/Box 3.6421077 HN14B 1/4-20 Hex Nut Bulk 9000/Box 64.821069 HN14C 1/4-20 Hex Nut 100/Box .7221066 HN38B 3/8-16 Hex Nut Bulk 3000/Box 9021067 HN38C 3/8-16 Hex Nut 100/Box 321086 HN38CSS 3/8 in. 302 Stainless Hex Nut 100/Box 321060 DOMNB38 3/8 in. Nuts & Bolts 125/Bag 821061 DOMNB14 1/4 in. Nuts & Bolts 125/Bag 321065 DOMB381B 3/8-16 x 1 Bolt Bulk 1000/Box 6021068 DOMB381C 3/8-16 x 1 Bolt 100/Box 621087 DOMB381CSS 3/8 in. x 1 in. 304 Stainless Bolt 100/Box 621063 DOMB38114B 3/8-16 x 1-1/4 Bolt Bulk 1000/Box 4921064 DOMB38112B 3/8-16 x 1-1/2 Bolt Bulk 800/Box 45Nuts & BoltsRod CouplingsItem # Code Description PackagingWeight(lbs.)21127 STRC12B 1/2in Rod Coupling-1-1/4in Long 800/Box 46.3221130 STRC12C 1/2in Rod Coupling-1-1/4in Long 100/Box 7.0421125 STRC14B 1/4in Rod Coupling-7/8in Long 2500/Box 46.2521128 STRC14C 1/4in Rod Coupling-7/8in Long 100/Box 1.8521126 STRC38B 3/8in Rod Coupling-1-1/4in Long 1250/Box 8821129 STRC38C 3/8in Rod Coupling-1-1/4in Long 100/Box 5.79Rod CouplingsC-ClampBeam ClampsThe Beam Clamp is a structural attachment to the top or bottom of metal I-beams,purlins, channel, or angle iron. It comes in both a large or small mouth and anElectro-Galvanized or plain finish. It is available for 3/8’’ and 1/2’’ threaded rod.Item # Code Description Packaging Weight(lbs.)13185 CC38N3/8in Plated Stamped C-Clamp w/ Lock100/BoxNut3913188 BC38NS 3/8in Plated Small Mouth Cast Beam- 100/Box 33Clamp w/ Lock Nut13189 BC12NS 1/2in Plated Small Mouth Cast Beam- 50/Box 34Clamp w/ Lock Nut13191 BC38NL 3/8in Plated Large Mouth Cast Beam-Clamp w/ Lock Nut100/Box 37Small Mouth ClampPAGE 8THREADED ROD & ACCESSORIES


Flat Drive, Flat S & Standing SStanding SStanding S Lock1 3 / 16’’1▪ Designed to reinforce the connection on the wider ductwork applications.▪ Available in 5ft. or 10ft. lengths.Item # Code Description Packaging Weight(lbs.)13235 SS-2210 22ga. 1in. Standing S 10ft. 10-10ft. pcs./Bundle 6913214 SS-2410 24ga. 1in. Standing S 10ft. 10-10ft. pcs./Bundle 4813216 SS12-2405 24ga. 1/2in. Standing S 5ft. 50-5ft. pcs./Bundle 1213215 SS-2610 26ga. 1in. Standing S 10ft. 10-10ft. pcs./Bundle 3913237 SS-2605 26ga. 1in. Standing S 5ft. 10-5ft. pcs./Bundle 2013228 SS12-2610 26ga. 1/2in. Standing S 10ft. 10-10ft. pcs./Bundle 2013212 SS12-2605 26ga. 1/2in. Standing S 5ft. 50-5ft. pcs./Bundle 1013217 SSSS-2410 300 Series Stainless Steel 10-10ft. pcs./Bundle 48Standing S 10ft.13210 SSAL-2410 Aluminum Standing S 10ft. 10-10ft. pcs./Bundle 20Flat DriveFlat Drive Cleat▪ Designed to secure the connection for lighter ductwork applications.▪ Perfect for lighter gauge and residential ductwork applications.▪ Tapered ends for an easy start.▪ Available in 5ft. or 10ft. lengths.Item # Code Description Packaging Weight(lbs.)13255 FD-2410 24ga. Flat Drive 10ft. 10-10ft. pcs./Bundle 1713211 FD-2405 24ga. Flat Drive 5ft. 10-5ft. pcs/Bundle 8.513257 FD-2610 26ga. Flat Drive 10ft. 10-10ft. pcs./Bundle 1413218 FD-2605 26ga. Flat Drive 5ft. 10-5ft. pcs./Bundle 713262 FDSS-2410 Stainless Steel Flat Drive 10ft. 10-10ft. pcs./Bundle 1713260 FDAL-2410 Aluminum Flat Drive 10ft. 10-10ft. pcs./Bundle 6Flat S LockFlat S Lock▪ Designed to secure the connection for lighter ductwork applications.▪ Available in 5ft. or 10ft. lengths.Item # Code Description Packaging Weight(lbs.)13256 FS-2410 24ga. Flat S Lock 10ft. 10-10ft. pcs./Bundle 3013213 FS-2405 24ga. Flat S Lock 5ft. 50-5ft. pcs./Bundle 1513258 FS-2610 26ga. Flat S Lock 10ft. 10-10ft. pcs./Bundle 2413219 FS-2605 26ga. Flat S Lock 5ft. 10-5ft. pcs./Bundle 1213277 FSSS-2410 Stainless Steel Flat S Lock 10ft. 10-10ft. pcs./Bundle 3013275 FSAL-2410 Aluminum Flat S Lock 10ft. 10-10ft. pcs./Bundle 8FLAT DRIVE, FLAT S & STANDING S PAGE 9


Cut-To-LengthCut-To-Length Flat Drive CleatItem # Code Description Packaging Weight (lbs.)13350 FDC0824 24 gage 8in Flat Drive 100/Box 1613351 FDC1024 24 gage 10in Flat Drive 100/Box 1913352 FDC1224 24 gage 12in Flat Drive 100/Box 2213353 FDC1424 24 gage 14in Flat Drive 100/Box 2513354 FDC1624 24 gage 16in Flat Drive 100/Box 28.513355 FDC1824 24 gage 18in Flat Drive 100/Box 31.513356 FDC2024 24 gage 20in Flat Drive 100/Box 3513357 FDC2224 24 gage 22in Flat Drive 100/Box 3813358 FDC2424 24 gage 24in Flat Drive 100/Box 41Cut-to-Length Flat Drive Cleat without a Tab is available upon request.Cut-to-Length Flat DriveItem # Code Description Packaging Weight (lbs.)13340 FDC8 26 gage 8in Flat Drive 100/Box 1313341 FDC10 26 gage 10in Flat Drive 100/Box 16Cut-to-Length Flat Drive Cleat without a Tab is available upon request.Cut-To-Length Flat S LockItem # Code Description Packaging Weight (lbs.)13310 FSC0824 24 gage 8in Flat S Lock 100/Box 2113311 FSC1024 24 gage 10in Flat S Lock 100/Box 2713312 FSC1224 24 gage 12in Flat S Lock 100/Box 3213313 FSC1424 24 gage 14in Flat S Lock 100/Box 3813314 FSC1524 24 gage 15in Flat S Lock 100/Box 40.513315 FSC1624 24 gage 16in Flat S Lock 100/Box 4313316 FSC1824 24 gage 18in Flat S Lock 100/Box 4913317 FSC2024 24 gage 20in Flat S Lock 100/Box 5413318 FSC2224 24 gage 22in Flat S Lock 100/Box 6013319 FSC2424 24 gage 24in Flat S Lock 100/Box 65Cut-to-Length Flat S LockItem # Code Description Packaging Weight (lbs.)13320 FSC08 26 gage 8in Flat S Lock 100/Box 1713321 FSC10 26 gage 10in Flat S Lock 100/Box 2213322 FSC12 26 gage 12in Flat S Lock 100/Box 2613323 FSC14 26 gage 14in Flat S Lock 100/Box 3113324 FSC15 26 gage 15in Flat S Lock 100/Box 3313325 FSC16 26 gage 16in Flat S Lock 100/Box 3513326 FSC18 26 gage 18in Flat S Lock 100/Box 4013327 FSC20 26 gage 20in Flat S Lock 100/Box 4413328 FSC22 26 gage 22in Flat S Lock 100/Box 4913329 FSC24 26 gage 24in Flat S Lock 100/Box 53PAGE 10CUT-TO-LENGTH


