<strong>BVM</strong> Parts List9. <strong>BVM</strong>-<strong>40</strong> SpecificationsViewable Parameters Maximum jar voltage. Minimum jar voltage. Selected jar voltage Overall string voltage.Display Backlit LCD, 4 x 20 characters.Power 115VAC 10% 60Hz, 200mA maximum.Fuses One MDL 0.5A, located in the rear panel AC power block.Inputs Up to <strong>40</strong> 12VDC jars.Outputs LCD screen. Alarm Relay (Form/Rev C)Reading Accuracy Cell voltage: 0.15% of reading 10mv String voltage, 0 to 600V: 0.2% of reading, 0.5VControl Switches Power on/off: Main <strong>BVM</strong> rocker switch on rear panel. Jar Select Two front panel momentary push button switches.Operating Environment Temperature range: 5C to <strong>40</strong>C (41F to 104F) Humidity range: 0% to 80% RH (non condensing) at 5C to 31C0% to 50% RH (non condensing) at 32C to <strong>40</strong>C Indoor use only. Installation category II Pollution degree 2.Packaging 7" width, 3.5" height, 14" depth. Weight 7.3 lbs.4200–043 13 Revision 2.02