September-2011<br />

4. Operation <strong>of</strong> the hoistway vent as required by the VA CAD St<strong>and</strong>ard SD-230923-08 in<br />

PG-18-4 will be independent <strong>of</strong> the fire alarm system unless a system smoke detector is<br />

required to be installed at the top <strong>of</strong> the hoistway for elevator recall purposes as<br />

identified above.<br />

I. <strong>Fire</strong> alarm systems shall monitor each water storage tank dedicated only for fire protection<br />

use (if applicable) for low level <strong>and</strong> low temperature <strong>and</strong> shall provide supervisory signals<br />

(monitoring is not required if the water storage tank is for combined fire protection <strong>and</strong><br />

domestic use).<br />

7.5 Communications between Buildings:<br />

A. Buildings shall communicate trouble, supervisory, <strong>and</strong> alarm signals to a main 24-hour<br />

staffed location such as the telephone operator or VA police. This is in addition to VA fire<br />

department notification. Provide a printer to make a hard copy <strong>of</strong> all signals <strong>and</strong> operator<br />

responses. A backup printer is recommended at another 24-hour staffed location.<br />

Coordinate with the facility.<br />

Note: Trouble <strong>and</strong> supervisory signals will be h<strong>and</strong>led at the 24-hour staffed location. The<br />

facility will have to institute a system to h<strong>and</strong>le supervisory signals immediately as required<br />

by the National <strong>Fire</strong> Alarm Code.<br />

B. Where staff response to carry out the fire plan is required from more than one building,<br />

provide notification to other buildings. Coordinate with the facility.<br />

------END-----­<br />

- 43 ­