Access DoorsFlat Access Doors<strong>Dyn</strong>-O-<strong>Mate</strong> Flat Insulated Access Doors(For Rectangular Duct)WeightItem # Code Description Packaging(lbs.)21177 MFADI48 4X8 FLAT Insulated Access Door 10 Pcs./Box 1221178 MFADI812 8X12 FLAT Insulated Access Door 10 Pcs./Box 3521179 MFADI1216 12X16 FLAT Insulated Access Door 5 Pcs./Box 29*High Temperature & other sizes available upon request.<strong>Dyn</strong>-O-<strong>Mate</strong> Flat Uninsulated Access Doors(For Rectangular Duct)WeightItem # Code Description Packaging(lbs.)21170 MFADU48 4X8 FLAT UN-IAD 10 Pcs./Box 1221171 MFADU812 8X12 FLAT UN-IAD 10 Pcs./Box 3521172 MFADU1216 12X16 FLAT UN-IAD 5 Pcs./Box 29Round Access Doors2000 degree High Temp.Access Doors<strong>Dyn</strong>-O-<strong>Mate</strong> Insulated Access Doors4 x 8 Round Access Doors (For Round Duct)WeightItem # Code Description Packaging(lbs.)21135 MRADI48-7 4X8-7RD Insulated Access Door 10 Pcs./Box 1221137 MRADI48-11 4X8-11RD Insulated Access Door 10 Pcs./Box 1221138 MRADI48-14 4X8-14RD Insulated Access Door 10 Pcs./Box 128 x 12 Round Access Doors (For Round Duct)WeightItem # Code Description Packaging(lbs.)21144 MRADI812-14 8X12-14RD Insulated Access Door 10 Pcs./Box 3521146 MRADI812-18 8X12-18RD Insulated Access Door 10 Pcs./Box 3521148 MRADI812-22 8X12-22RD Insulated Access Door 10 Pcs./Box 3512 x 16 Round Access Doors (For Round Duct)WeightItem # Code Description Packaging(lbs.)21151 MRADI216-18 12X16-18RD Insulated Access Door 5 Pcs./Box 2921154 MRADI1216-24 12X16-24RD Insulated Access Door 5 Pcs./Box 29<strong>Dyn</strong>-O-<strong>Mate</strong> Uninsulated Access Doors4 X 8 ROUND ACCESS DOORS (For Round Duct)WeightItem # Code Description Packaging(lbs.)21101 MRADU48-7 4X8-7RD UN-IAD 10 Pcs./Box 1221103 MRADU48-11 4X8-11RD UN-IAD 10 Pcs./Box 1221104 MRADU48-14 4X8-14RD UN-IAD 10 Pcs./Box 128 X 12 ROUND ACCESS DOORS (For Round Duct)WeightItem # Code Description Packaging(lbs.)21110 MRADU812-14 8X12-14RD UN-IAD 10 Pcs./Box 3521112 MRADU812-18 8X12-18RD UN-IAD 10 Pcs./Box 3521114 MRADU812-22 8X12-22RD UN-IAD 10 Pcs./Box 3512 X 16 ROUND ACCESS DOORS (For Round Duct)WeightItem # Code Description Packaging(lbs.)21117 MRADU1216-18 12X16-18RD UN-IAD 5 Pcs./Box 2921120 MRADU1216-24 12X16-24RD UN-IAD 5 Pcs./Box 292000º High Temp Access DoorsWeightItem # Code Description Packaging(lbs.)21190 MHTAD2000804 2000 Degree Door Only 8x4 10 Pcs./Box 1621191 MHTAD201208 2000 Degree Door Only 12x8 10 Pcs./Box 4121192 MHTAD201612 2000 Degree Door Only 16x12 5 Pcs./Box 3621195 MHTADC200804 2000 Degree Door w/Plate 8x4 10 Pcs./Box 3521196 MHTADC201208 2000 Degree Door w/Plate 12x8 10 Pcs./Box 7021197 MHTADC201612 2000 Degree Door w/Plate 16x12 5 Pcs./Box 59ACCESS DOORS PAGE 11


