Technical <strong>SIL2</strong> Requirements for the Application Program 9-7Table 9.1 Methods of Chang<strong>in</strong>g Your Application Program <strong>in</strong> RSLogix 5000• Users can edit the relay ladder logic portion of their programus<strong>in</strong>g one of the follow<strong>in</strong>g methods described <strong>in</strong> Table 9.1:Method: Required Steps: ControllerKeyswitchPosition:Offl<strong>in</strong>eOnl<strong>in</strong>eThe user performs the tasks described <strong>in</strong> the flow chart <strong>in</strong> Figure 9.1 onpage 9-5.1. Turn the controller key to the REM position.2. Use the Onl<strong>in</strong>e Edit Toolbar to start, accept, test and assemble youredits. The toolbar is shown below.startpend<strong>in</strong>grung editacceptpend<strong>in</strong>g rungeditsassembleprogrameditstestprogrameditsuntestprogrameditsPROGREMKey Po<strong>in</strong>ts to this Method:Users must revalidate the entireapplication before return<strong>in</strong>g tonormal operation.The project rema<strong>in</strong>s onl<strong>in</strong>e butoperates <strong>in</strong> the remote run mode.When edits are <strong>com</strong>pleted, usersare only required to validate thechanged portion of the applicationprogram.We re<strong>com</strong>mend that onl<strong>in</strong>e edits belimited to m<strong>in</strong>or programmodifications such as setpo<strong>in</strong>tchanges or ladder logic rungadditions, deletions andmodifications.a. Click the start pend<strong>in</strong>g rung edits button . A copy is madeof the rung you want to edit.b. Change your application program as needed. At this po<strong>in</strong>t, theorig<strong>in</strong>al program is still active <strong>in</strong> the controller. Your programchanges are made <strong>in</strong> the copied rungs. Changes do not affect theoutputs until you test program edits <strong>in</strong> step d.c. Click the accept pend<strong>in</strong>g rung edits button . Yourprogram changes are verified and downloaded to the controller.The controller now has the changed program and the orig<strong>in</strong>alprogram. However, the controller cont<strong>in</strong>ues to execute theorig<strong>in</strong>al program. You can see the state of the <strong>in</strong>puts, andchanges do not affect the outputs.d. Click the test program edits button .e. Click Yes to test the edits. Changes are now executed and affectthe outputs; the orig<strong>in</strong>al program is no longer executed. However,if you are not satisfied with the result of test<strong>in</strong>g the edits, youcan discard the new program by click<strong>in</strong>g on the untest programedits button if necessary. If you untest the edits, thecontroller returns to the orig<strong>in</strong>al program.IMPORTANT: This option tochange theapplication programis available forchanges to relayladder logic only.Users cannot usethis method tochange functionblock programm<strong>in</strong>g.For more detailed<strong>in</strong>formation on howto edit ladder logicwhile onl<strong>in</strong>e, seethe Logix5000Controllers QuickStart, publication<strong>1756</strong>-QS001.f. Click the assemble program edits button .g. Click Yes to assemble the edits. The changes are the onlyprogram <strong>in</strong> the controller, and the orig<strong>in</strong>al program is discarded.3. Perform a partial proof test of the portion of the application affectedby the program edits.4. Turn the controller key back to the RUN position to return the projectto Run mode. We re<strong>com</strong>mend you upload the new program to yourprogramm<strong>in</strong>g term<strong>in</strong>al to ensure consistency between theapplication <strong>in</strong> the controller and on the programm<strong>in</strong>g term<strong>in</strong>al.5. Remove the key.Publication <strong>1756</strong>-<strong>RM001B</strong>-<strong>EN</strong>-P - October 2003

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!