4. Operation <strong>of</strong> the hoistway vent as required by the VA CAD St<strong>and</strong>ard SD-230923-08 in<br />
PG-18-4 will be independent <strong>of</strong> the fire alarm system unless a system smoke detector is<br />
required to be installed at the top <strong>of</strong> the hoistway for elevator recall purposes as<br />
identified above.<br />
I. <strong>Fire</strong> alarm systems shall monitor each water storage tank dedicated only for fire protection<br />
use (if applicable) for low level <strong>and</strong> low temperature <strong>and</strong> shall provide supervisory signals<br />
(monitoring is not required if the water storage tank is for combined fire protection <strong>and</strong><br />
domestic use).<br />
7.5 Communications between Buildings:<br />
A. Buildings shall communicate trouble, supervisory, <strong>and</strong> alarm signals to a main 24-hour<br />
staffed location such as the telephone operator or VA police. This is in addition to VA fire<br />
department notification. Provide a printer to make a hard copy <strong>of</strong> all signals <strong>and</strong> operator<br />
responses. A backup printer is recommended at another 24-hour staffed location.<br />
Coordinate with the facility.<br />
Note: Trouble <strong>and</strong> supervisory signals will be h<strong>and</strong>led at the 24-hour staffed location. The<br />
facility will have to institute a system to h<strong>and</strong>le supervisory signals immediately as required<br />
by the National <strong>Fire</strong> Alarm Code.<br />
B. Where staff response to carry out the fire plan is required from more than one building,<br />
provide notification to other buildings. Coordinate with the facility.<br />
------END-----<br />
- 43