Vane and Rail▪ Hollow Turning Vane and Vane Rail are designed to redirect the air throughelbows and tees in the ductwork without significant loss of air pressure.Assembled Vane & Rail minimizes turbulence in the ductwork.▪ <strong>Duro</strong> Rail has self aligning tabs for easy vane installation.▪ 2in. Turning Vane are manufactured from 26-gauge galvanized steel.▪ 4in. Turning Vane are manufactured from 24-gauge galvanized steel.▪ 2in. and 4in. Vane Rail are manufactured from 24 or 22-gauge galvanizedsteel.2'' Vane & RailHollow Turning VaneItem # Code Description Packaging Weight(lbs.)13203 HTV2-2610 26ga. 2in.Turning Vane 10ft.13220 HTVAL2-10 Alum. 2in.Turning Vane 10ft.13224 HTVSS2-10 Stainless 2in.Turning Vane 10ft.13207 HTV4-2410 24ga. 4in.Turning Vane 10ft.13222 HTVAL4-10 Alum. 4in.Turning Vane 10ft.13226 HTVSS4-10 Stainless 4in.Turning Vane 10ft.5-10ft.pcs./Bundle5-10ft.pcs./Bundle5-10ft.pcs./Bundle5-10ft.pcs./Bundle5-10ft.pcs./Bundle5-10ft.pcs./BundleMasterSkid Qty.24 7200ft.13 7200ft.23 7200ft.55 2500ft.33 2500ft.58 2500ft.4'' Vane & RailVane RailItem # Code Description Packaging Weight(lbs.)13300 DHVR2-2210 2in.Vane Rail 10ft.13221 HVRAL2-10 Alum. 2in.Vane Rail 10ft.13225 HVRSS2-10 Stainless 2in.Vane Rail 10ft.13302 DHVR4-2210 4in.Vane Rail 10ft.13223 HVRAL4-10 Alum. 4in.Vane Rail 10ft.13227 HVRSS4-10 Stainless 4in.Vane Rail 10ft.Min. 24 Ga.(0.70 mm)Vanes2 1/4’’(57 mm) (57 mm)22 Ga. (0.85mm)PAGE 122 1/4’’2 1/4’’R(57 mm)45 o 45 o 4 1/2’’R(114 mm)RunnerType 2Min. 26 Ga.(0.55 mm)Vanes3 1/4’’(83 mm)1 1/8’’4 1/2’’(114mm)or 7’’(178mm)1 1/8’’(29 mm) (29 mm)(25 mm) 1‘’R2‘’R(51mm)45 o 45 oVANE & RAILMin. 24 Ga.(0.70 mm)Vanes10-10ft.pcs./Bundle10-10ft.pcs./Bundle10-10ft.pcs./Bundle10-10ft.pcs./Bundle10-10ft. 2 1/4’’pcs./Bundle(57 mm)10-10ft.pcs./Bundle2 1/4’’R2 1/4’’(57 mm)2 1/8’’(54 mm)22 Ga. (0.85mm)(57 mm)45 o 45 o 4 1/2’’R(114 mm)Runner Type 1Free area betweenDouble Wall VanesRunnerType Approximates 2elbowinlet area.RunnerType 2Min. 26 Ga.(0.55 mm)Vanes3 1/4’’(83 mm)1 1/2’’(38mm)MIN.4 1/2’’(114mm)or 7’’(178mm)Single Vane ScheduleSP R SP GASmall 2’’ 1 1/2’’ 24(51mm) (38mm) (0.70mm)Large 4 1/2’’ 3 1/4’’ 22MasterSkid Qty.46 4000ft.18 4000ft.30 4000ft.71 2000ft.36 1 1/8’’ 1 1/8’’ 2000ft.(29 mm) (29 mm)59 2000ft.(25 mm) 1‘’R2‘’R(51mm)45 o 45 o45 o R45 o2 1/8’’(54 mm)RunnerType 2SPMin. 24 Ga.(0.70 mm)Vanes2 1/4’’2 1/4’’(57 mm) (57 mm)22 Ga. (0.85mm)2 1/4’’R(57 mm)45 o 45 o 4 1/2’’R(114 mm)Runner Type 1Free area betweenDouble Wall VanesApproximates elbowinlet area.RunnerType 2Min. 26 Ga.(0.55 mm)Vanes3 1/4’’(83 mm)1 1/2’’(38mm)MIN.Single Vane ScheduleR SP GASmall 2’’ 1 1/2’’ 24(51mm) (38mm) (0.70mm)Large 4 1/2’’ 3 1/4’’ 22(114mm) (83mm) (0.85mm)4 1/2’’(114mm)or 7’’(178mm)See notes on fig.2-4. Other runnersmay be used as appropriate. Othervane sizes, spacings or configurationsare acceptable on designer approval.1 1/8’’1 1/8’’(29 mm) (29 mm)(25 mm) 1‘’R2‘’R(51mm)45 o 45 o45 o R45 oBolt, Screw orWeld RunnerTo DuctAs Described on page 2.5, Figure 2-3 of theSMACNA HVAC Duct Construction Standards, 2nd Ed., 1995.2 1/8’’(54 mm)RunnerType 2SP


<strong>Dyn</strong>-O-Wrap<strong>Dyn</strong>-O-Wrap<strong>Dyn</strong>-O-WrapA self-adhesive film which can protect uninstalled duct sections from the intrusionof contaminates. Available in different sizes and several varieties, includingPuncture Resistant Wrap and Reverse Puncture Resistant Wrap.DYN-O-WRAP▪ Excellent adhesion to ductwork, yet easily removable without leaving residue.▪ Color: Dark blue tint, UV resistant and waterproofItem # Code Description Packaging Wt. perRoll (lbs.)13380 DW24-200 <strong>Dyn</strong>-O-Wrap 24’’ x 200’ 6 Rolls/Box 613384 DW36-200 <strong>Dyn</strong>-O-Wrap 36’’ x 200’ 1 Roll/Box 913388 DW48-200 <strong>Dyn</strong>-O-Wrap 48” x 200’ 1 Roll/Box 14PUNCTURE RESISTANT DYN-O-WRAP & REVERSE PUNCTURE RESISTANT DYN-O-WRAP▪ Excellent adhesion to ductwork, yet easily removable without leaving residue.▪ Color: Light blue tint, UV resistant and waterproofPuncture ResistantItem # Code Description Packaging Wt. perRoll (lbs.)13382 PRW24-200 Puncture Resistant <strong>Dyn</strong>-O-Wrap 24” x 200’ 6 Rolls/Box 613386 PRW36-200 Puncture Resistant <strong>Dyn</strong>-O-Wrap 36” x 200’ 1 Roll/Box 913389 PRW48-200 Puncture Resistant <strong>Dyn</strong>-O-Wrap 48” x 200’ 1 Roll/Box 1413392 RPRW24-200 Reverse Puncture Resistant <strong>Dyn</strong>-O-Wrap 24” x 200’ 6 Rolls/Box 613393 RPRW36-200 Reverse Puncture Resistant <strong>Dyn</strong>-O-Wrap 36” x 200’ 1 Roll/Box 913394 RPRW48-200 Reverse Puncture Resistant <strong>Dyn</strong>-O-Wrap 48” x 200’ 1 Roll/Box 1413296 IDW24-200 <strong>Dyn</strong>-O-Wrap Imported 24" x 200' 1 Roll/Box 513297 IDW36-200 <strong>Dyn</strong>-O-Wrap Imported 36" x 200' 1 Roll/Box 813299 IDW24-500 <strong>Dyn</strong>-O-Wrap Imported 24" x 500' 1 Roll/Box 1213300 IDW36-500 <strong>Dyn</strong>-O-Wrap Imported 36" x 500' 1 Roll/Box 19Grille MaskingGrille Masking<strong>Duro</strong> <strong>Dyn</strong>e’s Grille Masking is a self-adhesive film specially designed as a protectivecovering for grilles and registers on the jobsite. The 8” width makes it ideal andquick to install on the most common sizes encountered. The Quick Tack adhesivestrongly adheres to air devices for many types of testing and yet pulls off easilywithout leaving residue.Item # Code Description Packaging Weight (lbs.)<strong>Dyn</strong>-O-Wrap Dispenser13396 GM8-200 Grille Masking 8in x 200ft. 3 Rolls/Box 36<strong>Dyn</strong>-O-Wrap Dispenser▪ Perfect solution for storing and dispensing different sizes and types of <strong>Dyn</strong>-O-Wrap▪ Allows for easy application (no awkward maneuvering).▪ Keeps wrap off of the floor to prevent dirt from adhering to the adhesive.Item # Code Description Packaging Weight (lbs.)43006 DWD1 <strong>Dyn</strong>-O-Wrap Dispenser 1 52DYN-O-WRAP PAGE 13


