Fire Protection Design Manual - Office of Construction and Facilities ...
Fire Protection Design Manual - Office of Construction and Facilities ...
Fire Protection Design Manual - Office of Construction and Facilities ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
September-2011<br />
� Installation instructions <strong>and</strong> sprinkler components designed to reduce the possibility <strong>of</strong><br />
the escutcheon being used as an anchor for hanging. One design approach involves a<br />
retaining collar that is attached to the sprinkler pipe with set screws. This design is<br />
intended to prevent the escutcheon from being pulled away from the ceiling surface. This<br />
design would not be appropriate where the ceiling surface is a lay-in ceiling. A lay-in<br />
ceiling allows access to numerous anchor points by the removal <strong>of</strong> or punching through<br />
a tile. Another design approach involves an escutcheon installed with spacers. This<br />
design is also intended to prevent the escutcheon from being pulled away from the<br />
ceiling surface. This approach may be compromised if there is deflection in the<br />
sprinkler piping such that the escutcheon can be pulled away from the ceiling surface. If<br />
this approach is to be used, plastic pipe should not be permitted (plastic pipe is not<br />
permitted for new VA facilities) <strong>and</strong> a hanger should be installed at each sprinkler drop<br />
to prevent pipe deflection.<br />
M. Install st<strong>and</strong>ard response sprinklers with intermediate temperature rating 93°C (200°F) or<br />
higher in elevator shafts, elevator pits, <strong>and</strong> elevator machine rooms. Install sprinklers in<br />
elevator shafts <strong>and</strong> pits only where required by NFPA 13. (Note: See Section 7 for<br />
necessary power shutdown requirements.)<br />
N. Do not use flow control (on/<strong>of</strong>f) sprinklers.<br />
O. Where buildings are required to be sub-divided into smoke compartments, segregate<br />
sprinklers into zones that correspond to the smoke compartments. Coordinate sprinkler<br />
zones with smoke (compartments) <strong>and</strong> fire alarm evacuation zones. Provide a flow switch,<br />
isolation valve, tamper switch, <strong>and</strong> pressure gage for each zone. Provide separate zones for<br />
paint spray booths, dust collectors, <strong>and</strong> lint collectors.<br />
P. Route the drain pipes for each sprinkler riser <strong>and</strong> test connection to the building exterior to<br />
facilitate testing. Do not terminate at service sinks as their drains are inadequate for test<br />
flow. Drain piping shall be 50 mm (2 in) minimum to accommodate discharge from full flow<br />
tests at maximum system pressure. <strong>Design</strong> exterior drains to prevent flooding or damage to<br />
l<strong>and</strong>scaping, <strong>and</strong> to prevent wetting <strong>of</strong> walkways.<br />
Q. Specify non-ferrous piping for all areas within Magnetic Resonance Imaging (MRI) suites.<br />
R. Determine <strong>and</strong> identify on drawings the location <strong>of</strong> fire pump, risers, all valves, fire<br />
department connections, drains, <strong>and</strong> points <strong>of</strong> connection with underground fire service<br />
main.<br />
6.2 St<strong>and</strong>pipes <strong>and</strong> <strong>Fire</strong> Hose Connections:<br />
A. St<strong>and</strong>pipes shall be installed in all buildings where required by NFPA 101, NFPA 45, or<br />
NFPA 1, except as modified by the following paragraphs.<br />
B. Install Class I hose connections per NFPA 14.<br />
C. Wet st<strong>and</strong>pipes are preferred.<br />
- 26