Tools & AccessoriesToolsTDC/TDF CRIMPER TOOLThe <strong>Dyn</strong>-O-<strong>Mate</strong> Crimper installs the TDC or TDF corner and crimps the edge overto hold the corner in place.CrimperCLEAT TOOLInstall the finishing cleat quickly and easily. The tool pulls the ductwork tightwhile installing the cleat and creating a quick, easy and clean seal on ductconnections over 48''.Item # Code Description Packaging Weight (lbs.)21072 DOMCRMP TDC/TDF Crimper 1 each 221070 DOMCT DOM Cleat Tool 1 each 121051 DCTDOM Deluxe Cleat Tool 1 each 1VANE DIMPLER• Replaces tack welding, chiseling, or other awkward and time consuming methods.• The Vane Dimpler can be used on the vane before or after placement onthe rail. Either way, its locked tight!• No other tools or welding equipment necessary.Item # Code Description Packaging Weight (lbs.)21062 DOM6 Vane Dimpler 1 each 1DOMCT Cleat ToolDeluxe Cleat ToolGasketingButyl and Neoprene Gaskets offer an easy-to-use sealant to provide a moistureand vapor-tight seal to prohibit water and dust from any connection at anyatmospheric pressure.BUTYL GASKET▪ Butyl gasket is a permanently soft caulking compound with a high percentageof virgin butyl rubber.▪ It will adhere to most dry, clean surfaces such as steel, aluminum, plastics,wood and concrete and can withstand movement without cracking.▪ Color: Grey, Black or Off White▪ Temperature range: -40°F to 249°F▪ Non-CorrosiveNEOPRENE GASKET▪ Neoprene gasket tape is a self-adhesive closed cell industrial foam comprisedof neoprene, PVC and Nitrile.▪ Great for use when connecting ductwork that might periodically have to betaken apart for maintenance purposes.▪ Color: Black▪ Temperature range: -40°F to 200°F▪ Good chemical resistance.Item # Code Description Packaging Weight(lbs.)21042 BTL500 Butyl Gasketing 25ft./Roll 500ft./Box 4621043 NEO750 Neoprene Gasketing 50ft./Roll 750ft./Box 1221045 BTL316-12DG 3/16in. x 1/2in. Non-UL Butyl Dark 500ft./Box 43Gray 25ft./Roll21046 BTL316-58LG 3/16in. x 5/8in. Non-UL Butyl Light 500ft./Roll 45Gray 25ft./Roll8261 BN316-34 3/16in. x 3/4in. Neoprene Gasketing 1000ft./Box 1450ft./Roll8151 BN516-34 5/16in. x 3/4in. Neoprene Gasketing50ft./Roll1000ft./Box 20Vane DimplerBN316-34BTL500NEO750PAGE 14TOOLS & ACCESSORIES


Tools & Accessories<strong>Dyn</strong>-O-Loc ®<strong>Dyn</strong>-O-Loc ®Tie rods can be used to support duct sizes over 48". <strong>Dyn</strong>-O-Locs insert into theends of the hollow tie rods to provide a means of attaching the rods to the duct.Available for use in 1/2in. and 3/4in. I.D. rods they are easily inserted and havebeen pull tested to withstand over 1900 lbs.Item # Code Description Packaging Weight (lbs.)21097 DOMRL12 1/2in. <strong>Dyn</strong>-O-Loc 250/Box 1321098 DOMRL34 3/4in. <strong>Dyn</strong>-O-Loc 250/Box 1321076 RLT <strong>Dyn</strong>-O-Loc Tool 1 each 1<strong>Dyn</strong>-O-Claw<strong>Dyn</strong>-O-ClawWhen conduits cross inside the ductwork, they can vibrate with the passing of airflowand create a rattling sound. The <strong>Dyn</strong>-O-Claw is designed to join conduits andeliminate their vibration in the duct. <strong>Dyn</strong>-O-Claws are easier and faster than otheralternatives such as ties or welding.Item # Code Description Packaging Weight (lbs.)21088 DOMDOC12 1/2in. <strong>Dyn</strong>-O-Claw 250/Box 4021089 DOMDOC34 3/4in. <strong>Dyn</strong>-O-Claw 200/Box 40'A'NosingTAPEDimensionsInsulation A1/2" 1-1/8"1" 1-5/8"1-1/2" 2-1/8"2" 2-5/8"<strong>Dyn</strong>-O-<strong>Mate</strong> Nosing▪ Protects exposed edge of the duct liner.▪ Minimizes the possibility of liner delaminating and causing blockage in the ductwork.▪ Manufactured from 26-gauge galvanized steel.▪ Designed with self adhesive tape for easy installation.▪ Available for ½in., 1in., 1-½in., and 2in. insulation.▪ Sold in 10 ft. lengths.Item#Code Description Packaging Weight(lbs.)21260 NOS012 Noising for 1/2 in. insulation - 10 ft. 1000ft./Bundle 1321261 NOS100 Noising for 1 in. insulation - 10 ft. 1000ft./Bundle 1621262 NOS112 Noising for 1-1/2 in. insulation - 10 ft. 1000ft./Bundle 1921263 NOS200 Noising for 2 in. insulation - 10 ft. 1000ft./Bundle 231"(REF)Pittsburgh LockOpening ToolPittsburgh Lock Opening ToolThe Pittsburgh Lock Opening Tool is used to open a longitudinal seam that is used inthe fabrication of sheet metal ductwork.Item # Code Description Packaging Weight (lbs.)10061 POT Pittsburgh Lock Opening Tool 1 1TOOLS & ACCESSORIES PAGE 15


<strong>Dyn</strong>-O-<strong>Mate</strong> ComponentsRecommended for 26 ga. through and including 14 ga. ductworkH SystemJ SystemH FLANGERollformed from 22ga. galvanized steel.H CORNER12 ga. galvanizedsteelJ FLANGERollformed from 20ga. galvanized steel.J CORNER11 ga. galvanizedsteelLarge sealant pocket on all flange systemsDYN-O-MATE METAL CLEAT• Roll formed from 20 ga.galvanized steel• 6” pieces• Suitable for driving in tightinstallations• Also available in PVCGasketingAvailable in Butyl and Closed Cell NeopreneBUTYL GASKETFlame Spread - 20Fuel Contribution - 0Smoke Density - 0Thickness - 3/16”Life Expectancy - 20 yr. min.Flash Point - 300° FCompression set - noneNEOPRENE GASKETFlame Spread - 10Fuel Contribution - 0Smoke Density - 0Thickness - 5/16”SEALANTFlame Spread - 5Smoke Density - 0Fuel Contribution - 0Life Expectancy - 20year minimumTDC/TDF NEOPRENEGASKETFlame Spread - 10Fuel Contribution - 0Smoke Density - 0Thickness - 3/16”Assembly InstructionsDOMJ Flange & DOMH FlangeStep 1: Cutting the AngleThe angle should be cut 1 5/16'' shorter than the duct dimensions,cutting the angle with the spine pointing up. Using a chop sawwith a 3 h.p. motor and a metal cutting blade helps to insure aclean edge with no burrs.Step 2: Frame Assembly & SeatingUsing a mallet, insert the corners into the shorter angles; installthe larger angles to complete the frame. The raised portion ofthe corner should be facing inward with the "<strong>Dyn</strong>-O-<strong>Mate</strong>" namevisible from the outside.Starting at a corner, use a mallet, hammer the completed frameonto the raw edge of the duct section. Moving in one direction,make sure the duct is seated into the mastic.NOTE: The duct section should not be notched.PAGE 16DYN-O-MATE COMPONENTS


Assembly InstructionsDOMJ Flange & DOMH Flange (continued)Step 3: Fastening the FrameThe frame can be fastened to the ductwork with either Hex Texscrews (10x3/4) or spot welds.NOTE: On installations of 3'' s.p. or above or on systems whereleakage is to be less than 1% spot welding is recommended.Tek screwing of the angle or spot welding must start within 3/4'' ofeach end of the angle at the duct section corners.STATIC PRESSUREDUCT SIZERECOMMENDED CENTERS1/2” to 1”1” to 2”To 48”49” to 96”Over 96”To 42”43” to 96”Over 96”At 4 corners & centerline30” centers18” centersAt 4 corners & centerline18” centers12” centersImportant: Since sheet metal ductworkinstallations are sometimes used bythe other trades as scaffolding, actualjob conditions should really indicatethe amount of spot welding or othermeans of fastening.2” to 3”To 36”37” to 72”Over 72”At 4 corners & centerline18” centers12” centers3” to 6”To 24”25” to 60”Over 60”At 4 corners & centerline18” centers12” centersOver 6”To 18”19” to 48”Over 48”At 4 corners & centerline12” centers8” centersStep 4: Gasket ApplicationApply a 2 to 3'' strip of gasket on the 4 exposed corners of one frame,as pictured.Starting at the center of the other mating frame, apply a single strap ofgasket completely around the inside edge of the frame. IMPORTANT:This gasket must also cover the exposed edge of the duct section andthe gap between the duct wall and the corner.Step 5: Installing the CleatSnap a 6'' piece of either metal or PVC cleat over the mating frame,using the following recommendations:• 1/2'' to 2''sp - 1 piece on 24''centers• 2'' to 3'' sp - 1 piece on 18'' centers• 4'' to 6'' sp - 1 piece on 12 '' centers• Over 10''sp - continuous cleatASSEMBLY INSTRUCTIONS PAGE 17


To Whom It May Concern:SUBJECT: Duct construction other than that in the HVAC-DCS-1985The foreword of the 1985 HVAC-DCS states that "Although standardization intrinsicallyinvolves selection, no intention of discrimination against the use of any product ormethod that would serve a designers's need equally or better exists." Additionally,recognition of equivalent or other construction is acknowledged in the text as follows:1. Italicized wording in paragraph one on page 1-12 states "a fifth alternative,that of using non-illustrated construction, is recognized based on sponsor demonstratedequivalency subject to the approval of authorities regulating use ofthis voluntary acceptance standard. SMACNA does not validate equivalency."2. Text on page 1-14 states that "certain joints have been assigned maximumpressure classes. Such restrictions are not intended to prohibit considerationof other limits where evidence of acceptability is presented under the equivalentconstruction principle."3. Paragraph S 1.18 on page 1-15 states that "Other construction that meets thefunctional criteria in Section VII or is as serviceable as that produced by theconstruction tables may be provided."4. A sentence on page 1-37 says "See Figure 1-4A for commentary on proprietaryjoint systems and see Section VII for joint performance evaluation."5. The text on page 1-38 "invites authorities to consider alternative constructions"and says "consult the manufacturers of alternative systems for ratings, assemblyrequirements and recommendations."6. Note 3 on page IV states that "the Association refrains from endorsement ofproprietary products." Note 4 on this page says "the Association will not reviewor judge products or components as being in compliance with the document."7. Paragraph S 3.3 on page 3-2 says "Nothing herein is intended to constituteimplied disapproval of the designer's consideration of other methods of construction."8. Paragraph S 3.26 on page 3-13 states that "Illustrations of accessories andsleeves and collars are representative of a class of such items and are notintended to preclude the use of components not precisely identical to these."9. Three alternative procedures for rating construction relative to the SMACNAtables are given on page 7-5, analysis, historical track record and testing.Commentary on witnessing tests and on use of test data is provided in the lastparagraph on page 7-11, ending with "Authorities are invited to evaluate suchconstruction based on evidence presented by sponsors." Otherwise, the performancecriteria used for the SMACNA rectangular duct tables are given inSection VII. General performance requirements are discussed on page 1-3.We think that these statements from the HVAC-DCS reflect a clear policy of SMACNA'sabstention from judging unillustrated components and systems as being equivalentwhile encouraging consideration of them based on evidence presented by sponsors.Otherwise, SMACNA has not published or authorized any addenda for the 1985 HVAC-DCS.Sincerely,John H. StrattonDirector, Technical ServicesPAGE 18SMACNA POLICY


1/2” W.G.Staticpos or negDuctDimen.SHOP STANDARDSRECTANGULAR DUCT REINFORCEMENTMinimum Rigidity Class* - Minimum Gage DuctReinforcement SpacingR=Midpoint ReinforcementT=Conduit Type Tie Rods*=These tests were done as comparative tests, and the actual duct deflection was not recorded. They did not exceedSMACNA Deflection Standards.Note: Two (2) Tie Rods - equally spaced (28'' centerline) were used8' 6' 5' 4' 3' 2 1/2' 2'26'' dn H-26 H-26 H-26 H-26 H-26 H-26 H-2627-30'' H-26 H-26 H-26 H-26 H-26 H-26 H-2631-36'' H-24 H-26 H-26 H-26 H-26 H-26 H-2637-42'' H-24 H-24 H-26 H-26 H-26 H-26 H-2643-48'' H-22 H-24 H-26 H-26 H-26 H-26 H-2649-54'' H-20 H-22 H-26 H-26 H-26 H-26 H-2655-60'' H-20 H-22 H-24 H-24 H-26 H-26 H-2661-72'' H-18 H-20 H-22 J26T H-24 H-24 H-24 H-2473-84'' J-16 H-18 H-22 J26T H-24 H-24 H-24 H-2485-96'' J-16 J-18 J22T H-20 J22 H-22 H-22 H-22 H-2297-108'' J22T J-18 J22T J-18 J22T H-18 J-22 H-18 J-22 H-18 J22109-120'' J22T J22T J22T J-18 J22T H-18 J-22 H-18 J22When referring to Table 1-3 thru Table 1-10 in the SMACNA HVAC Duct ConstructionStandards, 2 nd ed., 1995,Use the <strong>Dyn</strong>-O-<strong>Mate</strong> “H” Angle on Rigidity Class “F”, “G” and “H”Use the <strong>Dyn</strong>-O-<strong>Mate</strong> “J” Angle on Rigidity Classes above “H”The tables as shown here are the SMACNA Tables with those interpretationsalready substituted.These tests results are shown as follows:SMACNA TableVariationpermitted percertified test.DUCT CONSTRUCTION STANDARDS PAGE 19


SHOP STANDARDSRECTANGULAR DUCT REINFORCEMENTMinimum Rigidity Class* - Minimum Gage DuctReinforcement Spacing1” W.G.Staticpos or negDuctDimen.R=Midpoint ReinforcementT=Conduit Type Tie Rods*=These tests were done as comparative tests, and the actual duct deflection was not recorded. They did not exceedSMACNA Deflection Standards.Note: Two (2) Tie Rods - equally spaced (28'' centerline) were used8' 6' 5' 4' 3' 2 1/2' 2'14'' dn H-26 H-26 H-26 H-26 H-26 H-26 H-2615-20'' H-26 H-26 H-26 H-26 H-26 H-26 H-2621-24'' H-24 H-26 H-26 H-26 H-26 H-26 H-2625-30'' H-24 H-26 H-26 H-26 H-26 H-26 H-2631-36'' H-22 H-24 H-24 H-26 H-26 H-26 H-26 H-2637-42'' H-20 H-22 H-24 H-26 H-26 H-26 H-26 H-2643-48'' H-18 H-20 H-22 H-26 H-26 H-26 H-26 H-2649-54'' H-18 H-20 H-22 J-26 H-24 J-26 H-24 J-26 H-24 J-26 H-24 J-2655-60'' H-18 H-20 H-22 J-26 H-24 J-26 H-24 J-26 H-24 J-26 H-24 J-262426T61-72''' H-18 H-18 J H-22 J26T H-24 J26T H-24 J-26 H-24 J-2673-84'' J-16 J-18 J24T J-20 J22 H-22 J22 H-22 J-24 H-22 J-2485-96'' J-16 J-20 J-18 J-20 J-20 J22 H-20 J-22 H-2297-108'' J22T J-18 J22T J-18 J22T J-18 J-22 J-18 J-22109-120'' J22T J22T J-18 J22T J-18 J-22 J-18 J-22* Each duct system shall be constructed for the specific duct pressure classifications shown on the contractdrawings for the project. Where no specific duct pressure class designations are provided by the designer the1” water gage pressure class is the basis of compliance with these standards, regardless of velocity in the duct,except when the duct is variable volume: All variable volume duct upstream of VAV boxes has a 2” w.g. basis ofcompliance when the designer does not give a pressure class.*Because total pressure decreases in the direction of the flow a, duct construction pressure classification equalto fan outlet pressure (or to fan total static pressure rating) cannot economically be imposed on the entire ductsystem. Pressure in ducts near room air terminals is nearly always below 1/2” w.g.*Asterisks indicate wording that is taken directly and verbatim from the SMACNA HVAC Duct ConstructionStandards, 2nd ed., 1995.SMACNA TABLE 1-2 DUCT SEALING REQUIREMENTSSeal ClassClassASealing RequiredAll transverse joints, longitudinal seamsand duct wall penetrationsStatic PressureConstruction Class4” w.g. and upBAll transverse joints and longitudinalseams3” w.g.C Transverse Joint 2” w.g.In addition to the above, any variable air volume system duct of 1” and 1/2” w.g. construction class that is upstream of the VAV boxes shall meet Seal Class C.PAGE 20DUCT CONSTRUCTION STANDARDS


2” W.G.Staticpos or negDuctDimen.SHOP STANDARDSRECTANGULAR DUCT REINFORCEMENTMinimum Rigidity Class* - Minimum Gage DuctReinforcement SpacingR=Midpoint ReinforcementT=Conduit Type Tie Rods*=These tests were done as comparative tests, and the actual duct deflection was not recorded. They did not exceedSMACNA Deflection Standards.Note: Two (2) Tie Rods - equally spaced (28'' centerline) were used8' 6' 5' 4' 3' 2 1/2' 2'12'' dn H-26 H-26 H-26 H-26 H-26 H-26 H-2613-18'' H-24 H-24 H-26 H-26 H-26 H-26 H-2619-26'' H-22 H-24 H-26 H-26 H-26 H-26 H-2627-30'' H-20 H-22 H-24 H-26 H-26 H-26 H-2631-36'' H-18 H-20 H-22 H-24 H-24 H-26 H-26 H-2637-42'' H-16 H-18 H-20 H-24 H-24 H-24 H-26 H-26H22J26T2226T2226T43-48'' J-16 H-18 H-20 H-22 J26T H-24 H-24 H-2449-54'' J-16 H-18 J H-20 J H-24 H-24 H-2455-60'' J-16 J-18 J H-18 J H-22 H-24 H-2461-72''' J-16 J24T J-18 J26T H-22 H-22 H-24 H-2473-84'' J22T J-18 J22T J-20 J-24 J-22 J-24 J-22 H-2485-96'' J22T J-18 J22T J-18 J-20 J-20 J-22 J-22 J-2297-108'' JT22T JT22T K-18 JT22T J-18 J-22 J-18 J-22109-120'' JT22T JT22T JT22T K-18 J-22 J-18 J-222226T2226TTie Rod InstallationUsing the <strong>Dyn</strong>-O-<strong>Mate</strong> RODLOCK(Conduit Type Tie Rod) <strong>Duro</strong> <strong>Dyn</strong>e Corp., through a certified testing Program(in accordance with Chapter 7 of the SMACNA HVAC Duct Construction Standards, 2 nd ed. 1995) has usedthe Conduit Type Tie Rod being attached to the duct wall alone as the reinforcement for the panel tie rod.Example: 22 T Center tie rod:Where the Conduit Type Tie Rod is used as a flange reinforcement, “JT” or “HT”, the conduit type tie rod isinstalled as shown below:1/4-20 x 1’’ HexGrade 5 Bolt1’’ OD NEO/GALV. Washer(No Sealantrequired)Negative PressureConsult SMACNA construction standards page 2.97 Section 2.8.1 paragraph 7 for specifics onreinforcement recommendations for both Positive and negative pressure duct systems.1’’ROD LOCKDrive in withinstallation toolPull tested to 1,909 lbs.Drill 5/16dia holeinto ductwall1/2’’ ThinwallConduitDUCT CONSTRUCTION STANDARDS PAGE 21


SHOP STANDARDSRECTANGULAR DUCT REINFORCEMENTMinimum Rigidity Class* - Minimum Gage DuctReinforcement Spacing3” W.G.Staticpos or negDuctDimen.R=Midpoint ReinforcementT=Conduit Type Tie Rods*=These tests were done as comparative tests, and the actual duct deflection was not recorded. They did not exceedSMACNA Deflection Standards.Note: Two (2) Tie Rods - equally spaced (28'' centerline) were used8' 6' 5' 4' 3' 2 1/2' 2'12'' dn H-24 H-26 H-26 H-26 H-26 H-26 H-2613-18'' H-22 H-24 H-24 H-26 H-26 H-26 H-26 H-2619-22'' H-20 H-22 H-24 H-26 H-24 H-26 H-26 H-26 H-2623,24'' H-18 H-22 H-24 H-26 H-24 H-26 H-26 H-26 H-2625,26'' H-18 H-22 H-24 H-24 H-26 H-26 H-2627,28'' H-18 H-20 H-22 H-24 H-24 H-26 H-26 H-2629,30'' H-18 H-20 H-22 H-24 H-24 H-26 H-26 H-2631-36'' H-16 H-18 H-20 H-24 H-22 H-24 H-24 H-24 H-26 H-2637-42'' H-18 H-20 H-24 H-22 H-24 H-24 H-24 H-24 H-24 H-2643-48'' J-16 J-18 J26T H-20 J26T H-22 H-24 H-2449-54'' J-18 J26T J-18 J26T H-22 H-24 H-2455-60'' J-16 J24T J-18 J24T H-20 H-22 H-2461-72'' J24T J-16 J24T J-20 J24T J-22 J-24 J-2473-84'' J20T J20T J-18 J20T J-20 J-22 J-2285-96'' JT20T JT20T K-18 JT20T J-18 J-20 J-2097-108'' JT20T JT20T JT20T L-18 JT20 K-18 JT20109-120'' JT20T JT20T JT20T L-18 JT20 L-18 JT20This table shows some typical duct sizes and the weight that can besaved by changing gage per certified test:SMACNA TableVariation permitted per certified test.Duct SizeSq. Ft. per5'' Sect.Lbs./Sq. Ft..91Lbs./Sq. Ft.1.16Lbs./Sq. Ft.1.41Lbs./Sq. Ft.1.66Lbs./Sq. Ft.2.1626 ga. 24 ga. 22 ga. 20 ga. 18 ga.30/18 40 40 51 62 73 9536/24 50 50 64 76 83 11942/24 55 55 70 85 100 13148/24 60 60 76 93 110 14354/24 65 65 83 101 119 15460/30 75 75 96 116 137 17872/36 90 90 115 140 164 21484/48 110 110 140 171 201 26196/48 120 120 153 186 219 285PAGE 22DUCT CONSTRUCTION STANDARDS


4” W.G.Staticpos or negDuctDimen.SHOP STANDARDSRECTANGULAR DUCT REINFORCEMENTMinimum Rigidity Class* - Minimum Gage DuctReinforcement SpacingR=Midpoint ReinforcementT=Conduit Type Tie Rods*=These tests were done as comparative tests, and the actual duct deflection was not recorded. They did not exceedSMACNA Deflection Standards.Note: Two (2) Tie Rods - equally spaced (28'' centerline) were used8' 6' 5' 4' 3' 2 1/2' 2'10'' dn H-22 H-26 H-26 H-26 H-26 H-26 H-2611,12'' H-22 H-24 H-26 H-26 H-26 H-26 H-2613,14'' H-22 H-22 H-24 H-26 H-26 H-26 H-2615,16'' H-20 H-22 H-24 H-26 H-26 H-26 H-2617-20'' H-20 H-22 H-24 H-24 H-26 H-26 H-2621,22'' H-18 H-20 H-24 H-24 H-26 H-26 H-2623,26'' H-18 H-20 H-22 H-24 H-24 H-26 H-26 H-2627-30'' H-18 H-18 H-22 H-24 H-24 H-24 H-26 H-26 H-2631-36'' H-18 H-20 H-22 H-22 H-24 H-26 H-2637-42'' J-16 J-18 H-22 H-20 H-22 H-22 H-24 H-2643-48'' J-18 J26T J-18 J26T H-22 H-24 H-2449-54'' J-16 J24T J-18 J24T J-20 H-22 H-2455-60'' J-16 J22T J-16 J22T J-20 J-22 H-2461-72'' J20T J20T J-18 J-20 J-20 J-24 J-22 H-2473-84'' J20T J20T K-16 J20T J-18 J-20 J-20 J-2285-96'' JT20T JT20T JT20T K-18 JT20 J-2097-108'' JT18T JT18T JT20T L-18 JT20 L-18 JT20109-120'' JT18T JT18T JT18T L-18 JT18 L-18 JT18PrecautionsIn any given duct system, accidental overpressure could occur and must be accounted for by design provisions,such as fail safe features, replaceable release panels and static pressure switches that can shut downthe entire system. Note: On all duct systems that are to be tested for leakage, it is recommended that thefirst 100 feet of completed ductwork be tested before proceeding to complete the installation.SHIPPING L SHAPED DUCT WITH THE ANGLE INSTALLEDSTEP ONE STEP TWO STEP THREE STEP FOURComplete the frame andbend over the hammeredge of the Pitts-burghLock in the standardmanner.Notch the “hammeredge” of the femalePittsburgh Lock 1/4” ona 45 degree angle asshown.In the shop, install theangle on the duct withoutthe corner piece.In the field insert a cornerpiece into the angle at themale end of the PittsburghLock.DUCT CONSTRUCTION STANDARDS PAGE 23


SHOP STANDARDSRECTANGULAR DUCT REINFORCEMENTMinimum Rigidity Class* - Minimum Gage DuctReinforcement Spacing6” W.G.Staticpos or negDuctDimen.R=Midpoint ReinforcementT=Conduit Type Tie Rods*=These tests were done as comparative tests, and the actual duct deflection was not recorded. They did not exceedSMACNA Deflection Standards.Note: Two (2) Tie Rods - equally spaced (28'' centerline) were used8' 6' 5' 4' 3' 2 1/2' 2'10'' dn H-20 H-22 H-26 H-26 H-26 H-26 H-2611,12'' H-20 H-22 H-24 H-24 H-26 H-26 H-2613,14'' H-20 H-20 H-22 H-24 H-26 H-26 H-2615,18'' H-18 H-20 H-22 H-24 H-26 H-26 H-2619-22'' H-18 H-20 H-22 H-24 H-24 H-26 H-2623,24'' H-18 H-20 H-22 H-22 H-24 H-26 H-2625,28'' H-16 H-18 H-20 H-22 H-24 H-24 H-2429-30'' H-18 H-18 H24T H-22 H-24 H-24 H-2431-36'' J-16 J-18 H24T H-20 H-22 H-24 H-2437-42'' J-16 H24T J-18 H24T H-20 H-22 H-24 H-22 H-2443-48'' H24T J-18 H24T J-18 H-22 J-22 H-24 H-22 H-2449-54'' J20T J-16 J20T J-18 J-20 J-20 J-2255-60'' J20T H20T J-18 H20T J-20 J-2261-72'' JT20T JT20T K-16 JT20T J-18 J-20 J-2073-84'' JT20T JT20T JT20T L-16 JT20 K-18 JT2085-96'' JT18T JT18T JT18T IT16 JT18 L-18 JT1897-108'' JT18T JT18T JT18T JT16 JT18 L-18 JT18109-120'' JT18T JT18T JT18T KT16 JT18 KT18 JT18<strong>Dyn</strong>-O-<strong>Mate</strong> Angle as a Breakaway ConnectionA. <strong>Dyn</strong>-O-<strong>Mate</strong> frame.Use neoprene gasket between theframes. Secure duct to sleeve.B. Retaining angle, secured to sleeve only.C. Fire damper secured to sleeve.D. 20 ga. Sleeve up to 54” x 54'' - 18 ga.Sleeve 54” and up.E. Melt away (200°F) pvc cleat (typ). Install6” pieces 12” on center starting cleat atextreme end (corners).NOTE: Install duct and fire damper sleeve per normal installation procedures with bolts atthe corners until all ductwork is installed and testing is completed. After successful testing,the bolts at the corners of the fire damper sleeves are to be removed so as to insure thatduct will break away once cleats reach melting temperature of 200 degrees F.PAGE 24DUCT CONSTRUCTION STANDARDS


10” W.G.Staticpos or negDuctDimen.SHOP STANDARDSRECTANGULAR DUCT REINFORCEMENTMinimum Rigidity Class* - Minimum Gage DuctReinforcement SpacingR=Midpoint ReinforcementT=Conduit Type Tie Rods*=These tests were done as comparative tests, and the actual duct deflection was not recorded. They did not exceedSMACNA Deflection Standards.Note: Two (2) Tie Rods - equally spaced (28'' centerline) were used8' 6' 5' 4' 3' 2 1/2' 2'8'' dn H-20 H-22 H-24 H-24 H-26 H-26 H-269'',10'' H-20 H-20 H-22 H-24 H-26 H-26 H-2611'',12'' H-18 H-20 H-22 H-24 H-26 H-26 H-2613'',14'' H-18 H-18 H-20 H-22 H-24 H-26 H-2615-18'' H-16 H-18 H-20 H-20 H-24 H-24 H-2619'',20'' H-16 H-18 H-18 H-20 H-22 H-24 H-2421-24'' H-18 H-18 H-20 H-22 H-24 H-2425-28'' J-16 J-18 H-18 H-22 H-24 H-2429'',30'' J-16 J-18 H-22 H-24 H-2431-36'' J-16 J-18 J-20 H-22 H-2437-42'' J16T J-16 J-18 J-20 J-2243-48'' JT16 J-18 J-18 J-2249-54'' K-16 JT16 J-18 J-2055-60'' L-16 JT16 K-18 JT18 J-2061-72'' L-16 JT16 L-18 JT1873-84'' LT16 JT1685-96'' LT16 JT1697-108'' LT16 JT16109-120'' LT16 JT16Compliance to the 1998 California Mechanical Code AddendumNOTE:METAL NOSING MUST BE USED WHEREVER LINER IS PRECEDED BYUNLINED METAL; OTHERWISE WHEN VELOCITY EXCEEDS 4000 FPM(20.3 MPS) USE METAL NOSING ON EVERY LEADING EDGE.AIR FLOWAS DESCRIBED ON PAGE 2.24, FIGURE 2-19 OF THE SMACNA HVAC DUCTCONSTRUCTION STANDARDS, 2ND ED., 1995DETAIL ADUCT CONSTRUCTION STANDARDS PAGE 25


OperatingPressureTEST RESULTSThe following tests of rectangular duct sections and transverse joints were conducted in accordancewith Section VII of the SMACNA HVAC Duct Construction Standards, 2nded., 1995.Duct Size Section Length Duct Gauge Connector Type ConnectorDeflectionDuct Deflection1'' 72/12 60'' 18 ga. H .249 .6501'' 48/12 60'' 26 ga. H .050 .7501'' 60/21 60'' 26 ga. J .060 .7501'' 84/12 60''R 24 ga. J .072 .3841'' 96/12 60'' 20 ga. J .290 .7501'' 84/21 60''T 26 ga. J .060 .3502'' 60/21 60''T 26 ga. J .050 .0102'' 84/12 48'' 18 ga. J .250 .7402'' 72/12 60''R 24 ga. H .258 .7252'' 72/12 60'' 19 ga. J .230 .6502'' 48/12 60'' 24 ga. H .120 .8202'' 84/36 60''R 20 ga. J .168 .6702'' see note 84/21 60''T 26 ga. J .040 .4683'' 48/12 60'' 20 ga. H .165 .7303'' 72/12 60''R 24 ga. J .140 .7023'' 60/12 60'' 18 ga. J .131 *3'' 76/44 60''R 20 ga. J .220 .5003'' 60/15 60'' 16 ga. H .148 .7403'' 60/21 60''T 26 ga. J .090 .0404'' 72/12 60''R 24 ga. J .231 .4984'' 48/12 60''R 24 ga. H .164 .4984'' 48/12 60'' 20 ga. H .245 .8304'' 60/12 60'' 18 ga. J .160 *4'' 76/44 60''R 20 ga. J .278 .6004'' 60/21 60''T 26 ga. J .120 .1005'' 48/12 60''R 24 ga. H .210 .5255'' 48/12 60'' 18 ga. H .250


GageThickness in Inches Weight Thickness in MillimetersMin. Max. Nom.Min.lb/sfNom.Lb/sfMax.lb/sfNom.Kg/m²Min. Max. Nom.33323130292827262524232221201918171615141312111098.0060.0104.0112.0127.0142.0157.0172.0187.0217.0236.0266.0296.0326.0356.0406.0466.0525.0575.0650.0705.0854.0994.1143.1292.1442.1591.0120.0164.0172.0187.020.0217.0232.0247.0287.0316.0346.0376.0406.0436.0506.0566.0625.0695.0770.0865.1014.1174.1323.1472.1622.1771.0090 .2409 .376 .486.0134 .4204 .563 .665.0142 .4531 .594 .698.0157 .5143 .656 .759 3.20.0172 .5755 .719 .820.0187 .6367 .781 .881 3.81.0202 .6979 .844 .943.0217 .7591 .906 1.004 4.42.0247 .84071.167.0276 .9590 1.156 1.285 5.64.0306 1.08141.408.0336 1.2038 1.406 1.530 6.86.0336 1.32631.653.0396 1.4486 1.656 1.775 8.08.0456 1.65262.061.0516 1.8974 2.156 2.305 10.52.0575 2.13812.546.0635 2.342 2.656 2.832 12.96.0710 2.64813.138.0785 2.8725 3.281 3.525 16.01.0934 3.48044.133.1084 4.0516 4.531 4.786 22.11.1233 4.65055.394.1382 5.2675 5.781 6.002 28.21.1532 5.87956.614.1681 6.4874 6.875 7.222Galvanized Sheet Thickness Tolerances.1524.2642.2845.3188.3569.3950.4331.4712.5274.6010.6772.7534.8296.9061.0281.1811.3311.4631.6531.7842.1622.5232.9023.2803.6614.040.3048.4166.4369.4783.5169.5550.5931.6312.7274.8010.8772.95341.02961.1061.2881.4411.5911.7631.9532.2042.58232.9833.3623.7404.1214.500.2286.3404.3607.3988.4369.4750.5131.5512.6274.7010.7772.8534.92961.0061.1581.3111.4611.6131.8031.9942.3722.7533.1323.5103.8914.270NOTES:a. Based on ASTM A924/924M-94, Standard Specification for General Requirements for Sheet Steel, Metallic Coated by the Hot-Dip Process(formerly ASTMA525); and ASTMA653/A653M-94, Standard Specification for Sheet Steel, Zinc-Coat (Galvanized) or Zinc-Iron AlloyCoated (Galvanized) by the Hot-Dip Process.b. Tolerances are valid for 48 in. and 60 in. wide coil and cut length stock – other dimensions apply to other sheet widths and to strip.c. The lock forming grade of steel will conform to ASTM A653 (formerly ASTM A527).d. The steel producing industry recommends that steel be ordered by decimal thickness only. Thickness and zinc coating class can be stenciledon the sheet. The gage designation is retained for residual familiarity reference only.e. Minimum weight in this table is based on the following computation:Minimum sheet thickness minus 0.001 in. of G60 coating times 40.8 lb. per sf. per in. plus 0.0369 lb./sf of zinc.G90 stock would be comparably calculated from:(t-.00153 in.) 40.8 ÷ 0.05564=minimum weight.However, scale weight may run 2 % (or more) greater than theoretical weight. Actual weight may be near 40.82 lb. per sf per in.f. G60 coating, per ASTM A653 and ASTM A90, has 0.60 oz/sf (triple spot test) total for two sides. 0.59 oz/sf of zinc equals 0.001 in. 1oz is0.0017 in. and is 305.15 g/m².G90 coating is 0.90 oz/sf (triple spot test), or 0.00153 in. Magnetic gage measurement of zinc coating may have 15% error.g. ASTM D2092, Practice for Preparation of zinc-Coated Galvanized Steel Surfaces for Paint includes mill phosphatizing.h. ASTM A755 is the Specification for Sheet Metal, Metallic Coated by the Hot-Dip Process and Prepainted by the Coating Process forExterior Building <strong>Product</strong>s. Other information is available from the National Coal Coaters Association, Philadelphia, PA.i. Much chemical and atmospheric corrosion information is available from ASM international in Metals Park, Ohio and from NACE internationalin Houston, TX.j. A principle international standard is ISO 3575, Continuous Hot-Dip Process, Zinc-Coated Carbon Steel Sheet of Commercial, LockForming and Drawing Qualities.HVAC Duct Construction Standards Metal and Flexible • Third EditionPAGE 27


Most <strong>Dyn</strong>-O-<strong>Mate</strong> <strong>Product</strong>s are made in the U.S.A.*To verify any particular product please contact us.© <strong>Duro</strong> <strong>Dyn</strong>e Corp.Printed in USA 6/14BB021503<strong>Duro</strong> <strong>Dyn</strong>e East Division, Bay Shore, NY 631-249-9000 Fax: 631-249-8346<strong>Duro</strong> <strong>Dyn</strong>e Midwest Division, Fairfield, OH 513-870-6000 Fax: 513-870-6005<strong>Duro</strong> <strong>Dyn</strong>e West Division, Fontana, CA 562-926-1774 Fax: 562-926-5778<strong>Duro</strong> <strong>Dyn</strong>e Canada, Lachine, Quebec, Canada 514-422-9760 Fax: 514-636-0328www.durodyne.com E-mail: durodyne@durodyne.com